_124311_MEP_Winterville.pdf
PDF 5 MB Posted
- Attached to
- Construction Services for Blacksmith Shop
- Solicitation number
- PE-66377-NONST-2025-000000001
- Issued by
- Clayton County, Georgia
About this file
This document contains construction drawings and specifications for the Winterville Blacksmith Shop project in Winterville, GA. The project is being managed by Brandied History, LLC and involves the complete electrical distribution system, lighting, and lighting control for the new facility. The drawings include floor plans, schedules, and details related to the electrical, mechanical, and plumbing systems. Key details include the electrical panel and service information, lighting fixture schedule, mechanical equipment schedule, plumbing piping and fixture layouts, and associated specifications. The project is expected to commence on July 31, 2024. No specific contract term or renewal options are provided.
The document outlines the requirements for the electrical, mechanical, and plumbing systems, including acceptable manufacturers, installation standards, and testing procedures. Pricing terms, set asides, incumbents, funding sources, and other commercial details are not included. The document focuses on the technical requirements and design intent for the building systems to be provided as part of the construction project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
July 31, 2024
C lie nt R ev ie w D ra w in gs F or
W
IN
TE
R V
IL
LE
B
LA
C
KS
M
IT
H S
H O
P W in te rv ill e
G A
Brandied History, LLC
485 Oakland Ave, SE Atlanta, GA 30312
1601 Mansfield St Brunswick, GA 31520
(404) 723-7240
6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092
404.330.9798
PROJECT # 124311
E0.01
GENERAL
ABBREVIATIONS
AC
AMP FUSEAF
ABOVE FINISHED FLOORAFF
BELOW FINISHED CEILINGBFC
BREAKERBKR
CONNECTED OR CONNECTIONCONN
CTB
DOWNDN
EMPTY CONDUITEC
ELECTRICALELEC
FIRE ALARM CONTROL PANELFACP
FAA
G OR GRND
GFCI OR GF
ISOLATED GROUNDIG
SHORT CIRCUIT CURRENTISC
LIGHTINGLTG
MOUNTEDMTD
NATIONAL ELECTRICAL CODENEC
PANELPNL
RECEPTACLERECPT
TELEPHONETEL TELEPHONE
TTB
TELEVISIONTV
SPD
TYPICALTYP
TRANSFORMERXFMR
UNDERGROUNDUG
WEATHERPROOFWP
NEUTRALN
COPPERCU
ALUMINUMAL
CONDUITCND
NIGHT LIGHTNL
TELEPHONE TERMINAL BOARD
EQUIPMENT AS NOTED ON DRAWING.
DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R 18" AFF
DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R
18" AFF
AC
18" AFF
IN CEILINGJ
J
42" AFFS SWITCH
MOTORM
SYMBOLS DESCRIPTION
XX-#
LEGEND
42" AFFSWITCH - 3 WAY
DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R
DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R IN CEILING
18" AFF
TELEPHONE OUTLET 18" AFF
TELEPHONE / DATA COMBINATION OUTLET 18" AFF
TELEPHONE / DATA COMBINATION OUTLET
DATA OUTLET
DATA OUTLET
18" AFF
D
TV OUTLET 18" AFF
H
SMOKE DETECTOR. CEILING / WALL MOUNTEDD
H HEAT DETECTOR. CEILING/WALL MOUNTED
80" AFF
80" AFF
80" AFF
FIRE ALARM NOTIFICATION DEVICE. AUDIO.
FIRE ALARM NOTIFICATION DEVICE. VISUAL.
FIRE ALARM INITIATION DEVICE. PULL STATION. 42" AFF
42" AFF
42" AFFSWITCH - WALL MTD, LOW VOLTAGE, PILOT LIGHT
SWITCH - CEILING MOUNTED OCCUPANCY SENSOROS IN CEILING
42" AFFSWITCH - WALL MTD, DIMMING
TELEPHONE / DATA COMBINATION OUTLET
J
S3
SOS
SLV
SD
ELECTRICAL GENERAL NOTES
THE DESIGN OF THIS SET OF DOCUMENT IS BASED ON NEC 2020.
ELECTRICAL CONTRACTOR SHALL REFER TO ALL OTHER DESIGN DRAWINGS PRIOR TO BID AND RETAIN FULL UNDERSTANDING OF THE SCOPE OF
WORK.
FIXTURE TYPE INDICATED BY UPPER CASE CHARACTERS, SWITCHING AND GROUPING DESIGNATED BY LOWER CASE LETTER AND CIRCUIT BY
NUMBER (WHERE APPLICABLE).
REFER TO THE ARCHITECTURAL/INTERIORS REFLECTED CEILING PLANS FOR EXACT FIXTURE PLACEMENT AND DIMENSIONS.
REFER TO THE ARCHITECTURAL/INTERIORS DOCUMENTS FOR ACTUAL DEVICE LOCATIONS AND DIMENSIONS.
COORDINATE THE INSTALLATION OF ALL CEILING MOUNTED DEVICES (FIRE ALARM SYSTEM DEVICES AND SPEAKERS, SOUND SYSTEM SPEAKER, ETC.) TO BE SYMMETRICAL ABOUT LIGHT FIXTURES AND SPRINKLER HEADS. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN. TYPICAL.
ALL MOUNTING OF EQUIPMENT IS AS SHOWN UNLESS OTHERWISE NOTED. COORDINATE WITH ARCHITECT THE COLOR/FINISHES OF ALL
ELECTRICAL DEVICES, OUTLETS, COVERPLATES AND TRIM.
EMERGENCY BATTERY PACKS AND EXIT SIGNS SHALL BE CONNECTED AHEAD OF ANY SWITCHING DEVICES.
REFER TO MECHANICAL DRAWINGS FOR DUCT SMOKE DETECTOR LOCATIONS AND QUANTITIES OPERATION SHALL INCLUDE DUAL CONTACT BASE
WITH LOCAL EQUIPMENT SHUTDOWN AND FIRE ALARM SIGNAL INITIATION.
WHEN CONDUCTOR OR CONDUIT SIZE IS INDICATED FOR BRANCH CIRCUIT HOME RUN, THE CONDUCTOR AND CONDUIT SIZE INDICATED SHALL
BE USED FOR THE COMPLETE CIRCUIT.
REFER TO THE APPROPRIATE DRAWINGS FOR THE EXACT LOCATION AND REQUIREMENTS OF EQUIPMENT INSTALLED UNDER OTHER DIVISIONS OF
THE DOCUMENTS, WHICH REQUIRE ELECTRICAL SERVICE.
EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN ALL RACEWAYS.
WALL SWITCHES CONTROLLING CIRCUITS OF OPPOSITE PHASES SHALL NOT BE INSTALLED IN COMMON BOX UNLESS PERMANENT BARRIER IS
PROVIDED.
ALL HOME RUNS SHALL RUN PARALLEL TO STRUCTURE AS MUCH AS POSSIBLE WHERE CEILING IS EXPOSED.
ALL RACEWAY AND EQUIPMENT SUPPORTS AND HANGERS SHALL BE FULLY COORDINATED WITH STRUCTURAL DRAWINGS TO INSURE LOCATION
OF SAME OCCURS WITHIN FOUR (4) INCHES OF PANEL POINT ON BAR JOISTS.
COORDINATE LOCATION OF ALL FLOOR MOUNTED MECHANICAL AND PLUMBING EQUIPMENT IN ORDER TO VERIFY POWER & CONTROL RACEWAY
CONCEALED IN SLABS TERMINATED AT PROPER LOCATION.
DISCONNECT SWITCHES, MOTOR STARTERS AND OTHER ELECTRICAL EQUIPMENT INSTALLED ABOVE ACCESSIBLE CEILINGS, AND REQUIRING ACCESS FOR MAINTENANCE, SHALL BE INSTALLED WITH BOTTOM OF DEVICE ONE (1) FOOT ABOVE CEILING TO PROVIDE READY ACCESSIBILITY.
MECHANICAL, PLUMBING, FIRE PROTECTION AND OTHER EQUIPMENT ARE SHOWN ON FLOOR PLAN IN APPROXIMATE LOCATION. COORDINATE
WITH M, P, FP AND CONTRACT DRAWINGS/SUBMITTALS FOR EXACT LOCATION OF EQUIPMENT.
GENERAL DIAGRAMMATIC RACEWAY INTERCONNECTIONS OF EQUIPMENT, FIXTURES AND DEVICES ARE INDICATED ON FLOOR AND REFLECTED CEILING PLANS, REFER TO STRUCTURAL AND ARCHITECTURAL PLANS FOR ELEVATION CHANGES AND RACEWAY ROUTES.
RACEWAY FOR EXTERIOR LIGHTING MAY BE INDICATED OUTSIDE OF BUILDING FOOTPRINT FOR CLARITY. ROUTE ALL EXTERIOR LIGHTING RACEWAY
WITHIN BUILDING STRUCTURE.
POWER AND COMMUNICATIONS/DATA CONDUITS CAN CROSS AT 90°, BUT WHERE PARALLEL, SHALL BE A MINIMUM OF 8" APART.
TELEVISION AND RADIO ANTENNAS CABLES SHALL HAVE SURGE PROTECTION. GROUND ALL MASTS.
PROVIDE SURGE PROTECTION FOR ELECTRICAL AND TELEPHONE SERVICES.
PROVIDE SPD FOR FIRE ALARM CONTROL PANEL.
FIELD COORDINATE MECHANICAL AND PLUMBING EQUIPMENT ELECTRICAL CHARACTERISTICS WITH DIV.15 CONTRACTOR PRIOR TO ROUGH-IN.
