11-EXHIBIT 2 - Halifax Port Orange Pharmacy Renovation 2nd Floor CDs.pdf
PDF 3 MB Posted
- Attached to
- PHARMACY IV ROOM REMODEL FOR HHPO
- Solicitation number
- PROJ-25-099
- Issued by
- Volusia County, Florida
About this file
This is a construction document set for Halifax Health Medical Center's 2nd Floor Pharmacy Renovation project located at 1041 Dunlawton Ave, Port Orange, FL 32127, prepared by RS&H, Inc. The project involves renovating approximately 164 square feet of existing I.V. room space to meet USP 797 requirements, creating clean and ante rooms to support the Epic IV system. The renovation includes demolition of existing construction, installation of new partition walls, doors, HVAC systems including fan filter units, plumbing fixtures, electrical systems, and specialized finishes suitable for pharmaceutical compounding. The construction documents are dated June 23, 2025, and include architectural, mechanical, plumbing, electrical, and fire protection drawings with detailed specifications for materials and installation methods.
The project requires specialized cleanroom-grade materials including stainless steel fixtures, antimicrobial finishes, seamless vinyl flooring with integral base, HEPA filtration systems, and automatic sliding doors with access controls to maintain sterile conditions. The facility must comply with institutional Group I-2 occupancy requirements, NFPA codes, Florida Building Code, and healthcare facility guidelines. The drawings specify Owner Furnished Contractor Installed (OFCI) equipment including refrigeration units and laminar flow hoods. The project includes temporary construction barriers and negative air systems to prevent contamination during construction, coordination with existing building systems, and integration with the hospital's fire alarm, security, and HVAC infrastructure while maintaining operational continuity of adjacent healthcare spaces.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AEC PROJECT NUMBER
ISSUED FOR
CONSTRUCTION
REVISIONS
/2
/2
:4 :4
A
M A u to d e s k D o c s /2
H a lif a x P o rt
O ra n g e P h a rm a c y R e n o v a ti o n
/H a lif a x P o rt
O ra n g e
P h a rm a c y
R e n o v a ti o n n d
F lo o r_
A R
.r v t
20070225000
HALIFAX HEALTH MEDICAL CENTER
2ND FLOOR PHARMACY RENOVATION
1041 DUNLAWTON AVE,
PORT ORANGE, FL 32127
CONSTRUCTION DOCUMENTS
06/23/2025
BUILDING ID: BLDG. ID
Copyright © 2025. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
© 2025 RS&H, INC
SHEET INDEX
SHEET NUMBER SHEET NAME
00 GENERAL
G002 GENERAL NOTES, ABBREVIATIONS AND SYMBOLS
G003 ADA COMPLIANCE AND ACCESSIBILITY
G004 GENERAL PROJECT NOTES
G101 OVERALL 2ND FLOOR LIFE SAFETY PLAN
07 ARCHITECTURAL
A102 ENLARGED 2ND FLOOR DEMOLITION PLAN, FLOOR PLAN, REFLECTED CEILING PLAN AND NOTES
A401 INTERIOR ELEVATIONS AND DETAILS
A501 PARTITION TYPES
A601 DOOR SCHEDULE, DOOR TYPES, DETAILS, AND NOTES
08 INTERIORS
I101 FINISH, FLOOR PATTERN PLAN AND FINSIH SCHEDULE
10 FIRE PROTECTION
FP101 SECOND FLOOR FIRE PROTECTION PLAN
11 PLUMBING
P001 PLUMBING GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
P101 SECOND FLOOR PLUMBING PIPING PLANS
P701 PLUMBING RISER DIAGRAMS
13 MECHANICAL
M001 MECHANICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
M101 SECOND FLOOR MECHANICAL PLANS
M501 HVAC DETAILS & SCHEDULES
14. ELECTRICAL
E001 ELECTRICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
E100 OVERALL ELECTRICAL PLAN
E501 ELECTRICAL DETAILS
E601 ELECTRICAL SCHEDULES
E701 ONE LINE DIAGRAM
407-893-5800 Fax 407-264-6624
301 E. Pine Street, Suite 350 Orlando, Florida 32801 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956 *
5620 * LCC000210 * GB238
NO. DESCRIPTION DATE
ED101 SECOND FLOOR ELECTRICAL DEMOLITION PLANS
E101 SECOND FLOOR ELECTRICAL PLANS
ARCHITECTURAL ABBREVIATIONS PLAN SYMBOLS
1-HOUR RATED WALL 2-HOUR RATED WALL
3-HOUR RATED WALL SMOKE RATED WALL
BATT INSULATION CONCRETE
EARTH EXPOSED & FINISHED WOOD TRIM
GYPSUM / PLASTER MASONRY - BRICK
PLYWOOD
RIGID INSULATION STEEL
MATERIAL SYMBOLS
STUCCO / E.I.F.S.
