Parking Garage Drawings All Floors.pdf

PDF 4 MB Posted

Attached to
Garage Cleaning Services
Solicitation number
12259134
Issued by

About this file

These are architectural drawings for a multi-level parking garage at Joint Base Andrews, detailing the structural design and layout across five floors. The parking structure has a curved, multi-tiered design with a total capacity of 598 parking spaces, including:

  • Varied parking space dimensions including standard spaces (9'0" x 18'0"), ADA spaces (8'0" x 20'0"), and ramp parking spaces (8'6" x 17')
  • Floor-by-floor breakdown showing consistent parking distribution across levels
  • Detailed architectural elements including elevator lobbies, stairwells, electrical rooms, and a pedestrian connector
  • Open parking garage calculations indicating the perimeter and open area requirements for each tier, with slight variations between floors showing minimal differences in provided versus required open spaces

View the file

Other files

File Type Posted
Base Access Request Form_Updated.docx DOCX document
1040 Parking Garage Questions III.docx DOCX document
Garage Sq Footage.pdf PDF
Base Access Request Form II.docx DOCX document
HT001425R00300001 - amendment.pdf PDF
PWS - Garage Cleaning -v2.docx DOCX document
Instructions to Offerors.docx DOCX document
Solicitation - HT001425R0030.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

DN

RB RC RD

R19

R16.1

R16

R14

R13

RA

R-AE2102A2

R-AE2102

R-AE2101 A2

C2

B1

R-AE3101

C1

R-AE3101

R20

R17

R21

19'-11" 40'-0" 60'-0"

STORAGE

R-1Q01

RA

MP

U P

ELEVS

R1 R2

R3

R4

R5

R6

R7

'-0

'-0

'-1

1"2'- 2"

'-1

1"

'-0

'-0

'-0

'-1

1"

R-AE2101

C2

ELEV.

LOBBY

R-1Q04

2 2STAIR

R-1QS6

STAIR

R-1QS7

R18

R15

R6.1

A2

R-AE3208

RJ

RE RF

R12

R11

A4

R-AE3207

RH

A1

R-AE3101

'-0

'-0

40'-0" 19'-11"

8'-

5"

20'-0" 117'-0"

18'-2" 8'-10"

184'-0"

1'-9" 17'-11" 2'-1"

26'-6" 12'-3"9'-4"

'-4

34'-2"6'-10" 34'-2"

ELEC RM

R-1Q03

EMERGENCY

ELEC RM

R-1Q02

R10

R-AE2105

A3

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

OPEN PARKING GARAGE CALCULATIONS

TOTAL OPEN AREA OPEN AREA OPEN AREA OPEN AREA % OPEN AREA

PERIMETER REQUIRED PROVIDED DIFFERENCE DISTRIBUTION DISTRIBUTION OF

(SF) (SF) (SF) (SF) LENGTH (S.F.) TOTAL PERIMETER

1ST TIER 1037 1452 1492 39 417 40

2ND TIER 1037 1452 1738 286 645 62

3RD TIER 1037 1452 1737 286 804 78

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

A

ND

RE

W S, M

AR

YL

AN

D

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

A

ND

RE

W S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ted \D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

To mm y D .rv t 5/1

0/2

2 1 0:1

2:0 5 A

M

As indicated

PA

RK

IN

G

GA

RA

GE

GR

OU

ND

LE

VE

L P

LA

N

R-AE101

TED TED TAW

13041208

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

FLOOR 1

R1

ENTRY/

EXIT

LEVEL DESCRIPTION COUNT

Ramp Parking: 8'-6" x 17' 69 : 69

PRKG - ELEV. PIT Ramp Parking: 8'-6" x 17' 22

PRKG - ELEV. PIT: 22

PRKG - 1ST FLR Ramp Parking: 8'-6" x 17' 5 PRKG - 1ST FLR ADA: 8'-0" x 20'-0" 10 PRKG - 1ST FLR 9'-0" x 18'-0" 97

PRKG - 1ST FLR: 112

PRKG - 2ND FLR ADA: 8'-0" x 20'-0" 5 PRKG - 2ND FLR 9'-0" x 18'-0" 110

PRKG - 2ND FLR: 115

PRKG - 3RD FLR Ramp Parking: 8'-6" x 17' 30 PRKG - 3RD FLR 9'-0" x 18'-0" 125

PRKG - 3RD FLR: 155

PRKG - 4TH FLR 9'-0" x 18'-0" 125

PRKG - 4TH FLR: 125

Grand total: 598

100'0 20' 60'

1/32"=1'-0" GRAPHIC SCALE

20'

1 PEDESTRIAN CONNECTOR BRIDGE ABOVE

2 LIGHT WELL

3 DASHED BUBBLE DEPICTS AREA OF PRECAST WALL TO BE INSTALLED

LATER AT TEMPORARY VEHICLE ENTRY/EXIT. COORDINATE WITH

PHASING DRAWINGS.

4 MAIN GROUND FLOOR VEHICLE ENTRY/EXIT. ACCESS NOT AVAILABLE

DURING INITIAL PHASE OF CONSTRUCTION. COORDINATE WITH PHASING

DRAWINGS.

5 MAIN ENTRY

6 VISITOR/PATIENT DROP-OFF

7 FIRE EXTINGUISHER CABINET

8 HATCH INDICATES TO FILL DOUBLE T JOINTS ABOVE STORAGE ROOM

WITH 2 HOUR FIRE RATED ASSEMBLY PER UL #J804

9 TEMPORARY VEHICLE ENTRY/EXIT DURING INITIAL PHASE OF

CONSTRUCITON. COORDINATE WITH PHASING DRAWINGS.

RB RC RD

R19

R16.1

R16

RA

B1

R-AE3101

19'-11" 40'-0" 60'-0"

R20

R17

R-1QS6.1

R-1Q01.1

STORAGE

R-1Q01

R21

REF LINE

R-AE101B

REF LINE

R-AE101B

2'- 2"

'-1

1"

'-0

'-0

'-0

'-1

1"

1 1

R18

'-0

'-0

8'-0"8'-0"

7'- 0"

8'-0"8'-0"

'-4

16'-10"

R-AE4103

C1

2 2

2 2

8'-0"8'-0"

RE RF

R-AE2103

A1

R-AE2103A2

A1

R-AE3101

STAIR

R-1QS64

R-1Q01.2

5 5

40'-0" 19'-11" 184'-0"

3'-10" 18'-2" 20'-0"

1313 11

SL

OP

E

SL

OP

E

SL

OP

E

SL

OP

E

'-8

SL

OP

E

19'-11" 40'-0" 60'-0" 40'-0" 19'-11"

14'-9"

