Scrubbed USDA FA IT -3.2024 - DeficientFireSystemRepair.pdf
PDF 190 KB Posted
- Attached to
- Corvallis Sprinkler Repair- USDA/FS Location
- Solicitation number
- 1240BG25Q0021
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a Fire Alarm System Confidence Test report for the USDA Forestry Science Lab located at 3200 SW Jefferson Way in Corvallis, Oregon. The inspection was conducted from 3/12/2024 to 3/14/2024, using a Simplex 4100 control panel with digital transmission. The system is powered by 120V with a breaker overcurrent protection and uses sealed lead acid batteries. During the inspection, several issues were identified, including a non-functioning 2nd Floor West NAC circuit, inaccessible smoke detectors in certain rooms, and 1st Floor Central RPS batteries requiring replacement. The testing team noted problems accessing Rooms 112, 214/193.2, and Buildings 400/500. Subsequent corrections included accessing and testing Buildings 3000/4000 (all devices passed) and replacing the 1st Floor Central RPS batteries on 3/18.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions asked to date 05.27.25.pdf | ||
| IMG_1159.jpg | JPG image | |
| IMG_1160.jpg | JPG image | |
| IMG_1162.jpg | JPG image | |
| 1240BG25Q0021 NRE Commercial Supplies Combined SS RFQ.docx | DOCX document | |
| CORVALLISFIRE SPRINKLER PLANS.pdf | ||
| Attachment A Statement of work fire suppression system.docx | DOCX document | |
| Wage Determination 15-5567.txt | TXT text file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page: 1 Rev Date: 1/13/2023
FIRE ALARM SYSTEM System Certification Given
CONFIDENCE TEST REPAIRS RED YELLOW WHITE
Frequency Annual: Semi-Annual: Quarterly:
Date of Inspection:
Building Information Building Name: Building Address:
Building Owner: Phone Number: Owner Address:
Description of Property:
Fax:
System & Monitoring Information No
Monitoring Company Address:
Monitoring Company Fax: Monitoring Company E-Mail:
Control Panel Manufacturer: Model Number:
Means of Transmission: Entity which Alarms Are Transmitted:
Location of System:
Onsite location of site-specific software: Firmware revision number:
Testing Agency Information State Contractor License: Tech License Number:
E-mail:
Fax:
x
3/12/2024 - 3/14/2024
USDA Forestry Science Lab 3200 SW Jefferson Wy Corvallis OR
USDA 541-750-7375
Commercial Contact Person: Phone Number:
E-Mail:
Monitoring Company Name:
Monitoring Company Phone:
Simplex 4100
Digital
1st Floor FACP Rm102
Testing Agency Name: Address:
Central Station Monitoring Yes Account Number:
Page: 2 Rev Date: 1/13/2023
System Power Nominal Voltage:
Amps:
Location:
Overcurrent Protection type:
Amps:
Disconnecting Means Location:
Secondary Power:
Type:
Location:
Battery Type (If Applicable):
Calculated capacity:
Standby Mode (Hours):
Alarm Mode (Minutes):
Notifications prior to Testing:
Monitoring Company Contact:
Time:
Building Management Contact:
Time:
Building Occupants Contact:
Time
AHJ
Contact:
Time
Other if required:
Control Unit and Related Equipment Visual Inspection:
Functional Test:
Control Unit Comments:
Lamps/LED’s/LCD’s Comments:
Fuses Comments:
Trouble Signals Comments:
Disconnect Switches Comments:
Ground-fault Monitoring Comments:
Supervision Comments:
Local annunciator Comments:
Remote annunciator Comments:
Remote power panels Comments:
Secondary Power Visual Inspection:
Functional Test:
by front door
6 RPS 2per Floor
120v Data Closet Rm 102.2 in front of panel breaker panel 1BA circuit 19
Battery In Panel
Sealed Lead Acid 12/35 x2 x x
X X x x
X x x x x x
Page: 3 Rev Date: 1/13/2023
Battery Condition Comments:
Load Voltage Comments:
Discharge Test Comments:
Remote panel batteries Comments:
Batteries marked with date of manufacturer Comments:
Alarm and Supervisory Alarm Initiating Device (Attach supplementary sheets)
Notification Appliances (Attach supplementary sheets)
Interface Equipment (Attach supplementary sheets)
Supervising Station Monitoring Yes: No:
Alarm Signal Comments (Including Time):
Alarm restoration Comments (Including Time):
Trouble signal Comments (Including Time):