GRAVELGRASS
MASONRY - CONCRETE BLOCK
TILE / CARPET
XX
View Name
SCALE:1/8" = 1'-0"
DOOR TAG
CALLOUT HEAD & REGION
A101
A1
SIM
BUILDING SECTION
KEYNOTE
BUILDING SECTION LEVEL HEAD
A1
A101
SIM
A1
A101
SIM
A1
A101
SIM
A1
A101
SIM
Name Elevation
ROOM TAG WALL TAG
XXX
DETAIL SECTION
WINDOW & STOREFRONT TAG
MATERIAL TAG
VIEW REFERENCE
REVISION TAG
NORTH ARROW
XX
A101 A101
ELEVATION - EXTERIOR ELEVATION - INTERIOR
WALL SECTION
CEILING TAG
XXXX 12'-0" AFF
CEILING TYPE
CEILING HEIGHT
*NOTE - REFER TO PARTITION TYPE SHEET FOR INFO ON TAG
PT-1
FURNITURE & EQUIPMENT TAG TOILET ACCESSORY TAG
1i 1i
ROOM NAME
N
PN
SEE -/---
SEE -/---
N
PN
VICINITY MAP
LOCATION MAP
N
PN
X#-X
A
B
C
D
54321
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
SEAL:
/2
/2
:4 :4
A
M A u to d e s k D o c s /2
H a lif a x P o rt
O ra n g e P h a rm a c y R e n o v a ti o n
/H a lif a x P o rt
O ra n g e
P h a rm a c y
R e n o v a ti o n n d
F lo o r_
A R
.r v t
CONSTRUCTION DOCUMENTS
RS&H
MW
1041 DUNLAWTON AVE,
PORT ORANGE, FL 32127
2ND FLOOR PHARMACY
RENOVATION
20070225000
06/23/2025
RS&H
G002
GENERAL NOTES,
ABBREVIATIONS AND
SYMBOLS
© 2025 RS&H, INC
Copyright © 2025. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
& AND
@ AT
A/C AIR CONDITIONER
AB ANCHOR BOLT
ACT ACOUSTICAL CEILING TILE
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFS ABOVE FLOOR SLAB
AHU AIR HANDLING UNIT
ALUM ALUMINUM
ANOD ANODIZED
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATE OR APPROXIMATELY
ARCH ARCHITECTURE, ARCHITECTURAL
AVG AVERAGE
AWI ARCHITECTURAL WOODWORK INSTITUTE
BHMI BUILDER'S HARDWARE MANUFACTURER'S ASSOCIATION, INC.