R-AE5133

A1

R-AE5133

B1

R-AE5133

A2

R-AE5133

C1

R-AE5133

C3

R-AE5133

C2

2'-1"2'-1" 1'-9" 2'-0"

5'-

6'- 9"

2'- 1"

6'-

2"

8'-

9"

1'-

1"

2'-1"

16'-10"

1'-11 1/4"

2'-10 3/4" 3'-4"

2'-10 3/4"

3'-4"

4'-2"

4'-0"

4'-2"4'-0"

3'-4"

1'-11 1/4"

3'-1"

2'-7"

17 17

9'- 0" x1 8"

-0

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

@9'-

0 " x1

8'- 0 "

SP

AC

ES

9'- 0 " x1 8"

-0

SP

AC

ES

R- 1Q

.3

2'-10 3/4"

9'-0" x 18'-0"

12 SPACES @

A2

R-AE3203

A1

R-AE3203

A2

R-AE3202

A4

R-AE3203

8'-10" 54'-0" 9'-0" 27'-4 1/2"

R-AE2112

A1

R-AE2113 C1

R-AE2111A1

TYP

TYP

R-AE5135

A2

R-AE5135

A3

R-AE5131

C1

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

AN

DR

EW

S, MA

RY

LA

ND

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

AN

DR

EW

S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ted \D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

To mm y D .rv t 5/1

0/2

2 1 0:1

2:1 8 A

M

As indicated

PA

RK

IN

G

GA

RA

GE

- G

RO

UN

D

LE

VE

LP

LA

N

-S

EC

TO

R

A

R-AE101A

TED TED TAW

13041209

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R1A

1 LIGHT WELL

2 STEEL CAGE RAIN LEADER PROTECTION SEE DETAIL B3/AE5611

3 WHEEL STOP TYP. (SAFETY YELLOW)

4 VERTICAL WATERPROOFING SYSTEM IS TYPICAL WHERE FOUNDATION

WALL IS BELOW GRADE.

5 FLOOR DRAINS TYP. REFER TO PLUMBING SHEETS

7 2" BUILDING EXPANSION JOINT

8 4" WIDE PAINTED STRIPING

9 PRECAST DOUBLE 'T' JOINT TYPICAL

10 FIRE EXTINGUISHER CABINET. SEE SPEC SECTION 104400 FOR MORE

INFORMATION

11 CRICKET IN CONCRETE SLAB TO MOVE WATER AROUND OBSTACLE TO

FLOW TOWARDS TRENCH DRAIN AT SOUTH END

12 PROVIDE "SMOOTH RUB" FINISH ON ALL EXPOSED CONCRETE

FOUNDATION WALLS

13 PAINT LOWER 4'-0" OF CONCRETE COLUMMN "SAFETY YELLOW" (TYPICAL)

14 HATCH INDICATES TO FILL DOUBLE T JOINTS ABOVE STORAGE ROOM AND

SPRAY UNDERSIDE OF DOUBLE "T" DECK WITH SPRAY FIREPROOFING PER

2 HOUR FIRE RATED ASSEMBLY PER UL #J804

17 APPLY DECK COATING ON ALL PARKING/ DRIVE SURFACES, TYP.

DN

DN

RB RC RD

R16.1

R16

R14

R13

RA

R-AE2102A2

B1

R-AE3101

C1

R-AE3101

REF LINE

R-AE101A

REF LINE

R-AE101A

RG

R6

R7

'-0

'-0

'-1

1" 2'-

2"

A3

R-AE3201

RA

MP

U P

ELEV.

LOBBY

R-1Q04

R-AE4101

A1

R15

R6.1

8'-0" 8'-0" 8'-0" 8'-0"

RJ

2 2

2 2

R-1QS7.1

RE RF

R12

R11

R-AE2103

C1

R-AE4104

A1

SLOPE

A4

R-AE3207

RH

R-AE2103 C2

A1

R-AE3101

ELEV 5A & 5B

ELEV05

A1

R-AE3208

R-AE2101 A2

ELEC RM

R-1Q03

EMERGENCY

ELEC RM

R-1Q02

R-AE2111C1

R-AE2114

A1

13 13

13 13

19'-11" 40'-0" 60'-0" 40'-0" 19'-11"

SL

OP

E

SL

OP

E

SL

OP

E

SL

OP

E

SL

OP

E

SL

OP

E

14 14

6 6

10 10

14'-9"

6'-

1"

'-0

'-0

26'-6"

15'-3" 5'-7"

117'-0"15'-0" 200'-1"

6.733°

R-AE5133

C3

R-AE5133

C2

2'-1"

1'-9"

8'-

9"

15.8°20'-0" 12'-3" 9'-4"

16'-10"

1'-11 1/4"1'-11 1/4"

1'-5"

10 1/2"

11 1/4" 11 1/4"

2'-5" 1'-4"

1'-11"2'-5"

3'-4"

2'-7" 1'-4"

2'-7"

1'-0"

1'-0"

6"

R-AE4106

A1

6"

2'-7" +/-

R-AE4104

C2

9'- 0" x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8"

-0

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

8'- 6 "

X

'-0

5S

PA

CE

S

8'- 6 " x1 7'-

0 " 5S

PA

CE

S

9'- 0 " x1 8'-

0 " 4S

PA

CE

S

8'-0" x 20'-0"

7 SPACES @

R-AE5220

C1

STAIR

R-1QS7

'-4

'-0

R10

REF LINE

R-AE101A

A1

R-AE3202

A4

R-AE3202

A3

R-AE3202

'-4

3'-

5"

220000.C02

TYP

R-AE5135

A2

R-AE5135

A3

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

AN

DR

EW

S, MA

RY

LA

ND

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

AN

DR

EW

S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ted \D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

To mm y D .rv t 5/1

0/2

2 1 0:1

2:3 0 A

M

As indicated

PA

RK

IN

G

GA

RA

GE

- G

RO

UN

D

LE

VE

LP

LA

N

-S

EC

TO

R

B

R-AE101B

TED TED TAW

13041210

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R1B

1 DEPICTS LOCATION OF TEMPORARY ENTRY DURING PHASED

CONSTRUCTION

2 STEEL CAGE RAIN LEADER PROTECTION SEE DETAIL B3/AE5611

3 STEEL BOLLARD SEE DETAIL C1/AE5611

4 HANDICAPPED PARKING SIGN TYP. SEE R-AG SERIES DRAWINGS.

5 WHEEL STOP TYP. (SAFETY YELLOW)

6 VERTICAL WATERPROOFING SYSTEM IS TYPICAL WHERE FOUNDATION

WALL IS BELOW GRADE.

