12__Attachment_B_-_Generator_Maintenance_Service_Forms.xlsx
XLSX spreadsheet 40 KB Posted
- Attached to
- LBAO Generator Maintenance Services Federal contract opportunity
- Solicitation number
- 140R2021Q0095
About this file
This document contains maintenance forms and logs for generator maintenance services. It outlines a maintenance schedule and procedures for generators, including monthly testing at 30% load for 30 minutes and load testing every three years at 80% for four hours. Maintenance items are grouped into fuel, lubrication, cooling, exhaust, battery, electrical, engine/generator, and general categories. Readings and conditions are to be recorded after performing maintenance according to the schedule. Relatedly, solicitation number 140R2021Q0095 from the Department of the Interior Bureau of Reclamation seeks generator maintenance services.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140R2021Q0095_Amd_0001.pdf | ||
| 12__Amendment_0001_-_Questions_and_Answers_0001.pdf | ||
| 12__Wage_Determination_-_NV.pdf | ||
| 12__Wage_Determination_-_CA.pdf | ||
| Sol_140R2021Q0095.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Operation & Testing Log
ENGINE GENERATOR OPERATION AND TESTING LOG
| DATE: |
| PERFORMED BY: |
DIRECTIONS: Perform maintenance on items listed in Table 1. Fill in appropriate readings, add comments on condition and maintenance completed.
| TABLE 1: GENERATOR MAINTENANCE SERVICE DATA SHEET | |||
| ITEM NUMBER | ITEMS | FUNCTION | TESTING LOG SUMMARY |
| 1 | Run Time Meter | Record running time meter reading at start and end of test. | |
| 2 | Power Fail Test | Simulate normal power failure from a "cold start" by use of the test switch in the automatic transfer switch or by opening normal power supply to EPSS. | |
| 3 | Time Delay Start | Observe and record time delay or start. | |
| 4 | Crank Time | Record cranking time (terminated when engine starts). | |
| 5 | Transfer Switch | Transfer load to EPS (30% monthly) (80% every three years). | |
| 6 | (a). AC Volt |
(b). Hz
| (c). AC Amp | Record AC Voltage, frequency, and amperage. | |
| 7 | (a). Oil Pressure | |
| (b). DC Amp | Record initial oil pressure and battery-charging rate. | |
| 8 | (a). Oil Pressure |
(b). DC Amp
| (c). W/A Temperatuer | Record oil pressure, battery-charging rate, and water or air temperature after 15 mintues of running time. | |
| 9 | (a). Oil Pressure |
(b). DC Amp (c). W/A Temperature (d). AC Volts (e). Hz
| (f). AC Amp | Record prime mover and AC instruments, just prior to transfer. | ||
| 10 | Restore Normal | Return test switch to normal or re-establish normal power supply after a minimum running time of 30 minutes under 30% load (or after 4 hours under 80% load). | |
| 11 | T/D Re-transfer | Record time delay on re-transfer. | |
| 12 | T/D Stop | Record time delay on shutdown for units so equipped. | |
| 13 | Auto Mode | Return unit to as found configuration. |
Maint. Schedule
ENGINE GENERATOR MAINTENANCE SCHEDULE
Component (as applicable) PROCEDURE
X - Action R - Replace, if needed
| FREQUENCY | |
| I = Contract Initiation |
S = Semiannually A = Annually Nos. indicate hours
| Check if Complete | Visual Inspection | Check | Change | Clean | Test | Level 2 | ||||
| 1. Fuel | ||||||||||
| (a). | Main supply tank level | X | S | |||||||
| (b). | Day tank level | X | X | S | ||||||
| (c). | Day tank float switch | X | X | S | ||||||
| (d). | Supply or transfer pump operation | X | X | S | ||||||
| (e). | Solenoid valve operation | X | X | S | ||||||
| (f). | Strainer, filter, dirt leg, or combination | X | S | |||||||
| (g). | Water in system | X | X | S | ||||||
| (h). | Flexible hose and connectors | X | R | S | ||||||
| (i). | Tank vents and overflow piping obstructed | X | X | A | ||||||
| (j). | Piping | X | A | |||||||
| (k). | Gasoline or diesel fuel in main tank | R | 2 years | |||||||
| 2. Lubrication System | ||||||||||
| (a). | Oil level | X | X | S | ||||||
| (b). | Oil change | R | 50 hours or A | |||||||
| (c). | Oil filter(s) | X | 50 hours or A | |||||||
| (d). | Lube oil heater | X | S | |||||||
| (e). | Crankcase breather | X | R | X | S | |||||
| 3. Cooling System | ||||||||||
| (a). | Level | X | X | S | ||||||
| (b). | Antifreeze protection level | X | A | |||||||
