_124311_MEP_Winterville.pdf

PDF 5 MB Posted

Attached to
Construction Services for Blacksmith Shop
Solicitation number
PE-66377-NONST-2025-000000001
Issued by
Clayton County, Georgia

About this file

This document contains construction drawings and specifications for the Winterville Blacksmith Shop project in Winterville, GA. The project is being managed by Brandied History, LLC and involves the complete electrical distribution system, lighting, and lighting control for the new facility. The drawings include floor plans, schedules, and details related to the electrical, mechanical, and plumbing systems. Key details include the electrical panel and service information, lighting fixture schedule, mechanical equipment schedule, plumbing piping and fixture layouts, and associated specifications. The project is expected to commence on July 31, 2024. No specific contract term or renewal options are provided.

The document outlines the requirements for the electrical, mechanical, and plumbing systems, including acceptable manufacturers, installation standards, and testing procedures. Pricing terms, set asides, incumbents, funding sources, and other commercial details are not included. The document focuses on the technical requirements and design intent for the building systems to be provided as part of the construction project.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

July 31, 2024

C lie nt R ev ie w D ra w in gs F or

W

IN

TE

R V

IL

LE

B

LA

C

KS

M

IT

H S

H O

P W in te rv ill e

G A

Brandied History, LLC

485 Oakland Ave, SE Atlanta, GA 30312

1601 Mansfield St Brunswick, GA 31520

(404) 723-7240

6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092

404.330.9798

PROJECT # 124311

E0.01

GENERAL

ABBREVIATIONS

AC

AMP FUSEAF

ABOVE FINISHED FLOORAFF

BELOW FINISHED CEILINGBFC

BREAKERBKR

CONNECTED OR CONNECTIONCONN

CTB

DOWNDN

EMPTY CONDUITEC

ELECTRICALELEC

FIRE ALARM CONTROL PANELFACP

FAA

G OR GRND

GFCI OR GF

ISOLATED GROUNDIG

SHORT CIRCUIT CURRENTISC

LIGHTINGLTG

MOUNTEDMTD

NATIONAL ELECTRICAL CODENEC

PANELPNL

RECEPTACLERECPT

TELEPHONETEL TELEPHONE

TTB

TELEVISIONTV

SPD

TYPICALTYP

TRANSFORMERXFMR

UNDERGROUNDUG

WEATHERPROOFWP

NEUTRALN

COPPERCU

ALUMINUMAL

CONDUITCND

NIGHT LIGHTNL

TELEPHONE TERMINAL BOARD

EQUIPMENT AS NOTED ON DRAWING.

DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R 18" AFF

DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R

18" AFF

AC

18" AFF

IN CEILINGJ

J

42" AFFS SWITCH

MOTORM

SYMBOLS DESCRIPTION

XX-#

LEGEND

42" AFFSWITCH - 3 WAY

DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R

DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R IN CEILING

18" AFF

TELEPHONE OUTLET 18" AFF

TELEPHONE / DATA COMBINATION OUTLET 18" AFF

TELEPHONE / DATA COMBINATION OUTLET

DATA OUTLET

DATA OUTLET

18" AFF

D

TV OUTLET 18" AFF

H

SMOKE DETECTOR. CEILING / WALL MOUNTEDD

H HEAT DETECTOR. CEILING/WALL MOUNTED

80" AFF

80" AFF

80" AFF

FIRE ALARM NOTIFICATION DEVICE. AUDIO.

FIRE ALARM NOTIFICATION DEVICE. VISUAL.

FIRE ALARM INITIATION DEVICE. PULL STATION. 42" AFF

42" AFF

42" AFFSWITCH - WALL MTD, LOW VOLTAGE, PILOT LIGHT

SWITCH - CEILING MOUNTED OCCUPANCY SENSOROS IN CEILING

42" AFFSWITCH - WALL MTD, DIMMING

TELEPHONE / DATA COMBINATION OUTLET

J

S3

SOS

SLV

SD

ELECTRICAL GENERAL NOTES

THE DESIGN OF THIS SET OF DOCUMENT IS BASED ON NEC 2020.

ELECTRICAL CONTRACTOR SHALL REFER TO ALL OTHER DESIGN DRAWINGS PRIOR TO BID AND RETAIN FULL UNDERSTANDING OF THE SCOPE OF

WORK.

FIXTURE TYPE INDICATED BY UPPER CASE CHARACTERS, SWITCHING AND GROUPING DESIGNATED BY LOWER CASE LETTER AND CIRCUIT BY

NUMBER (WHERE APPLICABLE).

REFER TO THE ARCHITECTURAL/INTERIORS REFLECTED CEILING PLANS FOR EXACT FIXTURE PLACEMENT AND DIMENSIONS.

REFER TO THE ARCHITECTURAL/INTERIORS DOCUMENTS FOR ACTUAL DEVICE LOCATIONS AND DIMENSIONS.

COORDINATE THE INSTALLATION OF ALL CEILING MOUNTED DEVICES (FIRE ALARM SYSTEM DEVICES AND SPEAKERS, SOUND SYSTEM SPEAKER, ETC.) TO BE SYMMETRICAL ABOUT LIGHT FIXTURES AND SPRINKLER HEADS. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN. TYPICAL.

ALL MOUNTING OF EQUIPMENT IS AS SHOWN UNLESS OTHERWISE NOTED. COORDINATE WITH ARCHITECT THE COLOR/FINISHES OF ALL

ELECTRICAL DEVICES, OUTLETS, COVERPLATES AND TRIM.

EMERGENCY BATTERY PACKS AND EXIT SIGNS SHALL BE CONNECTED AHEAD OF ANY SWITCHING DEVICES.

REFER TO MECHANICAL DRAWINGS FOR DUCT SMOKE DETECTOR LOCATIONS AND QUANTITIES OPERATION SHALL INCLUDE DUAL CONTACT BASE

WITH LOCAL EQUIPMENT SHUTDOWN AND FIRE ALARM SIGNAL INITIATION.

WHEN CONDUCTOR OR CONDUIT SIZE IS INDICATED FOR BRANCH CIRCUIT HOME RUN, THE CONDUCTOR AND CONDUIT SIZE INDICATED SHALL

BE USED FOR THE COMPLETE CIRCUIT.

REFER TO THE APPROPRIATE DRAWINGS FOR THE EXACT LOCATION AND REQUIREMENTS OF EQUIPMENT INSTALLED UNDER OTHER DIVISIONS OF

THE DOCUMENTS, WHICH REQUIRE ELECTRICAL SERVICE.

EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN ALL RACEWAYS.

WALL SWITCHES CONTROLLING CIRCUITS OF OPPOSITE PHASES SHALL NOT BE INSTALLED IN COMMON BOX UNLESS PERMANENT BARRIER IS

PROVIDED.

ALL HOME RUNS SHALL RUN PARALLEL TO STRUCTURE AS MUCH AS POSSIBLE WHERE CEILING IS EXPOSED.

ALL RACEWAY AND EQUIPMENT SUPPORTS AND HANGERS SHALL BE FULLY COORDINATED WITH STRUCTURAL DRAWINGS TO INSURE LOCATION

OF SAME OCCURS WITHIN FOUR (4) INCHES OF PANEL POINT ON BAR JOISTS.

COORDINATE LOCATION OF ALL FLOOR MOUNTED MECHANICAL AND PLUMBING EQUIPMENT IN ORDER TO VERIFY POWER & CONTROL RACEWAY

CONCEALED IN SLABS TERMINATED AT PROPER LOCATION.

DISCONNECT SWITCHES, MOTOR STARTERS AND OTHER ELECTRICAL EQUIPMENT INSTALLED ABOVE ACCESSIBLE CEILINGS, AND REQUIRING ACCESS FOR MAINTENANCE, SHALL BE INSTALLED WITH BOTTOM OF DEVICE ONE (1) FOOT ABOVE CEILING TO PROVIDE READY ACCESSIBILITY.

MECHANICAL, PLUMBING, FIRE PROTECTION AND OTHER EQUIPMENT ARE SHOWN ON FLOOR PLAN IN APPROXIMATE LOCATION. COORDINATE

WITH M, P, FP AND CONTRACT DRAWINGS/SUBMITTALS FOR EXACT LOCATION OF EQUIPMENT.

GENERAL DIAGRAMMATIC RACEWAY INTERCONNECTIONS OF EQUIPMENT, FIXTURES AND DEVICES ARE INDICATED ON FLOOR AND REFLECTED CEILING PLANS, REFER TO STRUCTURAL AND ARCHITECTURAL PLANS FOR ELEVATION CHANGES AND RACEWAY ROUTES.

RACEWAY FOR EXTERIOR LIGHTING MAY BE INDICATED OUTSIDE OF BUILDING FOOTPRINT FOR CLARITY. ROUTE ALL EXTERIOR LIGHTING RACEWAY

WITHIN BUILDING STRUCTURE.

POWER AND COMMUNICATIONS/DATA CONDUITS CAN CROSS AT 90°, BUT WHERE PARALLEL, SHALL BE A MINIMUM OF 8" APART.

TELEVISION AND RADIO ANTENNAS CABLES SHALL HAVE SURGE PROTECTION. GROUND ALL MASTS.

PROVIDE SURGE PROTECTION FOR ELECTRICAL AND TELEPHONE SERVICES.

PROVIDE SPD FOR FIRE ALARM CONTROL PANEL.

FIELD COORDINATE MECHANICAL AND PLUMBING EQUIPMENT ELECTRICAL CHARACTERISTICS WITH DIV.15 CONTRACTOR PRIOR TO ROUGH-IN.