ADJUST ELECTRICAL CONNECTIONS IF NECESSARY TO MATCH ACTUAL EQUIPMENT IN FIELD. FOR EXAMPLE, COORDINATE THE NAMEPLATE OVERCURRENT PROTECTION DEVICE RATING OF MECHANICAL EQUIPMENT AMONG MECHANICAL AND ELECTRICAL SUBCONTRACTORS. ADJUST
CIRCUIT BREAKER TO MATCH NAMEPLATE RATING OF EQUIPMENT AT NO ADDITIONAL COST.
FIELD COORDINATE MECHANICAL AND PLUMBING EQUIPMENT REQUIREMENTS FOR ANY SUPPLEMENTAL POWER REQUIREMENTS, INCLUDING BUT NOT LIMITED TO CONTROL CIRCUITS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO BRING ALL EQUIPMENT TO ITS INTENDED
OPERATIONAL STATUS.
REFER TO FIRE PROTECTION DRAWINGS FOR LOCATIONS OF FLOW AND TAMPER SWITCHES.
EACH PENETRATION OF A FIRE RESISTANT RATED ASSEMBLY BY A PIPE, TUBE WIRE OR CONDUIT SHALL BE PROTECTED BY A THROUGH PENETRATION FIRE STOP SYSTEM THAT HAS BEEN TESTED ACCORDING TO ASTME 814 OR E199.
ELECTRIC RECEPTACLES, SWITCHES, OUTLETS, ETC. SHALL NOT BE INSTALLED BACK TO BACK ON FIRE RESISTANCE RATED WALLS. THEY SHALL
BE AT LEAST 24-INCHES APART.
LIGHT SWITCHES AND ELECTRICAL OUTLETS, LOCATED IN ROOMS ACCESSIBLE TO THE DISABLED SHALL BE LOCATED NO HIGHER THAN 48 INCHES AND NO LOWER THAN 15 INCHES ABOVE THE FINISHED FLOOR SURFACE. IF THE REACH OR THE CONTROL IS OVER AN OBSTRUCTION, THE MINIMUM HEIGHT SHALL BE REACHED TO 44 INCHES FOR A FORWARD APPROACH OR 46 INCHES FOR A SIDE APPROACH.
REFER TO LOW VOLTAGE CONSULTANT'S DRAWINGS FOR VOICE, DATA AND CATV OUTLET LOCATIONS. REFER TO LV CONSULTANT'S DRAWINGS
FOR ANY ADDITIONAL INFORMATION.
CONNECT ALL EXIT SIGNS TO NEAREST UNSWITCHED PORTION OF THE LIGHTING CIRCUIT IN THE AREA.
ELECTRICAL BOXES INSTALLED IN FIRE RATED WALLS SHALL MAINTAIN THE INTEGRITY OF THE RATED WALL.
SUPPORT ALL VERTICAL RACEWAY PER NEC TABLE 300.19(A).
MAKE ELECTRICAL CONNECTIONS TO ELECTRIC WATER COOLERS FROM GFCI PROTECTED OUTLET IN WALL BEHIND COOLER HOUSING. THE
OUTLET AND CORD SHALL NOT BE VISIBLE FROM PUBLIC VIEW.
COORDINATE WITH CUTSHEETS OF ALL EQUIPMENT TO BE INSTALLED AND PROVIDE ADDITIONAL CIRCUITS FOR CONTROLS IF REQUIRED BY
MANUFACTURER.
FINAL COLOR, FINISH AND OTHER AESTHETIC PORTIONS OF ALL DEVICES SHALL BE COORDINATED WITH ARCHITECT OR OWNER'S REPRESENTATIVE. THIS SET OF DRAWINGS DOES NOT SUPERCEDE ARCHITECTURAL OR INTERIOR DOCUMENTS.
ALL EXPOSED HORIZONTAL RUNS OF CONDUITS SHALL BE EITHER PARALLEL OR PERPENDICULAR TO EXTERIOR WALLS.
PROVIDE PLENUM RATED CABLES IF THE CABLES ARE EXPOSED AND ROUTED THROUGH PLENUM.
FOR ALL FUSES 1,200A OR HIGHER, PROVIDE ARC ENERGY REDUCTION PER NEC 240.67.
WHERE HIGHEST TRIP SETTING IN INSTALLED OVERCURRENT DEVICE IS 1,200A OR HIGHER, CONTRACTOR TO PROVIDE DOCUMENTATION OF CIRCUIT BREAKER(S) LOCATION AND PROVIDE AT LEAST ONE METHOD TO REDUCE CLEARING TIME VIA ENERGY-REDUCING MAINTENANCE SWITCH, INSTANTANEOUS TRIP SETTING, OR OTHER APPROVED METHOD AS LISTED PER NEC 240.87(B).
FIRE ALARM ANNUNCIATOR
PANEL
GROUND FAULT CIRCUIT
INTERRUPTER
GROUND
CABLE TV TERMINAL
BACKBOARD
6" ABOVE COUNTER SPACE OR
42" AFF
HOME RUN WITH WIRE TICKS. XX - PANEL
DESIGNATION, # - CIRCUIT DESIGNATION. WIRE
TICKS - (1) NEUTRAL , (3) HOT & (1) GROUND
FIRE ALARM NOTIFICATION DEVICE. AUDIO AND
VISUAL.
ELECTRICAL PANELBOARD. REFER TO
PANELBOARD SCHEDULE.
FUSED DISCONNECT SWITCH. SUBSCRIPT: AMP / #
OF POLES / ENCLOSURE / FUSE
DISCONNECT SWITCH. SUBSCRIPT: AMP / # OF
POLES / ENCLOSURE
TELEPHONE OUTLET. SUBSCRIPT: F - FIREMAN'S
PHONE, H - HOUSE PHONE, P - PAY PHONE
SWITCH - WALL MTD, INTEGRAL OCCUPANCY
SENSOR
JUNCTION BOX FLUSH IN FINSHED FLOOR WITH
COVER. SIZE PER NEC.
JUNCTION BOX FLUSH IN CEILING WITH COVER.
SIZE PER NEC.
JUNCTION BOX FLUSH IN WALL WITH COVER. SIZE
PER NEC.
SPECIAL RECEPTACLE, CONFIGURATION AND
ELECTRICAL CHARACTERISTIC AS NOTED ON DWG
QUADRAPLEX RECEPTACLE, 120V, 20A, NEMA
5-20R
QUADRAPLEX RECEPTACLE, 120V, 20A, NEMA
5-20R
42" AFF OR 6" ABOVE
COUNTER TOP
42" AFF OR 6" ABOVE
COUNTER TOP
FLUSH WITH FINISHED
FLOOR
FLUSH WITH FINISHED
FLOOR
42" AFF OR 6" ABOVE
COUNTER TOP
FLUSH WITH FINISHED
FLOOR
42" AFF OR 6" ABOVE
COUNTER TOP
42" AFF OR 6" ABOVE
COUNTER TOP
AS INDICATED ON
DWG
AS INDICATED ON
DWG
SURFACE MOUNTED
ON WALL
SURFACE MOUNTED
ON WALL
TYPICAL MOUNTING HEIGHT
UNLESS NOTED OTHERWISE
SURGE PROTECTIVE DEVICE
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text No. PE032227
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text lie nt R ev ie w D ra w in gs F or
W
IN
TE
R V
IL
LE
B
LA
C
KS
M
IT
H S
H O
P W in te rv ill e
G A
Brandied History, LLC
485 Oakland Ave, SE Atlanta, GA 30312
1601 Mansfield St Brunswick, GA 31520
(404) 723-7240
6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092
404.330.9798
PROJECT # 124311
E0.02
SPECIFICATIONS
SPECIFICATIONS SPECIFICATIONS
GENERAL
CONTRACTOR SHALL REFER TO ALL RELATED DOCUMENTS, ARCHITECTURAL, STRUCTURAL, CIVIL AND MEP DRAWINGS, AND FULLY UNDERSTAND
THE SCOPE OF WORK AND CONDITION OF CONSTRUCTION.
THE WORK UNDER THIS SPECIFICATIONS AND DRAWINGS SHALL INCLUDE ALL LABOR.
ALL INSTALLATION OF DEVICES AND CONNECTION OF CONDUCTORS SHALL BE PERFORMED BY LICENSED AND SKILLED ELECTRICIAN OR
JOURNEYMAN.
ALL WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE OWNER. IF ANY PORTION OF THE WORK IS FOUND UNSATISFACTORY BY THE OWNER, IT SHALL BE REMOVED AND REINSTALLED WITHOUT DELAY AT NO COST TO THE OWNER.
THE WORK INCLUDES, BUT NOT LIMITED TO:
THE COMPLETE ELECTRICAL DISTRIBUTION SYSTEM.
ROUGH-IN AND FINAL CONNECTIONS TO ALL DEVICES REQUIRING ELECTRICAL POWER, INCLUDING OWNER PROVIDED EQUIPMENT.
LIGHTING CONTROL
LIGHTING FIXTURES
EACH CONTRACTOR SHALL OBTAIN ALL PERMITS AND INSPECTIONS REQUIRED BY THE REGULATORY AUTHORITIES. ALL FEES RELATED TO OBTAINING PERMITS AND INSPECTION SHALL BE PAID FOR BY EACH CONTRACTOR IN HIS TRADE.
ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH LOCAL, COUNTY, STATE, AND NATIONAL ELECTRICAL CODE 2020, SPECIFICATIONS, UTILITY COMPANY REQUIREMENTS AND ALL INDUSTRY STANDARDS.
ANY DIFFERENCES IN ABOVE MENTIONED REQUIREMENTS, THE MOST STERN SHALL OVERRULE ALL OTHERS.
IN ADDITION TO ABOVE MENTIONED CODES AND SPECIFICATIONS, THE FOLLOWING INDUSTRY STANDARDS SHALL BE COMPLIED IF THEY ARE
MORE STRINGENT.
IEEE
IES
IECC 2015
ASHRAE 90.1
NFPA
NEMA
UL
ADA
THE MANUFACTURER'S PUBLISHED DIRECTIONS SHALL BE FOLLOWED IN THE DELIVERY, STORAGE, PROTECTION, INSTALLATION AND WIRING OF
ALL EQUIPMENT AND MATERIAL.
THE DRAWINGS SHOW DIAGRAMMATICALLY THE LOCATIONS OF THE VARIOUS LINES, CONDUITS, FIXTURES, AND EQUIPMENT AND THE METHOD OF CONNECTING AND CONTROLLING THEM. IT IS NOT INTENDED TO SHOW EVERY CONNECTION IN DETAIL AND ALL FITTINGS REQUIRED FOR A COMPLETE SYSTEM. THE SYSTEMS SHALL INCLUDE BUT ARE NOT LIMITED TO THE ITEMS SHOWN ON THE DRAWINGS. EXACT LOCATIONS OF THESE ITEMS SHALL BE DETERMINED BY REFERENCE TO THE GENERAL PLANS AND MEASUREMENTS AT THE BUILDING AND IN COOPERATION WITH THE OTHER SUBCONTRACTORS, AND IN ALL CASES, SHALL BE SUBJECT TO THE APPROVAL OF THE OWNER. THE OWNER RESERVES THE RIGHT TO MAKE ANY REASONABLE CHANGE IN THE LOCATION OF ANY PART OF THIS WORK WITHOUT ADDITIONAL COST TO THE OWNER.
CONTRACTOR SHALL SEEK APPROVAL FROM THE OWNER FOR ANY CHANGES TO THE SPECIFICATIONS OR CONTRACT DOCUMENTS.
ANY EXCEPTIONS, INCONSISTENCIES AND CONFLICTS IN CONTRACT DOCUMENTS, SPECIFICATIONS AND CONTRACT DOCUMENTS BY OTHER
TRADE SHALL BE BROUGHT TO ATTENTION TO THE OWNER PRIOR TO BID.
CONTRACTOR SHALL COORDINATE AND VERIFY THE WORK WITH EXISTING CONDITIONS AND THE WORK OF OTHER TRADE PRIOR TO ANY FABRICATIONS OR INSTALLATION. IF THE LAYOUT OF THE DEVICES ON DRAWINGS ARE IMPRACTICAL TO THE CONDITION IN FIELD, CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY PRIOR TO ANY FABRICATION OR INSTALLATION.
ELECTRICAL DEVICES ARE INDICATED ON DRAWINGS AT APPROXIMATE LOCATIONS. THE OWNER RESERVE THE RIGHT TO MAKE REASONABLE
CHANGES IN LOCATIONS WITHOUT ADDITIONAL COSTS.
THE LINES INDICATING BRANCH CIRCUITS DO NOT REPRESENT THE ROUTING OF ELECTRICAL CONDUITS. THEY INDICATE THE LAYOUT AND
CONTROL OF CIRCUITS.
PRODUCTS AND WORK
MATERIALS FURNISHED SHALL BE NEW AND BY STANDARD MANUFACTURERS AND MUST CONFORM TO THE NATIONAL BOARD OF FIRE UNDERWRITER'S REQUIREMENTS AND BEAR THE UNDERWRITER'S LABORATORIES' SEAL OF APPROVAL.
LISTED MANUFACTURERS, MODELS, OR CATALOGUE NUMBERS IN PART OR ALL SHALL ENTAIL TO INCLUDE THE PUBLISHED MANUFACTURER'S
DESCRIPTION AND SPECIFICATION.
CONTRACTOR SHALL NOT INTERPRET THAT THE LISTED MANUFACTURERS IN SPECIFICATIONS OR DRAWINGS TO EXCLUDE ALL OTHER
MANUFACTURERS.
CONTRACTOR SHALL MAKE CERTAIN THAT ALL EQUIPMENT FIT IN THE SPACE DESIGNATED AND DESIGNED FOR THE SURROUNDINGS IT
OCCUPIES.
COMPLETE CATALOGUE ILLUSTRATION AND DESCRIPTIONS OF ALL EQUIPMENT SHALL BE SUBMITTED TO THE OWNER PRIOR TO ORDERING ANY
EQUIPMENT.
ALL HORIZONTAL RUNS OF CONDUITS SHALL BE SUPPORTED BY MEANS OF APPROVED HANGER FROM THE STRUCTURAL CEILING.
COORDINATE THE WORK UNDER THIS SECTION WITH ALL OTHER TRADES.
CONDUITS AND RACEWAYS:
MANUFACTURERS: SQUARE D, B-LINE, ALLIED TUBE & CONDUIT, HOFFMAN, CARLON ELECTRICAL, WIREMOLD.
OUTDOORS EXPOSED: RIGID STEEL.
OUTDOORS CONCEALED ABOVE GROUND: RIGID STEEL.
OUTDOORS UNDERGROUND: TYPE EPC-40-PVC
OUTDOORS CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND MOTOR DRIVEN EQUIPMENT): LFMC.
BOXES AND ENCLOSURES ABOVE GROUND: NEMA 3R UNLESS NOTED OTHERWISE ON PLANS.
INDOORS EXPOSED NOT SUBJECT TO PHYSICAL DAMAGE: EMT. INDOORS EXPOSED NOT SUBJECT TO SEVERE PHYSICAL DAMAGE: EMT.
INDOORS EXPOSED SUBJECT TO SEVERE PHYSICAL DAMAGE: RIGID STEEL CONDUIT. INDOORS CONCEALED IN CEILINGS AND INTERIOR WALLS
AND PARTITIONS: EMT.
INDOORS CONNECTION TO VIBRATING EQUIPMENT: FMC, EXCEPT USE LFMC IN DAMP OR WET LOCATIONS.
INDOORS DAMP OR WET LOCATIONS: IMC.
INDOORS LOW-VOLTAGE CABLES: EMT.
CONDUCTORS:
COPPER CONDUCTORS #10 AND SMALLER: LABELED PER UL 83, TYPE THHN/THWN, SOLID COPPER 600 VOLT INSULATION, UNIFORM COLOR CODED JACKET WITH JACKET DATA. METAL CLAD (TYPE MC) CABLE WHERE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 330.
COPPER CONDUCTORS #8 OR LARGER: LABELED PER UL 83, TYPE THHN/THWN, STRANDED COPPER, 600VOLT INSULATION, UNIFORM COLOR
CODED JACKET WITH JACKET DATA.
ACCEPTABLE MANUFACTURERS OF CONDUCTORS:
PIRELLI, SOUTHWIRE, AETNA, REPUBLIC, AFC, ENCORE WIRE, KERITE
CONTRACTOR MAY USE ALUMINUM CONDUCTORS FOR #4 AWG OR LARGER IN THE PLACE OF COPPER CONDUCTORS. CONTRACTOR SHALL REFER TO NEC TABLE 310-16 FOR EQUIVALENT AMPACITY AND SHALL COMPENSATE FOR VOLTAGE DROP.
CONTRACTOR SHALL MAKE ADEQUATE ADJUSTMENT TO CONDUIT SIZES INDICATED SHOULD ALTERNATIVE CONDUCTOR INSULATION OR
MATERIAL BE UTILIZED.
MOLDED CASE CIRCUIT BREAKER:
INCLUDE SCHEDULE OF ALL FUSES, RATINGS, TIME COORDINATION DATA, MANUFACTURER'S STANDARD DATA AND TIME-CURRENT CURVES. ALL
DATA SHALL BE BASED ON TEST OF STANDARD PRODUCTS.
APPROVED MANUFACTURERS:
GENERAL ELECTRIC
CUTLER HAMMER
SQUARE D
SIEMENS
THERMAL-MAGNETIC BOLT-IN TYPE CIRCUIT BREAKERS WITH QUICK-MAKE, QUICK-BREAK CONTACTS; TRIP-FREE OPERATION WITH
OVER-THE-CENTER TOGGLE HANDLE OR NON-REMOVABLE MONOLITHIC TIE-HANDLE.
MULTI-POLE BREAKERS SHALL HAVE INTERNAL COMMON TRIP AND COMMON RESET WITH A SINGLE TOGGLE HANDLE OR NON-REMOVABLE
MONOLITHIC TIE-HANDLE.
TRIP RATINGS SHALL BE MOLDED ON THE HANDLE OR FACE OF BREAKER.
BREAKER TERMINALS SHALL BE RATED TO ACCOMMODATE A MINIMUM OF 75 DEGREE C. CONDUCTORS.
BREAKER SHALL BE RATED FOR MOUNTING AND OPERATION IN ANY POSITION; SHALL ACCOMMODATE AND MATCH THE TYPE OF TERMINATIONS
REQUIRED.
SINGLE POLE BREAKERS RATED 15 AND 20 AMPERES SHALL BE UL LABELED AS "SWITCHING BREAKERS" AT THE APPLIED CIRCUIT VOLTAGE.
