Attachment 5 Fire Alarm Inspection Report_2-26-26.pdf

PDF 1 MB Posted

Attached to
Upgrade Fire Alarm Control Panel & Replace Smoke and Heat Detectors (Morris, MN)
Solicitation number
1232SA26Q1444
Issued by

About this file

This is a fire alarm system inspection and testing record for the USDA-ARS-MWA (Agricultural Research Service - Midwest Area) facility located at 803 Iowa Ave, Morris, MN 56267. The inspection was conducted by BAN-KOE Companies, an alarm technician company based in Sioux Falls, SD, with lead inspector Aaron Haberman performing the work over two days (February 23-24, 2026) totaling 5 hours. The system was tested in accordance with NFPA 72, 2013 edition, Chapter 14, and passed all inspection and functional testing requirements.

The fire alarm system comprises an EST Model 3 control unit with 120 VAC primary power (20 amps) protected by a circuit breaker located at EP-1, and secondary power consisting of two 12VDC 44AH batteries located in a cabinet below the FACP. The system includes 26 manual fire alarm boxes, 75 ion detectors, 10 photo detectors, 6 duct detectors, and 24 heat detectors across multiple buildings, all configured on B-style circuits with integrity monitoring enabled. Notification appliances consist of three circuits with combination horn-strobe devices. All initiating devices (127 smoke detectors, 17 heat detectors, 18 pull stations, and 8 duct detectors distributed across nine buildings) were tested and passed. Secondary power batteries and all system components including control units, lamps/LEDs, fuses, trouble signals, disconnect switches, ground-fault monitoring, supervision, and interface equipment (door holders, HVAC shutdown, damper activation) passed both visual inspection and functional testing. Building management contact Beth Burmeister and building occupants contact Auden were notified at 11:00 on testing start and completion at 10:30 on February 24, 2026. The system was restored to normal operation on 2/24/2026 at 10:30 AM with no defects or malfunctions noted.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date Tech Name Start Stop Hours*

2/23/2026 AARON 1:30 4:30 3

2/24/2026 AARON 8:30 10:30 2

*Round to the Quarter Hour Total Hours: 5

Inspection Frequency: ANNUAL

Fire alarm Record of Inspection and Testing

Location:

USDA-ARS-MWA

803 IOWA AVE, MORRIS, MN 56267

PASS

Inspector Signature:

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA 72 CODES AND STANDARDS

Inspection Results:

AARON HABERMANLead Inspector Name:

ALARM TECHNICIANInspector Title:

Inspection Frequency:

Inspection/Test Start Date/Time: Inspection/Test Completion Date/Time:

1. PROPERTY INFORMATION

Name of Property:

Site Address:

Description of property:

Name of Property Representative:

Billing Address:

Phone:

2. TESTING AND MONITORING INFORMATION

Testing organization:

Address:

Phone:

Monitoring organization:

Address:

Phone:

Account number:

Means of transmission:

3. DESCRIPTION OF SYSTEM OR SERVICE

NFPA 72 Edition: Additional description of system(s):

3.1 Control Unit

Manufacturer: Model number:

3.2 Software and Firmware

3.3 System Documentation (if applicable)

Location:

3.3 System Power

3.3.1 Primary (Main) Power

Nominal voltage:

Overcurrent protection type:

DACT IP CELL COMBO OTHER

ANNUAL

2/24/26 10:30 AM2/23/26 1:30 PM

An owners Manual, a copy of the manufacturer's instructions, a written sequence of operation, record of completion and inspection documents are stored on site. WITH OWNER

Amps: Disconnecting means location: #3

N/APhone:

120 VAC

CIR BRKR

n/aN/A

SUPPORT@BANKOE.COM

EST 3

Entity to which alarms are retransmitted:

Phone line 1: Phone line 2:

Amps:

N/AN/A

N/A

Location: EP-1

SYSTEM RECORD OF INSPECTION AND TESTING

E-mail:Fax:

Fax: E-mail:

E-mail:Fax:

1-800-969-0963

4312 N HAINJE AVE, SIOUX FALLS, SD 57104

USDA-ARS-MWA

N/A

3.4

OFFICE

BAN-KOE COMPANIES

N/A

N/A

Firmware revision number:

N/A

803 IOWA AVE, MORRIS, MN 56267

803 IOWA AVE, MORRIS, MN 56267

3. DESCRIPTION OF SYSTEM OR SERVICE (continued)

3.3.2 Secondary Power

Type: Location:

Battery Type (if applicable):

4. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring Organization Time:

Building Management Time:

Building Occupants Time:

Authority having jurisdiction Time:

Other, if required Time:

5. DEVICES AND CIRCUIT INFORMATION

5.1 Initiating Devices

Manual Fire Alarm Boxes

Ion Detectors

Photo Detectors

Duct Detectors

Heat Detectors

Waterflow Switches

Supervisory Switches

Other (Specify):

Alarm verification feature is disabled enabled

5.2 Notification Appliances

Bells

Horns

Strobes

Speakers

Other (Specify):

No. of alarm notification appliance circuits:

Are circuits monitored for integrity? X Yes No

N/A N/A

Appliances Installed Circuit Style Appliances Tested

NA

2X 12VDC 44AH BATTERIES

75 B 75

Contact:

NA NA

11:00

N/A

Quantity of Quantity of

Contact: AUDEN

Contact: N/A

24 B 24

NA B NA

Quantity of Quantity of

Devices Installed Circuit Style Devices Tested 26 B 26

BATTERY CAB BELOW FACP

SLA

NA

10 B 10

6 B 6

N/A

NA B

Contact: N/A

X B

X

NA NA

B X

X B X

S

NA NA NA

COMBO HORN-STROBE

NA

SYSTEM RECORD OF INSPECTION AND TESTING (continued)

Contact: BETH BURMEISTER 11:00

6. TESTING RESULTS

6.1 Control Unit and Related Equipment

Control unit

Lamps/LEDs/LCDs

Fuses

Trouble signals

Disconnect switches

Ground-fault monitoring

Supervision

Local annunciator

Remote annunciators

Remote power panels

PASS

PASS

PASS

PASS

Description Visual

Inspection Functional

Test

PASS PASS

PASS

PASS

PASSPASS

PASS

PASS

PASS

PASS

PASS

PASS

PASS

PASS

PASS

PASS

SYSTEM RECORD OF INSPECTION AND TESTING (continued)

PASS

PASS

PASS

PASS

PASS

PASS

PASS

Comments

PASS

PASS

6. TESTING RESULTS (continued)

6.2 Secondary Power

6.3 Supervising Station Monitoring

Description

Alarm Signal

Alarm restore

Trouble signal

Trouble restore

Supervisory signal

Supervisory restore

6.4 Emergency Communication (Voice EVAC)

Paging Microphone Stations

Fire Fighters Phone

System Audibility

System Intelligibility

Prerecorded Message activation

Other NA NA N4

NA NA

6.5 Interface Equipment

Door Holders

HVAC Shutdown

Damper Activation

Elevator Recall

Suppression System

NA

NA

NA

NA

NA

NA

NA

Description Visual

Inspection Functional

Test Comments

Yes No Time Comments

NA

NA

NANA

NANANANA

NA

NA

NA

Battery condition

Load voltage

Discharge test

Charger test

Remote panel batteries

Description Visual

Inspection Functional

Test Comments

PASS PASS PASS

PASS

NA NA

NA

PASS PASS PASS

PASS

NA

NA

PASS PASS PASS

PASS PASS PASS

PASS PASS PASS

NA NA NA

NA

Description Visual

Inspection Functional

Test Comments

PASS PASS PASS

NA NA NA

PASS

PASS

PASS

PASS

PASS

PASS

PASS

PASS

SYSTEM RECORD OF INSPECTION AND TESTING (continued)

PASS PASS

PASS

PASS

NA NA

NANA

8. NOTIFICATIONS THAT TESTING IS COMPLETE

Monitoring Organization Time:

Building Management Time:

Building Occupants Time:

Authority having jurisdiction Time:

Other, if required Time:

9. SYSTEM RESTORED TO NORMAL OPERATION

Date: Time:

10. CERTIFICATION

This system as specified herein has been inspected and tested according to NFPA 72, 2013 edition, Chapter 14.

