18R0026FinalSpottedBearHydroeRenDrawings.pdf
PDF 6 MB Posted
- Attached to
- Spotted Bear Hydroelectric Renovation Federal contract opportunity
- Solicitation number
- 12034318R0026
About this file
RFP Solicitation 12034318R0026 Spotted Bear Hydroelectric Renovation - Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 12034318R0026Amendment0003QAs.pdf | ||
| 2002_SB_Dam_Repairs.pdf | ||
| 12034318R0026Amendment0002QAs.pdf | ||
| 12034318R0026FinalAmendment0001QAs.pdf | ||
| 18R0026FinalSpottedBearHydroRenSpecs.pdf | ||
| 20180725FinalSol18R0026SpottedBearHydroRenRFP.pdf | ||
| 18R0026FinalSpottedBearFlatheadCoBuildingMT180033WRates.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TECH. REVIEW:
DATE:
SHEET
015OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
COPYRIGHT MORRISON-MAIERLE, INC., 2015
SPOTTED BEAR
HYDROELECTRIC RENOVATIONG0.1
TOPOGRAPHIC & MECHANICAL
LEGEND, SYMBOLS, & NOTES
06-01-2015
JAC
KWS
WWW
KSJ
RJH
ACB
G0.2 003
ELECTRICAL LEGEND,
SYMBOLS, & NOTES
06-01-2015
TECH. REVIEW:
DATE:
SHEET
015OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
222 N. HIGGINS
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
14102
UNITED STATES DEPARTMENT OF AGRICULTURE
SPOTTED BEAR
HYDROELECTRIC RENOVATION
ABBREVIATIONS
A or AMP AMPERES
AC ALTERNATING CURRENT
A/C AIR CONDITIONING
AF AMP FUSE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AL ALUMINUM
AS AMP SWITCH
ATS AUTOMATIC TRANSFER SWITCH
BAS BUILDING AUTOMATION SYSTEM
BKR BREAKER
C RACEWAY/CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
C.O.
RACEWAY/CONDUIT ONLY, WITH PULL STRING
CNTRL CONTROL
CU COPPER
DISC DISCONNECT
DIST DISTRIBUTION
DPDT DOUBLE POLE DOUBLE THROW
DWG DRAWING
EA EACH
EF EXHAUST FAN
ELEC ELECTRIC
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EX OR
EXIST
EXISTING
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
FD FUSED DISCONNECT
FLR FLOOR
FO FIBER OPTIC
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
GEC GROUNDED ELECTRODE CONDUCTOR
GFI GROUND FALUT INTERRUPTER
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HTR HEATER
HVAC
HEATING, VENTILATING & AIR CONDITIONING
HZ HERTZ
J-BOX JUNCTION BOX
KVA KILOVOLT AMPERES
KW KILOWATTS
LTG LIGHTING
LPW LUMENS PER WATT
MAG MAGNETIC STARTER
MAN MANUAL
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH METAL HALIDE
MIN MINIMUM
MSS MOTOR STARTER SWITCH
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA
NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFD NON-FUSED DISCONNECT
NIC NOT IN CONTRACT
NO NORMALLY OPEN
# NUMBER
OAE OR APPROVED EQUAL
OC ON CENTER
OCPD OVERCURRENT PROTECTION DEVICE
OH OVERHEAD
P POLE
PB PUSHBUTTON
PNL PANEL
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
RECEPT RECEPTACLE
RCPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RVNR REDUCED VOLTAGE NON-REVERSING
RVR REDUCED VOLTAGE REVERSING
SP SINGLE POLE TOGGLE SWITCH
SPEC SPECIFICATION
SPST SINGLE POLE SINGLE THROW
SSPB START-STOP PUSHBUTTON
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TB TELEPHONE BOARD
TC TIME CLOCK
TD TIME DELAY
TEL TELEPHONE
TSP TWISTED SHIELDED PAIR
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
V VOLT
VA VOLT AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WATTS
WP WEATHERPROOF
W/O WITHOUT
XFMR TRANSFORMER
Y WYE CONNECTED
DELTA CONNECTED
PHASE
*THESE ABBREVIATIONS COMPRISE A STANDARD LIST;
NOT ALL ABBREVIATIONS APPEAR ON THIS PROJECT.
PROJECT NOTES:
1. PRIOR TO BID CONTRACTOR SHALL VISIT THE SITE. NOT ALL WORK
REQUIRED TO COMPLETE THE PROJECT IS SHOWN ON THE DRAWINGS. THE
CONTRACTOR SHALL BECOME THOROUGHLY FAMILIAR WITH ALL THE WORK
REQUIRED TO COMPLETE THE PROJECT IN ADDITION TO THE LOCAL
CONDITIONS AND INCLUDE SAID WORK IN THE BID.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL
ELECTRICAL SERVICE WORK WITH UTILITY. OWNER PAYS ALL FEES,
CONTRACTOR DOES ALL SCHEDULING AND COORDINATION OF WORK. IT IS
THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE ALL
SCHEDULES ARE MET.
3. GENERAL WORK PRACTICES FOR ELECTRICAL CONSTRUCTION SHALL BE IN
ACCORDANCE WITH NECA 1, "STANDARD PRACTICES FOR GOOD
WORKMANSHIP IN ELECTRICAL CONTRACTING." THIS PUBLICATION IS
AVAILABLE FROM NECA BY TELEPHONE AT 301-657-3110 OR ON-LINE AT
WWW.NECANET.ORG.
4. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING
RACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT POSSIBLE.
THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLE
TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND ALLOWED
PER CODE, FISHING THROUGH WALLS WITH MC CABLE IS PREFERRED TO
SURFACE-MOUNTED CONDUIT.
5. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF
LAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THE THE BALLASTS DO NOT
CONTAIN PCBs. THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY
IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBs.
6. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY
DISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM AND
BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN THAT
SPACE.
7. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE WITH
MECHANICAL FOR PLENUM SPACES AND PROVIDE PLENUM RATED CABLES
WHERE REQUIRED FOR LIGHTING CONTROL, DATA, FIRE ALARM AND ALL
OTHER L.V. SYSTEMS NOT INSTALLED IN CONDUIT. VERIFY CONDUIT
REQUIREMENTS ON DRAWINGS AND SPECIFICATIONS.
8. FIRE-RESISTANCE: PROVIDE A MINIMUM HORIZONTAL DISTANCE OF 24"
BETWEEN OUTLET BOXES LOCATED ON OPPOSITE SIDES OF
FIRE-RESISTANCE RATED WALLS. WHERE THIS IS NOT POSSIBLE INSTALL UL
LISTED PUTTY PADS ON ALL OUTLET BOXES NOT MEETING THE 24"
SEPARATION. PROVIDE A UL LISTED THROUGH -PENETRATION FIRESTOP FOR
PENETRATIONS OF FIRE-RESISTANCE RATED ASSEMBLIES.
9. CONDUCTORS ARE SIZED PER THE 75 DEGREE C RATING COLUMN OF NEC
TABLE 310.16. IF THE TERMINAL USED FOR A TERMINATION OF A PARTICULAR
CONDUCTOR IS NOT MARKED, OR THE TERMINAL IS MARKED FOR 60 DEGREE
C CONDUCTORS, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO EITHER
ADJUST THE AMPACITY OF THE CONDUCTOR TO MATCH THE 60 DEGREE
COLUMN OF TABLE 310.16, OR REPLACE THE TERMINAL WITH ONE RATED FOR
AT LEAST 75 DEGREES C
10. FOR 20A BRANCH CIRCUIT RUNS EXTENDING BEYOND 300 LINEAR FEET.
CONDUCTOR SIZE SHALL BE A MINIMUM OF #10 CU.
11. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH 120V BRANCH
CIRCUIT.
ELECTRICAL SYMBOL LEGEND: POWER PLANS
SYMBOL DESCRIPTION DESCRIPTION SYMBOL
BRANCH CIRCUIT PANELBOARD RACEWAY STUB-OUT OR STUB-UP WITH CAPPED END
PANEL AND CIRCUIT DESIGNATION ARE SHOWN NEXT
TO EACH DEVICE (PANEL NAME - CIRCUIT NUMBER).
BRANCH CIRCUIT WIRE SIZE IS #12 UNLESS NOTED
OTHERWISE. A SINGLE INSULATED GREEN GROUND
CONDUCTOR SHALL BE PROVIDED WITH EACH HOME
RUN. PROVIDE A SEPARATE NEUTRAL FOR EACH
CIRCUIT. HOME RUNS SHALL HAVE NO MORE THAN
THREE CIRCUITS. LINE VOLTAGE AND LOW VOLTAGE
WIRING IS NOT SHOWN ON PLANS. FOR EQUIPMENT
CIRCUITING, SEE MEP COORDINATION SCHEDULE.
SURFACE MOUNTED PLUGSTRIP. SUBSCRIPT DENOTES
TYPE AND STYLE. SEE TABLE BELOW:
TYPE A: PLUGSTRIP, POWER ONLY, OUTLET EVERY 3' OC
TYPE B: WIREMOLD SERIES 4000 POWER AND DATA
TYPE C: WIREMOLD SERIES 5400 POWER AND DATA
DUPLEX RECEPTACLE. (MOUNT AT +18" AFF. UNO.)
X-GFI-GFCI RECEPTACLE
WP-WEATHER PROOF WITH WHILE IN USE COVER
4PLEX RECEPTACLE. (MOUNT AT +18" AFF. UNO.)
X-GFI-GFCI RECEPTACLE
WP-WEATHER PROOF WITH WHILE IN USE COVER
LINE BREAK
ABOVE COUNTER DUPLEX RECEPTACLE MOUNTED 4"
ABOVE BACKSPLASH
SURFACE MOUNTED RACEWAY
ABOVE COUNTER 4PLEX RECEPTACLE MOUNTED 4"
ABOVE BACKSPLASH
RACEWAY CONCEALED IN WALL, FLOOR, OR CEILING IN
FINISHED SPACES, EXPOSED IN UNFINISHED
SPACES.
FLOOR OUTLET - HUBBEL MODEL #HBLCFB401CB
WITH COVER MODEL #HBLTCGNTBKSW, OR EQUAL.
RACEWAY BELOW FLOOR OR BELOW GRADE
FLOOR BOX WITH COMBINATION 4PLEX RECEPTACLE
AND 2 TELEPHONE/DATA OUTLETS. MANF HUBBEL
MODEL #HBLCFB401CB WITH COVER MODEL
#HBLTCGNTBKSW, OR EQUAL.
RACEWAY STUB-OUT OR STUB-UP WITH BUSHED END
JUNCTION BOX GROUNDING BUS
FLATSCREEN TV BOX; 2-GANG, FLUSH IN WALL,
HUBBELL RACO NSAV62M WITH NSAV6C COVER.