BIM BUILDING INFORMATION MODELING
BLDG BUILDING
BM BEAM
BO BOTTOM OF
BUR BUILT-UP ROOFING
CFMF COLD FORMED METAL FRAMING
CJ CONTROL JOINT
CL CENTERLINE
CL OTS CENTERLINE OF TENANT SEPARATION
CLG CEILING
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL. COLUMN
COLS COLUMNS
CONC CONCRETE
CONT CONTINUOUS
DIA DIAMETER
DR DOOR
DS DOWNSPOUT
DTL OR DET DETAIL
DWG DRAWING
EA EACH
EFS EXTERIOR FACE OF SHEATHING
EJ EXPANSION JOINT
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATION
ENG ENGINEER, ENGINEERING
EOS EDGE OF SLAB
EP ELECTRICAL PANEL
EPDM ETHYLENE PROPYLENE DIENE MONOMER
EQ EQUAL
EQUIP EQUIPMENT
ERD EMERGENCY ROOF DRAIN
ETD ESTIMATED TRAVEL DISTANCE
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION, EXPOSED
EXT EXTERIOR
FD FIRE DAMPER, FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISHED FLOOR
FFE FINISHED FLOOR ELEVATION
FHC FIRE HOSE CABINET
FID FLIGHT INFORMATION DISPLAY
FIN. FINISH, FINISHED
FLR FLOOR
FO FACE OF
FOB FACE OF BRICK
FOP FACE OF POST
FRP FIBER REINFORCED PANEL
FT FEET
FTG FOOTING
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GBF GYPSUM BOARD FURRING
GID GATE INFORMATION DISPLAY
GL GLASS
GP GLOSSY PAINT
GWB GYPSUM WALL BOARD
GYP GYPSUM
HB HOSE BIB
HDW HARDWARE
HGT OR HT HEIGHT
HKS HOOKS
HM HOLLOW METAL
HORIZ HORIZONTAL
HVAC HEATING VENTILATION & AIR CONDITIONING
i.e. THAT IS, SUCH AS
ID INSIDE DIAMETER
IFS INTERIOR FACE OF STUD
IN. INCH, INCHES
INSUL INSULATION
INT INTERIOR
JAN. JANITOR
JST JOIST
JT JOINT
KP KICK PLATE
LAM LAMINATE
LAV LAVATORY
LB POUND
LDG LANDING
LONG. LONGITUDINAL
LRV. LOUVER
LT LIGHT
LTG LIGHTING
LVP LUXURY VINYL PLANK
LVT LUXURY VINYL TILE
MATL MATERIAL
MAX. MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, & PLUMBING
MFGR MANUFACTURER
MGR MANAGER
MIN MINIMUM
MO MASONRY OPENING
MOD MODIFIED
MSC MISCELLANEOUS
MTL METAL
MUFID MULTI-USER FLIGHT INFORMATION DISPLAY
N/A NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO. NUMBER
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FUNISHED CONTRACTOR INSTALLED
OPG OPENING
OPP OPPOSITE
OSHA OCCUPATIONAL SAFETY AND HEALTH ACT
OVHD OVERHEAD
PDU POWER DISTRIBUTION UNIT
PLAM PLASTIC LAMINATE
PLYWD PLYWOOD
PNL PANEL
PR PAIR
PRE-FAB PRE-FABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, PRESSURE TREATED
PVC POLYVINYL CHLORIDE
QT QUARRY TILE
R RADIUS
RAF RAISED ACCESS FLOOR
RAG RETURN AIR GRILLE
RB RUBBER BASE
RD ROOF DRAIN
RECEP RECEPTION, RECEPTIONIST
REF REINFORCING, REINFORCEMENT
REQ'D REQUIRED
REV REVISED, REVISION
RO ROUGH OPENING
SC SEALED CONCRETE
SCHED SCHEDULE
SCW SOLID CORE WOOD
SECT SECTION
SF SQUARE FEET
SFRM SPRAYED FIRE RESISTIVE MATERIAL
SGP SEMI-GLOSS PAINT
SHT. SHEET
SHTS SHEETS
SIM SIMILAR
SPECS SPECIFICATIONS
SQ SQUARE
SQ IN. SQUARE INCHES
SS SERVICE SINK
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL, STRUCTURE
SUSP SUSPENDED
T&G TONGUE & GROOVE
TEL. TELEPHONE
TG TEMPERED GLASS
TO STL TOP OF STEEL
TOB TOP OF BRICK, TOP OF BEAM
TOS TOP OF STEEL, TOP OF SLAB
TOSH TOP OF SHEATHING
TOW TOP OF WALL
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
VB VAPOR BARRIER
VCT OR VT VINYL COMPOSITION TILE
VDC VIRTUAL DESIGN & CONSTRUCTION
VERT VERTICAL
VR VIRTUAL REALITY
W/ WITH
WC WATER CLOSET
WCO WALL CLEANOUT
WD WOOD
WMP WIRE MESH PARTITION
WWF WELDED WIRE FABRIC
YD YARD
Ø DIAMETER
407-893-5800 Fax 407-264-6624
301 E. Pine Street, Suite 350 Orlando, Florida 32801 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956 *
5620 * LCC000210 * GB238
NO. DESCRIPTION DATE
T-TURN CLEAR SPACE
5' - 0"
MIN.
