J3_-_Plans_Namekagon_Campground_Electric_Soil_Boring_Phone_Service.pdf
PDF 2 MB Posted
- Solicitation number
- 12569R19Q0034
About this file
Plans Namakagon
View the file
Other files
| File | Type | Posted |
|---|---|---|
| J2_-_Plans_Chippewa_Campground_Electric_Soil_Boring.pdf | ||
| J4_-__DB_Wage_Determination_WI20190015.pdf | ||
| RFQ_12569R19Q0034.docx | DOCX document | |
| J1_-_Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Map data ©2018 Google 1 mi
Namekagon Campground
4.7 ★★★★★· 10 reviews
Campground
Namekagon Campground
PROJECT SITE
T-01 COVER SHEET 03/21/2019
E-01 ELECTRICAL SITE PLAN AND DETAILS 03/21/2019
P-01 HOST SITE HOLDING TANK 03/21/2019
FOREST ENGINEER
DATE
DATE
DIRECTOR OF
ENGINEERING
DATE
FOREST SUPERVISOR
RO FACILITIES PROGRAM MANAGER DATETRAVEL DIRECTIONS:
LOCATED APPROXIMATELY 17 MILES EAST OF CABLE, DRIVE EAST ON HIGHWAY M 10.9 MILES TO HIGHWAY D. TURN LEFT (NORTH) ON D AND PROCEED 5.5 MILES TO FOREST ROAD 209. TURN LEFT (WEST) AND PROCEED 0.3 MILES TO
THE CAMPGROUND.
LAT: 46.24453
LONG: -91.08546
THE SCOPE OF THIS PROJECT IS TO PROVIDE ELECTRCIAL SERVICE TO 23 CAMPSITES AND
A DEDICATED WASTEWATER HOLDING TANK AT A NEW HOST SITE. THE WORK WILL ALSO
INCLUDE RELOCATING AN EXISTING ELECTRICAL PEDESTAL.
THE ELECTRIC SERVICE WILL BE SUPPLIED BY A BURIED ELECTRICAL LINE FROM TWO
TRANSFORMERS TO BE PROVIDED BY BAYFIELD ELECTRIC CO-OP.
THE WASTEWATER HOLDING TANK WILL BE A NOMINAL 1500 GALLON CONCRETE TANK
WITH TWO POLYPROPYLENE ACCESS RISERS. THE HOLDING TANK WILL BE PROVIDED
WITH A RED LED HIGH WATER ALARM LIGHT. THE ALARM SHALL BE ENERGIZED WITH
POWER FROM THE EXISTING HOST ELECTRICAL PEDESTAL. AN ADA ACCESSIBLE SEWER
DROP WITH A FOUR INCH THREADED PVC CAP INLET IS ALSO PART OF THIS PROJECT.
THE CONTRACTOR SHALL FURNISH ALL LABOR, TOOLS, AND EQUIPMENT NECESSARY FOR
THE PROPER EXECUTION OF THE WORK IN ACCORDANCE WITH LOCAL, STATE AND
NATIONAL CODES AND COMPLETE THE PROJECT IN AN ACCEPTABLE MANNER, READY
FOR USE, OCCUPANCY OR OPERATION BY THE OWNER.
THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS WITH THE DRAWING
DIMENSIONS. IF A CONFLICT IS FOUND OR IF FIELD CHANGES ARE MADE THAT DEVIATE
FROM THE PLANS, THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER'S
REPRESENTATIVE IMMEDIATELY, PRIOR TO CONSTRUCTION OR THE ORDERING OF ANY
MATERIALS.
ALL LOCATIONS TO BE REVIEWED/APPROVED BY CONTRACTING OFFICER'S
REPRESENTATIVE.
SITE 28
SITE 29
SITE 30
SITE 32
SITE 31
SITE 33
SITE 34
SITE 15
SITE 13
SITE 12
SITE 14
SITE 25
SITE 23
SITE 20
SITE 18
SITE 17
SITE 16
SITE 21
SITE 22
SITE 24
SITE 26
SITE 27
SITE 19
PROPOSED 20, 30, 50
AMP ELECTRICAL
PEDESTALS IN NEW
ELECTRICAL SERVICE
LOOP. 23 TOTAL.