MULTI-POLE BREAKERS RATED 100 AMPERES AND LARGER SHALL BE MOLDED CASE THERMAL-MAGNETIC BOLT-IN TYPE BREAKER WITH
ADJUSTABLE INSTANTANEOUS TRIP.
OVERCURRENT DEVICES RATED 1,000 AMPERES AND LARGER, SERVING LOADS GREATER THAN 150 VOLTS TO GROUND SHALL BE EQUIPPED WITH GROUND FAULT PROTECTION OF EQUIPMENT (GFPE) AS REQUIRED BY NEC ARTICLES 210.13 AND 230.95.
LIGHTING FIXTURE
SUBMITTAL:
SCHEDULE BY TYPE DESIGNATION ALL LIGHTING FIXTURES, EACH COMPLETE WITH DATA SHEET WITH COMPLETE PHYSICAL, ELECTRICAL AND
LIGHTING CHARACTERISTICS, LAMP TYPE AND LAMP DATA.
REFER TO THE "LIGHTING FIXTURE SCHEDULE" \IN THE DRAWINGS FOR INDIVIDUAL FIXTURE DESCRIPTIONS AND MANUFACTURER TYPES.
PROVIDE LAMPS FOR EACH FIXTURE OF QUANTITY, TYPE AND COLOR AS LISTED IN LIGHTING FIXTURE SCHEDULE. GE, SYLVANIA OR PHILIPS ARE
ACCEPTABLE.
EACH LIGHTING FIXTURE SHALL BE UL LABELED FOR PROPER OPERATION IN THE TYPE OF CEILING CONSTRUCTION AND FOR THE MOUNTING
ARRANGEMENT ON/IN WHICH IT IS INSTALLED.
FIELD VERIFY ACTUAL CEILING SLOPE FOR FIXTURES INSTALLED IN SAME AND ACTUAL FIELD DIMENSIONS AND ANGLES OF CONSTRUCTION FOR ANY FIXTURE CONFORMING THE SHAPE AND LENGTH OF SAME, FOR COORDINATION OF FIXTURE CONSTRUCTION.
PANELBOARD
SUBMITTAL:
INCLUDE SCHEDULE OF EACH PANELBOARD WITH ALL DEVICES AND COMPLETE WITH PHYSICAL AND ELECTRICAL DATA AND WITH RATINGS FOR EACH
COMPONENT INCLUDING BREAKER/FUSE OVERLAY CURVES.
LABELED PER UL #67 AND #50, CONFORM WITH NEMA #250 AND PB1, NFPA #70-384 AND 70-373.
ALL JUNCTION BOXES SHALL BE LABELED WITH PANEL AND CIRCUIT DESIGNATION.
PROVIDE TYPED CIRCUIT DIRECTORY WITH EACH CIRCUIT SERVING DEVICES AND AREA IT'S SERVING.
APPROVED MANUFACTURERS:
GENERAL ELECTRIC
CUTLER HAMMER
SQUARE D
SIEMENS
LIGHTING CONTROL
TIME SWITCHES:
SOLID STATE, PROGRAMMABLE, WITH ALPHANUMERIC DISPLAY; COMPLYING WITH UL 917. 20-A BALLAST LOAD, 120/240VAC.
TWO ON-OFF SET POINTS ON A 24-HOUR SCHEDULE AND ANNUAL HOLIDAY SCHDULE THAT OVERRIDES THE WEEKLY OPERATION ON HOLIDAYS.
ALLOW CONNECTION OF A PHOTOELECTRIC RELAY AS SUBSTITUTE FOR ON-OFF FUNCTION OF A PROGRAM.
BATTERY BACKUP FOR NOT LESS THAN SEVEN DAYS RESERVE TO MAINTAIN SCHEDULES AND TIME CLOCK.
INDOOR OCCUPANCY SENSORS:
WALL OR CEILING MOUNTED SOLID-STATE INDOOR OCCUPANCY SENSORS WITH A SEPARATE POWER PACK.
ADJUSTABLE TIME-DELAY OVER A RANGE OF 1 TO 30 MINUTES.
SENSOR OUTPUT: CONTACTS RATED TO OPERATE THE CONNECTED RELAY, COMPLYING WITH UL773A. SENSOR IS POWERED FROM POWER
PACK.
POWER PACK: DRY CONTACTS RATED FOR 20-A BALLAST LOAD AT 120 OR 277 VAC. AUTOMATIC LIGHT-LEVEL SENSOR: ADJUSTABLE FROM 2 TO 200 FC (21.5 TO 2152 LUX); TURN LIGHTS OFF WHEN SELECTED LIGHTING LEVEL IS PRESENT.
DUAL SENSOR TYPE: DETECT OCCUPANCY AREA USING PIR (PASSIVE INFRA-RED) AND ULTRASONIC DETECTION METHOD.
GROUNDING AND BONDING
ALL GROUNDING AND BONDING SHALL CONFORM TO NEC ARTICLE 250.
COPPER WIRE OR CABLE INSULATED FOR 600V UNLESS REQUIRED BY APPLICABLE CODE OR AUTHORITIES HAVING JURISDICTION.
INSTALL SOLID CONDUCTOR FOR #8 AWG AND SMALLER AND STRANDED CONDUCTORS FOR #6 OR LARGER.
INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS FOR ALL EQUIPMENT.
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text K
AutoCAD SHX Text I
No. PE032227
PANEL A
240/120V 2P 3W
BUS: 225A
AIC: 10,000
2"C, 2#3/0, #3/0N, #6G
DISC A
240/120V 2P 3W
200A
AIC: 10,000
1-1/2"C, 2#3/0, #3/0N
BUS: 200A
NEMA 3R
UTILITY
METAL WATER
SERVICE
BUILDING STEEL
ROD ELECTRODE
ENCASED IN
BUILDING FOOTING
AS PER 250.52(A)(5)
SERVICE DISCONNECT
EQUIPMENT
SERVICE
ENTRANCE
CONDUIT
JUMPER
GROUNDING
CLAMP
MATCH
ONE-LINE
GROUND ( )
WIRE SIZE
GROUNDING AND BONDING DETAIL
INTERSYSTEM
BONDING
TERMINATION
#4 CU
TO TELEPHONE
TERMINAL BOARD
TO CATV
#6 CU
MATCH ONE-LINE
GROUND ( ) WIRE SIZE
MAIN BONDING JUMPER
SIZE ACCORDING TO NEC
TABLE 250.102(C)(1)
3/4" x 10'
GROUND
ROD (MIN.
6' APART)
#2
CIRCUIT DESCRIPTION
LOAD
KVABKR
CKT
CKT
KVA CIRCUIT DESCRIPTIONBKR#
LOADCKT CKT
NOTE
NEUTRAL
BUS AMPS
VOLTSPanel AIC
MAIN BKR
LUGSFED FROM
MOUNTING
ROOM
STANDARD
MLO
10,000
240/120V 2P 3W
SURFACEA DISC A 100%
a 21 20/1 60/20.8 10.0 b 43 20/1 |1.1 a 65 20/1 30/20.7 4.9 b 87 20/1 |0.9 a 109 20/1 20/10.3 0.0 b 1211 20/1 20/10.3 0.0 a 1413 20/1 20/10.5 0.0 b 1615 20/1 20/10.5 0.0 a 1817 20/1 20/10.5 0.0 b 2019 20/1 20/10.2 0.0 a 2221 20/1 20/10.0 0.0 b 2423 20/1 20/10.0 0.0 a 2625 20/1 20/10.0 0.0 b 2827 20/1 20/10.0 0.0 a 3029 20/1 20/10.0 0.0 b 3231 20/1 20/10.0 0.0 a 3433 20/1 20/10.0 0.0 b 3635 20/1 20/10.0 0.0 a 3837 20/1 20/10.0 0.0 b 4039 20/1 20/10.0 0.0 a 4241 20/1 20/10.0 0.0
CONN
KVA
CONN
KVA
CALC
KVA
CALC
KVA
LIGHTING 0.7 0.9 (125%)
LARGEST MOTOR 0.1 0.0 (25%)
MOTORS 0.1 0.1 (100%)
RECEPTACLES 4.9 4.9 (50%>10)
CONTINUOUS 14.9 18.6 (125%)
TOTAL LOAD 24.5
BALANCED LOAD 102.2
A
PHASE A 99.4%
PHASE B 101%
EF-A, LIGHTING
RECEPTACLE
RECEPTACLE
FREEZER
REF
REF
DISPLAY
DISPLAY
DISPLAY
RECEPTACLE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
WH-1
MFCU-1, MHP-1
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
GENERAL SCHEDULE
CALLOUT SYMBOL VOLTS KVA BREAKER CIRCUIT WIRE CALLOUT DISCONNECT
DESCRIPTION
EF-A 120V 1P 2W 0.1 20/1 A-1 1/2"C,1#12,#12N,#12G
MFCU-1 240/120V 2P 3W 0.1 30/2 A-6,8 1/2"C,2#10,#10N,#10G FED FROM MHP-1
MHP-1 240/120V 2P 3W 4.8 30/2 A-6,8 1/2"C,2#10,#10N,#10G 30A/2P/NEMA 3R
WH-1 240/120V 2P 3W 10 60/2 A-2,4 3/4"C,2#6,#6N,#10G 60A/2P/NEMA 1
July 31, 2024
C lie nt R ev ie w D ra w in gs F or
W
IN
TE
R V
IL
LE
B
LA
C
KS
M
IT
H S
H O
P W in te rv ill e
G A
Brandied History, LLC
485 Oakland Ave, SE Atlanta, GA 30312
1601 Mansfield St Brunswick, GA 31520
(404) 723-7240
6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092
404.330.9798
PROJECT # 124311
E0.03
SCHEDULES
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text K
AutoCAD SHX Text I
LUMINAIRE SCHEDULE
CALLOUT SYMBOL LAMP DESCRIPTION MODEL VOLTS
D (1) 10.4W LED 6" LED RECESSED DIRECTIONAL WALLWASH LITHONIA
LDN6-35/10-LW6-MVOLT-EZ10
PROVIDE SLOPE TRIM
120V 1P 2W
F (1) 120W LED DECORATIVE SEMI-FLUSH CEILING LIGHT BARTLETT 14" SEMI-FLUSH
CEILING LIGHT
120V 1P 2W
P (1) 100W LED DECORATIVE PENDANT BARTLETT 9 1/4" MINI
PENDANT
120V 1P 2W
P1 (1) 100W LED DECORATIVE PENDANT BARTLETT 16 1/2" MINI
PENDANT
120V 1P 2W
S (1) 10.4W LED EXTERIOR SCONCE WITH BATTERY BACKUP TBD 120V 1P 2W
T (2) 1.4W LED EMERGENCY LIGHTING UNIT LITHONIA ELM2L-LED 120V 1P 2W
XC (2) 1.5W LED COMBINATION EXIT/EMERGENCY LIGHTING UNIT LITHONIA LHQM-LED-R-HO 120V 1P 2W
July 31, 2024
C lie nt R ev ie w D ra w in gs F or
W
IN
TE
R V
IL
LE
B
LA
C
KS
M
IT
H S
H O
P W in te rv ill e
G A
Brandied History, LLC
485 Oakland Ave, SE Atlanta, GA 30312
1601 Mansfield St Brunswick, GA 31520
(404) 723-7240
6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092
404.330.9798
PROJECT # 124311
E0.04
COMCHECK
RON KIGHT - EE 07-31-2024
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text K
AutoCAD SHX Text I
GF
GF
GF
GF
WP
GF
GF
D
D
D
D
D
D
P P P
P1
F
F
XC
XC
S
S
S
T
A
DISC A
T
UTILITY
WH-1
EF-A
MHP-1
MFCU-1
WP
GF
REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES.