7 FLOOR DRAINS TYP. REFER TO PLUMBING SHEETS

8 REMOVABLE PIPE BOLLARD SEE DETAIL C3/AE5611

10 4" WIDE PAINTED STRIPPING

11 FIRE EXTINGUISHER CABINET

12 CRICKET IN CONCRETE SLAB TO MOVE WATER AROUND OBSTACLE TO

FLOW TOWARDS TRENCH DRAIN AT SOUTH END

13 PROVIDE "SMOOTH RUB" FINISH ON ALL EXPOSED CONCRETE

FOUNDATION WALLS

14 PAINT LOWER 4'-0" OF CONCRETE COLUMMN "SAFETY YELLOW"

15 RAISED PLATFORM AT ELEVATION 1'-4"

16 RESTRICTED PARKING SIGN/STALL-"H.C. CAR SPACE" SEE R-AG SERIES

DRAWINGS.

17 RESTRICTED PARKING SIGN/STALL-"H.C. VAN SPACE" SEE R-AG SERIES

DRAWINGS.

18 RESTRICTED PARKING SIGN/STALL-"LOW EMISSION VEHICLE SPACE". SEE

R-AR SERIES DRAWINGS.

19 APPLY DECK COATING ON ALL PARKING/ DRIVE SURFACES, TYP.

20 TRENCH DRAIN ALONG PERIMETER

21 GUARDRAILS IN SHEAR WALL OPENINGS, TYPICAL, SEE PRECAST PANEL

ELEVATIONS FOR HEIGHTS

22 MOTORCYCLE PARKING

23 STOP SIGN

24 TEMPORARY VEHICLE ENTRY/EXIT DURING INITIAL PHASE OF

CONSTRUCITON. COORDINATE WITH PHASING DRAWINGS.

DN

DN

DN

RB RC RDRA

R-AE2102

C2

RG

R1

R2

R3

R4

R5

R6

R7

ELEV.

LOBBY

R-1Q04

R6.1

A2

R-AE3208

R 154'-0"

RJ

R-1QS7.1

RE RF

R12

R11

A1

R-AE3207

SLOPE

SLO

PE

A4

R-AE3207

RH

ELEV 5A & 5B

ELEV05

A1

R-AE3208

C2

R-AE3208

R-AE4104

C4

033000.A03

A1

R-AE3205

ELEC RM

R-1Q03

EMERGENCY

ELEC RM

R-1Q02

26'-6"

15'-3" 5'-7"

117'-0"15'-0" 200'-1"

R 143'-0"

138'-0"

'-6

1/ 2"

6.418°

7.455° 6.85°

6.925°

6.773°

6.733°

1'-9"

15.8°20'-0" 12'-3" 9'-4"

1'-4"

1'-0"

1'-0"

6"

R-AE4106

A1

6"

STAIR

R-1QS7

'-4

'-0

R10

AE4011

B1

055913.A01 4

R-AE2105

A3

C3

R-AE2104

220000.C02

TYP

TYP

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

A

ND

RE

W S, M

AR

YL

AN

D

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

A

ND

RE

W S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ dc s\D es kto p\A nd re ws

\LO

CA

L F

ILE

S\

4-

An dr ew s A

CC

_P ar kin g G ar ag e_

LO

CA

L.r vt

3/1 4/2

2 4

:03 :28

P M

As indicated

PA

RK

IN

G

GA

RA

GE

- G

RO

UN

D

LE

VE

L P

LA

N

- S

EC

TO

R

C

R-AE101C

ROD ROD TAW

13041211

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R1C

1 CENTER POINT OF RADIUS

2 OUTLINE OF CONNECTOR BRIDGE ABOVE

3 STEEL BOLLARD SEE DETAIL C1/AE5611

4 SEE A1/AE7002 FOR ENLARGED TRELLIS PLAN AND DETAILS

5 CRICKET WALK AROUND WALL FOR DRAINAGE

6 LINE OF WALK. SEE LANDSCAPE AND CIVIL FOR MORE INFORMATION AND

FINISH

MATERIAL NOTES

033000.A03 CONCRETE COLUMN

055913.A01 TRELLIS FRAMING SYSTEM

076000.U02 DOWNSPOUT

220000.C02 FLOOR DRAIN

R16.1

R16

R14

R13

RA

R-AE2102A2

R-AE2102

R-AE2101 A2

C2

B1

R-AE3101

C1

R-AE3101

R20

R17

R21

RA

MP

U P

RA

MP

D

OW

N

PEDESTRIAN

CONNECTOR

ENTRY/

EXIT

19'-11" 40'-0" 60'-0"

'-0

'-0

'-1

1"

2'- 2"34

'-1 1"

'-0

'-0

'-0

'-1 1"

RG

R1

R2

R3

R4

R5

R6

R7

R-AE2101

C2

1 1

ELEV.

LOBBY

R-2Q01

VESTIBULE

R-2Q04

STAIRS

R-2QS7

R18

R15

R6.1

A2

R-AE3208

RJ

2 2

2 2

2 2

2 2

RE RF

R12

R11

A4

R-AE3207

RH

A1

R-AE3101

'-0

'-0

40'-0" 19'-11"

183'-6"

'-1

18'-2" 6'-10" 34'-2" 34'-2" 8'-6" 18'-3"

15'-0" 20'-0" 117'-0" 26'-6" 12'-3"9'-3" 200'-0"

'-2

'-0

2'- 9"34

1'- 3"

1'-10"

6'- 0"

5'-0"

R10

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

OPEN PARKING GARAGE CALCULATIONS

TOTAL OPEN AREA OPEN AREA OPEN AREA OPEN AREA % OPEN AREA

PERIMETER REQUIRED PROVIDED DIFFERENCE DISTRIBUTION DISTRIBUTION OF

(SF) (SF) (SF) (SF) LENGTH (S.F.) TOTAL PERIMETER

1ST TIER 1037 1452 1492 39 417 40

2ND TIER 1037 1452 1738 286 645 62

3RD TIER 1037 1452 1737 286 804 78

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

A

ND

RE

W S, M

AR

YL

AN

D

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

A

ND

RE

W S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ted \D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

To mm y D .rv t 5/1

0/2

2 1 0:1

2:4 5 A

M

As indicated

PA

RK

IN

G

GA

RA

GE

- L

EV

EL

PL

AN

R-AE102

TED TED TAW

13041212

100'0 20' 60'

1/32"=1'-0" GRAPHIC SCALE

20'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

FLOOR 2FLOOR 2

R2

LEVEL DESCRIPTION COUNT

Ramp Parking: 8'-6" x 17' 69 : 69

PRKG - ELEV. PIT Ramp Parking: 8'-6" x 17' 22

PRKG - ELEV. PIT: 22

PRKG - 1ST FLR Ramp Parking: 8'-6" x 17' 5 PRKG - 1ST FLR ADA: 8'-0" x 20'-0" 10 PRKG - 1ST FLR 9'-0" x 18'-0" 97