DUPLEX RECEPTACLE AND SINGLE GANG DATA PORT.
(MOUNT AT +72" AFF. UNO.)
PUSHBUTTON (MOUNT AT +54" AFF, UNO.)
-EPO EMERGENCY POWER OFF
-ADA HANDICAP ACCESSIBLE DOOR (DEVICE BY OTHERS)
-ODO OVERHEAD DOOR OPERATOR (DEVICE BY OTHERS)
SPECIAL PURPOSE OUTLET, LETTER INDICATES TYPE.
(MOUNT AT +18" AFF. UNO.)
TYPE A: NEMA 5-20R
TYPE B: NEMA 5-30R
TYPE C: NEMA 5-50R
TYPE D: NEMA 6-20R
TYPE E: NEMA 6-30R
TYPE F: NEMA 6-50R
TYPE G: NEMA 14-20R
TYPE H: NEMA 14-30R
TYPE I: NEMA 14-50R
1. THESE SYMBOLS COMPRISE A STANDARD LIST; NOT ALL SYMBOLS APPEAR ON THIS PROJECT.
2. ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE ABOVE FINISHED FLOOR. MOUNTING HEIGHTS INDICATED ON ARCHITECTURAL WALL ELEVATIONS
OR AS NOTED SPECIFICALLY ON THE DRAWINGS OR IN THE SPECIFICATIONS SHALL TAKE PRECEDENCE OVER MOUNTING HEIGHTS LISTED.
X
PS-X
X
X
X
X
ELECTRICAL SYMBOL LEGEND: 1-LINES
SYMBOL DESCRIPTION DESCRIPTION SYMBOL
SWITCH BOARD OR PANEL BOARD; NAME, VOLTAGE,
PHASE, NUMBER OF WIRES WHEN INDICATED
DISCONNECT SWITCH ("XXAS' = SWITCH AMP RATING)
CT AND CUSTOMER POWER METER
FUSED DISCONNECT SWITCH ("XXAS/XXAF" - SW AND FUSE
AMP RATING)
MOTOR SYMBOL
COMBINATION MOTOR STARTER (STR SIZE, TYPE, AS, AF,
SEE MEP COORD. SCHEDULE)
UTILITY ELECTRIC METER AND BASE (BASE BY
CUSTOMER)
AUTOMATIC TRANSFER SWITCH
TRANSIENT VOLTAGE SURGE SUPPRESSION VARIABLE FREQUENCY DRIVE
LIGHTNING ARRESTOR FIXED MOUNT LV BREAKER
STRESS RELIEF CONE
FUSED SWITCH ("XXAS/XXAF" = SW AND FUSE AMP RATING)
POWER FACTOR CORRECTION CAPACITOR GENERATOR
MOTOR STARTER SWITCH WITH THERMAL OVERLOADS WALL MOUNTED BREAKER
CONTRACTOR NORMALLY OPEN, NORMALLY CLOSED
THERMAL OVERLOAD ELEMENT
TRANSFORMER
3-PHASE, 3-WIRE DELTA CONNECTION Δ
3-PHASE, 4 WIRE GROUNDED WYE CONNECTION
LP100
208/120V
3#. 4W
TVSS
VFD
M
CB
Y
ELECTRICAL SYMBOL LEGEND: LIGHTING PLANS
SYMBOL DESCRIPTION DESCRIPTION SYMBOL
1X4 SURFACE WALL MOUNT FLUORESCENT
PENDANT FIXTURE; HIGH BAY, LOW BAY, DECORATIVE.
1X4 2X2 2X4 RECESSED FLUORESCENT, 'a', AND
'b'.DESIGNATES SWITCH LEGS.
EXIT SIGN. ARROW(S) INDICATE DIRECTION OF TRAVEL,
SHADED AREA INDICATES ILLUMINATED FACE(S). STEM
INDICATES WALL MOUNTED. CELING MOUNTED
OTHERWISE.
1X4 2X2 2X4 RECESSED EMERGENCY FLUORESCENT,
'a', AND 'b'.DESIGNATES SWITCH.
EMERGENCY EGRESS BATTERY PACK, WALL MOUNT OR
CEILING MOUNT
1X4 2X2 2X4 SURFACE OR PENDANT FLUORESCENT, 'x'
DESIGNATES SWITCH LEG.
WALL MOUNTED SCONCE OR WALLPACK FIXTURE
1X4 2X2 2X4 SURFACE OR PENDANT EMERGENCY
FLUORESCENT, 'x' DESIGNATES SWITCH LEG.
SURFACE MOUNTED DOWNLIGHT
4' FLUORESCENT STRIP OR INDUSTRIAL, SURFACE OR
CHAIN HUNG
RECESSED CAN DOWNLIGHT
POLE MOUNTED FIXTURE RECESSED CAN WALLWASHER
LIGHTED BOLLARD
TRACK LIGHTING. SEE FIXTURE SCHEDULE AND LIGHTING
PLANS.
STANDARD LIGHTING CONTROLS: SWITCHES AND LINE VOLTAGE DIMMERS
TOGGLE SWITCH (MOUNT AT 46" AFF. UNO.)
SUBSCRIPTS:
X- INDICATES TYPENONE- SINGLE POLE
3- THREE-WAY
4- FOUR-WAY
D- DIMMER SWITCH - PHILIPS SUNRISE DIMMER -
ON/OFF.