1' - 0"
MIN.
1' - 0"3' - 0"
M
IN
2'
0"
M
IN
3'
0"
5'
0"
U-TURN AND PASSING SPACES
60" DIA.
PUSH SIDE DOOR CLEARANCE
NOTE:
Y=48" MIN. IF DOOR HAS A
CLOSER
Y
2"
M
IN
CLEAR
32" MIN.
PUSH SIDE DOOR CLEARANCE
NOTE:
X=12" MIN. IF DOOR HAS
BOTH A LATCH AND
CLOSER
M
IN
NOTE:
Y=54" IF DOOR HAS
CLOSER
PULL SIDE DOOR CLEARANCE
24" MIN.Y
8"
M
IN
PULL SIDE DOOR CLEARANCE
M
IN
18" MIN.
24" PREFERRED
NOTE:
X=36" MIN. IF Y=60"
X=42" MIN. IF Y=54"
PULL SIDE DOOR CLEARANCE
X
Y
PUSH SIDE DOOR CLEARANCE
NOTE:
Y=48" MIN. IF DOOR HAS
BOTH A LATCH AND
CLOSER
Y
2"
M
IN
54" MIN.
12"
CLEAR
32" MIN.
U .N
.O
8" 8" 8" 8" 8" 8" 8" 8"
8"
8" 8"
COUNTER DEPTH
24" MAX.
COUNTER & UNDERCOUNTER
OVER COUNTER
OUTLET
COMMON POWER
DATA/ AV CLUSTER
ISOLATED GROUND
POWER OR TELEPHONE
TYPICAL POWER GROUPING
ABOVE MILLWORK
PROVIDE GROMMETS
@ EACH GROUPING
WORK-SURFACE
TYPICAL POWER GROUPING
BELOW MILLWORK
PROVIDE GROMMET HOLE
@ EACH. GROUP
UNDER COUNTER OUTLET
8"
" 8" 8"
TYPICAL POWER GROUPING
COMMON POWER
DATA
ISOLATED GROUND
POWER OR PHONE
THERMOSTAT
LIGHTSWITCH
& DIMMERS
TYPICAL PHONE /
THERMOSTAT / SWITCH /
OUTLET / VISUAL ALARM
GROUPINGS AT CORNERS
EDGE OF WALL
VISUAL ALARM/
STROBE
8" 6"
6" - 8"
EQ EQ
THERMOSTAT
LIGHT SWITCH
& DIMMERS
TYPICAL PHONE / THERMOSTAT /
SWITCH / OUTLET / VISUAL ALARM
GROUPINGS BETWEEN COLUMNS
AND OPENINGS
WALL, COLUMN
OR OPENING
VISUAL ALARM/
STROBE
M
A X
ACCESSORIES
FIRE EXTINGUISHERS AND CABINETS
(F.E.) (F.E.C.)
NOTE: OBJECTS MOUNTED 27" OR
GREATER ABOVE FINISHED FLOOR
MUST NOT PROTRUDE FROM THE
FACE OF WALL MORE THAN 4".
6'-8" MINIMUM HEAD CLEARANCE IS
REQUIRED AT ALL TIMES.
T .O
. B R
A
IL
LE
T
E X
T
M A
X
TYPICAL BRAILLE ROOM SIGN @ GLASS SIDELIGHT
ROOM SIGNAGE
LOCATION, INCLUDE
BACKPLATE ON
OPPOSITE SIDE OF
GLASS, ALL LOCATIONS
BUILDING SIGNAGE TO BE PROVIDED AT
LOCATIONS AS REQUIRED BY 2010 ADA
STANDARDS FOR ACCESSIBLE DESIGN
4"
T .O
. B R
A
IL
LE
T
E X
T
M A
X
TYPICAL BRAILLE ROOM SIGN
ROOM SIGNAGE
LOCATION:
HOLD ROOM SIGN 2"
OFF FRAME UNLESS
NOTED
EDGE OF
DOOR 18" MIN.
