This is an Asbestos Containing Material and Hazardous Materials Inspection Report prepared by Red Cedar Consulting for the City of Jackson Community Development Department regarding the property located at 1231 Greenwood Avenue, Jackson, Michigan. The inspection was conducted on September 15, 2025, to comply with Environmental Protection Agency (EPA) and Occupational Safety and Health Administration (OSHA) requirements for demolition and renovation activities. The subject property is a 1,474 square foot residential building constructed in 1890 on a 0.38-acre parcel. Red Cedar Consulting collected thirty-one samples from thirteen distinct homogenous groups of suspect asbestos-containing materials and submitted them to APEX Research Inc. Laboratories for polarized light microscopy analysis. The inspection identified friable asbestos-containing materials in window glazing (up to 2 percent asbestos in 19 windows) and HVAC duct wrap, as well as Category I non-friable asbestos-containing material in floor tile (approximately 85 square feet). Additionally, thirty miscellaneous containers, twenty-five gallon containers of paint, eight quart containers of paint, and twenty-four spray cans of miscellaneous paint were documented as hazardous materials requiring proper removal and disposal.
The report recommends that all identified friable asbestos-containing materials, including the HVAC duct wrap and window glazing, be removed prior to any renovation or demolition activities. The Category I resilient floor covering must also be abated to mitigate future exposure. Per regulatory requirements, a Notification of Intent to Renovate/Demolish form must be filed with the Michigan Department of Environmental Quality-Air Quality Division at least ten working days prior to renovation or demolition activities. Asbestos abatement work must be performed by a certified asbestos abatement contractor in compliance with OSHA Asbestos Standards for Construction (29 CFR 1926.1101) and EPA NESHAP (40 CFR Part 61). The report notes that due to the age of construction and multiple additions or renovations, additional inspections may be required if suspect asbestos-containing materials not documented are encountered during demolition activities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1231_Greenwood_-_Demolition.pdf | ||
| 1231_GREENWOOD-_sewer_card.docx | DOCX document | |
| CDBG_Additional_Forms.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P.O. Box 13216 Lansing, MI 48901 Phone: 888.449.4566 Fax: 888.448.8739 www.redcedarconsulting.net
October 13, 2025
Mr. Brian Taylor City of Jackson Community Development Department Jackson, MI 49202
RE: Asbestos Containing Material and Hazardous Materials Inspection 1231 Greenwood Ave. Jackson, MI 49203 Parcel ID: 3-2275.1000
Dear Mr. Taylor:
Red Cedar Consulting has completed an asbestos-containing material (ACM) and hazardous materials inspection at 1231 Greenwood Ave. Jackson, Michigan (Subject Property). This inspection was completed at the request of the City of Jackson to comply with the United States Environmental Protection Agency (USEPA) requirements for demolition and renovation set forth under the National Emissions Standards for Hazardous Air Pollutants (NESHAP, 40 CFR Part 61). This inspection was also completed to comply with the Occupational Safety and Health Administration (OSHA) Asbestos Standards for Construction (29 CFR 1926.1101) which limits employee exposure to asbestos.
SUBJECT PROPERTY
The Subject Property is comprised of a .38-acre residential parcel which contains a 1474 square foot residential building (the Building) constructed in 1890. The Building was constructed on a concrete basement with two aboveground floors. The exterior walls of the Building were finished with wood lap under vinyl siding while the roof was sealed with asphalt shingles. The Building can be further divided into a front entry, living room, dining room, kitchen, bath and bedroom on the first floor while the second floor contains three bedrooms.
VISUAL INSPECTION AND SAMPLING
Asbestos Containing Materials Inspection
Jeff Cain of Red Cedar Consulting (Red Cedar), accredited State Of Michigan/EPA Asbestos Building Inspector (Accreditation Number A14057) who completed training per the Michigan Asbestos Workers Accreditation Act 440, completed an inspection of the Subject Property on September 15, 2025, for suspected asbestos containing building materials.
Project No.: 12-1027
This inspection, and subsequent sample collection was completed in accordance with the USEPA Asbestos Hazard Emergency Response Act (AHERA) (40 CFR Part 763) assessment and sampling protocol.