ALL RECEPTACLES SHALL BE GROUNDED AS REQUIRED BY ARTICLE 250-146.
FOR ALL KITCHEN EQUIPMENT, SEE EQUIPMENT SCHEDULE FOR ELECTRICAL CONNECTION
INFORMATION AND OTHER GENERAL INFORMATION. KITCHEN APPLIANCE CONNECTION
LOCATION TO BE COORDINATED WITH THE ACTUAL EQUIPMENT INSTALLED. REFER TO
ARCHITECTURAL DOCUMENTS FOR MOUNTING HEIGHT AND DIMENSIONS. COORDINATE EXACT
ELECTRICAL REQUIREMENTS WITH KITCHEN EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.
ALL SINGLE-PHASE RECEPTACLES RATED 150V TO GROUND OR LESS, 50A OR LESS AND
THREE-PHASE RECEPTACLES RATED 150V TO GROUND OR LESS, 100A OR LESS IN BAR,
KITCHEN, AND FOOD PREP AREAS SHALL BE GFI PER NEC 210.8(B). GFCI MUST BE READILY
ACCESSIBLE FOR TESTING. FOR RECEPTACLES OBSTRUCTED FROM ACCESSIBILITY BY
EQUIPMENT, ACCEPTABLE ALTERNATIVES TO A GFCI RECEPTACLE ARE REMOTE TEST BUTTONS,
GFCI BREAKERS, OR GFCI RECEPTACLES UPSTREAM ON THE SAME CIRCUIT.
COORDINATE FINAL RECEPTACLE PLACEMENTS AND MOUNTING HEIGHTS WITH
OWNER/ARCHITECT.
POWER NOTES
REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES.
PROVIDE UNSWITCHED HOT LEG OF CIRCUIT TO EMERGENCY LIGHTING AND EXIT SIGNS.
EXTERIOR LIGHTING SHALL BE CONTROLLED VIA TIME CLOCK AND PHOTOCELL.
LIGHTING NOTES
A-1
A-3
A-5 A-7
A-13 A-15 A-17
A-9
A-11
July 31, 2024
C lie nt R ev ie w D ra w in gs F or
W
IN
TE
R V
IL
LE
B
LA
C
KS
M
IT
H S
H O
P W in te rv ill e
G A
Brandied History, LLC
485 Oakland Ave, SE Atlanta, GA 30312
1601 Mansfield St Brunswick, GA 31520
(404) 723-7240
6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092
404.330.9798
PROJECT # 124311
E2.01
1/4" = 1'-0"
POWER PLAN
E2.01
FLOOR PLAN
E2.01
1/4" = 1'-0"
LIGHTING PLAN
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text K
AutoCAD SHX Text I lie nt R ev ie w D ra w in gs F or
W
IN
TE
R V
IL
LE
B
LA
C
KS
M
IT
H S
H O
P W in te rv ill e
G A
Brandied History, LLC
485 Oakland Ave, SE Atlanta, GA 30312
1601 Mansfield St Brunswick, GA 31520
(404) 723-7240
6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092
404.330.9798
PROJECT # 124311
M0.01
GENERAL &
DETAILS
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
CO2 CARBON DIOXIDE
D CONDENSATE DRAIN
DB DRY BULB
EA EXHAUST AIR
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
ESP EXTERNAL STATIC PRESSURE
EWH ELECTRIC WALL HEATER
F DEGREES FAHRENHEIT
FCU FAN COIL UNIT
FD FIRE DAMPER
FSD COMBINATION FIRE/SMOKE DAMPER
H HUMIDISTAT
IH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MA MAKE-UP AIR
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MBH 1,000 BTU PER HR
MVD MANUAL VOLUME DAMPER
NC NORMALLY CLOSED
NO NORMALLY OPEN
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
PIU POWER INDUCTION UNIT
RA RETURN AIR
RH RELIEF HOOD
RTU ROOFTOP UNIT
SA SUPPLY AIR
SP STATIC PRESSURE
UC UNDER CUT DOOR
VAV VARIABLE AIR VOLUME
WB WET BULB
ABBREVIATIONS
EAT ENTERING AIR TEMPERATURE
M MOTOR
MFCU MINI FAN COIL UNIT
MHP MINI HEAT PUMP
WL WALL LOUVER
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
CO2 CARBON DIOXIDE
D CONDENSATE DRAIN
DB DRY BULB
EA EXHAUST AIR
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
ESP EXTERNAL STATIC PRESSURE
EWH ELECTRIC WALL HEATER
F DEGREES FAHRENHEIT
FCU FAN COIL UNIT
FD FIRE DAMPER
FSD COMBINATION FIRE/SMOKE DAMPER
H HUMIDISTAT
IH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MA MAKE-UP AIR
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MBH 1,000 BTU PER HR
MVD MANUAL VOLUME DAMPER
NC NORMALLY CLOSED
NO NORMALLY OPEN
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
PIU POWER INDUCTION UNIT
RA RETURN AIR
RH RELIEF HOOD
RTU ROOFTOP UNIT
SA SUPPLY AIR
SP STATIC PRESSURE
UC UNDER CUT DOOR
VAV VARIABLE AIR VOLUME
WB WET BULB
ABBREVIATIONS
EAT ENTERING AIR TEMPERATURE
M MOTOR
MFCU MINI FAN COIL UNIT
MHP MINI HEAT PUMP
WL WALL LOUVER
BDD BACKDRAFT DAMPER
DH DEHUMIDIFIERDH DEHUMIDIFIER
U.N.O UNLESS NOTED OTHERWISEU.N.O UNLESS NOTED OTHERWISE
CU CONDENSING UNITCU CONDENSING UNIT
FURN FURNACEFURN FURNACE
LEGEND
SYMBOLS DESCRIPTION
X1 X2
DIFFUSER, GRILLE, REGISTER OR LOUVER TAG
X1 = TYPE, X2 = CFM
POSITIVE PRESSURE (AIR GOES OUT) DIFFUSER OR REGISTER, 4-WAY
AIR PATTERN (UNLESS OTHERWISE NOTED)
NEGATIVE PRESSURE (AIR GOES IN) GRILLE
POSITIVE PRESSURE AIRFLOW (TYP. SUPPLY)
NEGATIVE PRESSURE AIRFLOW (TYP. RETURN/EXHAUST)
FLEXIBLE DUCT
MANUAL VOLUME DAMPER (MVD)
FD
VERTICAL (TYP. WALL) FIRE DAMPER
FSD
VERTICAL (TYP. WALL) COMBINATION FIRE/SMOKE DAMPER
FD
HORIZONTAL (TYP. FLOOR/CEILING) FIRE DAMPER
FSD
HORIZONTAL (TYP. FLOOR/CEILING) COMBINATION FIRE/SMOKE
DAMPER
THERMOSTATT
INTERNALLY LINED DUCT
DUCT UP
DUCT UP
DUCT DOWN
SUPPLY DUCT
REMOTE TEMPERATURE SENSORS
HUMIDISTATH
EQUIPMENT TYPE
UNIT
EQUIPMENT NUMBER. WHERE A LETTER IS USED, THERE ARE MULTIPLE
INSTANCES.