CLEAR
FLOOR
SPACE
BUILDING SIGNAGE TO BE PROVIDED AT
LOCATIONS AS REQUIRED BY 2010 ADA
STANDARDS FOR ACCESSIBLE DESIGN
2"
THERMOSTAT
6" 4"
TYPICAL PHONE / THERMOSTAT / SWITCH /
OUTLET / VISUAL ALARM GROUPINGS AT
DOORS AND OPENINGS
VISUAL ALARM/
STROBE
LIGHT SWITCH
PAPER TOWEL
(FOLDED)
DISPENSER
PT1
OFCI
SOAP DISPENSER
SD1
OFCI
PROVIDE 2X WOOD BLOCKING TO WALL MOUNTED ACCESSORIES AS
REQUIRED, PER MANUFACTURER SPECIFICATION.
CFCI: CONTRACTOR FURNISHED CONTRACTOR INSTALLED
OFCI: OWNER FURNISHED CONTRACTOR INSTALLED
OFOI: OWNER FURNISHED OWNER INSTALLED
M1
CFCI
M
IN
9"
MS
CL
3'
0"
CFCI
FULL HEIGHT MIRROR MOTION SENSOR
ACTUATOR
TEMPERED GLASS
A
B
C
D
54321
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
SEAL:
/1
/2
:5 :4
P
M A u to d e s k D o c s /2
H a lif a x P o rt
O ra n g e P h a rm a c y R e n o v a ti o n
/H a lif a x P o rt
O ra n g e
P h a rm a c y
R e n o v a ti o n n d
F lo o r_
A R
.r v t
CONSTRUCTION DOCUMENTS
RS&H
MW
1041 DUNLAWTON AVE,
PORT ORANGE, FL 32127
2ND FLOOR PHARMACY
RENOVATION
20070225000
06/23/2025
RS&H
G003
ADA COMPLIANCE
AND ACCESSIBILITY
© 2025 RS&H, INC
Copyright © 2025. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
407-893-5800 Fax 407-264-6624
301 E. Pine Street, Suite 350 Orlando, Florida 32801 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956 *
1. THE EXISTING-TO-REMAIN PORTIONS OF THE LIFE SAFETY PLANS WERE PROVIDED TO THE ARCHITECT BY THE PROPERTY
OWNER. RS&H, INC., TAKES NO RESPONSIBILITY FOR THEIR ACCURACY.
2. THE LIFE SAFETY PLANS ARE "DIAGRAMMATIC ONLY". THEIR PURPOSE IS SOLELY TO REPRESENT THE LIFE SAFETYCOMPONENTS FOR THE PROJECT (AS INCLUDED IN THECONSTRUCTION DOCUMENTS PREPARED BY THE ARCHITECT,ELECTRICAL ENGINEER, ETC.). USE THE CONSTRUCTION DOCUMENTS (NOT THE LIFE SAFETY PLANS) FOR THE
IMPLEMENTATION OF THE REQUIRED LIFE SAFETY COMPONENTS INTO THE PROJECT.
3. ADVISE THE ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY LIFE SAFETY COMPONENT THAT IS SHOWN ON THE LIFE SAFETY PLANS BUT HAVE NOT BEEN INCLUDED IN THE CONSTRUCTION DOCUMENTS PREPARED BY THE ARCHITECT, ELECTRICAL ENGINEER, ETC.
4. FIELD VERIFY THAT THE REQUIRED VISIBILITY FOR EACH INDIVIDUALLY INSTALLED EXIT LIGHT IS NOT IN ANY WAY DIMINISHED DUE TO VISUAL INTERFERENCE CAUSED BY ANY OTHER LIGHT FIXTURE, DEVICE, SIGN, ETC. (COORDINATE WITH THE ARCHITECT'S REFLECTED CEILING PLANS, THE ELECTRICAL DRAWINGS, THE GRAPHICS DRAWINGS, ETC.)
5. EACH "WALL/PARTITION/BARRIER" CLASSIFICATION IN RED LETTERS ABOVE THE FINISH CEILING ON EACH SIDE OF ALL FIRE WALLS, RATED FIRE BARRIERS, RATED SMOKE BARRIERS, NON-RATED SMOKE PARTITIONS, ETC.