During the completion of the inspection, each area of the Subject Property was visually inspected for asbestos containing building materials (ACBM). Following the completion of the visual inspection, Red Cedar staff identified each suspect area of friable and non-friable ACBM and sorted them into one of three homogenous categories for sampling purposes. AHERA defines friable as a material that when dry, may be crumbled, pulverized, or reduced to powder by hand pressure. A homogenous area is defined by OSHA as an area of surfacing, thermal system insulation (TSI) or miscellaneous material that is uniform in color and texture. Surfacing materials are most commonly found in sprayed-on, troweled-on or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members. TSI refers to materials applied to pipes, fittings, boilers, ductwork, or other components to prevent heat loss or gain, or condensation. Any material that does not fall under the surfacing or TSI category, such as floor tile, drywall, and acoustical ceiling tile are placed into the miscellaneous materials category.
Following the completion of the visual inspection, Red Cedar staff identified the following materials as suspect ACBM:
• Asphalt Shingle
• Roof Tar
• Siding Paper
• Window Glaze
• 12”x12” Floor Tile
• Floor Tile Multi-layer
• 2’x4’ Ceiling Tile
• 1’x1’ Ceiling Tile
• Drywall and Joint Compound
• Plaster
Red Cedar staff collected thirty-one samples of suspect ACBM separated into thirteen distinct homogenous groups for laboratory analysis. Samples were collected and submitted to APEX Research Inc. Laboratories (APEX) (Accreditation Number 102118-0) for laboratory analysis. Analysis was completed utilizing polarized light microscopy (PLM) which is the Environmental Protection Agency (EPA) approved method for analysis of bulk materials for asbestos. PLM analysis completed pursuant to method (EPA 600/M4-82-020) identifies asbestos fiber bundles by the visual properties displayed when the sample is treated with various dispersion staining liquids. The laboratory report completed following the sample analysis indicates if asbestos is present, and at what percentage along with a description and percentage of other fibrous and non-fibrous materials and sample color. Chain-of-custody documentation was followed from sample collection through shipping and receiving of the samples at the designated laboratory. The documentation assures that samples will meet the quality assurance/quality control measures defined by AHERA. The laboratory analytical report prepared by APEX for the thirty-one samples is included as Attachment A.
Hazardous Materials Inspection
On September 15, 2025, the Subject Property was also inspected for the presence of hazardous materials which include but are not limited to polychlorinated biphenyls (PCBs) and potential mercury containing equipment and any items or containers that may contain or be classified as a hazardous or regulated material. Each material, if identified, was documented along with the approximate location. Any materials identified as hazardous are included in Table 1.
INSPECTION RESULTS AND RECOMMENDATIONS
During the completion of the asbestos inspection, thirty-one samples of suspect ACM were collected and are documented in Table 2 along with the Red Cedar sample number, description, friability, material type, ACM classification, sample location, material quantity and laboratory analytical results. A Site Diagram was prepared which provides the general building layout and sample locations and is included as Attachment B.
ACM, as defined by the USEPA NESHAP is “any material containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763 Section 1, Polarized Light Microscopy”.
Friable ACM is defined by NESHAP as any material containing more than 1 percent asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. Friable ACM is a concern due to the ease of unintentionally disturbing the ACM which may result in “visible emissions” which is known as a Fiber Release Episode.
Non-friable asbestos-containing material is defined as “material containing more than 1 percent asbestos that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure. Non-friable ACMs are separated into Category I and Category II ACM. Category I ACM is any asbestos containing packing’s, gaskets, resilient floor coverings (vinyl floor tile and linoleum are examples of these) and asphalt roofing products. Category II ACM is stated by NESHAP as any material excluding Category I non-friable ACM such as drywall, plaster or fiberboard insulation.
Presumed Asbestos Containing Material
Presumed Asbestos Containing Materials (PACM) are suspect surfacing, TSI and miscellaneous materials found in buildings constructed prior to 1980 which are classified as and due to the age of the structure, are assumed to be ACM and do not require sample collection and analysis. OSHA dictates that PACM may be “rebutted” following a complete inspection pursuant to AHERA protocol.
The HVAC Duct Wrap located in the Building was classified as PACM due to the age of the structure and samples were not collected.
Table 3 lists the location, material description, friability, condition, material type (surfacing, thermal or miscellaneous) and approximate quantity of all PACM documented at the Subject Property.
