12__Attachment_B_-_Generator_Maintenance_Service_Forms.xlsx

XLSX spreadsheet 40 KB Posted

Attached to
LBAO Generator Maintenance Services Federal contract opportunity
Solicitation number
140R2021Q0095
Issued by
Department of the Interior Bureau of Reclamation

About this file

This document contains maintenance forms and logs for generator maintenance services. It outlines a maintenance schedule and procedures for generators, including monthly testing at 30% load for 30 minutes and load testing every three years at 80% for four hours. Maintenance items are grouped into fuel, lubrication, cooling, exhaust, battery, electrical, engine/generator, and general categories. Readings and conditions are to be recorded after performing maintenance according to the schedule. Relatedly, solicitation number 140R2021Q0095 from the Department of the Interior Bureau of Reclamation seeks generator maintenance services.

View the file

Other files for this federal contract opportunity

Other files attached to LBAO Generator Maintenance Services, newest first.
File Type Posted
Sol_140R2021Q0095_Amd_0001.pdf PDF
12__Amendment_0001_-_Questions_and_Answers_0001.pdf PDF
12__Wage_Determination_-_NV.pdf PDF
12__Wage_Determination_-_CA.pdf PDF
Sol_140R2021Q0095.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Operation & Testing Log

ENGINE GENERATOR OPERATION AND TESTING LOG

DATE:
PERFORMED BY:

DIRECTIONS: Perform maintenance on items listed in Table 1. Fill in appropriate readings, add comments on condition and maintenance completed.

TABLE 1: GENERATOR MAINTENANCE SERVICE DATA SHEET
ITEM NUMBERITEMSFUNCTIONTESTING LOG SUMMARY
1Run Time MeterRecord running time meter reading at start and end of test.
2Power Fail TestSimulate normal power failure from a "cold start" by use of the test switch in the automatic transfer switch or by opening normal power supply to EPSS.
3Time Delay StartObserve and record time delay or start.
4Crank TimeRecord cranking time (terminated when engine starts).
5Transfer SwitchTransfer load to EPS (30% monthly) (80% every three years).
6(a). AC Volt

(b). Hz

(c). AC AmpRecord AC Voltage, frequency, and amperage.
7(a). Oil Pressure
(b). DC AmpRecord initial oil pressure and battery-charging rate.
8(a). Oil Pressure

(b). DC Amp

(c). W/A TemperatuerRecord oil pressure, battery-charging rate, and water or air temperature after 15 mintues of running time.
9(a). Oil Pressure

(b). DC Amp (c). W/A Temperature (d). AC Volts (e). Hz

(f). AC AmpRecord prime mover and AC instruments, just prior to transfer.
10Restore NormalReturn test switch to normal or re-establish normal power supply after a minimum running time of 30 minutes under 30% load (or after 4 hours under 80% load).
11T/D Re-transferRecord time delay on re-transfer.
12T/D StopRecord time delay on shutdown for units so equipped.
13Auto ModeReturn unit to as found configuration.

Maint. Schedule

ENGINE GENERATOR MAINTENANCE SCHEDULE

Component (as applicable) PROCEDURE

X - Action R - Replace, if needed

FREQUENCY
I = Contract Initiation

S = Semiannually A = Annually Nos. indicate hours

Check if CompleteVisual InspectionCheckChangeCleanTestLevel 2
1. Fuel
(a).Main supply tank levelXS
(b).Day tank levelXXS
(c).Day tank float switchXXS
(d).Supply or transfer pump operationXXS
(e).Solenoid valve operationXXS
(f).Strainer, filter, dirt leg, or combinationXS
(g).Water in systemXXS
(h).Flexible hose and connectorsXRS
(i).Tank vents and overflow piping obstructedXXA
(j).PipingXA
(k).Gasoline or diesel fuel in main tankR2 years
2. Lubrication System
(a).Oil levelXXS
(b).Oil changeR50 hours or A
(c).Oil filter(s)X50 hours or A
(d).Lube oil heaterXS
(e).Crankcase breatherXRXS
3. Cooling System
(a).LevelXXS
(b).Antifreeze protection levelXA
(c).AntifreezeXI, 3 years
(d).Adequate cooling water to heat exchangerXS
(e).Rod out heat exchangerXI, 3 years
(f).Adequate fresh air through radiatorXS
(g).Clean exterior of radiatorXA
(h).Fan and alternator beltXXS
(i).Water pump(s)XS
(j).Condition of flexible hoses and connectionXXS
(k).Jacket water heaterXS
(l).Inspect duct work, clean louversXXXA
(m).Louver motors and controlsXXXA
4. Exhaust System
(a).LeakageXXS
(b).Drain condensate trapXS
(c).Insulation and fire hazardsXS
(d).Excessive backpressureXA
(e).Exhaust system hangers and supportsXA
(f).Flexible exhaust sectionXS
5. Battery System
(a).Electrolyte levelXS
(b).Terminals clean and tightXXS
(c).Remove corrosion, case exterior clean and dryXXS
(d).Specific gravity or state of chargeXS
(e).Charger and charge rateXS
(f).Equalize chargeXS
6. Electrical System
(a).General inspectionXS
(b).Tighten control and power wiring connectionsXA
(c).Wire chafing where subject to movementXXS
(d).Operation of safeties and alarmsXXS
(e).Boxes, panels, and cabinetsXS
(f).Circuit breakers, fuses
Note: Operate circuit breakers by hand manuallyXXRXXA
(g).Transfer switch main contactsXXA
(h).Operate transfer switch electrically in both directions using the automatic control systemXXXXS
(i).Calibration of voltage-sensing relays/devicesXXA
(j).Wire insulation breakdownXI
7. Engine/Generator
(a).General inspectionXS
(b).Service air cleanerXXS
(c).Governor oil level and linkageXXS
(d).Governor oilXA
(e).Ignition system - plugs, points, coil, cap, rotor, secondary wire insulationXXRXXA
(f).Choke setting and carburetor adjustmentXS
(g).Injector pump and injectors for flow rate pressure, and/or spray patternXA
(h).Run generator loaded minimum of 30% nameplate rating monthly for 30 min.XS/30 Min.
(i).Run generator loaded minimum of 80% nameplate rating every 3 years for 4 hoursXI
(j).Valve clearanceXI
(k).Torque boltsXI
8. Generator
(a).Brush length appearance, free to move in holderXXXI, 3 years
(b).Commutator and slip ringsXXI, 3 years
(c).Rotor and statorXXI, 3 years
(d).Bearing(s)XRI, 3 years
(e).Bearing greaseXRI, 3 years
(f).ExciterXXXI, 3 years
(g).Voltage regulatorXXXA
(h).Measure and record resistance readings of windings with insulation tester (Megger)XA
9. General Condition
(a).Note any unusual condition of vibration, leakage, noise, temperature, or deteriorationXXS
10. Housekeeping
(a).Note any deficiencies in the housekeeping for the generator and working area.XXS
11. Restore System
(a).Restore system to as found condition.XS
* Maximum time between fuel renewals - more frequent replacement may be necessary