SITE PLAN
Scale: 1" = 200'-0"1
NORTH TRANSFORMER
AND EXISTING
ELECTRICAL PANEL
WITH METER.
PROPOSED NEW
HOST SITE
LOCATION
SOUTH TRANSFORMER AND
EXISTING ELECTRICAL
PANEL WITH METER.
SITE 19 ELECTRICAL PEDESTAL TO
BE DISCONNECTED FROM
EXISTING SOUTH TRANSFORMER
PANEL AND MOVED 35' INTO HOST
SITE.
ELECTRICAL SITE PLAN
AND DETAILS
E-01 002 003
SITE 28
SITE 29
SITE 30
SITE 32
SITE 31
SITE 33
SITE 34
SITE 15
SITE 13
SITE 12
SITE 14
SITE 25
SITE 23
SITE 20
SITE 18
SITE 17
SITE 16
SITE 21
SITE 22
SITE 24
SITE 26
SITE 27
SITE 19
LOOP A
ELECTRICAL CIRCUIT SCHEMATIC
Scale: 1" = 100'-0"2
NORTH TRANSFORMER
AND EXISTING
ELECTRICAL PANEL
WITH METER.
SOUTH TRANSFORMER AND
EXISTING ELECTRICAL
PANEL WITH METER.
LOOP B
LOOP C
LOOP D
LOOP E
LOOP F
PROPOSED NEW
HOST SITE
LOCATION
SITE 19 ELECTRICAL PEDESTAL TO
BE DISCONNECTED FROM
EXISTING SOUTH TRANSFORMER
PANEL AND MOVED 35' INTO HOST
SITE.
USE 350, 350, 4/0 ALUMINUM
WIRE TYPE URD DIRECT
BURIAL OR APPROVED
EQUAL.
SITE 28
SITE 29
SITE 30
SITE 32
SITE 31
SITE 33
SITE 34
SITE 15
SITE 13
SITE 12
SITE 14
SITE 25
SITE 23
SITE 20
SITE 18
SITE 17
SITE 16
SITE 21
SITE 22
SITE 24
SITE 26
SITE 27
SITE 19
LOOP A
ELECTRICAL CIRCUIT SCHEMATIC
Scale: 1" = 100'-0"3
NORTH TRANSFORMER AND
EXISTING ELECTRICAL
PANEL WITH METER.
SOUTH TRANSFORMER AND EXISTING
ELECTRICAL PANEL WITH METER.
LOOP B
LOOP C
LOOP D
LOOP E
LOOP F
NOTE:
PROPOSED ELECTRICAL
UNDERGROUND ROUTES.
UNDERGROUND WIRING SHALL
BE INSTALLED AS SHOWN AT A
MINIMUM DEPTH OF 24 INCHES.
CONTRACTOR SHALL SUBMIT AN
AS-BUILT PLAN OF THE FINAL
ELECTRICAL ROUTES.
PROPOSED NEW HOST
SITE LOCATION
SITE 19 ELECTRICAL PEDESTAL TO
BE DISCONNECTED FROM
EXISTING SOUTH TRANSFORMER
PANEL AND MOVED 35' INTO HOST
SITE.
USE SINGLE DIRECTIONAL
BORE FOR BOTH LOOPS.
SEE ELECTRICAL DESIGN
NOTES, NOTE 8.
USE SINGLE DIRECTIONAL
BORE FOR BOTH
CROSSES OF LOOP. SEE
ELECTRICAL DESIGN
NOTES, NOTE 8.
SEE ELECTRICAL DESIGN
NOTES, NOTE 8.
SEE ELECTRICAL DESIGN
NOTES, NOTE 8.
USE SINGLE DIRECTIONAL BORE
FOR BOTH CROSSES OF LOOP.
SEE ELECTRICAL DESIGN NOTES,
NOTE 8.
SEE ELECTRICAL DESIGN
NOTES, NOTE 8.