Table 4 provides a summary of all ACM documented at the Subject Property which includes the material location, description, and approximate quantity.
Friable ACM’s
Window glazing samples collected from the interior of the Building were found to contain up to 2% asbestos following analysis. The assessment to quantify the extent of this material identified nineteen windows at the following locations that would fall into the same homogenous group. The locations of the windows are listed below:
• Basement (4 windows 18” wide x 24” tall)
• Basement (1 window 18” wide x 36” tall)
• 1st Floor (2 windows 36” wide x 36” tall)
• 1st Floor (5 windows 36" wide x 60” tall)
• 1st Floor (2 windows 54" wide x 60” tall)
• 1st Floor (1 window 24" wide x 24” tall)
• 1st Floor (1 window 24” wide x 40” tall)
• 2nd Floor (3 windows 36" wide x 52” tall)
Duct Wrap identified in the building in conjunction with the forced air heating system is classified as friable ACM. The visual assessment to quantify the extent of this material identified HVAC Duct Wrap at the following locations within the basement, first and second floors:
• Front Entry (1 register, 10 sq. ft.)
• Living (1 register, 10 sq. ft.)
• Dining (1 register, 10 sq. ft.)
• Kitchen (1 register, 10 sq. ft.)
• Bedroom 1 (1 register, 10 sq. ft.)
• 2nd Fl. Bedroom 2 (1 register, 10 sq. ft. and vertical chase to basement, 25 sq. ft.)
• 2nd Fl. Bedroom 4 (1 register, 10 sq. ft. and vertical chase to basement, 25 sq. ft.)
Category I ACM
One type of resilient floor covering (Floor Tile Multi-layer) located within the 1st floor Bathroom was found to contain up to 2% Chrysotile asbestos. The assessment to quantify the extent of this material identified approximately 85 sq. ft. of this material within the Building.
Category II ACM
No Category II ACM was identified during the completion of this inspection.
RECOMMENDATIONS
Asbestos Containing Materials
HVAC material identified in the Building system and listed below is classified as friable ACM and should be removed prior to any renovation/demolition activities.
• Front Entry (1 register, 10 sq. ft.)
• Living (1 register, 10 sq. ft.)
• Dining (1 register, 10 sq. ft.)
• Kitchen (1 register, 10 sq. ft.)
• Bedroom 1 (1 register, 10 sq. ft.)
• 2nd Fl. Bedroom 2 (1 register, 10 sq. ft. and vertical chase to basement, 25 sq. ft.)
• 2nd Fl. Bedroom 4 (1 register, 10 sq. ft. and vertical chase to basement, 25 sq. ft.)
Friable asbestos containing window glazing was identified on nineteen windows throughout the Building.
The locations of these windows that should be abated prior to demolition/renovation activities are listed below:
• Basement (4 windows 18” wide x 24” tall)
• Basement (1 window 18” wide x 36” tall)
• 1st Floor (2 windows 36” wide x 36” tall)
• 1st Floor (5 windows 36" wide x 60” tall)
• 1st Floor (2 windows 54" wide x 60” tall)
• 1st Floor (1 window 24" wide x 24” tall)
• 1st Floor (1 window 24” wide x 40” tall)
• 2nd Floor (3 windows 36" wide x 52” tall)
Please note: Other different sized windows are located throughout the Building but these windows were assessed and found to be constructed either without window glazing or were sampled and found to not contain asbestos and therefore are not required to be removed.
The Category I resilient floor covering (Floor Tile Multilayer) is a non-friable ACM that should be abated to mitigate any future exposure.
Please note: The location of samples obtained during this inspection were in a random fashion and areas that were not identified during this inspection may be damaged or have become damaged since the inspection was completed. If Category I or Category II friable materials are discovered prior to or during the demolition/renovation process, these materials must be abated prior to commencement of any demolition/renovation activities at the Subject Property.
Hazardous Materials
Hazardous Materials identified at the Subject Property and documented in Table 1 which require proper removal and disposal consist of the following items:
• 5-Gallon Container Misc. (30)
• Gallon Container Misc. Paint (25)
• Quart Container Misc. Paint (8)
• Spray Can Misc. Paint (24)
REGULATORY REQUIREMENTS
A Notification of intent to Renovate/Demolish form must be filed with the Michigan Department of Environmental Quality- Air Quality Division at least 10 working days prior to any renovation or demolition activities at a site.