ADJUST ELECTRICAL CONNECTIONS IF NECESSARY TO MATCH ACTUAL EQUIPMENT IN FIELD. FOR EXAMPLE, COORDINATE THE NAMEPLATE OVERCURRENT PROTECTION DEVICE RATING OF MECHANICAL EQUIPMENT AMONG MECHANICAL AND ELECTRICAL SUBCONTRACTORS. ADJUST

CIRCUIT BREAKER TO MATCH NAMEPLATE RATING OF EQUIPMENT AT NO ADDITIONAL COST.

FIELD COORDINATE MECHANICAL AND PLUMBING EQUIPMENT REQUIREMENTS FOR ANY SUPPLEMENTAL POWER REQUIREMENTS, INCLUDING BUT NOT LIMITED TO CONTROL CIRCUITS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO BRING ALL EQUIPMENT TO ITS INTENDED

OPERATIONAL STATUS.

REFER TO FIRE PROTECTION DRAWINGS FOR LOCATIONS OF FLOW AND TAMPER SWITCHES.

EACH PENETRATION OF A FIRE RESISTANT RATED ASSEMBLY BY A PIPE, TUBE WIRE OR CONDUIT SHALL BE PROTECTED BY A THROUGH PENETRATION FIRE STOP SYSTEM THAT HAS BEEN TESTED ACCORDING TO ASTME 814 OR E199.

ELECTRIC RECEPTACLES, SWITCHES, OUTLETS, ETC. SHALL NOT BE INSTALLED BACK TO BACK ON FIRE RESISTANCE RATED WALLS. THEY SHALL

BE AT LEAST 24-INCHES APART.

LIGHT SWITCHES AND ELECTRICAL OUTLETS, LOCATED IN ROOMS ACCESSIBLE TO THE DISABLED SHALL BE LOCATED NO HIGHER THAN 48 INCHES AND NO LOWER THAN 15 INCHES ABOVE THE FINISHED FLOOR SURFACE. IF THE REACH OR THE CONTROL IS OVER AN OBSTRUCTION, THE MINIMUM HEIGHT SHALL BE REACHED TO 44 INCHES FOR A FORWARD APPROACH OR 46 INCHES FOR A SIDE APPROACH.

REFER TO LOW VOLTAGE CONSULTANT'S DRAWINGS FOR VOICE, DATA AND CATV OUTLET LOCATIONS. REFER TO LV CONSULTANT'S DRAWINGS

FOR ANY ADDITIONAL INFORMATION.

CONNECT ALL EXIT SIGNS TO NEAREST UNSWITCHED PORTION OF THE LIGHTING CIRCUIT IN THE AREA.

ELECTRICAL BOXES INSTALLED IN FIRE RATED WALLS SHALL MAINTAIN THE INTEGRITY OF THE RATED WALL.

SUPPORT ALL VERTICAL RACEWAY PER NEC TABLE 300.19(A).

MAKE ELECTRICAL CONNECTIONS TO ELECTRIC WATER COOLERS FROM GFCI PROTECTED OUTLET IN WALL BEHIND COOLER HOUSING. THE

OUTLET AND CORD SHALL NOT BE VISIBLE FROM PUBLIC VIEW.

COORDINATE WITH CUTSHEETS OF ALL EQUIPMENT TO BE INSTALLED AND PROVIDE ADDITIONAL CIRCUITS FOR CONTROLS IF REQUIRED BY

MANUFACTURER.

FINAL COLOR, FINISH AND OTHER AESTHETIC PORTIONS OF ALL DEVICES SHALL BE COORDINATED WITH ARCHITECT OR OWNER'S REPRESENTATIVE. THIS SET OF DRAWINGS DOES NOT SUPERCEDE ARCHITECTURAL OR INTERIOR DOCUMENTS.

ALL EXPOSED HORIZONTAL RUNS OF CONDUITS SHALL BE EITHER PARALLEL OR PERPENDICULAR TO EXTERIOR WALLS.

PROVIDE PLENUM RATED CABLES IF THE CABLES ARE EXPOSED AND ROUTED THROUGH PLENUM.

FOR ALL FUSES 1,200A OR HIGHER, PROVIDE ARC ENERGY REDUCTION PER NEC 240.67.

WHERE HIGHEST TRIP SETTING IN INSTALLED OVERCURRENT DEVICE IS 1,200A OR HIGHER, CONTRACTOR TO PROVIDE DOCUMENTATION OF CIRCUIT BREAKER(S) LOCATION AND PROVIDE AT LEAST ONE METHOD TO REDUCE CLEARING TIME VIA ENERGY-REDUCING MAINTENANCE SWITCH, INSTANTANEOUS TRIP SETTING, OR OTHER APPROVED METHOD AS LISTED PER NEC 240.87(B).

FIRE ALARM ANNUNCIATOR

PANEL

GROUND FAULT CIRCUIT

INTERRUPTER

GROUND

CABLE TV TERMINAL

BACKBOARD

6" ABOVE COUNTER SPACE OR

42" AFF

HOME RUN WITH WIRE TICKS. XX - PANEL

DESIGNATION, # - CIRCUIT DESIGNATION. WIRE

TICKS - (1) NEUTRAL , (3) HOT & (1) GROUND

FIRE ALARM NOTIFICATION DEVICE. AUDIO AND

VISUAL.

ELECTRICAL PANELBOARD. REFER TO

PANELBOARD SCHEDULE.

FUSED DISCONNECT SWITCH. SUBSCRIPT: AMP / #

OF POLES / ENCLOSURE / FUSE

DISCONNECT SWITCH. SUBSCRIPT: AMP / # OF

POLES / ENCLOSURE

TELEPHONE OUTLET. SUBSCRIPT: F - FIREMAN'S

PHONE, H - HOUSE PHONE, P - PAY PHONE

SWITCH - WALL MTD, INTEGRAL OCCUPANCY

SENSOR

JUNCTION BOX FLUSH IN FINSHED FLOOR WITH

COVER. SIZE PER NEC.

JUNCTION BOX FLUSH IN CEILING WITH COVER.

SIZE PER NEC.

JUNCTION BOX FLUSH IN WALL WITH COVER. SIZE

PER NEC.

SPECIAL RECEPTACLE, CONFIGURATION AND

ELECTRICAL CHARACTERISTIC AS NOTED ON DWG

QUADRAPLEX RECEPTACLE, 120V, 20A, NEMA

5-20R

QUADRAPLEX RECEPTACLE, 120V, 20A, NEMA

5-20R

42" AFF OR 6" ABOVE

COUNTER TOP

42" AFF OR 6" ABOVE

COUNTER TOP

FLUSH WITH FINISHED

FLOOR

FLUSH WITH FINISHED

FLOOR

42" AFF OR 6" ABOVE

COUNTER TOP

FLUSH WITH FINISHED

FLOOR

42" AFF OR 6" ABOVE

COUNTER TOP

42" AFF OR 6" ABOVE

COUNTER TOP

AS INDICATED ON

DWG

AS INDICATED ON

DWG

SURFACE MOUNTED

ON WALL

SURFACE MOUNTED

ON WALL

TYPICAL MOUNTING HEIGHT

UNLESS NOTED OTHERWISE

SURGE PROTECTIVE DEVICE

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text G

AutoCAD SHX Text A

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text K

AutoCAD SHX Text I

AutoCAD SHX Text No. PE032227

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text lie nt R ev ie w D ra w in gs F or

W

IN

TE

R V

IL

LE

B

LA

C

KS

M

IT

H S

H O

P W in te rv ill e

G A

Brandied History, LLC

485 Oakland Ave, SE Atlanta, GA 30312

1601 Mansfield St Brunswick, GA 31520

(404) 723-7240

6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092

404.330.9798

PROJECT # 124311

E0.02

SPECIFICATIONS

SPECIFICATIONS SPECIFICATIONS

GENERAL

CONTRACTOR SHALL REFER TO ALL RELATED DOCUMENTS, ARCHITECTURAL, STRUCTURAL, CIVIL AND MEP DRAWINGS, AND FULLY UNDERSTAND

THE SCOPE OF WORK AND CONDITION OF CONSTRUCTION.

THE WORK UNDER THIS SPECIFICATIONS AND DRAWINGS SHALL INCLUDE ALL LABOR.

ALL INSTALLATION OF DEVICES AND CONNECTION OF CONDUCTORS SHALL BE PERFORMED BY LICENSED AND SKILLED ELECTRICIAN OR

JOURNEYMAN.

ALL WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE OWNER. IF ANY PORTION OF THE WORK IS FOUND UNSATISFACTORY BY THE OWNER, IT SHALL BE REMOVED AND REINSTALLED WITHOUT DELAY AT NO COST TO THE OWNER.

THE WORK INCLUDES, BUT NOT LIMITED TO:

THE COMPLETE ELECTRICAL DISTRIBUTION SYSTEM.

ROUGH-IN AND FINAL CONNECTIONS TO ALL DEVICES REQUIRING ELECTRICAL POWER, INCLUDING OWNER PROVIDED EQUIPMENT.

LIGHTING CONTROL

LIGHTING FIXTURES

EACH CONTRACTOR SHALL OBTAIN ALL PERMITS AND INSPECTIONS REQUIRED BY THE REGULATORY AUTHORITIES. ALL FEES RELATED TO OBTAINING PERMITS AND INSPECTION SHALL BE PAID FOR BY EACH CONTRACTOR IN HIS TRADE.

ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH LOCAL, COUNTY, STATE, AND NATIONAL ELECTRICAL CODE 2020, SPECIFICATIONS, UTILITY COMPANY REQUIREMENTS AND ALL INDUSTRY STANDARDS.

