This document is a Certification Report for the load testing and inspection of a suspended access anchorage system located at 1920 Dayton Ave, Ames, IA 50010. The inspection and testing were conducted by Diversified Fall Protection on July 1, 2020, and the report is dated July 16, 2024. The report describes the testing procedures, equipment, and results, which indicated that all 46 rigid post roof anchors passed the 4,000 lb proof load test with no failures. The report also includes recommendations for ongoing inspections and user instructions.
The related federal contract opportunity is a solicitation (12505B24Q0317) issued by the USDA Agricultural Research Service for the annual inspection of USDA NCAH fall protection systems and equipment located in Ames, Iowa. This is a firm-fixed-price commercial item contract set aside for small businesses. The evaluation will be based on technical factors including meeting the specifications in Attachment 1 and acceptable past performance. Offers are due by August 20, 2024.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Certification Report (Page 1/4)
Diversified Fall Protection, LLC. | 24400 Sperry Drive | Cleveland, OH | (440) 348-9460
Certification Report Suspended Access Anchorage System
Date of Testing: 7/1/2020 Date of Report: 7/16/2024 Job Number: M1186
Site Location: Authorized Inspector:
1920 Dayton Ave.
Ames, IA 50010
Patrick Prestridge
General Information
On the dates referenced above, Diversified Fall Protection (DFP) completed the onsite load testing of the existing anchorages for use as part of a suspended access system located at the address referenced above. Inspection and testing were completed as directed by Tom Ferguson, qualified fall protection engineer, as confirmation of capacity and suitability for suspended access use. All testing was conducted in accordance with OSHA and ANSI recommendations.
This report describes the testing procedures, setup, equipment, data collection, analysis of the collected test data, as well as recommendations for repairs or modifications as necessary. Refer to Infinity Access LLC drawings dated 6/22/06 attached as Appendix C, for plan view locations and details for anchorages included in the testing. Only anchorages as identified in this report and attached drawings are included in the certification.
Description of Equipment Inspected
Rigid Post Roof Anchor (46)
Testing Prescriptions
Applied Load Pull Test Procedure: The load generating device (chain hoist or hydraulic cylinder) was attached to each anchorage point along with an in-line, calibrated dynamometer to measure the forces generated. During testing, inspectors gradually increased the load to reach the designated proof load, which was maintained for three (3) minutes, inelastic deformation (if applicable) was identified and recorded, as well as any other observations or issues with anchorage connection. Refer to Appendix A.
Test Limitations: The test results and data analysis expressed herein is not a warranty that the components tested are necessarily defect-free. DFP takes no responsibility for and makes no claims or opinions with respect to any latent or concealed defects or other defects which may not be visible, but which may exist prior to or as of the date of the test.
Equipment Inspection: Each anchorage component was additionally visually inspected for exposed, visible, and accessible components for any obvious signs of wear, loose or damaged mountings, scarring, cracking, rust, damage, bending, distortion, or corrosion. Anchorage equipment labels, tags, signage or user instructions made available were also inspected.
Certification Report (Page 2/4)
Test Results
SYSTEM QTY FAILED TEST LOAD
Rigid Post Roof Anchor 46 None 4,000 lbs.
Single Point Anchors YES NO N/A
Anchors have no apparent corrosion, cracks, or deterioration. ☒ ☐ ☐
Drain holes are plugged with silicone, plugs, or similar. ☒ ☐ ☐
Anchor U-Bars are free of obstruction for compatible connections. ☒ ☐ ☐
Anchors have positive structural connection with no demonstrated looseness. ☒ ☐ ☐
Anchor welds are free from cracks, corrosion, or other defects. ☒ ☐ ☐
No sign of yielding/permanent deformation or tampering. ☒ ☐ ☐
General Provisions YES NO N/A
Equipment quantities and locations are correctly represented on system drawing. ☒ ☐ ☐
Weatherproof flashings are secure and no apparent signs of water intrusion at roof mounted anchorages.
Provision for safe initial approach to the anchorage system at unprotected edge. ☒ ☐ ☐
Summary and Recommendations
Only the specified anchorages as identified in this report and associated drawings are certified for suspended access use, and are rated for a working load of 1,250 lbs (5,000 lbs fracture/detachment load, 4-1 Safety Factor) and may be used to support (1) equipment tieback OR (1) safety tieback.
We suggest that you continue to periodically inspect the roof anchors and inform DFP if any unsafe conditions arise between the required annual inspections. Authorized users must fully understand the operating procedures of the fall protection system and are responsible for performing daily inspections prior to each system use to confirm proper function prior to use. Anchor recertifications should take place at periods not to exceed 10 years from the date of inspection. All documentation of annual inspections, recertifications, and the anchorage system log-book should be kept in a safe storage area and should be made available upon request by persons using the system. DFP is committed to addressing any further questions or providing you with any future safety solutions. Please contact us with any questions or concerns.
Prepared by:
Alex Harp Field Engineer Diversified Fall Protection
Reviewed by:
Tom Ferguson Engineering Review Diversified Fall Protection
Certification Report (Page 3/4)
Appendix A Inspection Photos
Figure 1: Typical Applied Load Pull Test
Figure 2: Anchor Layout
Certification Report (Page 4/4)
Appendix B
Anchor Layout & Details
Page Intentionally Left Blank
| M1186 - USDA Recert Report (7.16.24).pdf |
| Date of Testing: 7/1/2020 |
| Date of Report: 7/16/2024 |
| TEST LOAD |
| FAILED |
| QTY |
| SYSTEM |
| 4,000 lbs. |
| None |
| 46 |
| Rigid Post Roof Anchor |
| Drawings.pdf |
| Fall Protection System Drawing (3 of 3).pdf |
| Fall Protection System Drawing (1 of 3).pdf |
| Fall Protection System Drawing (2 of 3).pdf |
| 2024-07-16T16:39:56-0400 | |