The Notification of Intent to Renovate/Demolish form must also be completed and submitted to the MIOSHA-Asbestos Program whenever demolition, encapsulation and/or renovation activities at a site involving greater than ten lineal feet and/or fifteen square feet of ACM will be completed.
Regulated asbestos containing materials per NESHAP (40 CFR Part 61) which falls into any of the following categories are ACM’s that must be removed prior to any renovation/demolition activities at the Subject Property.
• Friable asbestos material.
• Category I non-friable ACM that has become friable.
• Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading.
• Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of renovation or demolition operations.
Asbestos abatement should only be performed by a certified asbestos abatement contractor licensed to complete abatement work. The contractor must also follow the standards and requirements set forth per the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) and the USEPA NESHAP (40 CFR Part 61).
Additional information regarding the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) and the USEPA NESHAP (40 CFR Part 61) can be obtained by contacting the associated agency below.
NESHAP Asbestos Program MIOSHA-CSHD-Asbestos Program Department of Environmental Quality State of Michigan Phone: 517-284-6777 Phone: 517-284-7680 Email: asbestos@michigan.gov
DISCLAIMER
Red Cedar Consulting performed destructive testing methods in an attempt to access and inspect all areas of the Building. Unfortunately, due to the age of construction along with multiple additions/renovations that may have been completed on the Building, additional inspections may be required if suspect ACM material not documented within this report is encountered during renovation/demolition activities.
This report was prepared at the request and for exclusive use by the City of Jackson and may not be reproduced or sold without written permission from Red Cedar Consulting.
We appreciate the opportunity to provide the requested services. Please contact us at (888) 449-4566 with any questions or concerns.
Sincerely, Red Cedar Consulting
Aaron Paquet
Michigan/EPA Certified Asbestos Building Inspector (A30955)
©2025 Red Cedar Consulting, LLC.
Attachment A
APEX Research Laboratory Analytical Results
Certificate of Laboratory Analysis Test Method, Polarized Light Microscopy (PLM)
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 01 Asbestos Present: NO Cellulose - 40%
Cust. #: GA-HM-01A No Asbestos Observed Other - 60% Material: Roofing M/L Location:
Appearance: black,fibrous,nonhomogenous Layer: 1 of 2
Lab ID #: 119782 - 01a Asbestos Present: NO Cellulose - 40% Cust. #: GA-HM-01A No Asbestos Observed Other - 60% Material: Black Shingle Location:
Appearance: black,fibrous,nonhomogenous Layer: 2 of 2
Lab ID #: 119782 - 02 Asbestos Present: NO Cellulose - 40% Cust. #: GA-HM-01B No Asbestos Observed Other - 60% Material: Roofing M/L Location:
Appearance: black,fibrous,nonhomogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Project #: Jackson, MI
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. Liability limited to cost of analysis.
Project: 1231 Greenwood Ave.
NVLAP Lab Code 102118-0
APEX Research Inc., 7717 Kensington Ct., Brighton, MI 48116
(734) 449-9990, Fax (734) 449-9991 Page 1 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 02a Asbestos Present: NO Cellulose - 40%
Cust. #: GA-HM-01B No Asbestos Observed Other - 60% Material: Black Shingle Location:
Appearance: black,fibrous,nonhomogenous Layer: 2 of 2
Lab ID #: 119782 - 03 Asbestos Present: NO Cellulose - 10% Cust. #: GA-HM-02A No Asbestos Observed Other - 90% Material: Roof Tar Location:
Appearance: black,fibrous,homogenous Layer: 1 of 1
Lab ID #: 119782 - 04 Asbestos Present: NO Cellulose - 10% Cust. #: GA-HM-02B No Asbestos Observed Other - 90% Material: Roof Tar Location:
Appearance: black,fibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 2 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 05 Asbestos Present: NO Cellulose - 90%
Cust. #: GA-HM-03A No Asbestos Observed Other - 10% Material: Siding Paper Location:
Appearance: brown,fibrous,homogenous Layer: 1 of 1