GENERAL NOTES FOR LIFE SAFETY PLANS:
1. CONTRACTOR SHALL SUBMIT PLANS FOR A SEPARATE PERMIT FOR THIS WORK.
2. ALL WORK SHALL COMPLY WITH THE CURRENTTLY ADOPTED VERSION OF NFPA 13.
3. ALL WORK SHALL BE DONE BY A LICENSED CONTRACTOR EXPERIENCED WITH THIS TYPE OF WORK.
4. THE EXISTING SPRINKLER SYSTEM SHALL BE REUSED WHENEVER POSSIBLE. NEW HEADS SHALL BE PROVIDED AT
LOCATIONS AS REQUIRED.
5. CONTRACTOR TO PROVIDE TEMPORARY FIRE PROTECTION OF BUILDING AS REQUIRED.
6. PROVIDE SHOP DRAWINGS FOR ARCHITECT'S REVIEW, INCLUDING PIPING, PROPOSED LOCATIONS, AND NEW SPRINKLER HEADS, AT ALL LOCATIONS. PROVIDE SPRINKLER HEADS TO MATCH EXISTING HEADS, IF APPLICABLE.
GENERAL FIRE SPRINKLER NOTES:
GENERAL NOTES FOR DEMOLITION PLANS:
1. THE DEMOLITION DRAWINGS HAVE BEEN DEVELOPED FROM EXISTING DRAWINGS PROVIDED TO THE
ARCHITECT/ENGINEER BY THE OWNER, AND MAY NOT REFLECT ACTUAL FIELD CONDITIONS. PRIOR TO PROCEEDING WITH ANY WORK, VERIFY THE ACCURACY OF THESE DRAWINGS IN COMPARISON TO EXISTING FIELD CONDITIONS AND THEN IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY INCONSISTENCIES BETWEEN THESE DRAWINGS AND
ACTUAL CONDITIONS.
2. IF ANY EXISTING FIREPROOFING AND/OR RATED ASSEMBLIES ARE DAMAGED DURING DEMOLITION, THEY MUST BE REPAIRED TO CONFORM TO THE ORIGINAL FIRE PROTECTION REQUIREMENTS. THE INTEGRITY OF EXISTING RATED FLOOR, WALL, BARRIER AND ROOF ASSEMBLIES TO BE MAINTAINED THROUGHOUT ALL PHASES OF CONSTRUCTION.
3. REMOVE EXISTING CONSTRUCTION AS INDICATED. TYPICAL WALL REMOVAL SHALL INCLUDE MECHANICAL, PLUMBING, ELECTRICAL, COMMUNICATIONS AND SECURITY SYSTEMS, CABINETRY, DOORS AND WINDOWS, AND FINISHES CONTAINED AND ATTACHED. THEREIN. REMOVE DOORS, CABINET WORK, CASEWORK, WINDOWS, FRAMES, FINISHES, FIXTURES AND THEIR ATTACHEMENTS AS REQUIRED. AFTER REMOVAL, REPAIR HOLES IN EXISTING-TO-REMAIN FLOORS, WALLS, BARRIERS AND ROOFS TO COMPLY WITH ORIGINAL FIRE, SMOKE AND SOUND ASSEMBLIES, FIRE PROTECTION REQUIREMENTS, AND STRUCTURAL INTEGRITY. PREPARE SURFACES TO RECEIVE NEW FINISH PER
INTERIOR DESIGN DRAWINGS AND SPECIFICATIONS.
4. SEE OTHER DISCIPINE DRAWINGS FOR ADDITIONAL DEMOLTION SCOPE.
5. VERIFY THAT THE EXISTING CONSTRUCTION (INCLUDING DAMPERS, DUCT PENETRATIONS, DOORS, WINDOWS, FRAMES, ETC.) MEETS THE FIRE, SMOKE AND SOUND ASSEMBLY RATINGS DESIGNATED ON THE DRAWINGS AT ALL WALLS/PARTITIONS/BARRIERS, FLOORS AND ROOFS WHICH ENCLOSE OR TOUCH SPACES WHERE WORK IS BEING PERFORMED. MAKE ANY REPAIRS AND/OR MODIFICATIONS NECESSARY TO BRING THE EXISTING CONSTRUCTION UP TO THE PROPER INDICATED FIRE, SMOKE AND SOUND ASSEMBLY RATINGS. DOORS, WINDOWS, AND FRAMES WHICH DO NOT MEET THE REQUIREMENTS OF THE DESIGNATED WALL/PARTITION/BARRIER ASSEMBLIES (INCLUDING PROPER
LABELS) SHALL BE REPLACED. DESIGNATE AN ALLOWANCE FOR THIS WORK.