K- KEYED SWITCH
T- TIMER
P- PILOT LIGHT
OS-WALL SWITCH OCC SENSOR. WATTSTOPPER
DW100(SINGLE SWITCH OR DW-200 DUAL SWITCH).
a- SINGLE POLE LIGHTING SWITCH FOR ZONE a b- SINGLE POLE LIGHTING SWITCH FOR ZONE b ab- LIGHTING SWITCHES WITH MULTIPLE ZONES
CEILING MOUNT OCCUPANCY SENSOR. WATT
STOPPER DT-300 DUAL TECHNOLOGY CEILING MOUNT
OR EQUAL WITH BZ-50 POWER PACKS AS NEEDED.
WALL MOUNT OCCUPANCY SENSOR. WATT STOPPER
DT-200 DUAL TECHNOLOGY WALL MOUNT OR EQUAL WITH
BZ-50 POWER PACKS AS NEEDED.
PHOTOCELL. WATT STOPPER DLM LS-301 CEILING
MOUNT OR EQUAL
X
COPYRIGHT MORRISON-MAIERLE, INC., 2015
SHEET
015OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
COPYRIGHT MORRISON-MAIERLE, INC., 2015
SPOTTED BEAR
HYDROELECTRIC RENOVATIONG0.3
ABBREVIATIONS, NOTES, &
SUPPLEMENTAL DETAILS
06-01-2015
JAC
EXISTING EMT FROM
100A SERVICE PANEL
100A SERVICE PANEL
100A DISCONNECT
300A BALLAST LOAD
PANEL
WH METER
SPEED
CONTROLLER
CIRCUIT BREAKER
DISTRIBUTION PANEL
TI
TRANSFORMER
HIGH VOLTAGE
CABLE PARKING
STAND
HEATER UNIT
EX PRIMARY 5KV
EXISTING 5KV CABLE
TO BE PULLED BACK
TO NEW EXTERIOR
TRANSFORMER.
GENERATOR
OUTLET
BOX
SPEED
INCREASER
TURBINE
MOTORIZED
GATE VALVE
10" GATE VALVE
REMOVE, SAVE AND
REUSE
TAILRACE
STEEL COVERS
REMOVE APPROX. 16' OF EXST. 15" PVC
10" 90° BEND AND
VERTICAL SPOOL
REMOVE, SAVE AND
REUSE
15" PVC PIPE (TYP OF 2)
STEEL PLATE
MANIFOLD
CULVERT
(TYP OF 2)
EXISTING LIGHTING TO
BE REMOVED
EXISTING LIGHTING TO
BE REMOVED
TECH. REVIEW:
DATE:
SHEET
015OFPKG3
SPOTTED BEAR
HYDROELECTRIC RENOVATION
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
COPYRIGHT MORRISON-MAIERLE, INC., 2015
D1.1
DEMOLITION PLAN
DEMOLITION PLAN1
3/4"=1'
GENERAL NOTES:
A. LOCATION AND SIZE OF EXISTING EQUIPMENT, PIPING, AND FACILITIES
ARE FROM VARIOUS RECORD DRAWINGS AND FIELD MEASUREMENTS.
CONTRACTOR SHALL FIELD VERIFY ALL INFORMATION AND MAKE FIELD
OBSERVATIONS FOR ITEMS NOT SHOWN.
B. ALL DEMOLITION AND SALVAGE WORK SHALL BE COORDINATED AND
SCHEDULED WITH OWNER AND ENGINEER.
C. ALL ITEMS SHOWN TO BE REMOVED AND NOT SPECIFIED TO BE
SALVAGED OR RELOCATED SHALL BE REMOVED AND DISPOSED OF
OFF-SITE AT AN APPROVED LOCATION.
D. ALL EXISTING EQUIPMENT, PIPING, ELECTRICAL FACILITIES, ETC. NOT
SPECIFICALLY SHOWN TO BE REMOVED OR MODIFIED SHALL BE
PROTECTED BY THE CONTRACTOR. ANY ITEMS NOT SCHEDULED FOR
DEMOLITION THAT ARE DAMAGED DURING CONSTRUCTION SHALL BE
REPAIRED OR REPLACED BY THE CONTRACTOR AT NO ADDITIONAL
EXPENSE TO THE OWNER.
E. WHEREVER EXISTING FACILITIES ARE BOLTED TO CONCRETE AND CMU
FLOORS OR WALLS, CUT EXISTING BOLTS FLUSH WITH WALL OR FLOOR
AND COAT EXPOSED BOLT AT SURFACE WITH COAL TAR EPOXY.
F. EXISTING CONDUIT OR OTHER WALL PENETRATIONS RESULTING FROM
DEMOLITION OF ITEMS SHALL BE PLUGGED WITH NON-SHRINK GROUT,
SMOOTH FINISH, BOTH SIDES.
G. CONTRACTOR SHALL ALSO DEMOLISH AND REMOVE ANY EXISTING
CONCRETE DEADMAN/THRUST BLOCKS ENCASING EXISTING PIPING
WITHIN LIMITS SHOWN.
H. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE NO
CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS, BOXES,
AND OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE FINAL
PLACEMENT OF MATERIALS.
I. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF
FLOORS, WALLS, CEILINGS, AND ROOFS TO PERFORM THE REQUIRED
WORK DEPICTED IN THESE DOCUMENTS. THE CONTRACTOR IS
RESPONSIBLE FOR ALL PATCHING OF HOLES TO THE SATISFACTION OF
THE ARCHITECT/ENGINEER.