PRKG - 1ST FLR: 112

PRKG - 2ND FLR ADA: 8'-0" x 20'-0" 5 PRKG - 2ND FLR 9'-0" x 18'-0" 110

PRKG - 2ND FLR: 115

PRKG - 3RD FLR Ramp Parking: 8'-6" x 17' 30 PRKG - 3RD FLR 9'-0" x 18'-0" 125

PRKG - 3RD FLR: 155

PRKG - 4TH FLR 9'-0" x 18'-0" 125

PRKG - 4TH FLR: 125

Grand total: 598

1 LIGHT WELL

2 STEEL CAGE RAIN LEADER PROTECTION SEE DETAIL B3/AE5611

3 SURFACE MOUNTED PEDESTAL BOLLARD TYP. SEE DETAIL C5/AE5611

4 HANDICAPPED PARKING SIGN TYP. SEE R-AG SERIES DRAWINGS.

5 FIRE EXTINGUISHER CABINET

6 REFER TO CIVIL SHEETS FOR SITE PAVING

7 HATCH INDICATES TO FILL DOUBLE T JOINTS ABOVE STORAGE ROOM

AND SPRAY UNDERSIDE OF DOUBLE "T" DECK WITH SPRAY

FIREPROOFING PER 2 HOUR FIRE RATED ASSEMBLY PER UL #J804

R19

R16.1

R16

RA

B1

R-AE3101

R20

R17

RA

MP

D

OW

N

R21

REF LINE

R-AE102B

REF LINE

R-AE102B

R-2QS6.2

A3

R-AE4203

19'-11" 40'-0" 60'-0"

2'- 2"

'-1

1"

'-0

'-0

'-0

'-1

1" A2

R-AE32011 1

R18

R-AE4103

C3

ENTRY/

EXIT

3 3

R-2QS6.1

RE RF

R-AE2103

A1

R-AE2103A2

A1

R-AE3101

5 5

055200.R01

055200.R01

055200.R01055200.R01055200.R01055200.R01

40'-0" 19'-11"

R-AE2101

C2

R-AE2101 A2

R-AE2102A2

R-AE2111A1

10 10 10

10 10

10 10

12 12

9 9

183'-6"

'-2

'-0

'-3

'-1 1"

5'-

8"

7 7

R-AE5133

B2

R-AE5133

C3

16'-10"

6'- 8"

8'-

9"

8'-7" 20'-0"34'-2"58'-0"34'-2"6'-10"18'-2"3'-7"

5'-

8"

1'-

1"

40'-0"60'-0"40'-0"19'-11"15'-1"1'-9" 19'-11"

R 3'-0" R 3'-0 "R 3'-0"R 3'-0

R 3'-0 "R 3'-0"

R 3'-0 "R 3'-0"

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0" x1 8'-

0"

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'-0" x 18'-0"

4 SPACES @

9'-0" x 18'-0"

4 SPACES @

A2

R-AE3203

A1

R-AE3203

A2

R-AE3202

A4

R-AE3203

R-AE5133

B3

R-AE5133

A3 ABOVE SPANDREL

AT SPANDREL

R-AE5135

C3

R-AE5135

A2

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

AN

DR

EW

S, MA

RY

LA

ND

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

AN

DR

EW

S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ted \D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

To mm y D .rv t 5/1

0/2

2 1 0:1

3:2 0 A

M

As indicated

PA

RK

IN

G

GA

RA

GE

- L

EV

EL

2P

LA

N

- S

EC

TO

R A

R-AE102A

TED TED TAW

13041213

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R2A

1 LIGHT WELL, OPEN

2 STEEL CAGE RAIN LEADER PROTECTION SEE DETAIL B3/AE5611

3 SURFACE MOUNTED PEDESTAL BOLLARD TYP. SEE DETAIL C5/AE5611

4 WHEEL STOP TYP. (SAFETY YELLOW)

5 STEEL BOLLARD SEE DETAIL C1/AE5611

6 FLOOR DRAINS TYP. REFER TO PLUMBING SHEETS

7 2" BUILDING EXPANSION JOINT

8 FIRE EXTINGUISHER CABINET

9 DASHED LINE INDICATES OUTLINE OF STORAGE ROOM BELOW

10 4" WIDE PAINTED STRIPPING

11 HATCH INDICATES TO FILL DOUBLE T JOINTS ABOVE STORAGE ROOM AND

SPRAY UNDERSIDE OF DOUBLE "T" DECK WITH SPRAY FIREPROOFING PER 2

HOUR FIRE RATED ASSEMBLY PER UL #J804

12 PAINT LOWER 4'-0" OF CONCRETE COLUMN "SAFETY YELLOW"

13 APPLY DECK COATING ON ALL PARKING/ DRIVE SURFACES, TYP.

14 GUARDRAILS IN SHEAR WALL OPENINGS, TYPICAL, SEE PRECAST PANEL

ELEVATIONS FOR HEIGHTS

15 REFER TO CIVIL DRAWINGS FOR ENTRY DRIVE INFORMATION

16 CRICKET IN CONCRETE SLAB TO MOVE WATER AROUND OBSTACLE TO

FLOW TOWARDS DRAIN

MATERIAL NOTES

055200.R01 STEEL GUARDRAIL

R16.1

R16

R14

R13

RA

B1

R-AE3101

C1

R-AE3101

RA

MP

U P

REF LINE

R-AE102A

REF LINE

R-AE102A

RG

R7

'-0

'-0

'-1

1" 2'-

2"

A3

R-AE3201

ELEV.

LOBBY

R-AE4101

A4

R15

R6.1

RJ

STOR

R-2Q02

2 2

STAIRS

R-2QS7

RE RF

R12

R11

A4

R-AE3207

RH

A1

R-AE3101

ELEV 5A & 5B

ELEV05

A1

R-AE3208

0.2

'-0

'-0

'-0

R-AE2102A2

R-AE2101 A2

055200.R01055200.R01

R-AE2111C1

9 9

10 10

7 7

15'-0" 20'-0" 117'-0" 26'-6" 12'-3" 9'-3" 200'-0"

'-4

16'-10"

10 10

15'-3"

1'-9"

40'-0"60'-0"40'-0"19'-11"15'-1"1'-9"

1'- 9"

8'-

9"

19'-11"

R 3'-0 " R 3'-0" R 3'-0

" R 3'-0"

R 3'- 0"

8 8

9'- 0" x1 8'-

0"

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'-0" X 18'-0"

7 SPACES @

8'- 0" x2 0'-

0 " 2S

PA

CE

S

8'-0" x 20'-0"

3 SPACES @

R10

A1

R-AE3202

A4

R-AE3202

A3

R-AE3202

19 19

R-AE5135

C3

R-AE5135

A2

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

AN

DR

EW

S, MA

RY

LA

ND

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

AN

DR

EW

S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ted \D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