Signed: Printed Name: Date:

Organization: Title: Phone:

Qualifications:

11. NOTES

11.1 Inspector's Notes

11.2 General Comments

11.1 Defects or malfunctions not corrected at conclusion of system inspection, testing, or maintenance

11.3 Acceptance by Owner or Owners Representative:

The undersigned accepted the test report for the system as specified herein:

Signed: Printed Name: Date:

Organization: Title: Phone:

Email Address:

TESTED FACP AND ALL DEVICES, NOT FAULTS OR FAILURES DURING TEST

2/24/26

ALARM TECHNICIAN 800-969-0963

Contact: NA NA

Contact: BETH BURMEISTER 10:30

SYSTEM RECORD OF INSPECTION AND TESTING (continued)

BANKOE

2/24/2026 10:30

USDA

02/24/26

Contact:

Contact: NA NA

Contact: NA NA

AUDEN 10:30

AARON HABERMAN

Beth Burmeister

1. PROPERTY INFORMATION

Name of property:

Address:

2. INITIATING DEVICE TEST RESULTS

2.1 Sensativity Testing Sensitivity Testing

Date of Last Sensitivity Test: Required Sensitivity Testing Interval:

PASS

SMOKE

SMOKE BUILDING 11 RM A110 STORAGE

11 SMOKE BUILDING 11 A111 A112 MAIL ROOM

18 SMOKE BLD 1 HALL BY RM 34 JANITORS CLOSET

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

SMOKE

SMOKE PASS

PASS

SMOKE

SMOKE

SMOKE

SMOKE

27 SMOKE BLD 1 HALL41 BYRM 16 MENS REST RM

SMOKE BUILDING 1 LAB 40 WEST CHEM LAB

SMOKE BUILDING 1 HALL41 BY OFFICE 10

SMOKE BUILDING 1 LAB 13 PLANT B CHEM

PASS

PASS

PASS

PASS

PASS

SMOKE

INITIATING DEVICE

SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

Zone # or Address Location

1 SMOKE BLD 11 CONF RM A123 SOUTH DETECTOR

2 SMOKE BLD 11 CONF RM A123 NORTH DETECTOR

SMOKE

3 SMOKE BUILDING 11 RM A118 CONF STORAGE

4 SMOKE BUILDING 11 RM A122 PROJECTION

5 SMOKE BUILDING 11 RM A120 JANITOR

SMOKE

PASS

PASS

Device Type Test Results

PASS

SMOKE

PASS

SMOKE PASS8 SMOKE BUILDING 11 102 BY 120 JANITOR

PASS

SMOKE

PASS

PASS

7 SMOKE BUILDING 11 N102 BY CONF ROOM

12 SMOKE BUILDING 11 RM A108 WORKROOM

13 SMOKE BUILDING 1 HALL31 BY RM26 LIBRARY

14 SMOKE BUILDING 1 LAB 32 EAST CHEMICAL

15 SMOKE BLD 1 RM 35 STORAGE EAST CHEM

SMOKE

SMOKE

SMOKE BUILDING 11 102 BY 114 WOMENS

16 SMOKE BLD 1 RM 33 CLOSET EAST CHEM

PASS

PASS

SMOKE

23 SMOKE BUILDING 1 HALL12 BY ROOM 7SMOKE

SMOKE

SMOKE BUILDING 1 RM 34 JANITORS CLOSET

SMOKE

SMOKE

SMOKE

SMOKE

PASS

PASS

PASS

PASS

SMOKE 19 SMOKE BUILDING 1 RM 36 WEIGHING

20 SMOKE BUILDING 1 LAB 38 MIDDLE CHEM LAB

PASS

SMOKE PASS

PASS

SMOKE