06-01-2015
JAC
SPOTTED BEAR RANGER STATION
DIVERSION STRUCTURE
POWER HOUSE
S
O
U
T
H
F
O
R
K
F
L
A
T
H
E
A
D
I
V
E
R
N
F
NF-2826
A
D
D
I
T
I
O
N
C
E
E
K
0 300300 600150
HORIZ. SCALE
IN FEET
TECH. REVIEW:
DATE:
SHEET
OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
OVERALL SITE PLAN
COPYRIGHT MORRISON-MAIERLE, INC., 2015
SPOTTED BEAR
HYDROELECTRIC RENOVATIONC0.1
SITE LAYOUT
06-01-2015 015
JAC
LDC
0 55 102.5
HORIZ. SCALE
IN FEET
TECH. REVIEW:
DATE:
SHEET
015OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
DIVERSION SITE PLAN
1 SITE IMPROVEMENTS PLAN
1/2"=1'-0"
COPYRIGHT MORRISON-MAIERLE, INC., 2015
SPOTTED BEAR
HYDROELECTRIC RENOVATIONC0.2
DIVERSION IMPROVEMENT
PLANS
** FIELD VERIFY DIMENSIONS PRIOR TO SLIDE
GATE BRACKET FABRICATION.
* FIELD VERIFY FIT BETWEEN BAFFLE WALL AND
SLIDE GATE BRACKET/
06-01-2015
JAC
EXST CONCRETE WALL
EXST DEBRIS SCREEN
"Ø GALV THREADED
ANCHOR ROD w/ NUT &
WASHER EA SIDE
" THICK GALV STL
" THICK GALV STL
EXST CONCRETE WALL
APPROX CHANNEL BOTTOM
EXST CONCRETE FOOTING
"Ø GALV THREADED
ANCHOR ROD
(TYPOF 6)
GATE FULL OPEN
GATE INVERT
FIELD VERIFY EXST
CONCRETE FOOTING
ADD CONCRETE SILL UNDER
GATE AS NEEDED
GATE BRACKET EACH
SIDE SEE (TYP)
INVERT
EXST CONCRETE FOOTING
GATE FULL OPEN
INSTALL w/ INVERT AT LOWEST
FEASIBLE ELEVATION
SLIDE GATE NOT SHOWN FOR CLARITY
SLIDE GATE ATTACHMENT PER MFR
PROVIDE BOLT HOLES IN TOP TO
MATCH SLIDE GATE ATTACHMENT,
VERIFY SIZE, SPACING w/ MFR
TYP
"x3"xFULL HT SST
"x1'-6
"xFULL HT SST
"Ø HOLE FOR
"Ø SST ANCHOR
DRILL & EPOXY w/ HILTI HIT HY 200 w/ 4" MIN EMBED @ 18" OC
VERTICALLY
EXST CONC WALL
"x8
"x6" SPACED **
AT 1'-0" OC VERTICALLY
TYP
"x10"xFULL HT SST
ELEVATION
PLAN
TECH. REVIEW:
DATE:
SHEET
015OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
C.02
3 2'-0" SLUICE GATE DETAIL
3/4"=1'-0"
COPYRIGHT MORRISON-MAIERLE, INC., 2015
C.02
2 5'-0" SLIDE GATE DETAIL
3/4"=1'-0"C.02
1 FLOW DIVERSION PLATE
3/4"=1'-0"
SPOTTED BEAR
HYDROELECTRIC RENOVATIONC0.3
DIVERSION IMPROVEMENT
DETAILS
C.02
4 DETAIL
1 1/2"=1'-0"
** FIELD VERIFY DIMENSIONS PRIOR TO
SLIDE GATE BRACKET FABRICATION
06-01-2015
JAC
EXST WALKWAY
AND HANDRAIL
2'-0" SLUICE GATE
SEE
GATE HOIST
HANDWHEEL DRIVE
EXTENSION
HANDWHEEL
HANDWHEEL DRIVE EXTENSION
SUPPORT (TYP OF 2)
GALVANIZED COOPER B-LINE B3090 SUPPORT w/
U-BOLT & B3088 BASE STAND w/
"Ø GALVANIZED
ANCHORS DRILLED & EPOXIED w/ HILTI HIT HY 200.
MIN EMBED 4", VERIFY ANCHOR Ø w/ STAND MFR
EXST WALKWAY
AND HANDRAIL
5'-0" SLIDE GATE
SEE
GATE HOIST
CHAINWHEEL DRIVE
EXTENSION
SST CHAIN
CHAINWHEEL DRIVE EXTENSION
SUPPORT
GALVANIZED COOPER B-LINE B3090 SUPPORT w/
U-BOLT & B3088 BASE STAND w/
"Ø GALVANIZED
ANCHORS DRILLED & EPOXIED w/ HILTI HIT HY 200.