ANY DIFFERENCES IN ABOVE MENTIONED REQUIREMENTS, THE MOST STERN SHALL OVERRULE ALL OTHERS.

IN ADDITION TO ABOVE MENTIONED CODES AND SPECIFICATIONS, THE FOLLOWING INDUSTRY STANDARDS SHALL BE COMPLIED IF THEY ARE

MORE STRINGENT.

IEEE

IES

IECC 2015

ASHRAE 90.1

NFPA

NEMA

UL

ADA

THE MANUFACTURER'S PUBLISHED DIRECTIONS SHALL BE FOLLOWED IN THE DELIVERY, STORAGE, PROTECTION, INSTALLATION AND WIRING OF

ALL EQUIPMENT AND MATERIAL.

THE DRAWINGS SHOW DIAGRAMMATICALLY THE LOCATIONS OF THE VARIOUS LINES, CONDUITS, FIXTURES, AND EQUIPMENT AND THE METHOD OF CONNECTING AND CONTROLLING THEM. IT IS NOT INTENDED TO SHOW EVERY CONNECTION IN DETAIL AND ALL FITTINGS REQUIRED FOR A COMPLETE SYSTEM. THE SYSTEMS SHALL INCLUDE BUT ARE NOT LIMITED TO THE ITEMS SHOWN ON THE DRAWINGS. EXACT LOCATIONS OF THESE ITEMS SHALL BE DETERMINED BY REFERENCE TO THE GENERAL PLANS AND MEASUREMENTS AT THE BUILDING AND IN COOPERATION WITH THE OTHER SUBCONTRACTORS, AND IN ALL CASES, SHALL BE SUBJECT TO THE APPROVAL OF THE OWNER. THE OWNER RESERVES THE RIGHT TO MAKE ANY REASONABLE CHANGE IN THE LOCATION OF ANY PART OF THIS WORK WITHOUT ADDITIONAL COST TO THE OWNER.

CONTRACTOR SHALL SEEK APPROVAL FROM THE OWNER FOR ANY CHANGES TO THE SPECIFICATIONS OR CONTRACT DOCUMENTS.

ANY EXCEPTIONS, INCONSISTENCIES AND CONFLICTS IN CONTRACT DOCUMENTS, SPECIFICATIONS AND CONTRACT DOCUMENTS BY OTHER

TRADE SHALL BE BROUGHT TO ATTENTION TO THE OWNER PRIOR TO BID.

CONTRACTOR SHALL COORDINATE AND VERIFY THE WORK WITH EXISTING CONDITIONS AND THE WORK OF OTHER TRADE PRIOR TO ANY FABRICATIONS OR INSTALLATION. IF THE LAYOUT OF THE DEVICES ON DRAWINGS ARE IMPRACTICAL TO THE CONDITION IN FIELD, CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY PRIOR TO ANY FABRICATION OR INSTALLATION.

ELECTRICAL DEVICES ARE INDICATED ON DRAWINGS AT APPROXIMATE LOCATIONS. THE OWNER RESERVE THE RIGHT TO MAKE REASONABLE

CHANGES IN LOCATIONS WITHOUT ADDITIONAL COSTS.

THE LINES INDICATING BRANCH CIRCUITS DO NOT REPRESENT THE ROUTING OF ELECTRICAL CONDUITS. THEY INDICATE THE LAYOUT AND

CONTROL OF CIRCUITS.

PRODUCTS AND WORK

MATERIALS FURNISHED SHALL BE NEW AND BY STANDARD MANUFACTURERS AND MUST CONFORM TO THE NATIONAL BOARD OF FIRE UNDERWRITER'S REQUIREMENTS AND BEAR THE UNDERWRITER'S LABORATORIES' SEAL OF APPROVAL.

LISTED MANUFACTURERS, MODELS, OR CATALOGUE NUMBERS IN PART OR ALL SHALL ENTAIL TO INCLUDE THE PUBLISHED MANUFACTURER'S

DESCRIPTION AND SPECIFICATION.

CONTRACTOR SHALL NOT INTERPRET THAT THE LISTED MANUFACTURERS IN SPECIFICATIONS OR DRAWINGS TO EXCLUDE ALL OTHER

MANUFACTURERS.

CONTRACTOR SHALL MAKE CERTAIN THAT ALL EQUIPMENT FIT IN THE SPACE DESIGNATED AND DESIGNED FOR THE SURROUNDINGS IT

OCCUPIES.

COMPLETE CATALOGUE ILLUSTRATION AND DESCRIPTIONS OF ALL EQUIPMENT SHALL BE SUBMITTED TO THE OWNER PRIOR TO ORDERING ANY

EQUIPMENT.

ALL HORIZONTAL RUNS OF CONDUITS SHALL BE SUPPORTED BY MEANS OF APPROVED HANGER FROM THE STRUCTURAL CEILING.

COORDINATE THE WORK UNDER THIS SECTION WITH ALL OTHER TRADES.

CONDUITS AND RACEWAYS:

MANUFACTURERS: SQUARE D, B-LINE, ALLIED TUBE & CONDUIT, HOFFMAN, CARLON ELECTRICAL, WIREMOLD.

OUTDOORS EXPOSED: RIGID STEEL.

OUTDOORS CONCEALED ABOVE GROUND: RIGID STEEL.

OUTDOORS UNDERGROUND: TYPE EPC-40-PVC

OUTDOORS CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND MOTOR DRIVEN EQUIPMENT): LFMC.

BOXES AND ENCLOSURES ABOVE GROUND: NEMA 3R UNLESS NOTED OTHERWISE ON PLANS.

INDOORS EXPOSED NOT SUBJECT TO PHYSICAL DAMAGE: EMT. INDOORS EXPOSED NOT SUBJECT TO SEVERE PHYSICAL DAMAGE: EMT.

INDOORS EXPOSED SUBJECT TO SEVERE PHYSICAL DAMAGE: RIGID STEEL CONDUIT. INDOORS CONCEALED IN CEILINGS AND INTERIOR WALLS

AND PARTITIONS: EMT.

INDOORS CONNECTION TO VIBRATING EQUIPMENT: FMC, EXCEPT USE LFMC IN DAMP OR WET LOCATIONS.

INDOORS DAMP OR WET LOCATIONS: IMC.

INDOORS LOW-VOLTAGE CABLES: EMT.

CONDUCTORS:

COPPER CONDUCTORS #10 AND SMALLER: LABELED PER UL 83, TYPE THHN/THWN, SOLID COPPER 600 VOLT INSULATION, UNIFORM COLOR CODED JACKET WITH JACKET DATA. METAL CLAD (TYPE MC) CABLE WHERE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 330.

COPPER CONDUCTORS #8 OR LARGER: LABELED PER UL 83, TYPE THHN/THWN, STRANDED COPPER, 600VOLT INSULATION, UNIFORM COLOR

CODED JACKET WITH JACKET DATA.

ACCEPTABLE MANUFACTURERS OF CONDUCTORS:

PIRELLI, SOUTHWIRE, AETNA, REPUBLIC, AFC, ENCORE WIRE, KERITE

CONTRACTOR MAY USE ALUMINUM CONDUCTORS FOR #4 AWG OR LARGER IN THE PLACE OF COPPER CONDUCTORS. CONTRACTOR SHALL REFER TO NEC TABLE 310-16 FOR EQUIVALENT AMPACITY AND SHALL COMPENSATE FOR VOLTAGE DROP.

CONTRACTOR SHALL MAKE ADEQUATE ADJUSTMENT TO CONDUIT SIZES INDICATED SHOULD ALTERNATIVE CONDUCTOR INSULATION OR

MATERIAL BE UTILIZED.

MOLDED CASE CIRCUIT BREAKER:

INCLUDE SCHEDULE OF ALL FUSES, RATINGS, TIME COORDINATION DATA, MANUFACTURER'S STANDARD DATA AND TIME-CURRENT CURVES. ALL

DATA SHALL BE BASED ON TEST OF STANDARD PRODUCTS.

APPROVED MANUFACTURERS:

GENERAL ELECTRIC

CUTLER HAMMER

SQUARE D

SIEMENS

THERMAL-MAGNETIC BOLT-IN TYPE CIRCUIT BREAKERS WITH QUICK-MAKE, QUICK-BREAK CONTACTS; TRIP-FREE OPERATION WITH

OVER-THE-CENTER TOGGLE HANDLE OR NON-REMOVABLE MONOLITHIC TIE-HANDLE.

MULTI-POLE BREAKERS SHALL HAVE INTERNAL COMMON TRIP AND COMMON RESET WITH A SINGLE TOGGLE HANDLE OR NON-REMOVABLE

MONOLITHIC TIE-HANDLE.

TRIP RATINGS SHALL BE MOLDED ON THE HANDLE OR FACE OF BREAKER.

BREAKER TERMINALS SHALL BE RATED TO ACCOMMODATE A MINIMUM OF 75 DEGREE C. CONDUCTORS.

BREAKER SHALL BE RATED FOR MOUNTING AND OPERATION IN ANY POSITION; SHALL ACCOMMODATE AND MATCH THE TYPE OF TERMINATIONS

REQUIRED.

SINGLE POLE BREAKERS RATED 15 AND 20 AMPERES SHALL BE UL LABELED AS "SWITCHING BREAKERS" AT THE APPLIED CIRCUIT VOLTAGE.

MULTI-POLE BREAKERS RATED 100 AMPERES AND LARGER SHALL BE MOLDED CASE THERMAL-MAGNETIC BOLT-IN TYPE BREAKER WITH

ADJUSTABLE INSTANTANEOUS TRIP.