% of Total % of Triplex wire Circuit Loop A Voltage Voltage or From To Max. Amps Wire Length, ft Voltage Volt-amperes Wire Size Resistivity Drop Drop Quadplex wire Panel N Site 13 50 71 240 24200 350 0.0605 0.4% 0.4% Quadplex wire Site 13 Site 14 50 67 240 19400 350 0.0605 0.3% 0.6% Quadplex wire Site 14 Site 15 50 78 240 14600 350 0.0605 0.2% 0.9% Quadplex wire Site 15 Site 12 50 89 240 9600 350 0.0605 0.2% 1.1% Quadplex wire
% of Total % of Triplex wire
Circuit Loop B Voltage Voltage or From To Max. Amps Wire Length, ft Voltage Volt-amperes Wire Size Resistivity Drop Drop Quadplex wire Panel S Site 17 50 184 240 29000 350 0.0605 1.1% 1.1% Quadplex wire Site 17 Site 16 50 139 240 24200 350 0.0605 0.7% 1.8% Quadplex wire Site 16 Site 18 50 47 240 19400 350 0.0605 0.2% 2.0% Quadplex wire Site 18 Site 20 50 99 240 14600 350 0.0605 0.3% 2.3% Quadplex wire Site 20 Site 21 50 110 240 9600 350 0.0605 0.2% 2.5% Quadplex wire
% of Total % of Triplex wire
Circuit Loop C Voltage Voltage or From To Max. Amps Wire Length, ft Voltage Volt-amperes Wire Size Resistivity Drop Drop Quadplex wire Panel S Site 19 50 35 240 9600 350 0.0605 0.1% 0.1% Quadplex wire
% of Total % of Triplex wire
Circuit Loop D Voltage Voltage or From To Max. Amps Wire Length, ft Voltage Volt-amperes Wire Size Resistivity Drop Drop Quadplex wire Panel S Site 22 50 342 240 29000 350 0.0605 2.1% 2.1% Quadplex wire Site 22 Site 23 50 63 240 24200 350 0.0605 0.3% 2.4% Quadplex wire Site 23 Site 25 50 69 240 19400 350 0.0605 0.3% 2.7% Quadplex wire Site 25 Site 26 50 145 240 14600 350 0.0605 0.4% 3.1% Quadplex wire Site 26 Site 24 50 119 240 9600 350 0.0605 0.2% 3.4% Quadplex wire
% of Total % of Triplex wire
Circuit Loop E Voltage Voltage or From To Max. Amps Wire Length, ft Voltage Volt-amperes Wire Size Resistivity Drop Drop Quadplex wire Panel N Site 27 50 280 240 24200 350 0.0605 1.4% 1.4% Quadplex wire Site 27 Site 28 50 156 240 19400 350 0.0605 0.6% 2.1% Quadplex wire Site 28 Site 29 50 153 240 14600 350 0.0605 0.5% 2.5% Quadplex wire Site 29 Site 31 50 84 240 9600 350 0.0605 0.2% 2.7% Quadplex wire
% of Total % of Triplex wire
Circuit Loop F Voltage Voltage or From To Max. Amps Wire Length, ft Voltage Volt-amperes Wire Size Resistivity Drop Drop Quadplex wire Panel N Host 50 397 240 29000 350 0.0605 2.4% 2.4% Quadplex wire Host Site 33 50 54 240 24200 350 0.0605 0.3% 2.7% Quadplex wire Site 33 Site 34 50 90 240 19400 350 0.0605 0.4% 3.1% Quadplex wire Site 34 Site 32 50 81 240 14600 350 0.0605 0.2% 3.3% Quadplex wire Site 32 Site 30 50 72 240 9600 350 0.0605 0.1% 3.5% Quadplex wire
ELECTRICAL PEDESTAL DETAIL4
PROVIDE 15 AMP BREAKER
FOR ALARM LIGHT.
FOR HOST SITE ONLY.
ELECTRICAL DESIGN NOTES
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, TOOLS
EQUIPMENT AND TRANSPORTATION NECESSARY FOR THE PROPER EXECUTION OF
THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AND ALL INCIDENTAL
WORK NECESSARY TO COMPLETE THE PROJECT IN AN ACCEPTABLE MANNER,
READY FOR USE, OCCUPANCY OR OPERATION BY THE OWNER.