BACKDRAFT DAMPER (BDD)
SPECIFICATIONS SPECIFICATIONS
APPLICABLE CODES:
INTERNATIONAL FIRE CODE (IFC), 2018 EDITION
2020 IFC GA AMENDMENTS
INTERNATIONAL PLUMBING CODE (IPC), 2018 EDITION
2020, 2022 & 2023 IPC GA AMENDMENTS
INTERNATIONAL MECHANICAL CODE (IMC), 2018 EDITION
2020 IMC GA AMENDMENTS
INTERNATIONAL FUEL GAS CODE (IFGC), 2018 EDITION
2020 & 2022 IFGC GA AMENDMENTS
INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2015 EDITION
2020, 2022 & 2023 SUPPLEMENTS AND AMENDMENTS
GENERAL NOTES:
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CEILING
MOUNTED EQUIPMENT.
ALL DUCT DIMENSIONS INDICATED IN THESE DOCUMENTS ARE INSIDE-CLEAR DIMENSIONS.
PORTIONS OF DUCTWORK OR PIPING VISIBLE THROUGH GRILLES AND REGISTERS IN FINISHED
AREAS SHALL BE PAINTED FLAT BLACK. PAINT BLACK BEHIND ALL GRILLES.
ALL WIRING IN THE CEILING PLENUM SHALL BE PLENUM RATED CABLE.
MOUNTING FRAME OF CEILING MOUNTED AIR DISTRIBUTION DEVICES SHALL BE COMPATIBLE
WITH CEILING TYPE. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPE.
ALL FIRE SEPARATIONS MUST BE PROTECTED WHEN APPLICABLE.
PROVIDE NEW FILTERS (MERV 7 OR BETTER PER OWNER) FOR ALL APPLICABLE HVAC
EQUIPMENT AT THE END OF CONSTRUCTION.
ALL MATERIAL IN PLENUM MUST MEET FIRE AND SMOKE SPREAD AS REQUIRED BY NFPA 90A.
ALL ROOF PENETRATIONS TO BE 12" APART AND AT LEAST 12" AWAY FROM CURBS, WALLS,
AND DRAIN SUMPS TO PROVIDE ROOFING CONTRACTOR WITH SUFFICIENT ACCESS FOR
FLASHING EACH ROOF PENETRATION.
SUBSTITUTIONS MUST BE APPROVED IN WRITING BY ARCHITECT PRIOR TO BID SUBMISSION.
CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS AND SHALL BE FAMILIAR WITH THE
SCOPE AND REQUIREMENTS OF THIS PROJECT. ANY DISCREPANCIES OR LACK OF CLARITY IN
THE DOCUMENTS SHALL BE IDENTIFIED TO THE ARCHITECT OR ENGINEER PRIOR TO THE
SUBMISSION OF PRICING BIDS. WITH A SUBMITTED BID, CONTRACTOR IS ACCEPTING THESE
DOCUMENTS AS SUFFICIENT DEFINITION OF THE SCOPE OF WORK, AND ANY ADDITIONAL
COSTS BASED ON UNCLARITY OF CONTRACT DOCUMENTS WILL NOT BE CONSIDERED.
THE CONTRACTOR SHALL REFERENCE THE FULL SET OF CONSTRUCTION DOCUMENTS DURING
PRICING AND CONSTRUCTION FOR COORDINATION BETWEEN DISCIPLINES RELATIVE TO THE
MECHANICAL SCOPE.
GUARANTEE:
GUARANTEE THAT EACH PIECE OF APPARATUS SHALL BE OF THE CUSTOMARY STANDARD AND
QUALITY FURNISHED BY THE DESIGNED MANUFACTURER FOR THAT CATALOG NUMBER.
GUARANTEE THAT THE AIR SYSTEMS SHALL OPERATE WITHOUT AERODYNAMIC NOISE
GENERATED FROM THE FAULTY INSTALLATION OF DUCT WORK OR ANY COMPONENT OF THE
AIR DISTRIBUTION SYSTEM.
GUARANTEE THAT ALL SYSTEMS AND COMPONENTS SHALL BE PROVIDED WITH A ONE YEAR
WARRANTY FROM THE TIME OF DATE OF SUBSTANTIAL COMPLETION. THE WARRANTY SHALL
COVER ALL MATERIALS AND WORKMANSHIP. DURING THIS WARRANTY PERIOD, ALL DEFECTS IN
MATERIALS AND WORKMANSHIP SHALL BE CORRECTED BY REPAIR OR REPLACEMENT WITHOUT
INCURRING ADDITIONS TO THE CONTRACT.
EXISTING CONDITIONS:
CONTRACTOR SHALL VISIT THE SITE AND UNDERSTAND JOB CONDITIONS BEFORE SUBMITTING
A PROPOSAL. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY LOCATIONS AND
SIZES OF ALL EXISTING UTILITY SERVICES PRIOR TO SUBMITTING HIS PROPOSAL. NO
CONSIDERATION WILL BE GIVEN TO CLAIMS FOR EXTRA COST ARISING FROM CONTRACTOR'S
FAILURE TO BE FULLY COGNIZANT OF JOB OR SITE CONDITIONS EXISTING AT TIME OF
ACCEPTANCE OF BID.
ACTIVE SERVICES: WHEN ENCOUNTERED IN WORK, PROTECT, BRACE, SUPPORT EXISTING
ACTIVE SEWERS, GAS AND OTHER SERVICES REQUIRED FOR PROPER EXECUTION OF WORK. IF
EXISTING ACTIVE SERVICES ARE ENCOUNTERED THAT REQUIRE RELOCATION, RELOCATE AS
APPROVED. DO NOT PREVENT OR DISTURB OPERATION OF ACTIVE SERVICES THAT ARE TO
REMAIN.
INACTIVE SERVICES: WHEN ENCOUNTERED IN WORK, REMOVE, CAP OR PLUG INACTIVE
SERVICES, AS INDICATED.
INTERRUPTION OF SERVICES: WHERE WORK MAKES TEMPORARY SHUT-DOWNS OF SERVICES
UNAVOIDABLE, SHUT DOWN AT NIGHT, OR AT SUCH TIMES AS APPROVED BY OWNER, WHICH
WILL CAUSE LEAST INTERFERENCE WITH ESTABLISHED OPERATING ROUTINE. ARRANGE WORK
TO ASSURE THAT SERVICES WILL BE SHUT DOWN ONLY DURING TIME ACTUALLY REQUIRED TO
MAKE NECESSARY CONNECTION TO EXISTING WORK.
WHERE EXISTING WALLS, CEILINGS, FLOORS, ETC., ARE CUT OR OTHERWISE DAMAGED DURING
CONSTRUCTION, REPAIR ALL SURFACES TO THEIR ORIGINAL CONDITION.
SHOP DRAWINGS:
SUBMIT SHOP DRAWINGS FOR REVIEW. PDF FILES PREFERRED. SHOP DRAWINGS SHALL BE
BOUND INTO VOLUMES (FILES), WITH EACH VOLUME (FILE) CONTAINING ONE COPY OF ALL
SHOP DRAWINGS. ALL SHOP DRAWINGS SHALL BE SUBMITTED SIMULTANEOUSLY; NO SHOP
DRAWINGS WILL BE CHECKED UNTIL ALL HAVE BEEN SUBMITTED.
SUBMITTALS SHALL BE SUPPORTED BY DESCRIPTIVE MATERIAL, SUCH AS CATALOG CUTS,
DIAGRAMS, PERFORMANCE CURVES AND CHARTS PUBLISHED BY THE MANUFACTURER, TO
SHOW CONFORMANCE TO SPECIFICATION AND DRAWING REQUIREMENTS; MODEL NUMBERS
ALONE WILL NOT BE ACCEPTABLE. ALL LITERATURE SHALL CLEARLY INDICATE THE SPECIFIED
MODEL NUMBER, DIMENSIONS, ARRANGEMENT, RATING AND CHARACTERISTICS OF THE
PROPOSED EQUIPMENT. CAPACITIES AND RATINGS SHALL BE BASED ON CONDITIONS
INDICATED OR SPECIFIED HEREIN. ANY DEVIATIONS FROM SPECIFIED EQUIPMENT
(PARTICULARLY THOSE WHICH REQUIRE COORDINATION WITH OTHER TRADES) SHALL BE
CLEARLY NOTED IN A CONCISE LIST ON A SEPARATE SHEET.
TEST AND BALANCE:
TEST AND BALANCE (TAB) CONTRACTOR SHALL HOLD A CURRENT NATIONAL BALANCING
COUNCIL (NBC) CERTIFICATION AND POSSESS ACCURATE AND CALIBRATED INSTRUMENTS.
TAB WORK AND REPORTS SHALL BE PER NBC PRACTICAL STANDARDS, PROCEDURES AND
FORMS. ACCEPTIBLE ALTERNATIVE TAB FIRM CERTIFICATIONS/PROCEDURES: NEBB, AABC, OR
TABB.
PRIOR TO COMMENCEMENT OF THE TAB WORK, THE MECHANICAL SYSTEMS ARE TO BE
STARTED AND FULLY FUNCTIONING. A CHECKLIST PRIOR TAB WORK IS TO BE SENT TO THE
INSTALLING CONTRACTOR AND RETURNED ATTESTING TO THE READINESS OF THE SYSTEMS
FOR BALANCING.