| (c). | Antifreeze | X | I, 3 years | |||||||
| (d). | Adequate cooling water to heat exchanger | X | S | |||||||
| (e). | Rod out heat exchanger | X | I, 3 years | |||||||
| (f). | Adequate fresh air through radiator | X | S | |||||||
| (g). | Clean exterior of radiator | X | A | |||||||
| (h). | Fan and alternator belt | X | X | S | ||||||
| (i). | Water pump(s) | X | S | |||||||
| (j). | Condition of flexible hoses and connection | X | X | S | ||||||
| (k). | Jacket water heater | X | S | |||||||
| (l). | Inspect duct work, clean louvers | X | X | X | A | |||||
| (m). | Louver motors and controls | X | X | X | A | |||||
| 4. Exhaust System | ||||||||||
| (a). | Leakage | X | X | S | ||||||
| (b). | Drain condensate trap | X | S | |||||||
| (c). | Insulation and fire hazards | X | S | |||||||
| (d). | Excessive backpressure | X | A | |||||||
| (e). | Exhaust system hangers and supports | X | A | |||||||
| (f). | Flexible exhaust section | X | S | |||||||
| 5. Battery System | ||||||||||
| (a). | Electrolyte level | X | S | |||||||
| (b). | Terminals clean and tight | X | X | S | ||||||
| (c). | Remove corrosion, case exterior clean and dry | X | X | S | ||||||
| (d). | Specific gravity or state of charge | X | S | |||||||
| (e). | Charger and charge rate | X | S | |||||||
| (f). | Equalize charge | X | S | |||||||
| 6. Electrical System | ||||||||||
| (a). | General inspection | X | S | |||||||
| (b). | Tighten control and power wiring connections | X | A | |||||||
| (c). | Wire chafing where subject to movement | X | X | S | ||||||
| (d). | Operation of safeties and alarms | X | X | S | ||||||
| (e). | Boxes, panels, and cabinets | X | S | |||||||
| (f). | Circuit breakers, fuses | |||||||||
| Note: Operate circuit breakers by hand manually | X | X | R | X | X | A | ||||
| (g). | Transfer switch main contacts | X | X | A | ||||||
| (h). | Operate transfer switch electrically in both directions using the automatic control system | X | X | X | X | S | ||||
| (i). | Calibration of voltage-sensing relays/devices | X | X | A | ||||||
| (j). | Wire insulation breakdown | X | I | |||||||
| 7. Engine/Generator | ||||||||||
| (a). | General inspection | X | S | |||||||
| (b). | Service air cleaner | X | X | S | ||||||
| (c). | Governor oil level and linkage | X | X | S | ||||||
| (d). | Governor oil | X | A | |||||||
| (e). | Ignition system - plugs, points, coil, cap, rotor, secondary wire insulation | X | X | R | X | X | A | |||
| (f). | Choke setting and carburetor adjustment | X | S | |||||||
| (g). | Injector pump and injectors for flow rate pressure, and/or spray pattern | X | A | |||||||
| (h). | Run generator loaded minimum of 30% nameplate rating monthly for 30 min. | X | S/30 Min. | |||||||
| (i). | Run generator loaded minimum of 80% nameplate rating every 3 years for 4 hours | X | I | |||||||
| (j). | Valve clearance | X | I | |||||||
| (k). | Torque bolts | X | I | |||||||
| 8. Generator | ||||||||||
| (a). | Brush length appearance, free to move in holder | X | X | X | I, 3 years | |||||
| (b). | Commutator and slip rings | X | X | I, 3 years | ||||||
| (c). | Rotor and stator | X | X | I, 3 years | ||||||
| (d). | Bearing(s) | X | R | I, 3 years | ||||||
| (e). | Bearing grease | X | R | I, 3 years | ||||||
| (f). | Exciter | X | X | X | I, 3 years | |||||
| (g). | Voltage regulator | X | X | X | A | |||||
| (h). | Measure and record resistance readings of windings with insulation tester (Megger) | X | A | |||||||
| 9. General Condition | ||||||||||
| (a). | Note any unusual condition of vibration, leakage, noise, temperature, or deterioration | X | X | S | ||||||
| 10. Housekeeping | ||||||||||
| (a). | Note any deficiencies in the housekeeping for the generator and working area. | X | X | S | ||||||
| 11. Restore System | ||||||||||
| (a). | Restore system to as found condition. | X | S | |||||||
| * Maximum time between fuel renewals - more frequent replacement may be necessary |
Maint. Log
| ENGINE GENERATOR MAINTENANCE LOG | ||
| RECORD RESULTS OF PAGES 1 - 4 | Frequency |
S - Semiannually A - Annually Nos. indicate hours
| Performed By: |
| Date: |
Item No. Service Frequency Fill in appropriate readings, add comments on conditions and maintenance completed.