To mm y D .rv t 5/1

0/2

2 1 0:1

3:3 0 A

M

As indicated

PA

RK

IN

G

GA

RA

GE

- L

EV

EL

2P

LA

N

- S

EC

TO

R B

R-AE102B

TED TED TAW

13041214

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R2B

1 LIGHT WELL

2 STEEL CAGE RAIN LEADER PROTECTION SEE DETAIL B3/AE5611

3 SURFACE MOUNTED PEDESTAL BOLLARD TYP. SEE DETAIL C5/AE5611

4 RESTRICTED PARKING SIGN/STALL-"H.C. CAR SPACE" SEE R-AG SERIES

5 WHEEL STOP TYP. (SAFETY YELLOW)

6 2" EXPANSION JOINT

7 FIRE EXTINGUISHER CABINET

8 4" WIDE PAINTED STRIPPING

9 PAINT LOWER 4'-0" OF CONCRETE COLUMMN "SAFETY YELLOW"

10 FLOOR DRAINS TYP. REFER TO PLUMBING SHEETS

11 RESTRICTED PARKING SIGN/STALL-"LOW EMISSION VEHICLE SPACE". SEE

R-AR SERIES DRAWINGS.

12 RESTRICTED PARKING SIGN/STALL-"H.C. VAN SPACE" SEE R-AG SERIES

DRAWINGS.

13 HATCH INDICATES AREA TO BE RECEIVE WATERPROOF DECK COATING

(AND FILL JOINTS BETWEEN "T"s) TO PROTECT ENCLOSED ROOMS BELOW

14 APPLY DECK COATING ON ALL PARKING/ DRIVE SURFACES, TYP.

15 GUARDRAILS IN SHEAR WALL OPENINGS, TYPICAL, SEE PRECAST PANEL

ELEVATIONS FOR HEIGHTS

16 MOTORCYCLE PARKING

17 STOP SIGN

18 RESTRICTED PARKING SIGN/STALL-"EXPECTANT MOTHER"

19 CRICKET IN CONCRETE SLAB TO MOVE WATER AROUND OBSTACLE TO

FLOW TOWARDS DRAIN

MATERIAL NOTES

055200.R01 STEEL GUARDRAIL

UP

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RB RC RDRA

R-AE2102

C2

RG

R1

R2

R3

R4

R5

R6

R7

ELEV.

LOBBY

R-AE4101

A4

R6.1

A2

R-AE3208

19'-11" 40'-0" 60'-0"

VESTIBULE

R-2Q04

R 154'-0"

RJ

STOR

R-2Q02

STAIRS

R-2QS7

RE RF

R12R12

R11R11

R-AE4104

C1

A1

R-AE3207

A4

R-AE3207

RH

A1

R-AE3101

ELEV 5A & 5B

ELEV05

A1

R-AE3208

'-0

CORR

R-2Q03

R-AE2114

A1 15.8°

20'-0" 117'-0" 26'-6" 12'-3" 9'-3"

'-4

6.418°

7.455°

6.85°

6.925°

6.773°

6.733°

'-6

7/

138'-1"

R 142'-7"

15'-3"

1'-9"

1'- 9"

9'-0" X 18'-0"

7 SPACES @

8'-0" x 20'-0"

3 SPACES @

R10

AE4012

B1

R-AE2206

R-AE2207

055913.A01 5

R-AE2105

A3

A1

R-AE3202

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

A

ND

RE

W S, M

AR

YL

AN

D

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

A

ND

RE

W S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ dc s\D es kto p\A nd re ws

\LO

CA

L F

ILE

S\

4-

An dr ew s A

CC

_P ar kin g G ar ag e_

LO

CA

L.r vt

3/1 4/2

2 4

:04 :06

P M

As indicated

PA

RK

IN

G

GA

RA

GE

- L

EV

EL

PL

AN

- S

EC

TO

R C

R-AE102C

ROD ROD TAW

13041215

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R2C

1 CENTER POINT OF RADIUS

2 2" EXPANSION JOINT

3 SURFACE MOUNTED PEDESTAL BOLLARD TYP. SEE DETAIL C5/AE5611

4 DASHED LINES DEPICTS LINE OF ROOF ABOVE

5 SEE A1/AE7002 FOR ENLARGED TRELLIS PLAN AND DETAILS

R16.1

R16

R14

R13

RA

R-AE2102A2

R-AE2102

R-AE2101 A2

C2

B1

R-AE3101

C1

R-AE3101

R20

R17

R21

19'-11" 40'-0" 60'-0"

'-0

'-0

'-1

1" 2'-

2"

'-1 1"

'-0

'-0

'-0

'-0

'-1

1"

RGR1

R2

R3

R4

R5

R6

R7

RA

MP

U P

RA

MP

D

OW

N

R-AE2101

C2

ELEV.

LOBBY

R-3Q01

STAIRS

R-3QS6

STAIRS

R-3QS7

R18

R15

R6.1

A2

R-AE3208

ELEVS

RJ

2 2

RE RF

R12

R11

A4

R-AE3207

RH

A1

R-AE3101

'-0

'-0

40'-0" 19'-11"

183'-4"

20'-0" 117'-0" 26'-6" 12'-3"9'-3"

'-0

2'- 9"

185'-1"

6'-

1"

'-4

R10

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

OPEN PARKING GARAGE CALCULATIONS

TOTAL OPEN AREA OPEN AREA OPEN AREA OPEN AREA % OPEN AREA

PERIMETER REQUIRED PROVIDED DIFFERENCE DISTRIBUTION DISTRIBUTION OF

(SF) (SF) (SF) (SF) LENGTH (S.F.) TOTAL PERIMETER

1ST TIER 1037 1452 1492 39 417 40

2ND TIER 1037 1452 1738 286 645 62

3RD TIER 1037 1452 1737 286 804 78

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

A

ND

RE

W S, M

AR

YL

AN

D

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

A

ND

RE

W S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ gls \D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_ gls .rv t 3/1

5/2

2 5 :53

:51 P

M

As indicated

PA

RK

IN

G

GA

RA

GE

- L

EV

EL

PL

AN

R-AE103

TED TED TAW

13041216

100'0 20' 60'

1/32"=1'-0" GRAPHIC SCALE

20'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

FLOOR 3FLOOR 3

R3

LEVEL DESCRIPTION COUNT

Ramp Parking: 8'-6" x 17' 69 : 69

PRKG - ELEV. PIT Ramp Parking: 8'-6" x 17' 22

PRKG - ELEV. PIT: 22

PRKG - 1ST FLR Ramp Parking: 8'-6" x 17' 5 PRKG - 1ST FLR ADA: 8'-0" x 20'-0" 10 PRKG - 1ST FLR 9'-0" x 18'-0" 97