6. EXECUTE DEMOLITION IN CONFORMANCE WITH ALL CODES AND ORDINANCES AS SET FORTH BY ALL AUTHORITIES
HAVING JURISDICTION.
7. BRACE ALL EXISTING STRUCTURES AND ALL STRUCTURAL ELEMENTS AS NECESSARY DURING DEMOLITION.
8. DO NOT CUT EXISTING OR NEW STRUCTURAL WORK IN ANY MANNER THAT MAY RESULT IN A REDUCTION OF LOAD CARRYING CAPACITY OR LOAD/DEFLECTION RATIO. NOTIFY THE ARCHITECT AND BUILDING STRUCTURAL ENGINEER IN
WRITING OF ALL STRUCTURAL CUTS PRIOR TO EXECUTION.
9. WHERE EXISTING CONSTRUCTION IS FOUND TO CONTAIN ANY HAZARDOUS MATERIAL, IMMEDIATELY NOTIFY THE OWNER AND THE ARCHITECT IN WRITING. NOTE: REMOVAL, DISPOSAL AND REPLACEMENT OF THE HAZARDOUS
MATERIAL IS THE SOLE RESPONSIBILITY OF THE OWNER.
10. SEAL ALL EXISTING AND ABANDONED PIPE OR CONDUIT PENETRATIONS IN ACCORDANCE WITH THE APPROPRIATE U.L.
DESIGN.
11. REMOVE ALL EXISTING ABANDONED CEILING MOUNTED HANGER WIRES, SUPPORT BRACKETS, HANGER RODS, AND
MOUNTING STRAPS.
12. OBTAIN A HOT WORK PERMIT, IN ACCORDANCE WITH NFPA REQUIREMENTS, PRIOR TO BEGINNING ANY WELDING, CUTTING, BRAZING, GRINDING OR OTHER ACTIVITIES THAT GENERATES SPARK CAPABLE OF CAUSING COMBUSTION.
13. AS REQUIRED BY NFPA, REMOVE ALL FLAMMABLE ITEMS, INCLUDING BUT NOT LIMITED TO COMPRESSED AIR AND GAS CANS OR CYLINDERS (I.E. BRAZING, ACETYLENE, PROPANE TANKS, PAINT CANS, LUBRICANTS, ETC.) FROM THE JOB SITE WHEN THE PROJECT HAS BEEN VACATED BY CONSTRUCTION PERSONNEL AND DURING THE TIME THE FIRE
ALARM SYSTEM AND FIRE SUPPRESSION SYSTEM IS INACTIVE.
14. ALL MODIFICATIONS TO THE FIRE ALARM OR FIRE SPRINKLER SYSTEM, INCLUDING AUDIO/VISUAL COMMUNICATION DEVICES, SHALL BE DEFERRED TO THE AUTHORITY HAVING JURISDICTION UNDER SEPARATE SUBMITTAL.
15. REMOVE PORTION OF EXISTING SLAB AS REQUIRED TO INSTALL NEW PLUMBING. COORDINATE WITH PLUMBING
DRAWINGS.
16. PERFORM ALL DEMOLITION IN SWIFT AND SAFE MANNER WITH A METHOD THAT KEEPS NOISE AND DISTURBANCE TO A MINIMUM. PERFORM ANY DRILLING OR WELDING DURING NON-BUSINESS HOURS AND WEEKENDS OR AS NOTED IN
PROJECT SPECIFICATIONS.
17. PERFORM THE WORK REFERENCED HEREIN WITH NO DISRUPTION TO ON-GOING ACTIVITIES IN ADJACENT TENANT SPACES. THIS INCLUDES AFTER HOURS WORK, OVERTIME, AND ANY AND ALL SPECIAL MEANS AND METHODS.