| 1. Fuel | ||||
| (a). | Main supply tank level | S | ||
| (b). | Day tank level | S | ||
| (c). | Day tank float switch | S | ||
| (d). | Supply or transfer pump operation | S | ||
| (e). | Solenoid valve operation | S | ||
| (f). | Stainer, filter, dirt leg, or combination | S | ||
| (g). | Water in system | S | ||
| (h). | Flexible hose and connectors | S | ||
| (i). | Tank vents and overflow piping obstructed | A | ||
| (j). | Piping | A | ||
| (k). | Gasoline in main tank (when used) or diesel fuel | A | ||
| 2. Lubrication System | ||||
| (a). | Oil level | S | ||
| (b). | Oil change | 50 or A | ||
| (c). | Oil filter(s) | 50 or A | ||
| (d). | Lube oil heater | S | ||
| (e). | Crankcase breather | S | ||
| 3. Cooling System | ||||
| (a). | Level | S | ||
| (b). | Antifreeze protection level | A | ||
| (c). | Antifreeze | A | ||
| (d). | Adequate cooling water to heat exchanger | S | ||
| (e). | Rod out heat exchanger | A | ||
| (f). | Adequate fresh air through radiator | S | ||
| (g). | Clean exterior of radiator | A | ||
| (h). | Fan and alternator belt | S | ||
| (i). | Water pump(s) | S | ||
| (j). | Condition of flexible hoses and connection | S | ||
| (k). | Jacket water heater | S | ||
| (l). | Inspect duct work, clean louvers | A | ||
| (m). | Louver motors and controls | A | ||
| 4. Exhaust System | ||||
| (a). | Leakage | S | ||
| (b). | Drain condensate trap | S | ||
| (c). | Insulation and fire hazards | S | ||
| (d). | Excessive backpressure | A | ||
| (e). | Exhaust system hangers and supports | A | ||
| (f). | Flexible exhaust section | S | ||
| 5. Battery System | ||||
| (a). | Electrolyte level | S | ||
| (b). | Terminals clean and tight | S | ||
| (c). | Remove corrosion, case exterior clean and dry | S | ||
| (d). | Specific gravity or state of charge | S | ||
| (e). | Charger and change rate | S | ||
| (f). | Equalize charge | S | ||
| 6. Electrical System | ||||
| (a). | General inspection | S | ||
| (b). | Tighten control and power wiring connections | A | ||
| (c). | Wire chafing where subject to movement | S | ||
| (d). | Operation of safeties and alarms | S | ||
| (e). | Boxes, panels, and cabinets | S | ||
| (f). | Circuit breakers, fuses | |||
| Note: Operate circuit breakers by hand manually | A | |||
| (g). | Transfer switch main contracts | A | ||
| (h). | Operate transfer switch electrically in both directions using the automatic control system | S | ||
| (i). | Calibration of voltage-sensing relays/devices | A | ||
| (j). | Wire insulation breakdown | 5/500 | ||
| 7. Engine/Generator | ||||
| (a). | General inspection | S | ||
| (b). | Service air cleaner | S | ||
| (c). | Governor oil level and linkage | S | ||
| (d). | Governor oil | A | ||
| (e). | Ignition system - plugs, points, coil, cap, rotor, secondary wire insulation | A | ||
| (f). | Choke setting and carburetor adjustment | S | ||
| (g). | Injector pump and injectors for flow rate pressure, and/or spray pattern | A | ||
| (h). | Run generator loaded minimum of 30% nameplate rating monthly for 30 min. | S/30 min. | ||
| (i). | Run generator loaded minimum of 80% nameplate rating every 3 years for 4 hours | 3/4 | ||
| (j). | Valve clearance | 3/500 | ||
| (k). | Torque belts | 3/500 | ||
| 8. Generator | ||||
| (a). | Brush length appearance, free to move in holder | S | ||
| (b). | Commutator and slip rings | A | ||
| (c). | Rotor and stator | A | ||
| (d). | Bearing(s) | A | ||
| (e). | Bearing grease | A | ||
| (f). | Exciter | A | ||
| (g). | Voltage regulator | A | ||
| (h). | Measure and record resistance readings of windings with insulation tester (Megger) | A | ||
| 9. Additional Maintenance Items | ||||
| (Not already included in this form) | S | |||
| 10. General Condition | S | |||
| 11. Housekeeping | S | |||
| 12. Restore System | S |