PRKG - 1ST FLR: 112

PRKG - 2ND FLR ADA: 8'-0" x 20'-0" 5 PRKG - 2ND FLR 9'-0" x 18'-0" 110

PRKG - 2ND FLR: 115

PRKG - 3RD FLR Ramp Parking: 8'-6" x 17' 30 PRKG - 3RD FLR 9'-0" x 18'-0" 125

PRKG - 3RD FLR: 155

PRKG - 4TH FLR 9'-0" x 18'-0" 125

PRKG - 4TH FLR: 125

Grand total: 598

1 SURFACE MOUNTED PEDESTAL BOLLARD TYP. SEE DETAIL C5/AE5611

2 STEEL CAGE RAIN LEADER PROTECTION SEE DETAIL B3/AE5611

3 WHEEL STOP TYP. (SAFETY YELLOW)

4 FIRE EXTINGUISHER CABINET

5 ROOF OF CONNECTOR BRIDGE

UP DN

R19

R16.1

R16

RA

B1

R-AE3101

R20

19'-11" 40'-0" 60'-0"

R17

R21

REF LINE

R-AE103B

REF LINE

R-AE103B

A3

R-AE4203

2'- 2"

'-1

1"

'-0

'-0

'-0

'-1

1" A2

R-AE3201

RA

MP

D

OW

N

R18

19'-11" 40'-0" 60'-0"

R-AE4103

A1

2 2

2 2

RE RF

R-AE2103

A1

R-AE2103A2

A1

R-AE3101

40'-0" 19'-11"

R-AE2102A2R-AE2101 A2

R-AE2101

C2

7 7

5 5

5 5 5

8 8

183'-6"

'-1

1"

'-0

1'-10"

5'-

8"

8'-

9"

5'-

8"

5'-

40'-0" 19'-11"

18'-2"3'-7"

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0" x1 8'-

0"

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

8'- 6 " x1 7'-

0 "

SP

AC

ES

8'- 6 " x1 7'-

0 "

SP

AC

ES

9'-0" x 18'-0"

12 SPACES @

A2

R-AE3203

A1

R-AE3203

A2

R-AE3202

A4

R-AE3203

R-AE5135

A2

R-AE5135

C3

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

AN

DR

EW

S, MA

RY

LA

ND

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

AN

DR

EW

S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ted \D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

To mm y D .rv t 5/1

0/2

2 1 0:1

3:5 7 A

M

As indicated

PA

RK

IN

G

GA

RA

GE

- L

EV

EL

3P

LA

N

- S

EC

TO

R A

R-AE103A

TED TED TAW

13041217

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R3A

1 WHEEL STOP TYP. (SAFETY YELLOW)

2 STEEL CAGE RAIN LEADER PROTECTION SEE DETAIL B3/AE5611

3 2" BUILDING EXPANSION JOINT

4 FIRE EXTINGUISHER CABINET

5 4" WIDE PAINTED STRIPPING

6 PAINT LOWER 4'-0" OF CONCRETE COLUMMN "SAFETY YELLOW"

7 FLOOR DRAINS TYP. REFER TO PLUMBING SHEETS

8 CRICKET IN CONCRETE SLAB TO MOVE WATER AROUND OBSTACLE TO

FLOW TOWARDS DRAIN

9 APPLY DECK COATING ON ALL PARKING/ DRIVE SURFACES, TYP.

10 STOP SIGN

R16.1

R16

R14

R13

RA

B1

R-AE3101

C1

R-AE3101

REF LINE

R-AE103A

REF LINE

R-AE103A

RG

R6

R7

'-0

'-0

'-1

1" 2'-

2"

A3

R-AE3201

RA

MP

U P

ELEV.

LOBBY

R15

R6.1

SLOPE

19'-11" 40'-0" 60'-0"

RJ

MECH

R-3Q02

R-AE4102

A1

2 2

RE RF

R12

R11

R-AE2103

C1

A4

R-AE3207

RH

R-AE2103 C2

A1

R-AE3101

ELEV 5A & 5B

ELEV05

A1

R-AE3208

19'-11" 40'-0"

'-0

R-AE2101 A2

R-AE2102A2

R-AE2114

A1

5 5

40'-0" 19'-11"

7 7

6 99

7 57

'-0

'-0

'-0

5'- 8"

8'-

9"

20'-0" 117'-0" 26'-6" 12'-3" 9'-4"

185'-1"

076115.U01

11 11

9'- 0" x1 8'-

0 "

SP

AC

ES

9' - 0 " x1 8'-

0 "

SP

AC

ES

9' - 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

8'- 6 " x1 7'-

0 "

SP

AC

ES

8'- 6 " x1 7'-

0 "

SP

AC

ES

9'-0" x 18'-0"

11 SPACES @

9 9

R10

A1

R-AE3202

A4

R-AE3202

A3

R-AE3202

6'-3 1/2" 54'-0" 12'-8 1/2" 18'-2"

076115.A01

R-AE5135

A2 R-AE5135

C3

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

AN

DR

EW

S, MA

RY

LA

ND

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

AN

DR

EW

S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ted \D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

To mm y D .rv t 5/1

0/2

2 1 0:1

4:0 7 A

M

As indicated

PA

RK

IN

G

GA

RA

GE

- L

EV

EL

3P

LA

N

- S

EC

TO

R B

R-AE103B

TED TED TAW

13041218

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R3B

MATERIAL NOTES

076115.A01 METAL ROOF PANEL

076115.U01 GUTTER

1 WHEEL STOP TYP. (SAFETY YELLOW)

2 STEEL CAGE RAIN LEADER PROTECTION SEE DETAIL B3/AE5611

3 SURFACE MOUNTED PEDESTAL BOLLARD TYP. SEE DETAIL C5/AE5611

4 2" BUILDING EXPANSION JOINT

5 FIRE EXTINGUISHER CABINET

6 TRENCH DRAIN AT BOTTOM OF RAMP, SEE DETAIL C1 SHEET R-AE5226

7 4" WIDE PAINTED STRIPPING

8 FLOOR DRAINS TYP. REFER TO PLUMBING SHEETS

9 PAINT LOWER 4'-0" OF CONCRETE COLUMMN "SAFETY YELLOW"

10 CRICKET IN CONCRETE SLAB TO MOVE WATER AROUND OBSTACLE TO

FLOW TOWARDS DRAIN

11 APPLY DECK COATING TYPE 2 ON PARKING/ DRIVE SURFACE

12 APPLY DECK COATING TYPE 1 ON PARKING/ DRIVE SURFACE

13 GUARDRAILS IN SHEAR WALL OPENINGS, TYPICAL, SEE PRECAST PANEL

ELEVATIONS FOR HEIGHTS

UP

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RB RC RDRA

R-AE2102

C2

RGR1

R2

R3

R4

R5

R6

R7

ELEV.