OVERCURRENT DEVICES RATED 1,000 AMPERES AND LARGER, SERVING LOADS GREATER THAN 150 VOLTS TO GROUND SHALL BE EQUIPPED WITH GROUND FAULT PROTECTION OF EQUIPMENT (GFPE) AS REQUIRED BY NEC ARTICLES 210.13 AND 230.95.

LIGHTING FIXTURE

SUBMITTAL:

SCHEDULE BY TYPE DESIGNATION ALL LIGHTING FIXTURES, EACH COMPLETE WITH DATA SHEET WITH COMPLETE PHYSICAL, ELECTRICAL AND

LIGHTING CHARACTERISTICS, LAMP TYPE AND LAMP DATA.

REFER TO THE "LIGHTING FIXTURE SCHEDULE" \IN THE DRAWINGS FOR INDIVIDUAL FIXTURE DESCRIPTIONS AND MANUFACTURER TYPES.

PROVIDE LAMPS FOR EACH FIXTURE OF QUANTITY, TYPE AND COLOR AS LISTED IN LIGHTING FIXTURE SCHEDULE. GE, SYLVANIA OR PHILIPS ARE

ACCEPTABLE.

EACH LIGHTING FIXTURE SHALL BE UL LABELED FOR PROPER OPERATION IN THE TYPE OF CEILING CONSTRUCTION AND FOR THE MOUNTING

ARRANGEMENT ON/IN WHICH IT IS INSTALLED.

FIELD VERIFY ACTUAL CEILING SLOPE FOR FIXTURES INSTALLED IN SAME AND ACTUAL FIELD DIMENSIONS AND ANGLES OF CONSTRUCTION FOR ANY FIXTURE CONFORMING THE SHAPE AND LENGTH OF SAME, FOR COORDINATION OF FIXTURE CONSTRUCTION.

PANELBOARD

SUBMITTAL:

INCLUDE SCHEDULE OF EACH PANELBOARD WITH ALL DEVICES AND COMPLETE WITH PHYSICAL AND ELECTRICAL DATA AND WITH RATINGS FOR EACH

COMPONENT INCLUDING BREAKER/FUSE OVERLAY CURVES.

LABELED PER UL #67 AND #50, CONFORM WITH NEMA #250 AND PB1, NFPA #70-384 AND 70-373.

ALL JUNCTION BOXES SHALL BE LABELED WITH PANEL AND CIRCUIT DESIGNATION.

PROVIDE TYPED CIRCUIT DIRECTORY WITH EACH CIRCUIT SERVING DEVICES AND AREA IT'S SERVING.

APPROVED MANUFACTURERS:

GENERAL ELECTRIC

CUTLER HAMMER

SQUARE D

SIEMENS

LIGHTING CONTROL

TIME SWITCHES:

SOLID STATE, PROGRAMMABLE, WITH ALPHANUMERIC DISPLAY; COMPLYING WITH UL 917. 20-A BALLAST LOAD, 120/240VAC.

TWO ON-OFF SET POINTS ON A 24-HOUR SCHEDULE AND ANNUAL HOLIDAY SCHDULE THAT OVERRIDES THE WEEKLY OPERATION ON HOLIDAYS.

ALLOW CONNECTION OF A PHOTOELECTRIC RELAY AS SUBSTITUTE FOR ON-OFF FUNCTION OF A PROGRAM.

BATTERY BACKUP FOR NOT LESS THAN SEVEN DAYS RESERVE TO MAINTAIN SCHEDULES AND TIME CLOCK.

INDOOR OCCUPANCY SENSORS:

WALL OR CEILING MOUNTED SOLID-STATE INDOOR OCCUPANCY SENSORS WITH A SEPARATE POWER PACK.

ADJUSTABLE TIME-DELAY OVER A RANGE OF 1 TO 30 MINUTES.

SENSOR OUTPUT: CONTACTS RATED TO OPERATE THE CONNECTED RELAY, COMPLYING WITH UL773A. SENSOR IS POWERED FROM POWER

PACK.

POWER PACK: DRY CONTACTS RATED FOR 20-A BALLAST LOAD AT 120 OR 277 VAC. AUTOMATIC LIGHT-LEVEL SENSOR: ADJUSTABLE FROM 2 TO 200 FC (21.5 TO 2152 LUX); TURN LIGHTS OFF WHEN SELECTED LIGHTING LEVEL IS PRESENT.

DUAL SENSOR TYPE: DETECT OCCUPANCY AREA USING PIR (PASSIVE INFRA-RED) AND ULTRASONIC DETECTION METHOD.

GROUNDING AND BONDING

ALL GROUNDING AND BONDING SHALL CONFORM TO NEC ARTICLE 250.

COPPER WIRE OR CABLE INSULATED FOR 600V UNLESS REQUIRED BY APPLICABLE CODE OR AUTHORITIES HAVING JURISDICTION.

INSTALL SOLID CONDUCTOR FOR #8 AWG AND SMALLER AND STRANDED CONDUCTORS FOR #6 OR LARGER.

INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS FOR ALL EQUIPMENT.

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text G

AutoCAD SHX Text A

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text K

AutoCAD SHX Text I

No. PE032227

PANEL A

240/120V 2P 3W

BUS: 225A

AIC: 10,000

2"C, 2#3/0, #3/0N, #6G

DISC A

240/120V 2P 3W

200A

AIC: 10,000

1-1/2"C, 2#3/0, #3/0N

BUS: 200A

NEMA 3R

UTILITY

METAL WATER

SERVICE

BUILDING STEEL

ROD ELECTRODE

ENCASED IN

BUILDING FOOTING

AS PER 250.52(A)(5)

SERVICE DISCONNECT

EQUIPMENT

SERVICE

ENTRANCE

CONDUIT

JUMPER

GROUNDING

CLAMP

MATCH

ONE-LINE

GROUND ( )

WIRE SIZE

GROUNDING AND BONDING DETAIL

INTERSYSTEM

BONDING

TERMINATION

#4 CU

TO TELEPHONE

TERMINAL BOARD

TO CATV

#6 CU

MATCH ONE-LINE

GROUND ( ) WIRE SIZE

MAIN BONDING JUMPER

SIZE ACCORDING TO NEC

TABLE 250.102(C)(1)

3/4" x 10'

GROUND

ROD (MIN.

6' APART)

#2

CIRCUIT DESCRIPTION

LOAD

KVABKR

CKT

CKT

KVA CIRCUIT DESCRIPTIONBKR#

LOADCKT CKT

NOTE

NEUTRAL

BUS AMPS

VOLTSPanel AIC

MAIN BKR

LUGSFED FROM

MOUNTING

ROOM

STANDARD

MLO

10,000

240/120V 2P 3W

SURFACEA DISC A 100%

a 21 20/1 60/20.8 10.0 b 43 20/1 |1.1 a 65 20/1 30/20.7 4.9 b 87 20/1 |0.9 a 109 20/1 20/10.3 0.0 b 1211 20/1 20/10.3 0.0 a 1413 20/1 20/10.5 0.0 b 1615 20/1 20/10.5 0.0 a 1817 20/1 20/10.5 0.0 b 2019 20/1 20/10.2 0.0 a 2221 20/1 20/10.0 0.0 b 2423 20/1 20/10.0 0.0 a 2625 20/1 20/10.0 0.0 b 2827 20/1 20/10.0 0.0 a 3029 20/1 20/10.0 0.0 b 3231 20/1 20/10.0 0.0 a 3433 20/1 20/10.0 0.0 b 3635 20/1 20/10.0 0.0 a 3837 20/1 20/10.0 0.0 b 4039 20/1 20/10.0 0.0 a 4241 20/1 20/10.0 0.0

CONN

KVA

CONN

KVA

CALC

KVA

CALC

KVA

LIGHTING 0.7 0.9 (125%)

LARGEST MOTOR 0.1 0.0 (25%)

MOTORS 0.1 0.1 (100%)

RECEPTACLES 4.9 4.9 (50%>10)

CONTINUOUS 14.9 18.6 (125%)