2. ALL ELECTRICAL WORK SHALL BE IN COMPLIANCE WITH ALL NATIONAL,
STATE AND LOCAL CODES, ORDINANCES. ANY MODIFICATIONS AND/OR ADDITIONS
TO THESE PLANS REQUIRED FOR PROPER COMPLIANCE TO ANY APPLICABLE CODES
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
3. ELECTRICAL WORK SHALL BE DONE BY A LICENSED ELECTRICIAN WITH
AN ELECTRICAL PERMIT AND INSPECTION.
4. CONTRACTOR TO LOCATE EXISTING WATER, SEWER, AND ELECTRICAL
LINES AND ENSURE NO CONFLICTS WITH PROPOSED ELECTRICAL LINES.
5. THE ELECTRICAL CONTRACTOR SHALL COORDINATE UTILITY RUNS WITH
OTHER TRADES.
6. FURNISH AND INSTALL WIRING, DEVICES, PANELS, AND BREAKERS AS
REQUIRED. WHERE AN ELECTRICAL DEVICE AND/OR DISCONNECT IS REQUIRED BY
CODE BUT NOT SHOWN, IT SHALL BE FURNISHED AND INSTALLED BY THE
ELECTRICIAN.
7. THE ELECTRICAL CONTRACTOR SHALL INSTALL CIRCUIT DIRECTORY
WITH TYPED CIRCUIT DESIGNATION CARD ON THE INSIDE OF EACH PANEL BOARD
DOOR.
8. PEDESTALS ARE TO BE LOCATED ON RIGHT SIDE OF EACH SITE.
CONTRACTING OFFICER'S REPRESENTATIVE TO VERIFY/APPROVE PEDESTAL
LOCATION.
9. ELECTRICAL WIRING AT PAVED ROAD CROSSINGS SHALL BE
DIRECTIONALLY BORED. BORING IS ONLY REQUIRED IF ROAD HAS ALREADY BEEN
PAVED.
10. BAYFIELD ELECTRIC CO-OP TO PROVIDE BOTH TRANSFORMERS, THE
ELECTRICAL SERVICE LINE TO THE METER SOCKETS, AND THE ELECTRICAL SERVICE
METERS.
11. ELECTRICAL LOOPS A, E, AND F WILL HAVE ELECTRICAL SERVICE
SUPPLIED BY THE NORTH TRANSFORMER. ELECTRICAL LOOPS B, C, AND D WILL HAVE
ELECTRICAL SERVICE SUPPLIED BY THE SOUTH TRANSFORMER.
12. BAYFIELD ELECTRIC CO-OP CONTACT: BILL JOHNSON
(715-372-4287)
13. IF A NEW PANEL MOUNTING BOARD IS REQUIRED, PANEL SHALL BE
CONSTRUCTED OF TWO 4X4X10' GROUND CONTACT TREATED POSTS BURIED 48"
BELOW GROUND AND 3/4" TREATED PLYWOOD BACKER. FIELD LOCATE PER
CONTRACT OFFICER'S REPRESENTATIVE.
ELECTRICAL RISER DIAGRAM DETAIL - NORTH PANEL5
400 AMP MAIN BREAKER /
DISCONNECT
125 KVA TRANSFORMER.
PROVIDE MIN. 125 KVA
TRANSFORMER.
REPLACE EXISTING
NORTH TRANSFORMER.
SITE BREAKER PANEL.
PROVIDE ONE 200 AMP
BREAKER / DISCONNECT
FOR EACH ELECTRICAL
LOOP.
PROPOSED ELECTRICAL SERVICE METER
TO BE INSTALLED BY BAYFIELD ELECTRIC
CO-OP.
ELECTRIC
SUPPLY LINE
TO SITES
PROPOSED METER SOCKET.
CONTRACTOR TO PROVIDE
METER SOCKET.
ELECTRIC
SERVICE LINE
ELECTRICAL RISER DIAGRAM DETAIL - SOUTH PANEL6
400 AMP MAIN BREAKER /
DISCONNECT
106 KVA TRANSFORMER.
PROVIDE MIN. 106 KVA
TRANSFORMER.
REPLACE EXISTING
SOUTH TRANSFORMER.
SITE BREAKER PANEL.
PROVIDE ONE 200 AMP
BREAKER / DISCONNECT
FOR EACH ELECTRICAL
LOOP.
