This document is a Bill of Material (BOM) from Cummins Sales and Service for the City of Durango Rockridge Pump Station project, dated 29 April 2025. The quotation (Q-323541-04292025-11:17) details the procurement of a comprehensive generator and automatic transfer switch system, specifically a configurable diesel generator set with a 250kW capacity, designed for stationary emergency application. The generator features a green steel enclosure, UL 2200 listing, EPA Tier 3 emission certification, and includes specifications such as a 500-gallon fuel tank, PowerCommand 2.3 controller, and a wind rating of 150 MPH. The package also includes four Group 34 starting batteries, battery heaters, delivery to the site, and system start-up and testing services.

The automatic transfer switch is an OTEC Service Entrance Transfer Switch with electronic control, rated at 400 amps, configured for utility-to-genset application. The switch operates at 480 volts AC, 60 Hz, with a 3-phase, 3 or 4-wire system, and includes a Type 3R cabinet and a MODBUS RTU communication module. Both the generator and transfer switch come with a 2-year warranty. The comprehensive package is tailored to support the Rockridge Pump Station replacement project, ensuring robust power backup and seamless electrical transfer capabilities for the City of Durango's critical infrastructure.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project: City of Durango Rockridge Pump Station Quotation: Q-323541-04292025–11:17

Quotation: Q-323541 - 04292025 - 11:17 Page 1 of 3

29 April 2025

Bill of Material

Feature Code Description Qty

Generator DQDAA DQDAA, Genset, Configurable Diesel 1

Install-US-Stat U.S. EPA, Stationary Emergency Application

DQDAA_250DQDAA 250DQDAA, Diesel Genset, 60Hz, 250kW

DQDAA_P175-2 Enclosure Color - Green, Steel

DQDAA_L090-2 Listing - UL 2200

DQDAA_C215-2 Alarm - High Fuel Fill

DQDAA_A331-2 Duty Rating - Standby Power (ESP)

DQDAA_L169-2 Emission Certification, EPA, Tier 3, NSPS CI Stationary Emergency

DQDAA_B184-2 Exciter/Regulator - Permanent Magnet Generator, 3 Phase Sensor

DQDAA_R002-2 Voltage - 277/480, 3 Phase, Wye, 4 Wire

DQDAA_B259-2 Alternator - 60Hz, 12 Lead, Extended Range, 105/80C

DQDAA_F202-2 Steel Sound Attenuated Level 2 Enclosure, with Exhaust System

DQDAA_F206-2 Wind Rating - 150 MPH, Steel Housing

DQDAA_C203-2 Fuel Tank - Sub Base, 500 Gallon, UL142 Compliant

DQDAA_C127-2 Fuel Water Separator

DQDAA_C234-2 Spill/Fill Box - Fuel

DQDAA_H609-2 Control Mounting - Left Facing

DQDAA_H703-2 PowerCommand 2.3 Controller

DQDAA_H606-2 Analog Meters - AC Output

DQDAA_K631-2 Relays - Genset Status, User Configured

DQDAA_K796-2 Stop Switch - Emergency

DQDAA_KS53-2 Signals - Auxiliary, 8 Inputs/8 Outputs

DQDAA_H536-2 Control Display Language - English

DQDAA_KU94-2 Circuit Breaker or Entrance Box or Terminal Box - Right Only

Quotation: Q-323541 - 04292025 - 11:17 Page 2 of 3

DQDAA_4520 Terminal Box - Low Voltage, Left - None

DQDAA_KC66-2 Circuit Breaker - 400A, Right Circuit Breaker on Right side, 3 - Pole, UL 600, IEC 690 100%

DQDAA_4335 Load Connections Left Side - None

DQDAA_KB72-2 Circuit Breaker or Entrance Box - Bottom Entry,Right Side

DQDAA_KM69-2 Auxiliary contacts/Trip Alarm - Single Circuit Breaker

DQDAA_KM72-2 Shunt Trip - 24 Volts DC, Single Circuit Breaker

DQDAA_A366-2 Engine Governor - Electronic, Isochronous

DQDAA_A334-2 Engine Starter - 24 Volt DC Motor

DQDAA_D041-2 Engine Air Cleaner - Normal Duty

DQDAA_A333-2 Battery Charging Alternator

DQDAA_B786-2 External Battery Charger - 12 Amp, Regulated

DQDAA_E125-2 Engine Cooling - Radiator, High Ambient Air Temperature, Ship Fitted

DQDAA_H389-2 Shutdown - Low Coolant Level

DQDAA_H669-2 Engine Coolant - 50% Antifreeze, 50% Water Mixture

DQDAA_H036-2 Coolant Heater - 120V, Single Phase

DQDAA_H706-2 Engine Oil

DQDAA_L026-2 Cummins Certified Test Record

DQDAA_L028-2 Genset Warranty - 2 Years Base

DQDAA_L050-2 Literature - English

DQDAA_A412-2 Packing - None, Base Mounted Housing

Battery Starting Batteries (4) Grp 34 4

0333-0469 Battery Heater-120VAC, 200Watt 4

Freight & other charges

Delivery to site, off-loading not included 1

Service - start up & testing

System start up & testing 1

Automatic Transfer Switch OTECSEC OTECSEC, OTEC Service Entrance Transfer Switch-Electronic Control: 400A 1

OTECSEC_OTECSE

OTECSE400, Service Entrance TransferSwitch, PowerCommand, 400 Amp

OTECSEC_S043-7 Listing - UL 1008

OTECSEC_A035-7 Application - Utility to Genset

Quotation: Q-323541 - 04292025 - 11:17 Page 3 of 3

OTECSEC_B002-7 Cabinet - Type 3R

OTECSEC_A028-7 Poles - 3 (Solid Neutral)

OTECSEC_M079-7 Integral Control Power Supply

OTECSEC_A044-7 Frequency - 60 Hz

OTECSEC_A042-7 System - 3 Phase, 3 or 4 Wire

OTECSEC_M034-7 Genset Starting Battery - 24V DC

OTECSEC_R026-7 Voltage - 480 Volts AC

OTECSEC_C110-7 PC40 Control

OTECSEC_L102-7 Auxiliary Relay - Switch in Emergency Position - 24 Volts DC

OTECSEC_L103-7 Auxiliary Relay - Switch In Normal Position - 24 Volts DC

OTECSEC_M081-7 Interface - Communications Network, MODBUS RTU Module

OTECSEC_G004-7 Transfer Switch Warranty - 2 Year Comprehensive

OTECSEC_L216-7 Auxiliary Contact Module-8