TOTAL LOAD 24.5

BALANCED LOAD 102.2

A

PHASE A 99.4%

PHASE B 101%

EF-A, LIGHTING

RECEPTACLE

RECEPTACLE

FREEZER

REF

REF

DISPLAY

DISPLAY

DISPLAY

RECEPTACLE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

WH-1

MFCU-1, MHP-1

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

GENERAL SCHEDULE

CALLOUT SYMBOL VOLTS KVA BREAKER CIRCUIT WIRE CALLOUT DISCONNECT

DESCRIPTION

EF-A 120V 1P 2W 0.1 20/1 A-1 1/2"C,1#12,#12N,#12G

MFCU-1 240/120V 2P 3W 0.1 30/2 A-6,8 1/2"C,2#10,#10N,#10G FED FROM MHP-1

MHP-1 240/120V 2P 3W 4.8 30/2 A-6,8 1/2"C,2#10,#10N,#10G 30A/2P/NEMA 3R

WH-1 240/120V 2P 3W 10 60/2 A-2,4 3/4"C,2#6,#6N,#10G 60A/2P/NEMA 1

July 31, 2024

C lie nt R ev ie w D ra w in gs F or

W

IN

TE

R V

IL

LE

B

LA

C

KS

M

IT

H S

H O

P W in te rv ill e

G A

Brandied History, LLC

485 Oakland Ave, SE Atlanta, GA 30312

1601 Mansfield St Brunswick, GA 31520

(404) 723-7240

6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092

404.330.9798

PROJECT # 124311

E0.03

SCHEDULES

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text G

AutoCAD SHX Text A

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text K

AutoCAD SHX Text I

LUMINAIRE SCHEDULE

CALLOUT SYMBOL LAMP DESCRIPTION MODEL VOLTS

D (1) 10.4W LED 6" LED RECESSED DIRECTIONAL WALLWASH LITHONIA

LDN6-35/10-LW6-MVOLT-EZ10

PROVIDE SLOPE TRIM

120V 1P 2W

F (1) 120W LED DECORATIVE SEMI-FLUSH CEILING LIGHT BARTLETT 14" SEMI-FLUSH

CEILING LIGHT

120V 1P 2W

P (1) 100W LED DECORATIVE PENDANT BARTLETT 9 1/4" MINI

PENDANT

120V 1P 2W

P1 (1) 100W LED DECORATIVE PENDANT BARTLETT 16 1/2" MINI

PENDANT

120V 1P 2W

S (1) 10.4W LED EXTERIOR SCONCE WITH BATTERY BACKUP TBD 120V 1P 2W

T (2) 1.4W LED EMERGENCY LIGHTING UNIT LITHONIA ELM2L-LED 120V 1P 2W

XC (2) 1.5W LED COMBINATION EXIT/EMERGENCY LIGHTING UNIT LITHONIA LHQM-LED-R-HO 120V 1P 2W

July 31, 2024

C lie nt R ev ie w D ra w in gs F or

W

IN

TE

R V

IL

LE

B

LA

C

KS

M

IT

H S

H O

P W in te rv ill e

G A

Brandied History, LLC

485 Oakland Ave, SE Atlanta, GA 30312

1601 Mansfield St Brunswick, GA 31520

(404) 723-7240

6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092

404.330.9798

PROJECT # 124311

E0.04

COMCHECK

RON KIGHT - EE 07-31-2024

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text G

AutoCAD SHX Text A

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text K

AutoCAD SHX Text I

GF

GF

GF

GF

WP

GF

GF

D

D

D

D

D

D

P P P

P1

F

F

XC

XC

S

S

S

T

A

DISC A

T

UTILITY

WH-1

EF-A

MHP-1

MFCU-1

WP

GF

REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATIONS OF ALL CEILING

MOUNTED DEVICES.

ALL RECEPTACLES SHALL BE GROUNDED AS REQUIRED BY ARTICLE 250-146.

FOR ALL KITCHEN EQUIPMENT, SEE EQUIPMENT SCHEDULE FOR ELECTRICAL CONNECTION

INFORMATION AND OTHER GENERAL INFORMATION. KITCHEN APPLIANCE CONNECTION

LOCATION TO BE COORDINATED WITH THE ACTUAL EQUIPMENT INSTALLED. REFER TO

ARCHITECTURAL DOCUMENTS FOR MOUNTING HEIGHT AND DIMENSIONS. COORDINATE EXACT

ELECTRICAL REQUIREMENTS WITH KITCHEN EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.

ALL SINGLE-PHASE RECEPTACLES RATED 150V TO GROUND OR LESS, 50A OR LESS AND

THREE-PHASE RECEPTACLES RATED 150V TO GROUND OR LESS, 100A OR LESS IN BAR,

KITCHEN, AND FOOD PREP AREAS SHALL BE GFI PER NEC 210.8(B). GFCI MUST BE READILY

ACCESSIBLE FOR TESTING. FOR RECEPTACLES OBSTRUCTED FROM ACCESSIBILITY BY

EQUIPMENT, ACCEPTABLE ALTERNATIVES TO A GFCI RECEPTACLE ARE REMOTE TEST BUTTONS,

GFCI BREAKERS, OR GFCI RECEPTACLES UPSTREAM ON THE SAME CIRCUIT.

COORDINATE FINAL RECEPTACLE PLACEMENTS AND MOUNTING HEIGHTS WITH

OWNER/ARCHITECT.

POWER NOTES

REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATIONS OF ALL CEILING

MOUNTED DEVICES.

PROVIDE UNSWITCHED HOT LEG OF CIRCUIT TO EMERGENCY LIGHTING AND EXIT SIGNS.

EXTERIOR LIGHTING SHALL BE CONTROLLED VIA TIME CLOCK AND PHOTOCELL.

LIGHTING NOTES

A-1

A-3

A-5 A-7

A-13 A-15 A-17

A-9

A-11

July 31, 2024

C lie nt R ev ie w D ra w in gs F or

W

IN

TE

R V

IL

LE

B

LA

C

KS

M

IT

H S

H O

P W in te rv ill e

G A

Brandied History, LLC

485 Oakland Ave, SE Atlanta, GA 30312

1601 Mansfield St Brunswick, GA 31520

(404) 723-7240

6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092

404.330.9798

PROJECT # 124311

E2.01

1/4" = 1'-0"

POWER PLAN

E2.01

FLOOR PLAN

E2.01

1/4" = 1'-0"

LIGHTING PLAN

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text G

AutoCAD SHX Text A

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text G

AutoCAD SHX Text K

AutoCAD SHX Text I lie nt R ev ie w D ra w in gs F or

W

IN

TE

R V

IL

LE

B

LA

C

KS

M

IT

H S

H O

P W in te rv ill e

G A

Brandied History, LLC

485 Oakland Ave, SE Atlanta, GA 30312

1601 Mansfield St Brunswick, GA 31520

(404) 723-7240

6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092

404.330.9798

PROJECT # 124311

M0.01

GENERAL &

DETAILS

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

CO2 CARBON DIOXIDE

D CONDENSATE DRAIN

DB DRY BULB

EA EXHAUST AIR

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

ESP EXTERNAL STATIC PRESSURE

EWH ELECTRIC WALL HEATER

F DEGREES FAHRENHEIT

FCU FAN COIL UNIT

FD FIRE DAMPER

FSD COMBINATION FIRE/SMOKE DAMPER

H HUMIDISTAT

IH INTAKE HOOD

LAT LEAVING AIR TEMPERATURE

LWT LEAVING WATER TEMPERATURE

MA MAKE-UP AIR

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MBH 1,000 BTU PER HR

MVD MANUAL VOLUME DAMPER

NC NORMALLY CLOSED

NO NORMALLY OPEN

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

PIU POWER INDUCTION UNIT

RA RETURN AIR

RH RELIEF HOOD

RTU ROOFTOP UNIT

SA SUPPLY AIR

SP STATIC PRESSURE

UC UNDER CUT DOOR

VAV VARIABLE AIR VOLUME

WB WET BULB

ABBREVIATIONS

EAT ENTERING AIR TEMPERATURE

M MOTOR

MFCU MINI FAN COIL UNIT

MHP MINI HEAT PUMP

WL WALL LOUVER

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

CO2 CARBON DIOXIDE

D CONDENSATE DRAIN

DB DRY BULB

EA EXHAUST AIR

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

ESP EXTERNAL STATIC PRESSURE

EWH ELECTRIC WALL HEATER

F DEGREES FAHRENHEIT

FCU FAN COIL UNIT

FD FIRE DAMPER

FSD COMBINATION FIRE/SMOKE DAMPER

H HUMIDISTAT

IH INTAKE HOOD

LAT LEAVING AIR TEMPERATURE

LWT LEAVING WATER TEMPERATURE

MA MAKE-UP AIR

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MBH 1,000 BTU PER HR

MVD MANUAL VOLUME DAMPER

NC NORMALLY CLOSED

NO NORMALLY OPEN

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

PIU POWER INDUCTION UNIT

RA RETURN AIR

RH RELIEF HOOD

RTU ROOFTOP UNIT

SA SUPPLY AIR

SP STATIC PRESSURE

UC UNDER CUT DOOR

VAV VARIABLE AIR VOLUME

WB WET BULB

ABBREVIATIONS

EAT ENTERING AIR TEMPERATURE

M MOTOR

MFCU MINI FAN COIL UNIT

MHP MINI HEAT PUMP

WL WALL LOUVER

BDD BACKDRAFT DAMPER

DH DEHUMIDIFIERDH DEHUMIDIFIER

U.N.O UNLESS NOTED OTHERWISEU.N.O UNLESS NOTED OTHERWISE

CU CONDENSING UNITCU CONDENSING UNIT

FURN FURNACEFURN FURNACE

LEGEND

SYMBOLS DESCRIPTION

X1 X2

DIFFUSER, GRILLE, REGISTER OR LOUVER TAG

X1 = TYPE, X2 = CFM

POSITIVE PRESSURE (AIR GOES OUT) DIFFUSER OR REGISTER, 4-WAY

AIR PATTERN (UNLESS OTHERWISE NOTED)

NEGATIVE PRESSURE (AIR GOES IN) GRILLE

POSITIVE PRESSURE AIRFLOW (TYP. SUPPLY)

NEGATIVE PRESSURE AIRFLOW (TYP. RETURN/EXHAUST)

FLEXIBLE DUCT

MANUAL VOLUME DAMPER (MVD)

FD

VERTICAL (TYP. WALL) FIRE DAMPER

FSD

VERTICAL (TYP. WALL) COMBINATION FIRE/SMOKE DAMPER

FD

HORIZONTAL (TYP. FLOOR/CEILING) FIRE DAMPER

FSD

HORIZONTAL (TYP. FLOOR/CEILING) COMBINATION FIRE/SMOKE

DAMPER

THERMOSTATT

INTERNALLY LINED DUCT

DUCT UP

DUCT UP

DUCT DOWN

SUPPLY DUCT

REMOTE TEMPERATURE SENSORS

HUMIDISTATH

EQUIPMENT TYPE

UNIT

EQUIPMENT NUMBER. WHERE A LETTER IS USED, THERE ARE MULTIPLE

INSTANCES.