PROPOSED ELECTRICAL SERVICE METER
TO BE INSTALLED BY BAYFIELD ELECTRIC
CO-OP.
ELECTRIC
SUPPLY LINE
TO SITES
PROPOSED METER SOCKET.
CONTRACTOR TO PROVIDE
METER SOCKET.
ELECTRIC
SERVICE LINE
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
(R9)
EASTERN REGION
NAMEKAGON LAKE
CAMPGROUND
IMPROVEMENTS
CHEQUAMEGON-NICOLET
NATIONAL FOREST
03/21/2019
CJM/JS
JS
CJM
190321
United States Department of Agriculture Forest Service
190321
GREAT DIVIDE
RANGER DISTRICT
D or al an d S tre et
U ni ve rs ity
A ve nu e, S ui te
K in gs fo rd , M ic hi ga n
W ill is to n, N or th
D ak ot a
P ho ne
6)
-5
P ho ne
1)
-5
Fa x:
(9
) 7
-5
E m ai l:
m tn en gi ne er in g@ m tn en g.
ne t
M O
U N
TA
IN
E N
G
IN
EE
R
IN
G
, I N
C
DRAWING TITLE
TH
E
O W
N E
R A
G R
E E
S T
O
IN
D E
M N
IF
Y
A N
D H
O
LD
M O
U N
TA
IN
E N
G
IN
E E
R
IN
G , I
N C
. H A
R M
LE
S
S F
R O
M A
N Y
D A
M A
G E
, L
IA
B
IL
IT
Y
O R
C O
S T, IN
C
LU
D
IN
G
A
TT
O R
N E
Y 'S
F E
E S
A N
D C
O S
T O
F D
E
FE
N S
E A
R
IS
IN
G
F R
O M
A N
Y C
H A
N G
E S
O R
A
LT
E R
A
TI
O N
S M
A D
E B
Y A
N Y
O N
E O
TH
E
R T
H A
N M
O U
N
TA
IN
E
N G
IN
E
E R
IN
G
, I N
C
O R
F R
O M
A N
Y R
E U
S E
O F
TH
E
D R
A W
IN
G
S A
N D
D A
TA
W
IT
H
O U
T
TH
E P
R
IO
R W
R
IT
TE
N
C O
N S
E N
T O
F M
O U
N
TA
IN
E
N G
IN
E
E R
IN
G
, I N
C
FIELD LOCATE NEW
TRANSFORMER, METER AND
CONTROL PANEL PER POWER
COMPANY AND CONTRACTING
OFFICER'S REPRESENTATIVE
Phone Service Note:
Contractor shall coordinate with phone service provider to relocate phone service from SITE 19 to new host site. New phone service shall have appropriate pedestal as recommended by phone company.
Contractor to cover all expenses associated with work.
P-01 003 003
HOST SITE
HOLDING TANK
6"
SLOPE TO
HOLDING TANK
MIN. 1/4" PER FOOT
(MIN. 2% SLOPE)
5'-0" MIN.
3' -0
" M
IN
SEWER DROP NOTES:
1. MIN. CLEAR MANEUVERING
SPACE NEEDED. DO NOT
BLOCK WITH GUARD POSTS,
TIRE STOP, OR ANY OTHER
FEATURES.
2. FINISHED GRADE SLOPE IS
NOT TO EXCEED 1.5% IN ANY
DIRECTION THROUGHOUT
THE CLEAR MANEUVERING
SPACE. CAN BE SLOPED UP
TO 2.5% IF NEEDED FOR
DRAINAGE, ONLY IF SURFACE
IS OTHER THAN CONCRETE,
ASPHALT, OR BOARDS.
3. PIPING TO BE SCHEDULE 40
PVC. PVC CEMENT GLUE ALL
PIPE JOINTS.
ACCESSIBLE CAMPSITE SEWER DROP DETAIL
Scale: 1/2" = 1'-0"3
SECTION
PLAN
FINISHED GRADE
CLEAR
MANEUVERING
SPACE
FI
E
LD
4" SCHEDULE
40 PVC
THREADED
CAP
4" SCHEDULE 40
PVC 90° LONG
SWEEP ELBOW
FI
T
HOLDING TANK PLAN VIEW
Scale: 1" = 1'-0"4
MAX WATER
LEVEL
HOLDING TANK SECTION DETAIL
Scale: 1" = 1'-0"5
NOTE: ALL SEWER PIPING TO BE 4" SCHEDULE 40 PVC.