6 SMOKE BUILDING 11 A116 DINING ROOM

PASS

SMOKE PASS

21 SMOKE BUILDING 1 RM 39 STORAGE NORTH

22 SMOKE BUILDING 1 RM 39 STORAGE SOUTH

SMOKE

2. INITIATING DEVICE TEST RESULTS (continued)

PASS

PASS

PASS

PASS

SMOKE

SMOKE

SMOKE

HEAT

PULL

SMOKE BUILDING 4 GREENHOUSE ACCESS 15

0032 SMOKE BUILDING 1 18A DROP TOWER

0033 SMOKE BLD 1 RM 18B 186 DROP TOWER EAST

SMOKE

Address Location

0028 SMOKE BUILDING 1 RM 14 BOILER MEZZ N.

0029 SMOKE BUILDING 1 RM 14 BOILER MEZZ S.SMOKE

SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

0030 SMOKE BLD 1 HALL44 BYRM 18 DROP TOWER

0031 SMOKE BLD 1 RM 18 DROP TOWER ENTRY

PASS

Test Results

INITIATING DEVICES

SMOKE PASS

Device Type

Sensitivity Range

Measured Sensitivity

SMOKE PASS

SMOKE PASS

PASS

SMOKE PASS

SMOKE PASS

SMOKE PASS

SMOKE

SMOKE BLD 1 OFFICE 21 COMPUTER TECH

0039 SMOKE BUILDING 1 HALL31 BY 23 ENTRY

0040 SMOKE BUILDING 1 OFFICE 24

0041 SMOKE BUILDING 1 RM 30 MECHANICAL

0042 SMOKE BUILDING 1 RM 27 RECORDS

PASS

HEAT PASS

SMOKE PASS

0049 HEAT BUILDING 4 G.H. SOIL MIXING

0050 DUCT BUILDING 4 G.H. SINK ROOM

SMOKE PASS

SMOKE

0047 SMOKE BUILDING 4 15A GREENHOUSE ACCESS

0043 SMOKE BUILDING 1 OFFICE 25

0044 SMOKE BUILDING 1 RM 26 LIBRARY

0045 SMOKE BUILDING 1 OFFICE 1

0046SMOKE PASS

SMOKE

PASS

SMOKE PASS

SMOKE PASS

SMOKE

0051 DUCT BUILDING 4 G.H. SINK ROOM

0052 SMOKE BUILDING 4 BAY 1 GREENHOUSE HALL

0053 SMOKE BUILDING 4 BAY 2 GREENHOUSE HALL

SMOKE PASS

HEAT HEAT BUILDING 4 LAB 13A NORTH PASS

0054 SMOKE BUILDING 4 BAY 4 GREENHOUSE HALL

PULL

135 PULL BUILDING 11 RM A201 MECHANICAL

PASS

SMOKE PASS

SMOKE 0056 DUCT BUILDING 11 MECHANICAL MEZZ EAST

0057 DUCT BUILDING 11 MECHANICAL MEZZ WEST

134 PULL BUILDING 11 RM A116 LUNCH ROOM

DUCT BUILDING 1 RTU 3

DUCT BUILDING 1 RTU 2 NORTH

DUCT BUILDING 1 RTU 2 SOUTH

HEAT BUILDING 1 LAB 13A SOUTH

PULL BUILDING 11 A101 ENTRY

SMOKE PASS

SMOKE PASS

PASS

PASS

SMOKE PASS

0036 SMOKE BUILDING 1 HALLBY RM 37 JANITOR

0037 SMOKE BUILDING 1 RM 37 JANITOR

SMOKE PASS

SMOKE

0035 SMOKE BLD 1 RM 18B 186 DROP TOWER WEST

0034 SMOKE BLD 1 RM 18B 186 DROP TOWER MIDDLE

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

PULL PASS

PASS

PASS

SMOKE PASS

PASSSMOKE 0048 SMOKE BUILDING 4 G.H. SINK ROOM

SMOKE

Test Results

PULL 136 PULL BUILDING 11 RM A107 RECEIVING PASS

0143 PULL BUILDING 1 HALL 41 BY ROOM 10 PASS

PULL 0144 PULL BUILDING 1 HALL LAB 13 PLANT BIO CHEM PASS