BACKDRAFT DAMPER (BDD)

SPECIFICATIONS SPECIFICATIONS

APPLICABLE CODES:

INTERNATIONAL FIRE CODE (IFC), 2018 EDITION

2020 IFC GA AMENDMENTS

INTERNATIONAL PLUMBING CODE (IPC), 2018 EDITION

2020, 2022 & 2023 IPC GA AMENDMENTS

INTERNATIONAL MECHANICAL CODE (IMC), 2018 EDITION

2020 IMC GA AMENDMENTS

INTERNATIONAL FUEL GAS CODE (IFGC), 2018 EDITION

2020 & 2022 IFGC GA AMENDMENTS

INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2015 EDITION

2020, 2022 & 2023 SUPPLEMENTS AND AMENDMENTS

GENERAL NOTES:

REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CEILING

MOUNTED EQUIPMENT.

ALL DUCT DIMENSIONS INDICATED IN THESE DOCUMENTS ARE INSIDE-CLEAR DIMENSIONS.

PORTIONS OF DUCTWORK OR PIPING VISIBLE THROUGH GRILLES AND REGISTERS IN FINISHED

AREAS SHALL BE PAINTED FLAT BLACK. PAINT BLACK BEHIND ALL GRILLES.

ALL WIRING IN THE CEILING PLENUM SHALL BE PLENUM RATED CABLE.

MOUNTING FRAME OF CEILING MOUNTED AIR DISTRIBUTION DEVICES SHALL BE COMPATIBLE

WITH CEILING TYPE. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPE.

ALL FIRE SEPARATIONS MUST BE PROTECTED WHEN APPLICABLE.

PROVIDE NEW FILTERS (MERV 7 OR BETTER PER OWNER) FOR ALL APPLICABLE HVAC

EQUIPMENT AT THE END OF CONSTRUCTION.

ALL MATERIAL IN PLENUM MUST MEET FIRE AND SMOKE SPREAD AS REQUIRED BY NFPA 90A.

ALL ROOF PENETRATIONS TO BE 12" APART AND AT LEAST 12" AWAY FROM CURBS, WALLS,

AND DRAIN SUMPS TO PROVIDE ROOFING CONTRACTOR WITH SUFFICIENT ACCESS FOR

FLASHING EACH ROOF PENETRATION.

SUBSTITUTIONS MUST BE APPROVED IN WRITING BY ARCHITECT PRIOR TO BID SUBMISSION.

CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS AND SHALL BE FAMILIAR WITH THE

SCOPE AND REQUIREMENTS OF THIS PROJECT. ANY DISCREPANCIES OR LACK OF CLARITY IN

THE DOCUMENTS SHALL BE IDENTIFIED TO THE ARCHITECT OR ENGINEER PRIOR TO THE

SUBMISSION OF PRICING BIDS. WITH A SUBMITTED BID, CONTRACTOR IS ACCEPTING THESE

DOCUMENTS AS SUFFICIENT DEFINITION OF THE SCOPE OF WORK, AND ANY ADDITIONAL

COSTS BASED ON UNCLARITY OF CONTRACT DOCUMENTS WILL NOT BE CONSIDERED.

THE CONTRACTOR SHALL REFERENCE THE FULL SET OF CONSTRUCTION DOCUMENTS DURING

PRICING AND CONSTRUCTION FOR COORDINATION BETWEEN DISCIPLINES RELATIVE TO THE

MECHANICAL SCOPE.

GUARANTEE:

GUARANTEE THAT EACH PIECE OF APPARATUS SHALL BE OF THE CUSTOMARY STANDARD AND

QUALITY FURNISHED BY THE DESIGNED MANUFACTURER FOR THAT CATALOG NUMBER.

GUARANTEE THAT THE AIR SYSTEMS SHALL OPERATE WITHOUT AERODYNAMIC NOISE

GENERATED FROM THE FAULTY INSTALLATION OF DUCT WORK OR ANY COMPONENT OF THE

AIR DISTRIBUTION SYSTEM.

GUARANTEE THAT ALL SYSTEMS AND COMPONENTS SHALL BE PROVIDED WITH A ONE YEAR

WARRANTY FROM THE TIME OF DATE OF SUBSTANTIAL COMPLETION. THE WARRANTY SHALL

COVER ALL MATERIALS AND WORKMANSHIP. DURING THIS WARRANTY PERIOD, ALL DEFECTS IN

MATERIALS AND WORKMANSHIP SHALL BE CORRECTED BY REPAIR OR REPLACEMENT WITHOUT

INCURRING ADDITIONS TO THE CONTRACT.

EXISTING CONDITIONS:

CONTRACTOR SHALL VISIT THE SITE AND UNDERSTAND JOB CONDITIONS BEFORE SUBMITTING

A PROPOSAL. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY LOCATIONS AND

SIZES OF ALL EXISTING UTILITY SERVICES PRIOR TO SUBMITTING HIS PROPOSAL. NO

CONSIDERATION WILL BE GIVEN TO CLAIMS FOR EXTRA COST ARISING FROM CONTRACTOR'S

FAILURE TO BE FULLY COGNIZANT OF JOB OR SITE CONDITIONS EXISTING AT TIME OF

ACCEPTANCE OF BID.

ACTIVE SERVICES: WHEN ENCOUNTERED IN WORK, PROTECT, BRACE, SUPPORT EXISTING

ACTIVE SEWERS, GAS AND OTHER SERVICES REQUIRED FOR PROPER EXECUTION OF WORK. IF

EXISTING ACTIVE SERVICES ARE ENCOUNTERED THAT REQUIRE RELOCATION, RELOCATE AS

APPROVED. DO NOT PREVENT OR DISTURB OPERATION OF ACTIVE SERVICES THAT ARE TO

REMAIN.

INACTIVE SERVICES: WHEN ENCOUNTERED IN WORK, REMOVE, CAP OR PLUG INACTIVE

SERVICES, AS INDICATED.

INTERRUPTION OF SERVICES: WHERE WORK MAKES TEMPORARY SHUT-DOWNS OF SERVICES

UNAVOIDABLE, SHUT DOWN AT NIGHT, OR AT SUCH TIMES AS APPROVED BY OWNER, WHICH

WILL CAUSE LEAST INTERFERENCE WITH ESTABLISHED OPERATING ROUTINE. ARRANGE WORK

TO ASSURE THAT SERVICES WILL BE SHUT DOWN ONLY DURING TIME ACTUALLY REQUIRED TO

MAKE NECESSARY CONNECTION TO EXISTING WORK.

WHERE EXISTING WALLS, CEILINGS, FLOORS, ETC., ARE CUT OR OTHERWISE DAMAGED DURING

CONSTRUCTION, REPAIR ALL SURFACES TO THEIR ORIGINAL CONDITION.

SHOP DRAWINGS:

SUBMIT SHOP DRAWINGS FOR REVIEW. PDF FILES PREFERRED. SHOP DRAWINGS SHALL BE

BOUND INTO VOLUMES (FILES), WITH EACH VOLUME (FILE) CONTAINING ONE COPY OF ALL

SHOP DRAWINGS. ALL SHOP DRAWINGS SHALL BE SUBMITTED SIMULTANEOUSLY; NO SHOP

DRAWINGS WILL BE CHECKED UNTIL ALL HAVE BEEN SUBMITTED.

SUBMITTALS SHALL BE SUPPORTED BY DESCRIPTIVE MATERIAL, SUCH AS CATALOG CUTS,

DIAGRAMS, PERFORMANCE CURVES AND CHARTS PUBLISHED BY THE MANUFACTURER, TO

SHOW CONFORMANCE TO SPECIFICATION AND DRAWING REQUIREMENTS; MODEL NUMBERS

ALONE WILL NOT BE ACCEPTABLE. ALL LITERATURE SHALL CLEARLY INDICATE THE SPECIFIED

MODEL NUMBER, DIMENSIONS, ARRANGEMENT, RATING AND CHARACTERISTICS OF THE

PROPOSED EQUIPMENT. CAPACITIES AND RATINGS SHALL BE BASED ON CONDITIONS

INDICATED OR SPECIFIED HEREIN. ANY DEVIATIONS FROM SPECIFIED EQUIPMENT

(PARTICULARLY THOSE WHICH REQUIRE COORDINATION WITH OTHER TRADES) SHALL BE

CLEARLY NOTED IN A CONCISE LIST ON A SEPARATE SHEET.

TEST AND BALANCE:

TEST AND BALANCE (TAB) CONTRACTOR SHALL HOLD A CURRENT NATIONAL BALANCING

COUNCIL (NBC) CERTIFICATION AND POSSESS ACCURATE AND CALIBRATED INSTRUMENTS.

TAB WORK AND REPORTS SHALL BE PER NBC PRACTICAL STANDARDS, PROCEDURES AND

FORMS. ACCEPTIBLE ALTERNATIVE TAB FIRM CERTIFICATIONS/PROCEDURES: NEBB, AABC, OR

TABB.

PRIOR TO COMMENCEMENT OF THE TAB WORK, THE MECHANICAL SYSTEMS ARE TO BE

STARTED AND FULLY FUNCTIONING. A CHECKLIST PRIOR TAB WORK IS TO BE SENT TO THE

INSTALLING CONTRACTOR AND RETURNED ATTESTING TO THE READINESS OF THE SYSTEMS

FOR BALANCING.