LOBBY

R6.1

A2

R-AE3208

R 154'-0"

19'-11" 40'-0" 60'-0"

SLOPE

SLO

PE

RJ

MECH

R-3Q02

R-AE4102

A1

RE RF

R12R12

R11R11

A1

R-AE3207

A4

R-AE3207

RH

ELEV 5A & 5B

ELEV05

A1

R-AE3208

19'-11" 40'-0"

'-0

C2

R-AE3208

'-0

20'-0" 117'-0" 26'-6" 12'-3" 9'-4"

185'-1"

R 143'-0"

6.418°

7.455°

6.85°

6.925°

15.8°

6.773°

6.733°

138'-0 41/256"

'-6

7/

076115.U01

R-AE4105

D4

9'-0" x 18'-0"

11 SPACES @

9 9

R10R10

R-AE2105

A3

C3

R-AE2104

A1

R-AE3202

A4

R-AE3202

6'-3 1/2" 54'-0" 12'-8 1/2" 18'-2"

076115.A01

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

A

ND

RE

W S, M

AR

YL

AN

D

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

A

ND

RE

W S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ma d\D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

MA

D.

rvt 3/1

5/2

2 1 :04

:29 P

M

As indicated

PA

RK

IN

G

GA

RA

GE

- L

EV

EL

PL

AN

- S

EC

TO

R C

R-AE103C

ROD TED TAW

13041219

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R3C

1 CENTER POINT OF RADIUS

2 2" BUILDING EXPANSION JOINT

3 SHADED AREA INDICATES SPRAYED FIREPROOFING ON UNDERSIDE OF

ROOF TO MAINTAIN 2 HOUR RATING FROM BRIDGE CONNECTOR TO

PARKING GARAGE 10'-0" FROM FACE OF PARKING GARAGE

MATERIAL NOTES

076115.A01 METAL ROOF PANEL

076115.U01 GUTTER

R16.1

R16

R14

R13

RA

R-AE2102A2

R-AE2102

R-AE2101 A2

C2

B1

R-AE3101

C1

R-AE3101

R20

R17

R21

19'-11" 40'-0" 60'-0"

'-0

'-0

'-1

1" 2'-

2"34 '-1

1"

'-0

'-0

'-0

'-1

1"

A1

RA

MP

D

OW

N

R-AE2101

C2

ELEV.

LOBBY

R-4Q01

STAIRS

R-4QS6

STAIRS

R-4QS7

R18

R15

ELEVS

RE RF

R12

R11

A4

R-AE3207

RH

A1

R-AE3101

40'-0" 19'-11"

'-0

'-0

3 3

3 3

3 3

'-0

8'-

5"

183'-6"

18'-2"

1'-10"

20'-0" 117'-0" 26'-6" 12'-3"9'-3"

185'-0"

'-4

2'- 9"

'-0

6'-

1"

R101'- 9" 1'-10"

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

OPEN PARKING GARAGE CALCULATIONS

TOTAL OPEN AREA OPEN AREA OPEN AREA OPEN AREA % OPEN AREA

PERIMETER REQUIRED PROVIDED DIFFERENCE DISTRIBUTION DISTRIBUTION OF

(SF) (SF) (SF) (SF) LENGTH (S.F.) TOTAL PERIMETER

1ST TIER 1037 1452 1492 39 417 40

2ND TIER 1037 1452 1738 286 645 62

3RD TIER 1037 1452 1737 286 804 78

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

A

ND

RE

W S, M

AR

YL

AN

D

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

A

ND

RE

W S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ dc s\D es kto p\L

OC

AL

F

ILE

S\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_ dc s.r vt 4/1

7/2

2 1 :58

:53 P

M

As indicated

PA

RK

IN

G

GA

RA

GE

- L

EV

EL

PL

AN

R-AE104

TED DLT TAW

13041220

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

FLOOR 4FLOOR 4

R4

100'0 20' 60'

1/32"=1'-0" GRAPHIC SCALE

20'

LEVEL DESCRIPTION COUNT

Ramp Parking: 8'-6" x 17' 69 : 69

PRKG - ELEV. PIT Ramp Parking: 8'-6" x 17' 22

PRKG - ELEV. PIT: 22

PRKG - 1ST FLR Ramp Parking: 8'-6" x 17' 5 PRKG - 1ST FLR ADA: 8'-0" x 20'-0" 10 PRKG - 1ST FLR 9'-0" x 18'-0" 97

PRKG - 1ST FLR: 112

PRKG - 2ND FLR ADA: 8'-0" x 20'-0" 5 PRKG - 2ND FLR 9'-0" x 18'-0" 110

PRKG - 2ND FLR: 115

PRKG - 3RD FLR Ramp Parking: 8'-6" x 17' 30 PRKG - 3RD FLR 9'-0" x 18'-0" 125

PRKG - 3RD FLR: 155

PRKG - 4TH FLR 9'-0" x 18'-0" 125

PRKG - 4TH FLR: 125

Grand total: 598

1 WHEEL STOP TYP. (SAFETY YELLOW)

2 SURFACE MOUNTED PEDESTAL BOLLARD TYP. SEE DETAIL C5/AE5611

3 FLOOR DRAINS TYP. REFER TO PLUMBING SHEETS

4 FIRE EXTINGUISHER CABINET

5 OUTLINE OF CONNECTOR ROOF BELOW

R19

R16.1

R16

RA B1

R-AE3101

R20

R17

R21

A3

R-AE4203

19'-11" 40'-0" 60'-0"

2'- 2"

'-1

1"

'-0

'-0

'-0

'-1

1"

REF LINE

R-AE104B

REF LINE

R-AE104B

A2

R-AE3201

RA

MP

D

OW

N

R18

R-AE4103

A3

RE RF

R-AE2103

A1

R-AE2103A2

A1

R-AE3101

40'-0" 19'-11"

2 2

R-AE2101

C2

R-AE2101 A2

R-AE2102A2

5 5 5 5

8 8

'-1

1"

5'- 8"

8'-

9"

5'-

5'-

8"

'-0

1'-10"1'-10"

183'-6"

40'-0" 19'-11"60'-0"40'-0"19'-11"

10 10

9'- 0" x1 8'-

0"

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0" x1 8'-

0"

SP

AC

ES

69'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'-0" x 18'-0"

12 SPACES @

A2

R-AE3203

A1

R-AE3203

A2

R-AE3202

A4

R-AE3203

27'-0" 9'-4 1/2" 53'-7 1/2"

10'-3" 26'-1"