Lab ID #: 119782 - 06 Asbestos Present: NO Cellulose - 90% Cust. #: GA-HM-03B No Asbestos Observed Other - 10% Material: Siding Paper Location:
Appearance: brown,fibrous,homogenous Layer: 1 of 1
Lab ID #: 119782 - 07 Asbestos Present: YES Other - 98% Cust. #: GA-HM-04A Chrysotile - 2% Material: Basement Window Glaze Location:
Appearance: white,fibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 3 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 08 Asbestos Present:
Cust. #: GA-HM-04B Material: Basement Window Glaze Location: NOT ANALYZED Appearance:
Layer: 1 of 1
Lab ID #: 119782 - 09 Asbestos Present: YES Other - 98% Cust. #: GA-HM-05A Chrysotile - 2% Material: 1st Floor Window Glaze Location:
Appearance: white,fibrous,homogenous Layer: 1 of 1
Lab ID #: 119782 - 10 Asbestos Present:
Cust. #: GA-HM-05B Material: 1st Floor Window Glaze Location: NOT ANALYZED Appearance:
Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 4 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 11 Asbestos Present: YES Other - 98%
Cust. #: GA-HM-06A Chrysotile - 2% Material: 2nd Floor Window Glaze Location:
Appearance: white,fibrous,homogenous Layer: 1 of 1
Lab ID #: 119782 - 12 Asbestos Present:
Cust. #: GA-HM-06B Material: 2nd Floor Window Glaze Location: NOT ANALYZED Appearance:
Layer: 1 of 1
Lab ID #: 119782 - 13 Asbestos Present: NO Other - 100% Cust. #: GA-HM-07A No Asbestos Observed Material: 12"x12" Blue Floor Tile Location:
Appearance: blue,nonfibrous,homogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 5 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 13a Asbestos Present: NO Other - 100%
Cust. #: GA-HM-07A No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 119782 - 14 Asbestos Present: NO Other - 100% Cust. #: GA-HM-07B No Asbestos Observed Material: 12"x12" Blue Floor Tile Location:
Appearance: blue,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 119782 - 14a Asbestos Present: NO Other - 100% Cust. #: GA-HM-07B No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 6 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 15 Asbestos Present: NO Other - 100%
Cust. #: GA-HM-08A No Asbestos Observed Material: 12"x12" Brown Floor Tile Location:
Appearance: brown,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 119782 - 15a Asbestos Present: NO Other - 100% Cust. #: GA-HM-08A No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 119782 - 16 Asbestos Present: NO Other - 100% Cust. #: GA-HM-08B No Asbestos Observed Material: 12"x12" Brown Floor Tile Location:
Appearance: brown,nonfibrous,homogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 7 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 16a Asbestos Present: NO Other - 100%
Cust. #: GA-HM-08B No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 119782 - 17 Asbestos Present: YES Other - 98% Cust. #: GA-HM-09A Chrysotile - 2% Material: White Floor Tile M/L Location:
Appearance: white,fibrous,homogenous Layer: 1 of 6
Lab ID #: 119782 - 17a Asbestos Present: NO Cellulose - 1% Cust. #: GA-HM-09A No Asbestos Observed Other - 99% Material: Mastic Location:
Appearance: black,nonfibrous,homogenous Layer: 2 of 6
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 8 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 17b Asbestos Present: YES Other - 98%
Cust. #: GA-HM-09A Chrysotile - 2% Material: Beige Floor Tile Location:
Appearance: beige,fibrous,homogenous Layer: 3 of 6
Lab ID #: 119782 - 17c Asbestos Present: NO Cellulose - 1% Cust. #: GA-HM-09A No Asbestos Observed Other - 99% Material: Mastic Location:
Appearance: black,nonfibrous,homogenous Layer: 4 of 6
Lab ID #: 119782 - 17d Asbestos Present: NO Cellulose - 80% Cust. #: GA-HM-09A No Asbestos Observed Other - 20% Material: Fiberboard Location:
Appearance: brown,fibrous,nonhomogenous Layer: 5 of 6
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 9 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 17e Asbestos Present: NO Cellulose - 40%
Cust. #: GA-HM-09A No Asbestos Observed Other - 60% Material: Sheet Floor/Felt Location:
Appearance: brown,fibrous,nonhomogenous Layer: 6 of 6
Lab ID #: 119782 - 18 Asbestos Present:
Cust. #: GA-HM-09B Material: White Floor Tile M/L Location: NOT ANALYZED Appearance:
Layer: 1 of 6
Lab ID #: 119782 - 18a Asbestos Present: NO Cellulose - 1% Cust. #: GA-HM-09B No Asbestos Observed Other - 99% Material: Mastic Location:
Appearance: black,nonfibrous,homogenous Layer: 2 of 6
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 10 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 18b Asbestos Present:
Cust. #: GA-HM-09B Material: Beige Floor Tile Location: NOT ANALYZED Appearance:
Layer: 3 of 6
Lab ID #: 119782 - 18c Asbestos Present: NO Cellulose - 1% Cust. #: GA-HM-09B No Asbestos Observed Other - 99% Material: Mastic Location:
Appearance: black,nonfibrous,homogenous Layer: 4 of 6
Lab ID #: 119782 - 18d Asbestos Present: NO Cellulose - 80% Cust. #: GA-HM-09B No Asbestos Observed Other - 20% Material: Fiberboard Location:
Appearance: brown,fibrous,nonhomogenous Layer: 5 of 6
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 11 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 18e Asbestos Present: NO Cellulose - 40%
Cust. #: GA-HM-09B No Asbestos Observed Other - 60% Material: Sheet Floor/Felt Location:
Appearance: brown,fibrous,nonhomogenous Layer: 6 of 6
Lab ID #: 119782 - 19 Asbestos Present: NO Cellulose - 40% Cust. #: GA-HM-10A No Asbestos Observed Mineral Wool - 30% Material: 2'x4' Drop Ceiling Tile Other - 30% Location:
Appearance: beige,fibrous,homogenous Layer: 1 of 1
Lab ID #: 119782 - 20 Asbestos Present: NO Cellulose - 40% Cust. #: GA-HM-10B No Asbestos Observed Mineral Wool - 30% Material: 2'x4' Drop Ceiling Tile Other - 30% Location:
Appearance: beige,fibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 12 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 21 Asbestos Present: NO Cellulose - 90%
Cust. #: GA-HM-11A No Asbestos Observed Other - 10% Material: 1'x1' Ceiling Tile Location:
Appearance: brown,fibrous,homogenous Layer: 1 of 1
Lab ID #: 119782 - 22 Asbestos Present: NO Cellulose - 90% Cust. #: GA-HM-11B No Asbestos Observed Other - 10% Material: 1'x1' Ceiling Tile Location:
Appearance: brown,fibrous,homogenous Layer: 1 of 1
Lab ID #: 119782 - 23 Asbestos Present: NO Cellulose - 20% Cust. #: GA-HM-12A No Asbestos Observed Other - 80% Material: Drywall Location:
Appearance: white,fibrous,nonhomogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 13 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 23a Asbestos Present: NO Other - 100%
Cust. #: GA-HM-12A No Asbestos Observed Material: Joint Compound Location:
Appearance: white,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 119782 - 24 Asbestos Present: NO Cellulose - 20% Cust. #: GA-HM-12B No Asbestos Observed Other - 80% Material: Drywall Location:
Appearance: white,fibrous,nonhomogenous Layer: 1 of 2
Lab ID #: 119782 - 24a Asbestos Present: NO Other - 100% Cust. #: GA-HM-12B No Asbestos Observed Material: Joint Compound Location:
Appearance: white,nonfibrous,homogenous Layer: 2 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 14 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 25 Asbestos Present: NO Other - 100%
Cust. #: GA-HS-01A No Asbestos Observed Material: Plaster Finish Coat on Lathe Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 119782 - 25a Asbestos Present: NO Hair - 5% Cust. #: GA-HS-01A No Asbestos Observed Other - 95% Material: Plaster Base Coat Location:
Appearance: grey,fibrous,homogenous Layer: 2 of 2
Lab ID #: 119782 - 26 Asbestos Present: NO Other - 100% Cust. #: GA-HS-01B No Asbestos Observed Material: Plaster Finish Coat on Lathe Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 15 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 26a Asbestos Present: NO Hair - 2%
Cust. #: GA-HS-01B No Asbestos Observed Other - 98% Material: Plaster Base Coat Location:
Appearance: grey,fibrous,homogenous Layer: 2 of 2
Lab ID #: 119782 - 27 Asbestos Present: NO Other - 100% Cust. #: GA-HS-01C No Asbestos Observed Material: Plaster Finish Coat on Lathe Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 119782 - 27a Asbestos Present: NO Hair - 2% Cust. #: GA-HS-01C No Asbestos Observed Other - 98% Material: Plaster Base Coat Location:
Appearance: grey,fibrous,homogenous Layer: 2 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 16 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 28 Asbestos Present: NO Other - 100%