PREFERRED TAB FIRM: P-TAB.COM

CEILING FAN:

CEILING MOUNTED EXHAUST FANS SHALL BE OF THE CENTRIFUGAL DIRECT DRIVE TYPE. THE

FAN HOUSING SHALL BE CONSTRUCTED OF STEEL. THE PLASTIC DUCT COLLAR SHALL BE A

TAPERED SLEEVE FOR EASE OF CONNECTION TO 3 IN AND 4 IN ROUND DUCTWORK AND SHALL

INCLUDE A BACKDRAFT DAMPER. THE GRILLE SHALL BE CONSTRUCTED OF NON-YELLOWING

HIGH STRENGTH POLYMER AND ATTACHED TO THE HOUSING WITH TORSION SPRINGS. THE

WHEELS SHALL BE CONSTRUCTED OF HIGH STRENGTH POLYMER. THE ACCESS FOR WIRING

SHALL BE EXTERNAL. THE MOTOR DISCONNECT SHALL BE INTERNAL AND OF THE PLUG IN TYPE.

ALL FANS SHALL BEAR THE AMCA CERTIFIED RATINGS SEALS FOR SOUND AND AIR

PERFORMANCE AND SHALL BE U.L. LISTED.

DUCTLESS SPLIT SYSTEM

CEILING CASSETTE INDOOR UNIT

STANDARD PREFILTER IS INCLUDED WITH INDOOR UNIT

CHOICE OF FAN SPEEDS: LOW, MEDIUM, HIGH

INDOOR UNIT POWERED FROM OUTDOOR UNIT

AUTO RESTART FOLLOWING A POWER OUTAGE

BASE HEATER

LIMITED WARRANTY: FIVE YEARS ON PARTS AND DEFECTS AND SEVEN YEARS ON THE

COMPRESSOR

SEE SCHEDULE FOR LIST OF ACCEPTABLE MANUFACTURERS.

DIFFUSERS, GRILLES, & REGISTERS:

EGGCRATE GRILLE:

RETURN GRILLES SHALL BE TITUS MODEL 50F FOR THE SIZES AND MOUNTING TYPES AS

SHOWN ON THE PLANS AND OUTLET SCHEDULE. RETURN GRILLES MUST PROVIDE A FREE AREA

OF AT LEAST 90%. OUTER BORDERS SHALL BE CONSTRUCTED OF HEAVY EXTRUDED

ALUMINUM WITH A THICKNESS OF 0.040-0.050 INCH AND SHALL HAVE COUNTERSUNK

SCREW HOLES FOR A NEAT APPEARANCE. BORDER WIDTH SHALL BE 1¼ INCHES ON ALL SIDES

AND SHALL BE INTERLOCKED AT THE FOUR CORNERS AND MECHANICALLY STAKED TO FORM A

RIGID FRAME. CHOICE OF THREE SIZES OF ALUMINUM GRID: ½ X ½ X ½ INCH, ½ X ½ X 1

INCH, OR 1 X 1 X 1 INCH SHALL BE AVAILABLE.

OPTIONAL OPPOSED-BLADE VOLUME DAMPER SHALL BE CONSTRUCTED OF HEAVY GAUGE

STEEL OR ALUMINUM. DAMPER MUST BE OPERABLE FROM THE FACE OF THE GRILLE.

PLAQUE DIFFUSERS:

ARCHITECTURAL SQUARE PANEL CEILING DIFFUSERS SHALL BE OF THE SIZES AND MOUNTING

TYPES SHOWN ON THE PLANS AND OUTLET SCHEDULE. THE FACE PANEL IS REMOVABLE BY

MEANS OF FOUR HANGER BRACKETS. THE EXPOSED SURFACE OF THE FACE PANEL SHALL BE

SMOOTH, FLAT, AND FREE OF VISIBLE FASTENERS.

THE BACK OF THE FACE PANEL SHALL HAVE AN AERODYNAMICALLY SHAPED, ROLLED EDGE TO

ENSURE A TIGHT HORIZONTAL DISCHARGE PATTERN. CEILING DIFFUSERS WITH A 24 X 24-INCH FULL FACE SHALL HAVE NO LESS THAN AN 18 X 18-INCH FACE PANEL SIZE. CEILING DIFFUSERS WITH A 12 X 12-INCH FULL FACE SHALL HAVE NO LESS THAN A 9 X 9-INCH FACE PANEL SIZE.

THE BACKPAN SHALL BE ONE PIECE PRECISION DIE-STAMPED AND SHALL INCLUDE AN

INTEGRALLY DRAWN INLET. THE DIFFUSER NECK SHALL HAVE A MINIMUM OF 1¼-INCH DEPTH

AVAILABLE FOR DUCT CONNECTION.

THE FINISH SHALL BE #26 WHITE. THE FINISH SHALL BE AN ANODIC ACRYLIC PAINT, BAKED AT

315°F FOR 30 MINUTES. THE PENCIL HARDNESS MUST BE HB TO H.

THE PAINT MUST PASS A 100-HOUR ASTM B117 CORROSIVE ENVIRONMENTS SALT SPRAY

TEST WITHOUT CREEPAGE, BLISTERING OR DETERIORATION OF FILM. THE PAINT MUST PASS A

250-HOUR ASTM D870 WATER IMMERSION TEST. THE PAINT MUST ALSO PASS THE ASTM

D2794 REVERSE IMPACT CRACKING TEST WITH A 50-INCH POUND FORCE APPLIED.

OPTIONAL ROUND DAMPER SHALL BE CONSTRUCTED OF HEAVY GAUGE STEEL. DAMPER MUST

BE OPERABLE FROM THE FACE OF THE DIFFUSER. OPTIONAL DIRECTIONAL BLOW CLIPS SHALL

BE AVAILABLE TO RESTRICT THE DISCHARGE AIR IN CERTAIN DIRECTIONS.

OPTIONAL MOLDED INSULATION BLANKET SHALL BE AVAILABLE. THE INSULATION WILL BE R-6, FOIL-BACKED, AND PROVIDE AN ADDITIONAL 1-INCH GAP AROUND THE NECK TO INSTALL

INSULATED FLEX DUCT.

THE MANUFACTURER SHALL PROVIDE PUBLISHED PERFORMANCE DATA FOR THE SQUARE

PANEL DIFFUSER. THE DIFFUSER SHALL BE TESTED IN ACCORDANCE WITH ANSI/ASHRAE

STANDARD 70-1991.

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text G

AutoCAD SHX Text A

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text No. 034608

AutoCAD SHX Text J

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text U

AutoCAD SHX Text C

AutoCAD SHX Text H

AutoCAD SHX Text A lie nt R ev ie w D ra w in gs F or

W

IN

TE

R V

IL

LE

B

LA

C

KS

M

IT

H S

H O

P W in te rv ill e

G A

Brandied History, LLC

485 Oakland Ave, SE Atlanta, GA 30312

1601 Mansfield St Brunswick, GA 31520

(404) 723-7240

6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092

404.330.9798

PROJECT # 124311

M2.01

1/4" = 1'-0"

MECHANICAL FLOOR PLAN

M2.01

MECHANICAL

FLOOR PLAN

NO SCALE

CONDENSATE TRAP (DRAW THROUGH UNIT)

1" PLUS MAXIMUM NEGATIVE

STATIC PRESSURE

X1 =

NOTES

LOCATE TRAPS SO AS TO BE

ACCESSIBLE FOR CLEANING.

1.

HALF OF X1X2 =

X1+X2+PIPE Ø+INSULATIONX3 =

WHERE:

AIR UNIT

CASING

X3FLOW

X2

X1

CLEANOUT CAP, CLOSED DURING

UNIT OPERATION

PIPE FULL SIZE

AIR UNIT DRAIN

CONNECTION,

MINIMUM

OPEN END

PIPE (EXTERIOR)

CAPPED

(INTERIOR)

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text G

AutoCAD SHX Text A

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text No. 034608

AutoCAD SHX Text J

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text U

AutoCAD SHX Text C

AutoCAD SHX Text H

AutoCAD SHX Text A lie nt R ev ie w D ra w in gs F or

W

IN

TE

R V

IL

LE

B

LA

C

KS

M

IT

H S

H O

P W in te rv ill e

G A

Brandied History, LLC

485 Oakland Ave, SE Atlanta, GA 30312

1601 Mansfield St Brunswick, GA 31520

(404) 723-7240

6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092

404.330.9798

PROJECT # 124311

P0.01

GENERAL

GENERAL

ALL WORK SHALL COMPLY WITH ALL STATE, CITY AND LOCAL CODES, RULES AND REGULATIONS. CONTRACTOR SHALL SECURE ALL REQUIRED PERMITS AND INSPECTIONS

ASSOCIATED WITH THIS WORK, AND SHALL PAY ALL COSTS AND FEES INVOLVED.

ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE BEST RECOGNIZED PRACTICE IN THE FIELD CONCERNED. MANUFACTURED ITEMS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S PRINTED DIRECTIONS, SPECIFICATIONS AND RECOMMENDATIONS.

CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS AND SHALL BE FAMILIAR WITH THE SCOPE AND REQUIREMENTS OF THIS PROJECT. ANY DISCREPANCIES OR LACK OF CLARITY IN THE DOCUMENTS SHALL BE IDENTIFIED TO THE ARCHITECT OR ENGINEER PRIOR TO THE SUBMISSION OF PRICING BIDS. WITH A SUBMITTED BID, CONTRACTOR IS ACCEPTING THESE DOCUMENTS AS SUFFICIENT DEFINITION OF THE SCOPE OF WORK, AND ANY ADDITIONAL COSTS BASED ON UNCLARITY OF CONTRACT DOCUMENTS WILL

NOT BE CONSIDERED.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND LOCATIONS FOR EQUIPMENT INSTALLATION PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS. ALL EQUIPMENT AND DEVICES SHALL BE INSTALLED SUCH THAT THEY ARE EASILY ACCESSIBLE AND SERVICABLE. THIS EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO: PLUMBING FIXTURES, WATER HEATERS, EXPANSION TANKS, PUMPS, BACKFLOW PREVENTERS, VALVES, MIXING VALVES, THERMOMETERS, GAUGES, TRAP PRIMERS AND CLEANOUTS.

THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE FULL SET OF CONSTRUCTION DOCUMENTS, INCLUDING ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL & ELECTRICAL DRAWINGS (AS APPLICABLE) TO ENSURE ALL PLUMBING WORK IS COORDINATED WITH PHYSICAL CONDITIONS AND ALL OTHER TRADES.

THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE ARCHITECTURAL DRAWINGS TO ENSURE THERE IS ADEQUATE WALL THICKNESS SUCH THAT ALL PIPING, FIXTURE CARRIERS, WALL CLEANOUTS, WALL BOXES, WALL HYDRANTS AND ACCESS PANELS WILL FIT IN THE WALL SPACE. CONTRACTOR SHALL NOTIFY THE ARCHITECT IF WALL SPACE

IS INADEQUATE PRIOR TO COMMENCING WORK.

THE CONTRACTOR SHALL OBTAIN EXACT WALL, FIXTURE, AND LAYOUT DIMENSIONS FROM THE ARCHITECTURAL DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ROUGH-IN AND INSTALLATION DRAWINGS FOR ALL PLUMBING FIXTURES, KITCHEN EQUIPMENT AND OWNER FURNISHED EQUIPMENT (AS APPLICABLE), AND SHALL COORDINATE THE PLUMBING INSTALLATION PRIOR TO COMMENCING THE WORK. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND INSTALLING ALL NECESSARY VALVES, CONNECTIONS, TRAPS, ACCESS PANELS, UNIONS, ESCUTCHEONS, WATER HAMMER ARRESTORS, VACUUM BREAKERS, RELIEF VALVES, PIPE INSULATION, AND EQUIPMENT SPECIALTY DEVICES AS REQUIRED TO FACILITATE COMPLETE AND OPERATIONAL CONDITIONS WHICH ARE IN STRICT COMPLIANCE WITH THE MANUFACTURER'S

INSTALLATION INSTRUCTIONS.

THESE DRAWINGS ARE DIAGRAMMATIC AND DO NOT REFLECT ALL POSSIBLE PHYSICAL CONDITIONS. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS AND EXACT LOCATIONS OF EQUIPMENT AND FIXTURES. PROVIDE NECESSARY PIPING OFFSETS TO COORDINATE WITH THE BUILDING STRUCTURE, WORK OF OTHER TRADES, AND

CONNECTION TO SITE UTILITIES (AS APPLICABLE).

COORDINATE THE ELECTRICAL REQUIREMENTS AND CHARACTERISTICS OF ALL PLUMBING EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO ISSUING SUBMITTALS OR

PURCHASING EQUIPMENT.

UNLESS NOTED OTHERWISE, ALL DRAINAGE PIPING SHALL BE SLOPED AT A MINIMUM OF 18" PER FOOT. 2" SANITARY PIPING AND ALL GREASE WASTE PIPING SHALL BE SLOPED

AT 14" PER FOOT.

DOMESTIC WATER PIPING SHALL BE PURGED OF DELETERIOUS MATTER AND DISINFECTED PRIOR TO UTILIZATION. PIPING TO BE FLUSHED AND STERILIZED IN ACCORDANCE

WITH IPC 610.1 AND ALL APPLICABLE LOCAL AND STATE HEALTH DEPARTMENT STANDARDS.

ALL DOMESTIC WATER PIPING, SANITARY P-TRAPS AND GREASE WASTE PIPING SUBJECT TO FREEZING SHALL BE INSULATED AND PROVIDED WITH HEAT TRACE. CONDENSATE PIPING SUBJECT TO FREEZING WITHIN WALK-IN FREEZERS SHALL BE INSULATED AND PROVIDED WITH HEAT TRACE. PIPING INSTALLED IN EXTERIOR WALLS SHALL BE WRAPPED IN 1" THICK PIPE INSULATION AND BE LOCATED ON THE INTERIOR SIDE OF THE BUILDING INSULATION. IF INSTALLED IN EXTERIOR BLOCK WALLS, INTERSTITIAL SPACES SHALL BE

FILLED WITH FOAM INSULATION.

IN CONCEALED LOCATIONS WHERE PIPING, OTHER THAN CAST-IRON OR GALVANIZED STEEL, IS INSTALLED THROUGH HOLES OR NOTCHES IN STUDS, JOISTS, OR SIMILAR

MEMBERS LESS THAN 11

2" FROM THE NEAREST EDGE OF MEMBER, PIPE SHALL BE PROTECTED BY STEEL SHIELD PLATES IN ACCORDANCE WITH IPC 305.6.

PIPE PENETRATIONS THROUGH FIRE RATED WALLS OR FLOORS SHALL HAVE EQUIVALENTLY RATED SLEEVES AND SHALL BE SEALED AND FIRE CAULKED WITH A U.L. LISTED FIRE STOPPING SYSTEM INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S LISTED DETAILS AND SPECIFICATIONS.

THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH THE REQUIREMENTS OF THE COUNTY HEALTH DEPARTMENT AND OTHER LOCAL AUTHORITIES HAVING JURISDICTION REGARDING CROSS CONNECTION CONTROL OR OBTAINING A FOOD SERVICE PERMIT (AS APPLICABLE). REPORT ANY OBSERVED DISCREPANCIES TO THE

ARCHITECT OR ENGINEER PRIOR TO COMMENCING WITH THE WORK.

CONTRACTOR SHALL CONFIRM PLUMBING FIXTURE FINISHES WITH THE ARCHITECTURAL SCHEDULES & DETAILS (AS APPLICABLE).

PROFICIENT ENGINEERING WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND THE DESIGN INTENT THEY CONVEY, OR PROBLEMS WHICH ARISE FROM OTHER'S FAILURE TO OBTAIN AND/OR FOLLOW PROFICIENT'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC IN NATURE.

HANGERS AND SUPPORTS

HANGERS SHALL BE COMPLETE WITH RODS AND SUPPORTS PROPORTIONED TO THE SIZE OF PIPE TO BE SUPPORTED, IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

SIZE HANGERS FOR INSULATED PIPING TO BEAR ON OUTSIDE OF INSULATION. PROVIDE INSULATION PROTECTORS AT HANGERS BEARING ON THE OUTSIDE OF INSULATION.

PROVIDE A RIGID INSERT OR RIGID INSULATION AT EACH INSULATION PROTECTOR.

WHERE SEVERAL PIPES 21

2" AND SMALLER RUN PARALLEL AND IN THE SAME PLANE, THEY MAY BE SUPPORTED ON GANG OR MULTIPLE HANGERS. LARGER PIPING SHALL BE

INDEPENDENTLY HUNG, RUN PARALLEL AND BE EQUALLY SPACED.

PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH IPC SECTION 308, AND SPACING OF HANGERS SHALL NOT EXCEED THE LIMITS SET FORTH IN TABLE 308.5. PIPES SHALL

BE SUPPORTED WITHIN 1'-0" OF EACH ELBOW.

VERTICAL PIPE SUBJECT TO MOVEMENT SHALL BE SUPPORTED FROM THE WALL BY MEANS OF A PIPE CLAMP.

SUPPORT DOMESTIC WATER PIPING IN SPACES BEHIND PLUMBING FIXTURES BY BRACKETS AND U-BOLTS SECURED TO WASTE AND VENT STACKS. SIZE U-BOLTS TO BEAR ON

THE PIPING.

AFTER HANGER RODS ARE INSTALLED IN FINISHED CONCRETE CEILING, FILL THE REMAINING OPENING WITH CEMENT SO THAT NO HOLE SHOWS AT THE CEILING.

WHERE COPPER PIPING IS USED, NONFERROUS METAL SUPPORT(S) OR PROPER ISOLATION BETWEEN DISSIMILAR MATERIALS SHALL BE PROVIDED.

PIPE HANGERS AND SUPPORTS SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH RECOMMENDATIONS SET FORTH IN MANUFACTURER'S STANDARDIZATION

SOCIETY STANDARD PRACTICES NO. SP-69 AND SP-58.

SLEEVES AND PENETRATIONS

SLEEVES SHALL BE PROVIDED WHERE PIPES PASS THROUGH WALLS, FLOORS AND ROOFS.

PROVIDE STANDARD WEIGHT STEEL SLEEVES IN CONCRETE AND MASONRY CONSTRUCTION, PROVIDE 26GA GALVANIZED SHEET METAL SLEEVES IN INTERIOR DRYWALL CONSTRUCTION. SLEEVES SHALL BE THE FULL THICKNESS OF WALLS AND SHALL ALLOW FOR THE FULL THICKNESS OF PIPE INSULATION, WHERE APPLICABLE.

SLEEVES MAY BE OMITTED WHEN OPENINGS ARE CORE DRILLED FOR CONCEALED VERTICAL AND HORIZONTAL PIPING. SLEEVES ARE NOT REQUIRED AT INDIVIDUAL PLUMBING

FIXTURES OR IN CONCRETE FLOOR SLABS ON GRADE, UNLESS OTHERWISE NOTED.

SLEEVES FOR ALL PIPING PENETRATING FIRE RATED WALLS AND FLOORS SHALL BE PROVIDED WITH 3M PIPE BARRIER NO. CP-25 FIRE PROOFING CAULKING, OR EQUAL, IN ANNULAR SPACE BETWEEN SLEEVE AND PIPING.

This is the start of the file's text. The full file is on GovTribe.