R-AE5135

C3

R-AE5135

A2

A1

R-AE5224

A1

R-AE5224

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

AN

DR

EW

S, MA

RY

LA

ND

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

AN

DR

EW

S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ dc s\D es kto p\A nd re ws

\LO

CA

L F

ILE

S\

4-

An dr ew s A

CC

_P ar kin g G ar ag e_

LO

CA

L.r vt

3/1 4/2

2 4

:04 :54

P M

As indicated

PA

RK

IN

G

GA

RA

GE

-L

EV

EL

4P

LA

N -S

EC

TO

R A

R-AE104A

TED DLT TAW

13041221

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R4A

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

1 WHEEL STOP TYP. (SAFETY YELLOW)

2 2" BUILDING EXPANSION JOINT

3 FLOOR DRAINS TYP. REFER TO PLUMBING SHEETS

4 LIGHT POLE ATOP COLUMN, COORDINATE W/ ELECTRICAL

5 4" WIDE PAINTED STRIPPING

6 GUARDRAILS IN SHEAR WALL OPENINGS, TYPICAL, SEE PRECAST

PANEL ELEVATIONS FOR HEIGHTS

7 PAINT LOWER 4'-0" OF CONCRETE COLUMMN "SAFETY YELLOW"

8 FIRE EXTINGUISHER CABINET

9 STOP SIGN

10 APPLY DECK COATING TYPE 1 ON PARKING/ DRIVE SURFACE

11 SEE R - AE4105 FOR ROOF PLAN

R16.1

R16

R14

R13

RA

R-AE2101 A2

B1

R-AE3101

C1

R-AE3101

'-0

'-0

'-1

1" 2'-

2"

REF LINE

R-AE104A

REF LINE

R-AE104A

A3

R-AE3201

ELEV.

LOBBY

R15

RJ

ELEV ELEC CLOSET

R-4Q02

R-AE4102

A4

RE RF

R12

R11

R-AE2103

C1

A4

R-AE3207

RH

R-AE2103 C2

A1

R-AE3101

ELEV 5A & 5B

ELEV05

R-AE2102A2

4 44 4

R-AE2114

A1

7 7

40'-0" 19'-11"60'-0"40'-0"19'-11"

'-0

'-0

5'- 8"

8'-

9"

20'-0" 117'-0" 26'-6" 12'-3" 9'-3"

185'-0"

9 9

9'- 0" x1 8'-

0"

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AC

ES

9'- 0 " x1 8'-

0 "

SP

AA

CE

S

9'-0" x 18'-0"

11 SPACES @

R10

C3

R-AE2104

A1

R-AE3202

A4

R-AE3202

A3

R-AE3202

6'-7 1/2" 53'-8" 13'-0 1/2" 18'-0"

A3

R-AE3204

R-AE5135

C3

R-AE5135

A2

A1

R-AE5224

A1

R-AE5224

A. REFER TO GI2000 SERIES SHEETS FOR STANDARD SYMBOLS AND

ABBREVIATIONS, AND EXPANSION JOINT, INSULATION AND FIREPROOFING

SCHEDULES.

B. SEE GS SERIES SHEETS FOR LIFE SAFETY INFORMATION.

C. DIMENSIONS ARE FROM CENTER OF THE COLUMN TO FACE OF CMU OR

STUD, AND FROM FACE OF METAL STUD TO FACE OF METAL STUD,

UNLESS OTHERWISE NOTED.

D. REFER TO SHEET CG509 FOR HANDICAP PARKING STRIPING, WHEEL STOP.

E. REFER TO SHEETS AE8001 - AE8003 FOR PARTITION TYPES, AND PARTITION

DETAILS.

F. REFER TO SHEET AE8101 FIRESTOP INFORMATION FOR PENETRATIONS

THROUGH RATED FLOORS AND PARTITIONS.

G. REFER TO SHEETS R-AG101A THRU R-AG5001 FOR SIGNAGE ASSOCIATED

WITH PARKING GARAGE

H. REFER TO SHEET R-AE2110 FOR ENLARGED ELEVATION KEYPLAN

I. REFER TO SHEETS R-AE4111 - R-AE4114 FOR REFLECTED CEILINGS

J. REFER TO SHEETS R-AE4204 AND R-AE4205 FOR TYPICAL PRECAST STAIR

AND RAILING LAYOUT, AND DETAILS.

SHEET NOTES

KEY NOTES: XX

RATED PARTITION LEGEND

2 HOUR FIRE BARRIER

IROLFF

A R C H I T E C

R E G I S T E R E D

7952R

ST

A TE O

AD

T

OB

ERT E D WA R D

Y OHE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

DE

PA

RT

ME

NT

O

F

TH

E

NA

VY

AM

BU

LA

TO

RY

C

AR

E

CE

NT

ER

IP

T

JO

IN

T

BA

SE

AN

DR

EW

S, MA

RY

LA

ND

JO

IN

T

BA

SE

A

ND

RE

W

S, M

AR

YL

AN

D

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

W

AS

HI

NG

TO

N

JO

IN

T

BA

SE

AN

DR

EW

S

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N40080-10-C-0151

850427

DRAWFORM REVISION: 10 MARCH 2009

NOTES:

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

4750 New Broad Street Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

C:

\U se rs\ ma d\D oc um en ts\

4- An dr ew s A

CC

_P ar kin g G ar ag e_ Ce ntr al_

MA

D.

rvt 3/1

5/2

2 1 :04

:35 P

M

As indicated

PA

RK

IN

G

GA

RA

GE

-L

EV

EL

4P

LA

N -S

EC

TO

R B

R-AE104B

TED DLT TAW

13041222

NKEYPLAN

AMBULATORY CARE CENTER

JOINT BASE ANDREWS, MD

R4B

50'0 10' 30'

1/16"=1'-0" GRAPHIC SCALE

10'

1 WHEEL STOP TYP. REFER TO CIVIL FOR DETAILS

2 SURFACE MOUNTED PEDESTAL BOLLARD TYP. SEE DETAIL C5/AE5611

3 LIGHT POLE ATOP COLUMN, COORDINATE W/ ELECTRICAL

4 2" BUILDING EXPANSION JOINT

5 FLOOR DRAINS TYP. REFER TO PLUMBING SHEETS

6 PAINT LOWER 4'-0" OF CONCRETE COLUMMN "SAFETY YELLOW"

7 4" WIDE PAINTED STRIPPING

8 FIRE EXTINGUISHER CABINET

9 APPLY DECK COATING TYPE 1 ON PARKING/ DRIVE SURFACE

10 GUARDRAILS IN SHEAR WALL OPENINGS, TYPICAL, SEE PRECAST PANEL

ELEVATIONS FOR HEIGHTS

11 OUTLINE OF CONNECTOR ROOF BELOW

12 SEE R - AE4105 FOR ROOF PLAN