Cust. #: GA-HS-01D No Asbestos Observed Material: Plaster Finish Coat on Lathe Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 119782 - 28a Asbestos Present: NO Hair - 2% Cust. #: GA-HS-01D No Asbestos Observed Other - 98% Material: Plaster Base Coat Location:
Appearance: grey,fibrous,homogenous Layer: 2 of 2
Lab ID #: 119782 - 29 Asbestos Present: NO Other - 100% Cust. #: GA-HS-01E No Asbestos Observed Material: Plaster Finish Coat on Lathe Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 17 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 29a Asbestos Present: NO Hair - 2%
Cust. #: GA-HS-01E No Asbestos Observed Other - 98% Material: Plaster Base Coat Location:
Appearance: grey,fibrous,homogenous Layer: 2 of 2
Lab ID #: 119782 - 30 Asbestos Present: NO Other - 100% Cust. #: GA-HS-01F No Asbestos Observed Material: Plaster Finish Coat on Lathe Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 119782 - 30a Asbestos Present: NO Hair - 2% Cust. #: GA-HS-01F No Asbestos Observed Other - 98% Material: Plaster Base Coat Location:
Appearance: grey,fibrous,homogenous Layer: 2 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 18 of 19
Report To: ARI Report # 25-119782 Mr. Aaron Paquet Date Collected: 09/15/25 Red Cedar Consulting Date Received: 09/18/25 P.O. Box 13216 Date Analyzed: 09/24/25 Lansing, MI 48901 Date Reported: 09/25/25
Project #: Jackson, MI Project: 1231 Greenwood Ave.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 119782 - 31 Asbestos Present: NO Other - 100%
Cust. #: GA-HS-01G No Asbestos Observed Material: Plaster Finish Coat on Lathe Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 119782 - 31a Asbestos Present: NO Hair - 5% Cust. #: GA-HS-01G No Asbestos Observed Other - 95% Material: Plaster Base Coat Location:
Appearance: grey,fibrous,homogenous Layer: 2 of 2
Lab ID #: Asbestos Present:
Cust. #:
Material:
Location:
Appearance:
Layer: of
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 19 of 19
Attachment B Figure 1 Site Diagram
Figure 1a Site Diagram
Note: Figure created by Red Cedar Consulting Asbestos Sample Locations 1231 Greenwood Ave.
-Not To Scale- Jackson, MI
Figure 1b Site Diagram
Note: Figure created by Red Cedar Consulting Asbestos Sample Locations
Figure 1c Site Diagram
Note: Figure created by Red Cedar Consulting Asbestos Sample Locations
Tables
Table 1 - Summary of Hazardous Materials, 1231 Greenwood Ave., Jackson, Michigan
Hazardous Materials Description and Location
Location Material Description Quantity
Exterior 5 Gallon Container Misc. Paint 14
Exterior Gallon Container Misc. Paint 17
Exterior Quart Container Misc. Paint 8
Exterior Spray Can Misc. Paint 12
Basement 5 Gallon Container Misc. Paint 16
Basement Gallon Container Misc. Paint 8
Basement Spray Can Misc. Paint 12
Table 2 - Summary of Sample Descriptions and Asbestos Laboratory Results, 1231 Greenwood Ave. Jackson, Michigan
Sample Number Sample Description Friable Material
Type Material
Classification
% Asbestos Laboratory
Result Sample Location Approx. Material
Quantity
GA-HM-01A Roofing Multilayer No M Category I ND/ND South side of Building NA
GA-HM-01B Roofing Multilayer No M Category I ND/ND North side of Building NA
GA-HM-02A Roof Tar No M Category I ND Center of Building/over Living Room NA
GA-HM-02B Roof Tar No M Category I ND Center of Building/over Living Room NA
GA-HM-03A Siding Paper Yes M Category II ND North side of Building NA
GA-HM-03B Siding Paper Yes M Category II ND South side of Building NA GA-HM-04A Basement Window Glaze Yes M Category II 2% CH Basement 5 Windows
GA-HM-04B Basement Window Glaze Yes M Category II NA Basement NA
GA-HM-05A 1st Floor Window Glaze Yes M Category II 2% CH Dining Room 11 Windows GA-HM-05B 1st Floor Window Glaze Yes M Category II NA Floor Porch NA
GA-HM-06A 2nd Floor Window Glaze Yes M Category II 2% CH South side B3 Window 3 Windows
GA-HM-06B 2nd Floor Window Glaze Yes M Category II NA West side B3 Window NA
GA-HM-07A 12”x12” Blue Floor Tile No M Category I ND/ND South side of Dining Room NA
GA-HM-07B 12”x12” Blue Floor Tile No M Category I ND/ND North side of Dining Room NA
GA-HM-08A 12”x12” Brown Floor Tile No M Category I ND/ND Center of Kitchen NA
GA-HM-08B 12”x12” Brown Floor Tile No M Category I ND/ND North side of Kitchen NA
GA-HM-09A Floor Tile Multi-layer No M Category I 2% CH/ND/2%
CH/ND/ND/ND
1st Floor Entry to Bathroom 85 sq. ft.
