12505B24Q0145-Bidding RFIs-Morris MNL-Replace Elec Panels-USDA responses.pdf
PDF 82 KB Posted
- Attached to
- Replace Electrical Panels Federal contract opportunity
- Solicitation number
- 12505B24Q0145
About this file
This document contains Requests for Information (RFIs) related to Solicitation 12505B24Q0145 for the replacement of electrical panels at the North Central Soil Conservation Research Laboratory (NCSCRL) USDA-ARS facility in Morris, MN.
The key details are:
- The USDA will not accept reuse of the existing electrical panel backboxes and requires that the panels be replaced in their entirety, including all conduit and wiring modifications.
- The USDA has determined that the new electrical panels must have a 22kAIC rating based on their calculations of the available fault current.
- Local electrical inspections are not required for this federal property, and the contractor does not need to provide any additional fault current calculations.
- This is a total small business set-aside solicitation with a NAICS code of 238210. Quotes are due by 2:00 PM ET on June 6, 2024, and the award will be made to the lowest price technically acceptable offeror.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| updated 06-24-2024-SOW-NCSCRL Morris MN-Replace Electrical Panels.pdf | ||
| Provisions and Clauses.pdf | ||
| breaker 3.jpg | JPG image | |
| out building 2.jpg | JPG image | |
| breaker 6.jpg | JPG image | |
| breaker 1.jpg | JPG image | |
| breaker 5.jpg | JPG image | |
| green house breaker panel.jpg | JPG image | |
| breaker 2.jpg | JPG image | |
| out building 1.jpg | JPG image | |
| breaker 4.jpg | JPG image | |
| Wage Determination MN.pdf | ||
| Wage Determination.pdf | ||
| Statement of Work.pdf | ||
| Provisions and Clauses.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Requests for Information Solicitation 12505B24Q0145 Replace Electric Panels North Central Soil Conservation Research Laboratory (NCSCRL) USDA-ARS, Morris, MN
RFI-1-1
Question 1: Will you Accept New Panel Interiors for the Panels that have Backboxes which are “Piped In” (Conduits Enter from at least 2 Sides). My Question is, if we Extend the Existing Backboxes for Proper Depth, will you accept with the Existing Backboxes Remaining in Place?
The Reason I ask is because the New Panel Tubs of Today are 20” Wide x 42”- 48” Tall x 6” Deep. We’d be Cutting Existing Conduits with Wires in them. Then Trying to “Shoehorn the New Backboxes in without Wrecking the Existing Wires”.
Answer 1: USDA: Proposals shall be based on replacing electrical panels in their entirety (panel enclosure, interior, front, cover, breakers, etc.) and shall include all conduit and wiring modifications for the replacement. Reuse of existing backboxes are not acceptable, this is due to their width of being approximately 16” and concerns that the code-complaint wire bending space will be provided with new panel interiors.
Question 2: How and or Who came up with the 22k AIC Rating for the New Panels? 22kAIC Breakers will Cost a Considerable % More. Did someone do the Calculations? Are there 1 Line Diagrams available to do the Calculations?
Answer 2: USDA: New panels shall have 22K AIC rating as specified. (Note: USDA has performed calculations to determine available fault current at each new panel using information from utility company, information from existing drawings, and on-line fault current calculator – the specified 22K AIC rating was determined from this effort.)
Question 3: Is the USDA Site required to have State or City Electrical Permits and Inspections? Most Government Sites are Not Required to have Inspections but are Required to Follow NEC Rules. I know the Electrical Inspector for this Area (if he has Jurisdiction) will want Available Fault Current Ratings at Each Panel. Do you Require Available Fault Current Ratings be Calculated and Labeled for Each Panel? If Required there would be a lot of Information to be Gathered.
Answer 3: USDA: Local electrical inspectors do not have jurisdiction at federal property. Please see Answer 2 regarding determination of the specified AIC rating. Contractors shall not include any costs in their proposal for calculating available fault currents at each new panel.