PREFERRED TAB FIRM: P-TAB.COM
CEILING FAN:
CEILING MOUNTED EXHAUST FANS SHALL BE OF THE CENTRIFUGAL DIRECT DRIVE TYPE. THE
FAN HOUSING SHALL BE CONSTRUCTED OF STEEL. THE PLASTIC DUCT COLLAR SHALL BE A
TAPERED SLEEVE FOR EASE OF CONNECTION TO 3 IN AND 4 IN ROUND DUCTWORK AND SHALL
INCLUDE A BACKDRAFT DAMPER. THE GRILLE SHALL BE CONSTRUCTED OF NON-YELLOWING
HIGH STRENGTH POLYMER AND ATTACHED TO THE HOUSING WITH TORSION SPRINGS. THE
WHEELS SHALL BE CONSTRUCTED OF HIGH STRENGTH POLYMER. THE ACCESS FOR WIRING
SHALL BE EXTERNAL. THE MOTOR DISCONNECT SHALL BE INTERNAL AND OF THE PLUG IN TYPE.
ALL FANS SHALL BEAR THE AMCA CERTIFIED RATINGS SEALS FOR SOUND AND AIR
PERFORMANCE AND SHALL BE U.L. LISTED.
DUCTLESS SPLIT SYSTEM
CEILING CASSETTE INDOOR UNIT
STANDARD PREFILTER IS INCLUDED WITH INDOOR UNIT
CHOICE OF FAN SPEEDS: LOW, MEDIUM, HIGH
INDOOR UNIT POWERED FROM OUTDOOR UNIT
AUTO RESTART FOLLOWING A POWER OUTAGE
BASE HEATER
LIMITED WARRANTY: FIVE YEARS ON PARTS AND DEFECTS AND SEVEN YEARS ON THE
COMPRESSOR
SEE SCHEDULE FOR LIST OF ACCEPTABLE MANUFACTURERS.
DIFFUSERS, GRILLES, & REGISTERS:
EGGCRATE GRILLE:
RETURN GRILLES SHALL BE TITUS MODEL 50F FOR THE SIZES AND MOUNTING TYPES AS
SHOWN ON THE PLANS AND OUTLET SCHEDULE. RETURN GRILLES MUST PROVIDE A FREE AREA
OF AT LEAST 90%. OUTER BORDERS SHALL BE CONSTRUCTED OF HEAVY EXTRUDED
ALUMINUM WITH A THICKNESS OF 0.040-0.050 INCH AND SHALL HAVE COUNTERSUNK
SCREW HOLES FOR A NEAT APPEARANCE. BORDER WIDTH SHALL BE 1¼ INCHES ON ALL SIDES
AND SHALL BE INTERLOCKED AT THE FOUR CORNERS AND MECHANICALLY STAKED TO FORM A
RIGID FRAME. CHOICE OF THREE SIZES OF ALUMINUM GRID: ½ X ½ X ½ INCH, ½ X ½ X 1
INCH, OR 1 X 1 X 1 INCH SHALL BE AVAILABLE.
OPTIONAL OPPOSED-BLADE VOLUME DAMPER SHALL BE CONSTRUCTED OF HEAVY GAUGE
STEEL OR ALUMINUM. DAMPER MUST BE OPERABLE FROM THE FACE OF THE GRILLE.
PLAQUE DIFFUSERS:
ARCHITECTURAL SQUARE PANEL CEILING DIFFUSERS SHALL BE OF THE SIZES AND MOUNTING
TYPES SHOWN ON THE PLANS AND OUTLET SCHEDULE. THE FACE PANEL IS REMOVABLE BY
MEANS OF FOUR HANGER BRACKETS. THE EXPOSED SURFACE OF THE FACE PANEL SHALL BE
SMOOTH, FLAT, AND FREE OF VISIBLE FASTENERS.
THE BACK OF THE FACE PANEL SHALL HAVE AN AERODYNAMICALLY SHAPED, ROLLED EDGE TO
ENSURE A TIGHT HORIZONTAL DISCHARGE PATTERN. CEILING DIFFUSERS WITH A 24 X 24-INCH FULL FACE SHALL HAVE NO LESS THAN AN 18 X 18-INCH FACE PANEL SIZE. CEILING DIFFUSERS WITH A 12 X 12-INCH FULL FACE SHALL HAVE NO LESS THAN A 9 X 9-INCH FACE PANEL SIZE.
THE BACKPAN SHALL BE ONE PIECE PRECISION DIE-STAMPED AND SHALL INCLUDE AN
INTEGRALLY DRAWN INLET. THE DIFFUSER NECK SHALL HAVE A MINIMUM OF 1¼-INCH DEPTH
AVAILABLE FOR DUCT CONNECTION.
THE FINISH SHALL BE #26 WHITE. THE FINISH SHALL BE AN ANODIC ACRYLIC PAINT, BAKED AT
315°F FOR 30 MINUTES. THE PENCIL HARDNESS MUST BE HB TO H.
THE PAINT MUST PASS A 100-HOUR ASTM B117 CORROSIVE ENVIRONMENTS SALT SPRAY
TEST WITHOUT CREEPAGE, BLISTERING OR DETERIORATION OF FILM. THE PAINT MUST PASS A
250-HOUR ASTM D870 WATER IMMERSION TEST. THE PAINT MUST ALSO PASS THE ASTM
D2794 REVERSE IMPACT CRACKING TEST WITH A 50-INCH POUND FORCE APPLIED.
OPTIONAL ROUND DAMPER SHALL BE CONSTRUCTED OF HEAVY GAUGE STEEL. DAMPER MUST
BE OPERABLE FROM THE FACE OF THE DIFFUSER. OPTIONAL DIRECTIONAL BLOW CLIPS SHALL
BE AVAILABLE TO RESTRICT THE DISCHARGE AIR IN CERTAIN DIRECTIONS.
OPTIONAL MOLDED INSULATION BLANKET SHALL BE AVAILABLE. THE INSULATION WILL BE R-6, FOIL-BACKED, AND PROVIDE AN ADDITIONAL 1-INCH GAP AROUND THE NECK TO INSTALL
INSULATED FLEX DUCT.
THE MANUFACTURER SHALL PROVIDE PUBLISHED PERFORMANCE DATA FOR THE SQUARE
PANEL DIFFUSER. THE DIFFUSER SHALL BE TESTED IN ACCORDANCE WITH ANSI/ASHRAE
STANDARD 70-1991.
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text No. 034608
AutoCAD SHX Text J
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text U
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text A lie nt R ev ie w D ra w in gs F or
W
IN
TE
R V
IL
LE
B
LA
C
KS
M
IT
H S
H O
P W in te rv ill e
G A
Brandied History, LLC
485 Oakland Ave, SE Atlanta, GA 30312
1601 Mansfield St Brunswick, GA 31520
(404) 723-7240
6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092
404.330.9798
PROJECT # 124311
M2.01
1/4" = 1'-0"
MECHANICAL FLOOR PLAN
M2.01
MECHANICAL
FLOOR PLAN
NO SCALE
CONDENSATE TRAP (DRAW THROUGH UNIT)
1" PLUS MAXIMUM NEGATIVE
STATIC PRESSURE
X1 =
NOTES
LOCATE TRAPS SO AS TO BE
ACCESSIBLE FOR CLEANING.
1.
HALF OF X1X2 =
X1+X2+PIPE Ø+INSULATIONX3 =
WHERE:
AIR UNIT
CASING
X3FLOW
X2
X1
CLEANOUT CAP, CLOSED DURING
UNIT OPERATION
PIPE FULL SIZE
AIR UNIT DRAIN
CONNECTION,
MINIMUM
OPEN END
PIPE (EXTERIOR)
CAPPED
(INTERIOR)
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text No. 034608
AutoCAD SHX Text J
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text U
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text A lie nt R ev ie w D ra w in gs F or
W
IN
TE
R V
IL
LE
B
LA
C
KS
M
IT
H S
H O
P W in te rv ill e
G A
Brandied History, LLC
485 Oakland Ave, SE Atlanta, GA 30312
1601 Mansfield St Brunswick, GA 31520
(404) 723-7240
6991 Peachtree Industrial Blvd Building 700 Peachtree Corners, Georgia 30092
404.330.9798
PROJECT # 124311
P0.01
GENERAL
GENERAL
ALL WORK SHALL COMPLY WITH ALL STATE, CITY AND LOCAL CODES, RULES AND REGULATIONS. CONTRACTOR SHALL SECURE ALL REQUIRED PERMITS AND INSPECTIONS
ASSOCIATED WITH THIS WORK, AND SHALL PAY ALL COSTS AND FEES INVOLVED.
ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE BEST RECOGNIZED PRACTICE IN THE FIELD CONCERNED. MANUFACTURED ITEMS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S PRINTED DIRECTIONS, SPECIFICATIONS AND RECOMMENDATIONS.
CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS AND SHALL BE FAMILIAR WITH THE SCOPE AND REQUIREMENTS OF THIS PROJECT. ANY DISCREPANCIES OR LACK OF CLARITY IN THE DOCUMENTS SHALL BE IDENTIFIED TO THE ARCHITECT OR ENGINEER PRIOR TO THE SUBMISSION OF PRICING BIDS. WITH A SUBMITTED BID, CONTRACTOR IS ACCEPTING THESE DOCUMENTS AS SUFFICIENT DEFINITION OF THE SCOPE OF WORK, AND ANY ADDITIONAL COSTS BASED ON UNCLARITY OF CONTRACT DOCUMENTS WILL
NOT BE CONSIDERED.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND LOCATIONS FOR EQUIPMENT INSTALLATION PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS. ALL EQUIPMENT AND DEVICES SHALL BE INSTALLED SUCH THAT THEY ARE EASILY ACCESSIBLE AND SERVICABLE. THIS EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO: PLUMBING FIXTURES, WATER HEATERS, EXPANSION TANKS, PUMPS, BACKFLOW PREVENTERS, VALVES, MIXING VALVES, THERMOMETERS, GAUGES, TRAP PRIMERS AND CLEANOUTS.
THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE FULL SET OF CONSTRUCTION DOCUMENTS, INCLUDING ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL & ELECTRICAL DRAWINGS (AS APPLICABLE) TO ENSURE ALL PLUMBING WORK IS COORDINATED WITH PHYSICAL CONDITIONS AND ALL OTHER TRADES.
THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE ARCHITECTURAL DRAWINGS TO ENSURE THERE IS ADEQUATE WALL THICKNESS SUCH THAT ALL PIPING, FIXTURE CARRIERS, WALL CLEANOUTS, WALL BOXES, WALL HYDRANTS AND ACCESS PANELS WILL FIT IN THE WALL SPACE. CONTRACTOR SHALL NOTIFY THE ARCHITECT IF WALL SPACE
IS INADEQUATE PRIOR TO COMMENCING WORK.
THE CONTRACTOR SHALL OBTAIN EXACT WALL, FIXTURE, AND LAYOUT DIMENSIONS FROM THE ARCHITECTURAL DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ROUGH-IN AND INSTALLATION DRAWINGS FOR ALL PLUMBING FIXTURES, KITCHEN EQUIPMENT AND OWNER FURNISHED EQUIPMENT (AS APPLICABLE), AND SHALL COORDINATE THE PLUMBING INSTALLATION PRIOR TO COMMENCING THE WORK. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND INSTALLING ALL NECESSARY VALVES, CONNECTIONS, TRAPS, ACCESS PANELS, UNIONS, ESCUTCHEONS, WATER HAMMER ARRESTORS, VACUUM BREAKERS, RELIEF VALVES, PIPE INSULATION, AND EQUIPMENT SPECIALTY DEVICES AS REQUIRED TO FACILITATE COMPLETE AND OPERATIONAL CONDITIONS WHICH ARE IN STRICT COMPLIANCE WITH THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
THESE DRAWINGS ARE DIAGRAMMATIC AND DO NOT REFLECT ALL POSSIBLE PHYSICAL CONDITIONS. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS AND EXACT LOCATIONS OF EQUIPMENT AND FIXTURES. PROVIDE NECESSARY PIPING OFFSETS TO COORDINATE WITH THE BUILDING STRUCTURE, WORK OF OTHER TRADES, AND
CONNECTION TO SITE UTILITIES (AS APPLICABLE).
COORDINATE THE ELECTRICAL REQUIREMENTS AND CHARACTERISTICS OF ALL PLUMBING EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO ISSUING SUBMITTALS OR
PURCHASING EQUIPMENT.
UNLESS NOTED OTHERWISE, ALL DRAINAGE PIPING SHALL BE SLOPED AT A MINIMUM OF 18" PER FOOT. 2" SANITARY PIPING AND ALL GREASE WASTE PIPING SHALL BE SLOPED
AT 14" PER FOOT.
DOMESTIC WATER PIPING SHALL BE PURGED OF DELETERIOUS MATTER AND DISINFECTED PRIOR TO UTILIZATION. PIPING TO BE FLUSHED AND STERILIZED IN ACCORDANCE
WITH IPC 610.1 AND ALL APPLICABLE LOCAL AND STATE HEALTH DEPARTMENT STANDARDS.
ALL DOMESTIC WATER PIPING, SANITARY P-TRAPS AND GREASE WASTE PIPING SUBJECT TO FREEZING SHALL BE INSULATED AND PROVIDED WITH HEAT TRACE. CONDENSATE PIPING SUBJECT TO FREEZING WITHIN WALK-IN FREEZERS SHALL BE INSULATED AND PROVIDED WITH HEAT TRACE. PIPING INSTALLED IN EXTERIOR WALLS SHALL BE WRAPPED IN 1" THICK PIPE INSULATION AND BE LOCATED ON THE INTERIOR SIDE OF THE BUILDING INSULATION. IF INSTALLED IN EXTERIOR BLOCK WALLS, INTERSTITIAL SPACES SHALL BE
FILLED WITH FOAM INSULATION.
IN CONCEALED LOCATIONS WHERE PIPING, OTHER THAN CAST-IRON OR GALVANIZED STEEL, IS INSTALLED THROUGH HOLES OR NOTCHES IN STUDS, JOISTS, OR SIMILAR
MEMBERS LESS THAN 11
2" FROM THE NEAREST EDGE OF MEMBER, PIPE SHALL BE PROTECTED BY STEEL SHIELD PLATES IN ACCORDANCE WITH IPC 305.6.
PIPE PENETRATIONS THROUGH FIRE RATED WALLS OR FLOORS SHALL HAVE EQUIVALENTLY RATED SLEEVES AND SHALL BE SEALED AND FIRE CAULKED WITH A U.L. LISTED FIRE STOPPING SYSTEM INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S LISTED DETAILS AND SPECIFICATIONS.
THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH THE REQUIREMENTS OF THE COUNTY HEALTH DEPARTMENT AND OTHER LOCAL AUTHORITIES HAVING JURISDICTION REGARDING CROSS CONNECTION CONTROL OR OBTAINING A FOOD SERVICE PERMIT (AS APPLICABLE). REPORT ANY OBSERVED DISCREPANCIES TO THE
ARCHITECT OR ENGINEER PRIOR TO COMMENCING WITH THE WORK.
CONTRACTOR SHALL CONFIRM PLUMBING FIXTURE FINISHES WITH THE ARCHITECTURAL SCHEDULES & DETAILS (AS APPLICABLE).
PROFICIENT ENGINEERING WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND THE DESIGN INTENT THEY CONVEY, OR PROBLEMS WHICH ARISE FROM OTHER'S FAILURE TO OBTAIN AND/OR FOLLOW PROFICIENT'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC IN NATURE.
HANGERS AND SUPPORTS
HANGERS SHALL BE COMPLETE WITH RODS AND SUPPORTS PROPORTIONED TO THE SIZE OF PIPE TO BE SUPPORTED, IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
SIZE HANGERS FOR INSULATED PIPING TO BEAR ON OUTSIDE OF INSULATION. PROVIDE INSULATION PROTECTORS AT HANGERS BEARING ON THE OUTSIDE OF INSULATION.
PROVIDE A RIGID INSERT OR RIGID INSULATION AT EACH INSULATION PROTECTOR.
WHERE SEVERAL PIPES 21
2" AND SMALLER RUN PARALLEL AND IN THE SAME PLANE, THEY MAY BE SUPPORTED ON GANG OR MULTIPLE HANGERS. LARGER PIPING SHALL BE
INDEPENDENTLY HUNG, RUN PARALLEL AND BE EQUALLY SPACED.
PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH IPC SECTION 308, AND SPACING OF HANGERS SHALL NOT EXCEED THE LIMITS SET FORTH IN TABLE 308.5. PIPES SHALL
BE SUPPORTED WITHIN 1'-0" OF EACH ELBOW.
VERTICAL PIPE SUBJECT TO MOVEMENT SHALL BE SUPPORTED FROM THE WALL BY MEANS OF A PIPE CLAMP.
SUPPORT DOMESTIC WATER PIPING IN SPACES BEHIND PLUMBING FIXTURES BY BRACKETS AND U-BOLTS SECURED TO WASTE AND VENT STACKS. SIZE U-BOLTS TO BEAR ON
THE PIPING.
AFTER HANGER RODS ARE INSTALLED IN FINISHED CONCRETE CEILING, FILL THE REMAINING OPENING WITH CEMENT SO THAT NO HOLE SHOWS AT THE CEILING.
WHERE COPPER PIPING IS USED, NONFERROUS METAL SUPPORT(S) OR PROPER ISOLATION BETWEEN DISSIMILAR MATERIALS SHALL BE PROVIDED.
PIPE HANGERS AND SUPPORTS SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH RECOMMENDATIONS SET FORTH IN MANUFACTURER'S STANDARDIZATION
SOCIETY STANDARD PRACTICES NO. SP-69 AND SP-58.
SLEEVES AND PENETRATIONS
SLEEVES SHALL BE PROVIDED WHERE PIPES PASS THROUGH WALLS, FLOORS AND ROOFS.
PROVIDE STANDARD WEIGHT STEEL SLEEVES IN CONCRETE AND MASONRY CONSTRUCTION, PROVIDE 26GA GALVANIZED SHEET METAL SLEEVES IN INTERIOR DRYWALL CONSTRUCTION. SLEEVES SHALL BE THE FULL THICKNESS OF WALLS AND SHALL ALLOW FOR THE FULL THICKNESS OF PIPE INSULATION, WHERE APPLICABLE.
SLEEVES MAY BE OMITTED WHEN OPENINGS ARE CORE DRILLED FOR CONCEALED VERTICAL AND HORIZONTAL PIPING. SLEEVES ARE NOT REQUIRED AT INDIVIDUAL PLUMBING
FIXTURES OR IN CONCRETE FLOOR SLABS ON GRADE, UNLESS OTHERWISE NOTED.
SLEEVES FOR ALL PIPING PENETRATING FIRE RATED WALLS AND FLOORS SHALL BE PROVIDED WITH 3M PIPE BARRIER NO. CP-25 FIRE PROOFING CAULKING, OR EQUAL, IN ANNULAR SPACE BETWEEN SLEEVE AND PIPING.