1232SA25Q0114 Questions and Answers.pdf

PDF 199 KB Posted

Attached to
Repair of 2 Radiators on Standby Generators
Solicitation number
1232SA25Q0114
Issued by

About this file

This document is a Questions and Answers (Q&A) file for Solicitation #1232SA25Q0114 regarding the repair of two radiators on standby generators located at a USDA Agricultural Research Service facility in Ft. Pierce, Florida. The Q&A provides detailed site-specific information for potential contractors, including that the generators are located inside a room, have 120V power outlets available, and require consecutive repair work - first on the 1000kW generator, then the 750kW generator. Both radiators are Modine Industrial Heat Exchanger units, and the solicitation allows for either repair or manufacturer-suggested replacement, provided specifications match. Contractors will need to park within 100 feet of the generators and have sufficient clearance to remove the radiators.

The solicitation is set aside for small businesses under NAICS code 811310, with a business size standard of $12.5 million. The government intends to award a firm fixed-price purchase order with a 60-day performance period. Quotes are due by June 17, 2025, at 1:00 p.m. Central, and must be submitted electronically to the Contract Officer, Erin M. Riffey. The award will be based on the Lowest Priced Technically Acceptable quote, and offerors must have an active SAM.gov registration and complete required representations and certifications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation # 1232SA25Q0114 Subject Requirement: Repair of Two Radiators on Standby Generators

Questions and Answers:

1. Are the generators located inside or outside of an enclosure?

• They are located inside a room.

2. If mounted outside, do they have an awning or roof over them? How much clearance from the roof to the radiator?

• They are mounted inside.

3. If mounted inside, do the doors have enough clearance to remove the radiators?

• Yes.

4. How far is the nearest available parking spot to the generators?

• Within 100’.

5. Will we have access to power onsite?

• Yes. 120V outlets are inside the room.

6. Are you wanting them done at the same time or consecutively?

• Consecutively. 1000kW first, then the 750kW, per the Statement of Work.

7. Will replacement with a new radiator be acceptable versus repair?

• If it is the manufacturer suggested replacement and the specifications match, yes.

8. Can you provide information on the radiators?

• Radiator Information plates provided below.