PULL 0141 PULL BUILDING 1 HALL 31 BY LIBRARY PASS

PULL 0142 PULL BUILDING 1 HALL 31 BY NORTH ENTRY PASS

INITIATING DEVICES

SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

Device Type Address Location Sensitivity

Range Measured Sensitivity

PULL 0147 PULL BUILDING 1 RM 49 BOILER SOUTH PASS

PULL 0148 PULL BUILDING 1 MECHANICAL ATTIC PASS

PULL 0145 PULL BUILDING 1 HALL 41 BY RM 16 MENS BATH PASS

PULL 0146 PULL BUILDING 1 RM 49 BOILER NORTH PASS

PULL

PULL 158 PULL BUILDING 4 GREENHOUSE HALL PASS

HEAT 0251 HEAT BUILDING 7 QUONSET BELOW MEZZ PASS

PULL 0149 PULL BUILDING 1 MECH ATTIC EAST PASS

PULL 157 PULL BUILDING 4 HEADHOUSE GH SINK RM PASS

HEAT 0254 HEAT BUILDING 7 QUONSET FRONT OF BLD PASS

HEAT 0255 HEAT BUILDING 6 BUTLER SOUTH PASS

HEAT 0252 HEAT BUILDING 7 QUONSET ABOVE MEZZ PASS

HEAT 0253 HEAT BUILDING 7 QUONSET ON CEILING PASS

SMOKE 0258 SMOKE BUILDING 9 GROWTH CHAMB RM WEST PASS

HEAT 0259 HEAT BUILDING 3 SOIL PROCESSING EAST PASS

HEAT 0256 HEAT BUILDING 6 BUTLER NORTH PASS

SMOKE 0257 SMOKE BUILDING 9 GROWTH CHAMB RM EAST PASS

HEAT 0262 HEAT BULDING 2 RM 55 REPAIR SHOP PASS

HEAT 0263 HEAT BUILDING 2 RM 56A MACHINE SHOP PASS

HEAT 0260 HEAT BUILDING 3 SOIL PROCESSING WEST PASS

HEAT 0261 HEAT BUILDING 2 SHOP 54 PASS

HEAT 0266 HEAT BUILDING 2 RM 56 PLANT PROC WEST PASS

HEAT 0267 HEAT BUILDING 2 RM 56 PLANT PROC EAST PASS

HEAT 0264 HEAT BUILDING 2 RM 56B CARPENTRY SHOP PASS

HEAT 0265 HEAT BUILDING 2 RM56 PLANT PROC. WEST PASS

SMOKE 0270 SMOKE BUILDING 8 HALL113 BY ROOM 112 PASS

SMOKE 0271 SMOKE BUILDING 8 OFFICE 112 PASS

HEAT 0268 HEAT BUILDING 2 RM 56 PLANT PROC EAST PASS

HEAT 0269 HEAT BUILDING 2 RM 57 THRESHING PASS

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

SMOKE 0274 SMOKE BUILDING 8 OFFICE 110 PASS

SMOKE 0275 SMOKE BUILDING 8 OFFICE 109 PASS

SMOKE 0272 SMOKE BUILDING 8 OFFICE 111 PASS

SMOKE 0273 SMOKE BUILDING 8 HALL113 BY ROOM 115 PASS

PULL BUILDING 7 QUONSET FRONT DOOR

PULL BUILDING 8 RM 114 MECHANICAL

PULL BUILDING 8 HALL 113 BY ROOM 112

SMOKE 0278 SMOKE BUILDING 8 HALL113 NORTH EXIT PASS

SMOKE 0279 SMOKE BUILDING 8 OFFICE 107 PASS

SMOKE BUILDING 8 OFFICE 108 PASS

SMOKE 0277 SMOKE BUILDING 8 HALL113 BY ROOM 108 PASS

HEAT 0282 HEAT BUILDING 8 LAB 105 PLANT PHYS PASS

SMOKE 0283 SMOKE BUILDING 8 104 SOIL LAB PASS

SMOKE 0280 SMOKE BUIDLING 8 RM 106 PLANT PHYS PASS

SMOKE 0281 SMOKE BUILDING 8 HALL126 BY PLANT PHYS PASS

SMOKE 0286 SMOKE BUILDING 8 LAB 103 AGRONOMY PASS