ALL PIPE JOINTS SHALL BE PVC CEMENT GLUED.
LOCATE TANK MIN. 10' FROM ALL WATERLINES.
FI
T
24" DIA SECURED
MANHOLE COVER
24" TUF-TITE RISER. SEE DETAIL
7, 8, AND 9. FIELD FIT DEPTH.
WEIGHTED FLOAT
SWITCH ASSEMBLY.
MOUNT WEIGHT AND
SWITCH TO ACTIVATE
WHEN WATER LEVEL
IS 18" FROM TOP OF
INSIDE OF TANK.
FLOAT SWITCH
CABLE PROVIDED
WITH FLOAT (TYP)
INLET PIPE.
SLOPE 1/4" PER FOOT
(MIN. 2% SLOPE)
FROM SEWER DROP.
24" DIA SECURED
MANHOLE COVER
FLOAT SWITCH GROUND
CONDUCTOR SHALL BE
SOLIDLY GROUNDED.
BAFFLE
4x4 TREATED
WOOD POST. FIELD
LOCATE PER
RANGER WITHIN
10'-0" OF TANK
1" PVC COVERED
RIGID CONDUIT
AC-POWERED RED
LED ALARM LIGHT.
ATTACH SECURELY
TO POST.
PROPOSED ELECTRICAL
LINE FROM ELECTRICAL
PEDESTAL. LINE SHALL
NOT CROSS OVER ANY
OTHER UTILITY LINE.
FINISHED GRADE
12'-0"
11'-6"
6' -0
5' -6
4" 4'
-0
3"
2 1/2" TAPER (TYP)
5" 3'
-9
6"
4' -1
1"
3"
3"
4"
2'-0" 2'-0"
3"
4' -0
1' -6
" M
IN
3'-0" MIN
3"
" M
IN
FI
E
LD
F
IT
3"
3' -0
9" M
IN
FI
E
LD
HOLDING TANK CAPACITY
1500 GALLON NOMINAL CAPACITY
1600 GALLON ULTIMATE CAPACITY
EYELET
FITTING
CARABINER
NEMA 3R JUNCTION
BOX. ATTACH
SECURELY TO POST.
SITE PLAN
Scale: 1" = 200'-0"1
NORTH TRANSFORMER
AND ELECTRICAL
PANEL
PROPOSED NEW
HOST SITE
LOCATION
SOUTH
TRANSFORMER AND
ELECTRICAL PANEL
AND UTILITY LAYOUT PLAN
Scale: 1" = 20'-0"2
PROPOSED NOMINAL 1500 GALLON HOLDING TANK.
HOLDING TANK TO BE LOCATED IN CLEARING NORTH
OF THE SITE. FIELD FIT TO MINIMIZE DISTURBED AREA.
PROPOSED ELECTRICAL PEDESTAL.
CONTRACTOR TO ENSURE NO CONFLICTS
WITH PROPOSED SEPTIC OR ELECTRICAL
LINES.
PROPOSED 4" SCHEDULE
40 PVC SEWER LINE
SEWER DROP.
SEE DETAIL 3.
ALARM LIGHT. CONNECT TO PROPOSED
ELECTRICAL PEDESTAL. SEE DETAIL 5
NEW
HOST SITE
10'-0
45'-0"
10'-0"
FIELD
FIT
FIELD FIT
NEW ELECTRIC LINE TO ALARM LIGHT. LINE
TO BE 12-2 DIRECT BURIAL CABLE WITH
GROUND @ 24" BELOW GRADE. CONNECT
LINE AT NEW BREAKER AND CIRCUIT AT
EXISTING ELECTRICAL PEDESTAL.
60'-0"
EXISTING CONCRETE SLABS TO BE
REMOVED. RESTORE AREA WITH 6" OF
1-1/4" DENSE GRADED BASE. FINISH GRADE
HOST SITE WITH 4" OF 1-1/4" DENSE
GRADED BASE AND CROWN SITE WITH
1-1/2% SLOPE FROM CENTER TO EDGE.