Trouble restoration Comments (Including Time):
Supervisory Signal Comments (Including Time):
Supervisory Restoration Comments (Including Time):
Public Emergency Alarm Reporting System Yes: No:
Alarm Signal Comments (Including Time):
Alarm restoration Comments (Including Time):
Trouble signal Comments (Including Time):
Trouble restoration Comments (Including Time):
Supervisory Signal Comments (Including Time):
Supervisory Restoration Comments (Including Time):
Notifications that testing is Complete:
Monitoring Company Contact:
Building Management Contact:
X X
X X x x
X X
X
X x x x x
Page: 4 Rev Date: 1/13/2023
Time: Time:
Building Occupants Contact:
Time
AHJ
Contact:
Time
Other if required:
System restored to normal operation Date:
Time:
By:
System Certification Signed: Printed Name:
Organization: Title:
Phone: License # (with NICET or State License):
Wrap Up counts & Information System Devices Total Number of Units in
Building Total Number Units
Tested Test Results Acceptable
N/A YES NO
Bells, Horns & Chimes Voice Speakers (voice clarity) Operations Test
1. Smoke Detector
2. Duct Detector
Sensitivity Test
1. Smoke Detector
2. Duct Detector
Heat Detectors Sprinkler Flow Switches Sprinkler Supervisory Switches Visual Alarm Devices Manual Pull Stations Automatic Door Unlocks Automatic Door Release
Communication Equipment Total Number of Units in Building
Total Number Units Tested
Test Acceptable
N/A YES NO
Phone Sets Phone Jacks Call-in Signal
03/14/2024
0930 0930
65 65 x
221 X
10 x
19 x
5 x
4 x
98 x
29 x
1 x
Page: 5 Rev Date: 1/13/2023
SYSTEM FUNCTIONALITY YES NO
Number of stories?
Do all locking devices release upon activation of the fire alarm system?
Do all locking devices release upon power failure?
Does the door to roof unlock?
Do doors unlock but not unlatch?
Is there an access key at the control panel for doors that fail to unlock?
System Devices Total Number of Units in
Building
Total Number Units Tested Test Acceptable
N/A YES NO
Electric Strike
Electric Bolt
Other locking devices
Building is not equipped with Stairway Door Lock system.
Acceptance by Owner or Owner’s Representative:
Signed: Printed Name:
Date: Organization:
Title: Phone:
Problems Found:
X x x x x12
2nd Floor West NAC circuit NOT working, unable to access Rm 199.6 smoke detectors
1st Floor Central RPS batteries need replaced Room 112 does not exist, cant find devices Rm 214/193.2 cannot find devices
No access to Bldgs 400/500
Page: 6 Rev Date: 1/13/2023
Corrections Made:
3/18 accessed and tested Bldg 3000/4000 all devices passed
3/18 Replaced Batteries in RPS 1st floor Central
Page: 7 Rev Date: 1/13/2023
Notification Appliance Supplementary Record of Inspection & Testing
This form is supplemental to the system record of inspection & testing. This form is to be completed by the system inspection and testing contractor at the time of the inspection and/or test.
Inspection/Test Date & Time: ______________ Completed Date &Time: ___________
Number of supplementation pages Attached: _______
Property Information Name of Property:
Address:
Notification Appliance Test Results Appliance Type Location / Identifier: Pass Fail Other
Page: 8 Rev Date: 1/13/2023
Supplementary Record of Inspection & Testing (Continued)
Notification Appliance Test Results Appliance Type Location / Identifier: Pass Fail Other
Page: 9 Rev Date: 1/13/2023
Initiation Devices Supplementary Record of Inspection & Testing
This form is supplemental to the system record of inspection & testing. This form is to be completed by the system inspection and testing contractor at the time of the inspection and/or test.
Inspection/Test Date & Time: ______________ Completed Date &Time: ___________
Number of supplementation pages Attached: _______
Property Information Name of Property:
Address:
Initiating Device Test Results Device Type Location / Identifier & Address: Pass Fail Other
Page: 10 Rev Date: 1/13/2023
Supplementary Record of Inspection & Testing (Continued)
Initiating Device Test Results Device Type Location / Identifier & Address: Pass Fail Other