This document is a set of Questions and Answers related to a federal contract opportunity for annual inspection of the fire alarm systems at the Rocky Mountain Research Station Moscow Forestry Sciences Lab in Moscow, Idaho.
The contract opportunity, Solicitation Number 1240BG24Q0059, is for the annual inspection and testing of the fire alarm systems in the main building (20,493 square feet over 3 stories with 2 additional landings) and the rain lab (6,400 square feet, 1 story with a loft). The Government does not have an incumbent contractor for this work and is seeking a new contractor to perform the inspections in compliance with NFPA 72. The questions cover details about the existing fire alarm system, including the types of panels, whether any components are not fully operational, and the availability of approved fire alarm prints and an elevator reset key on site. The answers indicate the Government has not identified any known issues with the system at this time.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Q and A (5).pdf | ||
| Previous Inspection Sheet.pdf | ||
| Q and A (3).pdf | ||
| Commercial Services_Combined_Updated.pdf | ||
| Q and A.pdf | ||
| Commercial Services_Combined.pdf | ||
| Statement of Work.pdf | ||
| wage.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1240BG24Q0059 – FIRE ALARM INSPECTIONS – MOSCOW ID
1. Is there incumbent and what is the award no.?
a. No – no prior award
2. What are the square footages of each building, and what are the building levels?
a. Rain Lab – 1 story with a loft, 6,400sf
b. Main Building – 3 stories with 2 additional landings, 20,493sf
3. Will there be a site visit at location?
a. No
4. Can you provide information on what types of panels there are?
a.
b.
5. As far as the working order of the equipment, is there anything known to be not working or not fully operational?
a. The is no known issues at this time.
6. Do you have copies of the approved FA prints.(Digital or hard copies)
a. I’m not entirely sure what FA prints are. I believe he is asking for the site plans detailing where the fire alarms are. We have hard copies of these.
7. If the system has elevator recall when the alarm is tested, do you have the elevator reset key on site?
a. we do have the reset key on site.
File details come from the government source that posted it. Updated .