MIN EMBED 4", VERIFY ANCHOR Ø w/ STAND MFR
TECH. REVIEW:
DATE:
SHEET
015OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
COPYRIGHT MORRISON-MAIERLE, INC., 2015
C.02
B SECTION
1/2"=1'-0"C.02
A SECTION
1/2"=1'-0"
SPOTTED BEAR
HYDROELECTRIC RENOVATIONC0.4
DIVERSION IMPROVEMENT
SECTIONS
06-01-2015
JAC
SHEET
015OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
COPYRIGHT MORRISON-MAIERLE, INC., 2015
ALUMINUM BAFFLE PLAN
1 1/2"=1'-0"
EXST FOOTING (TYP)
1'-3"1'-3"
5'-6"
" ALUM PLATE
EXST CONC WALL (TYP)
EXST HYDROPOWER INTAKE
(TYP OF 2)
NEW 6"X6" REINF CONC SILL
SEE DETAIL
SEE DETAIL
1 DETAIL
3"=1'-0"
TYP
ALUM L1
"x1
"x
" (TYP)
" ALUM PLATE
2 DETAIL
3"=1'-0"
TYP
L2"x2"x
" ALUM
" ALUM PLATE (TYP)
A SECTION
1"=1'-0"
3 DETAIL
1 1/2"=1'-0"
SEE DETAIL SIM, BEND
ANGLES OR FABRICATE NEW
BUILT UP ANGLE w/ CORRECT
ORIENTATION
SPOTTED BEAR
HYDROELECTRIC RENOVATIONC0.5
DIVERSION IMPROVEMENT PLAN
& DETAILS
ALUMINUM SCREEN PLAN
1 1/2"=1'-0"
NOTE:
ALUMINUM BAFFLE BELOW NOT SHOWN FOR CLARITY
B SECTION
1 1/2"=1'-0"
4 DETAIL
1 1/2"=1'-0"
SEE DETAIL
SEE DETAIL
5 DETAIL
1 1/2"=1'-0" -
6 DETAIL
3"=1'-0"
ALUM L2"X2"x
SCREEN ABOVE NOT
SHOWN FOR CLARITY
TYP
ALUM L2"x2"x
2"
2"
ALUM L1
"x1
"x
" (TYP)
NOTE:
SUPPORT 6'-6" IN HEIGHT.
TYP (2) LOCATIONS.
10"X
" ALUM PLATE
"Ø HOLE FOR
"Ø SST
THREADED ANCHOR ROD.
DRILL & EPOXY w/ HILTI HIT
HY 200 OR EQUAL w/ 4" MIN
EMBED
NOTE:
1. FIELD VERIFY ALL DIMENSIONS
PRIOR TO FABRICATION.
EXISTING INLET SCREEN
TO BE REMOVED
EXISTING INLET SCREEN
TO BE REMOVED
1'-3"
SEE DETAIL
** FIELD VERIFY CONCRETE
FOOTING HEIGHT
06-01-2015
JAC
SHEET
015OFPKG3
SPOTTED BEAR
HYDROELECTRIC RENOVATION
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
COPYRIGHT MORRISON-MAIERLE, INC., 2015
POWER HOUSE PIPING PLAN
1/2"=1'-0"
M1.1
GENERAL NOTES:
A. TAIL RACE DISCHARGE SYSTEM ASSUMPTIONS:
B. EXISTING PENSTOCK PIPING AND FITTING SHOWN SHADED FOR
REFERENCE.
A SECTION
1/2"=1'-0"
POWERHOUSE MECHANICAL PLAN &
DETAILS
TWO 24" DIAMETER CSP PIPES
INLET PROTRUDING FROM CONCRETE WALL (0.9 LOSS COEF.)
ZERO SLOPE FOR 90-FEET
SIX FEET OF FALL OVER SECOND HALF OF 180-FEET PIPES
16" WATER DEPTH IN TAIL RACE BASIN (DOES NOT INCLUDE
TURBULENCE CREATED BY DISCHARGED WATER)
DESIGN NOTES:
1. PVC PIPE SHALL BE SCH 80, TYPE 1, GRADE 1,
CLASS 12454-B CONFORMING TO ASTM D1785.
FITTINGS SHALL BE SCH 80 THREADED AND
CONFORM TO ASTM D2464. INSTALL UNIONS AT
BOTH END CONNECTIONS. SECURE PIPING TO
NEW CONCRETE CURB WITH PIPE UNI-STRUTS
SUPPORTS.
2. PVC BALL VALVE SHALL BE RATED 150-PSI @
105°F, ASTM D1784, TYPE 1, GRADE 1 PVC BODY,
BALL, AND STEM. VALVES SHALL BE END ENTRY,
DOUBLE UNION DESIGN, REPLACEABLE
ELASTOMER SEATS AND VITON OR TEFLON
O-RING STEM SEALS.
3. (DELETED)
4. EXISTING PVC PENSTOCKS ARE ASTM D3033
PSP SDR-41 CLASS 100-PSI WITH ID = 14.554",
OD = 15.300", AND AVERAGE WALL THICKNESS =
0.373". CONTRACTOR TO VERIFY LOCATION OF
EXISTING PIPE JOINTS. PROVIDE MAXIMUM 4'-0"
PIPE LENGTH BETWEEN TRANSITION
COUPLERS AND EXISTING PIPE JOINT.
5. CAST 316 SST WALL PIPES IN CONCRETE FOR
BALLAST TANK DRAIN AND RETURN. MATCH
PIPING DIAMETER. TRANSITION FROM PVC
PIPING TO SST WALL PIPE AT 90° FITTING
BEFORE CONCRETE PENETRATION. THREADED
ENDS ON SST WALL PIPE FOR CONNECTION TO
PVC PIPING.