SMOKE 0287 SMOKE BUILDING 8 102 WEED RESEARCH PASS

SMOKE 0284 SMOKE BUILDING 8 HALL126 BY ROOM 118 PASS

SMOKE 0285 SMOKE BUILDING 8 HALL 126 BY RM 123 PASS

SMOKE 0290 SMOKE BUILDING 8 LAB 124 PASS

SMOKE 0291 SMOKE BUILDING 8 RM 119 INSTRUMENT RM PASS

SMOKE 0288 SMOKE BUILDING 8 HALL126 BY LAB 102 WEED PASS

SMOKE 0289 SMOKE BUILDING 8 RM 125 CLOSET PASS

SMOKE 0294 SMOKE BUILDING 8 RM 121 PASS

SMOKE 0295 SMOKE BUILDING 8 118A INSTRUMENT PASS

SMOKE 0292 SMOKE BUILDING 8 RM 123 PASS

SMOKE 0293 SMOKE BUILDING 8 RM 120 PASS

SMOKE 0298 SMOKE BUILDING 8 116A STORAGE CLOSET PASS

SMOKE 0299 SMOKE BUILDING 8 LAB 116 ELECTRONICS PASS

HEAT 0296 HEAT BUILDING 8 RM 118 PASS

SMOKE 0297 SMOKE BUILDING 8 LAB 117 MICROBIOLOGY PASS

SMOKE 0302 SMOKE BUILDING 8 RM 114 MECHANICAL PASS

DUCT 0303 DUCT BUILDING 8 MECH PENT ABOVE 115 PASS

SMOKE 0300 SMOKE BUILDING 8 RM 116B OFFICE PASS

SMOKE 0301 SMOKE BUILDING 8 RM 115 JANITOR PASS

PASS

PASS

PULL 0379 PULL BUILDING 7 QUONSET REAR DOOR

PASS

PULL 0378 PASS

PASS

PULL

PULL

PULL 388 PULL BUILDING 8 HALL 126 BY ROOM 107 PASS

INITIATING DEVICES

SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

Device Type Address Location Sensitivity

Range Measured Sensitivity Test Results

SMOKE 0276

PULL 391 PULL BUILDING 9 GROWTH CHAMBER ROOM PASS

PULL 0380 PULL BUILDING 6 BUTLER WALK IN DOOR

PASS

PULL 387 PULL BUILDING 8 HALL 126 BY ROOM 102

PULL 392 PULL BUILDING 3 SOIL PROCESSING PASS

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

Device Type Address Location Sensitivity

Range Measured Sensitivity Test Results

PULL 393 PULL BUILDING 2 RM 54 SHOP WEST DOOR PASS

INITIATING DEVICES

PULL 394 PULL BUILDING 2 RM 56 PLANT PROCESS PASS

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

1. PROPERTY INFORMATION

Name of property:

Address:

2. BATTERY TEST RESULTS

PASSAUX 3 BESIDE FACP 12VDC 7AH 2 UNKNOWN UNKNOWN

PASS

AUX 1 BESIDE FACP 12VDC 7AH 2 UNKNOWN UNKNOWN PASS

AUX 2 BESIDE FACP

UNKNOWN PASS

BPS1 ABOVE FACP 12VDC 7AH 2 UNKNOWN UNKNOWN PASS

FACP MAIN PANEL 12VDC 44AH 2 UNKNOWN

UNKNOWN UNKNOWN

BATTERY

SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

2/23/26 1:30 PM 2/24/26 10:30 AM

803 IOWA AVE, MORRIS, MN 56267

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

Location Description Battery Type / Size Quantity Test Result Date

Manufactured Date Installed

12VDC 7AH 2

File details come from the government source that posted it. Updated .