GA-HM-09B Floor Tile Multi-layer No M Category I NA/ND/NA/
ND/ND/ND
North side of 1st Floor Bathroom NA
GA-HM-10A 2’x4’ Drop Ceiling Tile Yes M Category II ND Living Room NA
GA-HM-10B 2’x4’ Drop Ceiling Tile Yes M Category II ND Kitchen NA GA-HM-11A 1’x1’ Ceiling Tile Yes M Category II ND Kitchen NA
GA-HM-11B 1’x1’ Ceiling Tile Yes M Category II ND Dining Room NA
GA-HM-12A Drywall with Joint Compound Yes M Category II ND/ND North side of Kitchen NA GA-HM-12B Drywall with Joint Compound Yes M Category II ND/ND South side of Kitchen NA
GA-HS-01A Plaster on Lathe No S Category II ND/ND BR1 Ceiling NA
Table 2 - Summary of Sample Descriptions and Asbestos Laboratory Results, 1231 Greenwood Ave. Jackson, Michigan
Sample Number Sample Description Friable Material
Type Material
Classification
% Asbestos Laboratory
Result Sample Location Approx. Material
Quantity
GA-HS-01B Plaster on Lathe No S Category II ND/ND Living Room Ceiling NA
GA-HS-01C Plaster on Lathe No S Category II ND/ND BR1 Wall NA
GA-HS-01D Plaster on Lathe No S Category II ND/ND Living Room Wall NA GA-HS-01E Plaster on Lathe No S Category II ND/ND 2nd Floor B2 Ceiling NA
GA-HS-01F Plaster on Lathe No S Category II ND/ND 2nd Floor B3 Wall NA
GA-HS-01G Plaster on Lathe No S Category II ND/ND 2nd Floor B2 Wall NA
Notes:
Material Types Abbreviations
M = Miscellaneous building material NQ = Not quantified TSI = Thermal System Insulation NA = Not Analyzed S = Surfacing Material ND = Not detected. Laboratory result is less than 1 % asbestos PC = Point Count Analysis lin. ft. = linear feet CH = Chrysotile Asbestos sq. ft. = square feet
Asbestos Containing Material (ACM) is defined as any material containing more than 1 percent asbestos as determined utilizing Polarized Light Microscopy.
Table 3 - Summary of All Asbestos Containing Materials, 1231 Greenwood Ave. Jackson, Michigan
Asbestos Containing Material Description and Location
Location Material Description Friable Condition Material Type Approx. Quantity
Front Entry (1 register, 10 sq. ft.)
Living (1 register, 10 sq. ft.)
Dining (1 register, 10 sq. ft.)
Kitchen (1 register, 10 sq. ft.)
Bedroom 1 (1 register, 10 sq. ft.)
2nd Fl. Bedroom 2 (1 register, 10 sq. ft. and vertical chase to basement, 25 sq. ft.)
2nd Fl. Bedroom 4 (1 register, 10 sq. ft. and vertical chase to basement, 25 sq. ft.)
HVAC Duct Wrap Yes Fair TSI 120 sq. ft.