06-01-2015
JAC
SHEET
015OFPKG3
SPOTTED BEAR
HYDROELECTRIC RENOVATION
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
COPYRIGHT MORRISON-MAIERLE, INC., 2015
M1.2
M1.1
B SECTION
1/2"=1'-0"
1 DETAIL
1 1/2"=1'-0"
DETAILS
M1.1
C SECTION
1"=1'-0"
2 DETAIL
3"=1'-0"
M1.1
3 DETAIL
1"=1'-0"
06-01-2015
JAC
E0.1:E1.1
13 CONTROLS SCHEMATIC
KSJ
RJH
ACB
E0.1 013
ELECTRICAL DETAILS
06-01-2015
TECH. REVIEW:
DATE:
SHEET
015OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
222 N. HIGGINS
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
14102
UNITED STATES DEPARTMENT OF AGRICULTURE
SPOTTED BEAR
HYDROELECTRIC RENOVATION
1. CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF CONDUCTORS AND
RACEWAYS.
2. CONTROL PANEL IS FURNISHED BY CONTROLS CONTRACTOR.
INSTALLED BY ELECTRICAL CONTRACTOR.
3. EVERYTHING WITHIN THE DASHED LINE IS PROVIDED BY CONTROLS
CONTRACTOR.
4. PROVIDED BY ELECTRICAL CONTRACTOR.
5. PROVIDE CONTROLS FROM PLC TO BALLAST TANK, LEVEL SWITCH AND
THERMAL OVERLOADS. (2)#18CU IN 1/2" C. FOR EACH. COORDINATE WITH
TURBINE MANUFACTURER FOR ALL CONTROLS AND WIRE/CONDUIT REQUIRED.
6. PROVIDE CONTROLS FROM PLC TO HPU CONTROLS. (2)#18CU IN 1/2" C.
COORDINATE WITH TURBINE MANUFACTURER FOR ALL CONTROLS AND
WIRE/CONDUIT REQUIRED.
7. PROVIDE CONTROLS FROM PLC TO GUIDE VAIN TO (2) LEVEL SWITCHES
(OPEN-CLOSE). (2)#18CU IN 1/2" C. FOR EACH. COORDINATE WITH TURBINE
MANUFACTURER FOR ALL CONTROLS AND WIRE/CONDUIT REQUIRED.
8. PROVIDE CONTROLS FROM PLC TO TURBINE VIBRATION SENSOR. (2)#18CU IN
1/2" C. COORDINATE WITH TURBINE MANUFACTURER FOR ALL CONTROLS AND
WIRE/CONDUIT REQUIRED.
9. PROVIDE CONTROLS FROM PLC TO RTU CONTROLS FOR THERMAL OVERLOADS.
(2)#18CU IN 1/2" C. COORDINATE WITH TURBINE MANUFACTURER FOR ALL
CONTROLS AND WIRE/CONDUIT REQUIRED.
KEY NOTES
EXCITER
FIELD
480V, 77KW
SYNCHRONOUS
GENERATOR
1P,60Hz
62KW CROSS
FLOW TURBINE
GUIDE VANE
SOL.
GUIDE VANE
OILDYNES
VR
VRB
MULTI STAGE
RESISTIVE
LOAD BANK
60KW
LOAD BANK
GOVERNOR
PANEL
LIGHTING: TO BE
HARDWIRED WITH
MC CABLE THROUGH
THE POWERHUB SO
THAT EITHER POWER
SOURCE MAY BE
USED.
OTHER
LOADS
SERVICE
PANEL
120VAC TO
GUIDE VANE
CONTROL
TO
CUSTOMER
LOADS
ELECTRIC CONTROL PANEL/ SWITCH GEAR
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE NO
CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS, BOXES,
AND OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE FINAL
PLACEMENT OF MATERIALS.
2. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF
FLOORS, WALLS, CEILINGS, AND ROOFS TO PERFORM THE REQUIRED
WORK DEPICTED IN THESE DOCUMENTS. THE CONTRACTOR IS
RESPONSIBLE FOR ALL PATCHING OF HOLES TO THE SATISFACTION OF
THE ARCHITECT/ENGINEER.
GENERAL NOTES:
52G
250AT
250AF
CT 1-2
250/5
MANUAL
OPEN/CLOSE
AUTO
LEVEL
CONTROL
POWER
BLOCK
480V 120V
GPT
120VAC
CONTROL
POWER
GPT1-2
4/1
100 A
100KVA
EXISTING PRIMARY
DIRECT BURY 4/0 REYNALDS
METALS-L-4/0 AWG AL .090" XLP 5KV
100PCT AND 133PCT INSULATION
LEVEL MV-90 SUNLIGHT RESISTANT.
(UL) 1978 BURIED 2' DEEP ON
AVERAGE.
NEMA 3R LIQUID FILLED, STEP UP TRANSFORMER 480V,
1 Ø, 60HZ TO 2400V 1 Ø, 60HZ.