Maint. Log

ENGINE GENERATOR MAINTENANCE LOG
RECORD RESULTS OF PAGES 1 - 4Frequency

S - Semiannually A - Annually Nos. indicate hours

Performed By:
Date:

Item No. Service Frequency Fill in appropriate readings, add comments on conditions and maintenance completed.

1. Fuel
(a).Main supply tank levelS
(b).Day tank levelS
(c).Day tank float switchS
(d).Supply or transfer pump operationS
(e).Solenoid valve operationS
(f).Stainer, filter, dirt leg, or combinationS
(g).Water in systemS
(h).Flexible hose and connectorsS
(i).Tank vents and overflow piping obstructedA
(j).PipingA
(k).Gasoline in main tank (when used) or diesel fuelA
2. Lubrication System
(a).Oil levelS
(b).Oil change50 or A
(c).Oil filter(s)50 or A
(d).Lube oil heaterS
(e).Crankcase breatherS
3. Cooling System
(a).LevelS
(b).Antifreeze protection levelA
(c).AntifreezeA
(d).Adequate cooling water to heat exchangerS
(e).Rod out heat exchangerA
(f).Adequate fresh air through radiatorS
(g).Clean exterior of radiatorA
(h).Fan and alternator beltS
(i).Water pump(s)S
(j).Condition of flexible hoses and connectionS
(k).Jacket water heaterS
(l).Inspect duct work, clean louversA
(m).Louver motors and controlsA
4. Exhaust System
(a).LeakageS
(b).Drain condensate trapS
(c).Insulation and fire hazardsS
(d).Excessive backpressureA
(e).Exhaust system hangers and supportsA
(f).Flexible exhaust sectionS
5. Battery System
(a).Electrolyte levelS
(b).Terminals clean and tightS
(c).Remove corrosion, case exterior clean and dryS
(d).Specific gravity or state of chargeS
(e).Charger and change rateS
(f).Equalize chargeS
6. Electrical System
(a).General inspectionS
(b).Tighten control and power wiring connectionsA
(c).Wire chafing where subject to movementS
(d).Operation of safeties and alarmsS
(e).Boxes, panels, and cabinetsS
(f).Circuit breakers, fuses
Note: Operate circuit breakers by hand manuallyA
(g).Transfer switch main contractsA
(h).Operate transfer switch electrically in both directions using the automatic control systemS
(i).Calibration of voltage-sensing relays/devicesA
(j).Wire insulation breakdown5/500
7. Engine/Generator
(a).General inspectionS
(b).Service air cleanerS
(c).Governor oil level and linkageS
(d).Governor oilA
(e).Ignition system - plugs, points, coil, cap, rotor, secondary wire insulationA
(f).Choke setting and carburetor adjustmentS
(g).Injector pump and injectors for flow rate pressure, and/or spray patternA
(h).Run generator loaded minimum of 30% nameplate rating monthly for 30 min.S/30 min.
(i).Run generator loaded minimum of 80% nameplate rating every 3 years for 4 hours3/4
(j).Valve clearance3/500
(k).Torque belts3/500
8. Generator
(a).Brush length appearance, free to move in holderS
(b).Commutator and slip ringsA
(c).Rotor and statorA
(d).Bearing(s)A
(e).Bearing greaseA
(f).ExciterA
(g).Voltage regulatorA
(h).Measure and record resistance readings of windings with insulation tester (Megger)A
9. Additional Maintenance Items
(Not already included in this form)S
10. General ConditionS
11. HousekeepingS
12. Restore SystemS