25'-0
HOST SITE CONSTRUCTION
HOLDING TANK NOTES:
1. HOLDING TANK SHALL BE CONCRETE. ALL ADDITIONAL HOLES FOR PIPING
SHALL BE EITHER FILLED DURING MANUFACTURE OR GROUTED INSIDE AND OUT
WITH NO PLASTIC, RUBBER OR NYLON PLUGS.
2. RISER SHALL BE ATTACHED SO AS TO FORM A WATER TIGHT SEAL BETWEEN
THE RISER AND THE TANK. FOR NON-LOCKABLE LIDS HEX HEAD SCREWS SHALL BE
USED FOR SECURING LID TO RISER. PHILLIPS, TORX, SLOTTED, SQUARE, OR
SIMILAR STYLE HEADS MAY NOT BE USED. THE RISER LID SHALL HAVE A CONFINED
SPACE SIGN (PRE-APPROVED SIGN - SETON'S M7073 SIGN WWW.SETON.COM) OR
HAVE THE WORDS “DANGER CONFINED SPACE DO NOT ENTER” CAST INTO THE
LID.
3. TANK SHALL MEET WI CONSTRUCTION SPECIFICATIONS.
4. TANK SHALL BE SET LEVEL.
5. TANK TO BE FILLED WITH WATER TO THE TOP OF THE TANK AND ALLOWED
TO SET FOR 24 HOURS AND CHECKED FOR LEAKS BEFORE BACKFILLING. IF
WATER LEVEL CHANGES, FIND AND REPAIR LEAK AND RETEST FOR 24 HOURS.
TANK TO BE BACKFILLED AFTER SUCCESSFUL WATER TESTING. TANK MAY BE
PUMPED OUT ONTO THE GROUND (AVOIDING EROSION) AFTER BACKFILLING.
6. BACK FILL SHALL NOT HAVE ANY ORGANIC MATERIAL, NOR 3” OR LARGER
STONES. BACK FILL TO BE COMPACTED IN 12” LIFTS.
7. PIPE INLETS AND OUTLETS SHALL BE SUPPLIED WITH A CAST-IN-PLACE
FLEXIBLE BOOT. GROUTING OF THE PIPE IN PLACE AT THE TANK IS NOT
PERMITTED.
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
(R9)
EASTERN REGION
NAMEKAGON LAKE
CAMPGROUND
IMPROVEMENTS
CHEQUAMEGON-NICOLET
NATIONAL FOREST
03/21/2019
CJM/JS
JS
CJM
190321
United States Department of Agriculture Forest Service
190321
GREAT DIVIDE
RANGER DISTRICT
D or al an d S tre et
U ni ve rs ity A ve nu e, S ui te
K in gs fo rd
, M ic hi ga n
W ill is to n, N or th
D ak ot a
P ho ne
6)
-5
P ho ne
1)
-5
Fa x:
(9
) 7
-5
E m ai l:
m tn en gi ne er in g@ m tn en g.
ne t
M O
U N
TA
IN
E N
G
IN
EE
R
IN
G
, I N
C
DRAWING TITLE
TH
E
O W
N E
R A
G R
E E
S T
O
IN
D E
M N
IF
Y
A N
D H
O
LD
M O
U N
TA
IN
E N
G
IN
E E
R
IN
G , I
N C
. H A
R M
LE
S
S F
R O
M A
N Y
D A
M A
G E
, L
IA
B
IL
IT
Y
O R
C O
S T, IN
C
LU
D
IN
G
A
TT
O R
N E
Y 'S
F E
E S
A N
D C
O S
T O
F D
E
FE
N S
E A
R
IS
IN
G
F R
O M
A N
Y C
H A
N G
E S
O R
A
LT
E R
A
TI
O N
S M
A D
E B
Y A
N Y
O N
E O
TH
E
R T
H A
N M
O U
N
TA
IN
E
N G
IN
E
E R
IN
G
, I N
C
O R
F R
O M
A N
Y R
E U
S E
O F
TH
E
D R
A W
IN
G
S A
N D
D A
TA
W
IT
H
O U
T
TH
E P
R
IO
R W
R
IT
TE
N
C O
N S
E N
T O
F M
O U
N
TA
IN
E
N G
IN
E
E R
IN
G
, I N
C
FINISHED
GRADE
V A
R
IE
S . S
E E
D E
TA
IL
A
N D
4"
M
IN
" M
IN
4"
4" TOPSOIL OR
WISDOT 1-1/4"
DENSE GRADED
BASE. MATCH
EXISTING.