5KVA, 480V-120/240V, 1 Ø,
60HZ PANEL 'A' EATON
MINI POWER CENTER
P48G11S05P OR EQUAL
480V,1P
120/240 1P
XANTREX POWERHUB 1800
MANUFACTURER: XANTREX
PART NUMBER: PH1800-GFP
(2) TWO BATTERIES (PURCHASED SEPARATELY):
STANDARD GROUP 27. MAXIMUM DIMENSIONS OF BATTERY
TO BE 12"W X 6.75"D X 9"H (INCLUDING TERMINAL POSTS)
30AS
30AF
COPYRIGHT MORRISON-MAIERLE, INC., 2015
PROVIDE
MANUFACTURER
RECOMMENDED
CONDUCTORS
AND RACEWAYS
FEEDER SCHEDULE
SETS IN
PARALLEL
75 DEG
COPPER
FEEDER
NUMBER AMPS
WIRE
QTY PER
CONDUIT CONDUIT
PHASE QTY
AND AWG NEUTRAL AWG
GROUND
AWG
0.2N 20 3W 1 3/4" 2#12 1#12 1#12
0.3 30 3W 1 3/4" 2#10 1#10
0.4N 40 3W 1 1" 2#8 1#8 1#10
1 100 3W 1 1 1/4" 2#3 1#8
2.5 250 3W 1 2 1/2" 2#250 1#250 1#4
3 300 3W 1 2 1/2" 2#350 1#350 1#4
DISPLAY PANEL
FOUR AC RECEPTACLES
8 9
N
G
SWITCHGEAR CONTROL
PANEL (BY MANUFACTURER)
METAL
UNDERGROUND
WATER PIPE
10'
GND RODS
#6 CU #1/0 CU
E0.1:E1.1
16 GROUNDING DETAIL
240V, 2P, NEMA1
(3)#12 CU
MANUAL MAIN
BREAKER
30A DISCONNECT
5KVA MINI POWER
CENTER COMBINATION
XFMR AND PANEL 'A'.
BACKUP BATTERY
EX 2400V
SWITCHGEAR/CONTROL
PANEL
(BY TURBINE MANUFACTURER)
GOVERNOR PANEL
(BY TURBINE MANUFACTURER)
EQUIPMENT PAD
BALLAST TANK
(BY TURBINE MANUFACTURER)
NEW LIQUID FILLED
TRANSFORMER
F
F
TO SWITCH GEAR
4" HOUSE KEEPING
PAD
A-1
A-1
A-3
A-3
A-7
A-5
A-7
A-2
METER
120V POWER IN 3/4" C.
TO
CONTROL
PANEL
77KW, 480V, 1 Ø, 3W, 60HZ
SYNCHRONOUS GENERATOR.
TO EXISTING SPOTTED
BEAR FACILITY
CIRCUIT VIA BACKUP
BATTERY
FWW
A-4
E1.1
POWER PLAN16
3/4" = 1'
KSJ
RJH
ACB
E1.1 014
POWER PLAN
06-01-2015
TECH. REVIEW:
DATE:
SHEET
015OFPKG3
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
222 N. HIGGINS
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
14102
UNITED STATES DEPARTMENT OF AGRICULTURE
SPOTTED BEAR
HYDROELECTRIC RENOVATION
KEY NOTES
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO COORDINATE
WITH EACH OTHER AND VERIFY THAT THERE ARE NO CONFLICTS IN LOCATION
OF DUCTS, CONDUITS, DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUT
THIS PROJECT BEFORE FINAL PLACEMENT OF MATERIALS.
2. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,
WALLS, CEILINGS, AND ROOFS TO PERFORM THE REQUIRED WORK DEPICTED
IN THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL
PATCHING OF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.
3. EXISTING CIRCUITS SHOWN ARE FROM AS BUILTS. VERIFY EXACT CIRCUIT #'S
ON SITE.
4. SEE SHEET E0.1 AND HYDROELECTRIC GENERATION EQUIPMENT PACKAGE
SPECIFICATIONS FOR CONTROLS AND DETAILED ELECTRICAL CONNECTIONS.
GENERAL NOTES:
LUMINAIRE SCHEDULE
TYPE LAMPS DESCRIPTIONS MANUFACTURER CATALOG NO. OR SERIES
MOUNTING/
VOLTAGE
F 39W LED INDUSTRIAL STRIP LIGHT. LITHONIA FEM4 LED-3L-IMAFL
SURFACE/
1. INTERCEPT EXISTING 5KV LINE AND EXTEND TO NEW TRANSFORMER.
2. 4-20mA SIGNAL #18 CU SHIELDED TWISTED PAIR IN 3/4" C. FOR METER
COMMUNICATIONS.
COPYRIGHT MORRISON-MAIERLE, INC., 2015
SHEET
015OFPKG3
SPOTTED BEAR
HYDROELECTRIC RENOVATION
PKG.
NO.
PKG1
PKG2
DESIGNED:
CADD:
SUB SHEET NO. TITLE OF SHEET
REVISIONS
www.aearchitects.com
ARCHITECTS
B I L L I N G S, M T 59101
FAX 4 0 6 . 2 4 8 . 2 4 2 7
PH 4 0 6 . 2 4 8 . 2 6 3 3
6 0 8 N O R T H 2 9 T H
H I S T O R I C
I N T E R I O R S
A R C H I T E C T U R E
PC
PROJECT No
FAX 4 0 6 . 7 2 1 . 1 8 8 7
224 N. HIGGINS, SUITE B
MISSOULA, M T 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3 XXXXXXXX
XXX
DRAWING NO.
0 1 2 3 4 5 6 7 8 9 10 inches
UNITED STATES DEPARTMENT OF AGRICULTURE
FLATHEAD NATIONAL FOREST
14102
COPYRIGHT MORRISON-MAIERLE, INC., 2015
SD1.1
STANDARD DETAILS
06-01-2015
JAC
| 14102_Cover |
| 14102_Cover |
| Layout1 |
COMPLETE SET
File details come from the government source that posted it.