SEWER LINE.
SEWER LINE TRENCH DETAIL
Scale: 1/2" = 1'-0"6
2'-0" MIN.
NOTE: MAINTAIN MIN. 10' CLEARANCE BETWEEN
WATER LINE AND SEWER LINE.
NATIVE OR
EXISTING BACKFILL
NATIVE BACKFILL WITH
NO COBBLES AND
BOULDERS (>2"DIA.)
FINISHED
GRADE
" M
IN
D E
P
TH
4"
4" TOPSOIL OR WISDOT
1-1/4" DENSE GRADED
BASE. MATCH EXISTING.
4" M
IN
" M
IN
ELECTRICAL LINE
ELECTRICAL LINE TRENCH DETAIL
Scale: 1/2" = 1'-0"7
2'-0" MIN.
NATIVE OR
EXISTING BACKFILL
NATIVE BACKFILL WITH
NO COBBLES AND
BOULDERS (>2"DIA.)
Drainage and Septic Products Tuf-Tite, Inc.
1200 Flex Court Lake Zurich, Illinois 60047
TELEPHONE: 847.550.1011
TOLL FREE: 800.382.7009
FAX: 847.550.8004
PART NAME:
PART #:
Material: Copolymer Polypropylene Color: Green
AA
25.00
24.60
4.50 3.10
25.90
24" RISER LID
24 - RISL - GREEN
THIS AREA MAY BE FILLED WITH
CONCRETE FOR ADDITIONAL WEIGHT
A-ASECTION
PERMANENT FOAMED-IN
POLYURETHANE GASKET
• • • © TUF·TITE® RISER LID DETAIL8
Drainage and Septic Products Tuf-Tite, Inc.
1200 Flex Court Lake Zurich, Illinois 60047
TELEPHONE: 847.550.1011
TOLL FREE: 800.382.7009
FAX: 847.550.8004
PART NAME:
PART #:
Material: Copolymer Polypropylene Color: Green
BB
24.20
24.65
25.60
6.00
26.00 7.10
24" RISER
24- RIS - GREEN
B-BSECTION
n~ll ~n
-Pl
- -:::1
I
_ ,. _ I ··+--··- - - -I
1-=::- I 1w
JI
~I-,
• • • © TUF·TITE®
Drainage and Septic Products Tuf-Tite, Inc.
1200 Flex Court Lake Zurich, Illinois 60047
TELEPHONE: 847.550.1011
TOLL FREE: 800.382.7009
FAX: 847.550.8004
PART NAME:
PART #:
Material: Copolymer Polypropylene Color: Green
A A
1.60
30.00
24.60
24" TAR
24 - TAR - GREEN
A-ASECTION 0 0~
r -- ------------------·- -l
• • • © TUF·TITE®
RISER DETAIL9
RISER TAR DETAIL10
RISER NOTES:
1. RISER LID SHALL HAVE A CONFINED SPACE SIGN (SETON MODEL M7073
SIGN) OR HAVE THE WORDS "DANGER - CONFINED SPACE - DO NOT ENTER"
CAST INTO THE LID.
2. NOTE: SECURE LID TO RISER WITH HEX HEAD SCREWS
| Sht-1-Title Sheet / Drawing Index |
| Viewport-17 |
| Viewport-4 |
| Sht-2-Electrical |
| VP-Floor Plan-10 |
| VP-Floor Plan-11 |
| VP-Floor Plan-12 |
| Viewport-1 |
| Viewport-13 |
| Viewport-6 |
| Sht-3-Water and Sewer |
| Viewport-9 |
| Viewport-8 |
| VP-Floor Plan-13 |
| VP-Floor Plan-14 |
| Viewport-7 |
| Viewport-5 |
| Viewport-10 |
| Viewport-2 |
File details come from the government source that posted it.