18. COORDINATE ALL CONSTRUCTION ACTIVITIES IN ADJACENT TENANT SPACES WITH BUILDING MANAGER.
1. TYPICAL PARTITION TYPE IS "A3-D" UNLESS OTHERWISE NOTED.
2. DIMENSIONS SHOWN ON THE FLOOR PLANS ARE: TO FACE OF STUD AT METAL STUD PARTITIONS/BARRIERS OR TO OUTSIDE FACE OF EXISTING WALLS. EXTREMELY CRITICAL MINIMUM DIMENSIONS MAY BE INDICATED AS "MINIMUM", "CLEAR", “HOLD” OR "MINIMUM CLEAR".
3. "MINIMUM", "CLEAR", “HOLD” OR "MINIMUM CLEAR" DIMENSIONS MUST ACCOUNT FOR THE THICKNESS OF THE
SCHEDULED FINISH MATERIALS PRIOR TO "LAYING OUT" METAL STUD PARTITIONS/BARRIERS.
4. SEE EQUIPMENT SHEETS FOR EQUIPMENT INFORMATION AND SCHEDULES.
5. SEE INTERIOR OR FINISH SHEETS FOR FINISH INFORMATION, LOCATIONS OF ACCENT WALLS, AND WALL PROTECTION.
6. ALL PARTITIONS SCHEDULED TO RECEIVE TILE OR IN WET LOCATIONS, SHALL BE CONSTRUCTED OF WATER-
RESISTANT CORE GYPSUM WALL BOARD.
7. WHERE A ONE-HOUR RATED BARRIER OR A NON-RATED PARTITION IS SHOWN AS A CONTINUATION OF A TWO-HOUR RATED BARRIER OR COLUMN ENCASEMENT, THE OUTSIDE FACE OF THE GYPSUM BOARD SHALL BE ALIGNED. STUDS SHALL BE OFFSET AND/OR ADDITIONAL LAYERS OF GYPSUM BOARD SHALL BE PROVIDED (AS REQUIRED TO PROVIDE
FACE ALIGNMENT OF GYPSUM BOARD) WHILE MAINTAINING THE REQUIRED RATED INTEGRITY.
8. DO NOT INSTALL GYPSUM WALL BOARD IN DIRECT CONTACT WITH THE FLOOR OR STRUCTURE ABOVE WHERE APPLICABLE. STOP GYPSUM WALL BOARD ½ FROM FLOOR OR STRUCTURE AND SEAL AS REQUIRED.
9. PROVIDE PLYWOOD AND/OR METAL BLOCKING IN WALL BEYOND TVs, MILLWORK, CABINETRY, SHELVING, DOOR AND
WALL STOPS, AND WALL MOUNTED FURNITURE WITHIN OFFICES.
10. BLOCKING IN RATED WALLS TO BE FIRE RETARDANT AND SEALED WITH FIRE RETARDANT SEALANT PER UL
REQUIREMENTS OR UTILIZE METAL STRAPPING.
11. REFER TO STRUCTURAL DRAWINGS FOR SHEATHING REQUIREMENTS AND LOCATION OF EXTERIOR AND INTERIOR
SHEAR WALLS.
12. LOCATE HINGE SIDE OF ALL DOORS 4 INCHES FROM ADJACENT PARTITION, MEASURED FROM INSIDE FACE OF FRAME, U.N.O.
13. BRACE ALL WALLS OVER 12'-0" IN LENGTH BETWEEN INTERSECTING PARTITIONS TO STRUCTURE TO RESIST LATERAL
LOADING.
14. LOCATIONS WHERE PARTITIONS TERMINATE AT WINDOW MULLIONS, CENTER THE PARTITION ON THE MULLION, U.N.O.
DO NOT FASTEN INTO MULLIONS. REFER TO DETAILS ON PLANS.
15. PROPERLY PREPARE WALLS TO RECEIVE NEW FINISH(ES). JOINTS SHALL NOT BE VISIBLE AFTER NEW FINISH HAS
BEEN APPLIED. REFER TO FINISH SCHEDULE(S) AND SPECIFICATIONS.
16. USE GYPSUM WALLBOARD ACCESSORIES AS SPECIFIED.
17. ALL PARTITIONS CONTAINING SANITARY OR ROOF DRAIN PLUMBING TO BE INSULATED WITH ACOUSTICAL BATTING.
18. PROVIDE ACOUSTICAL SEALANT AROUND ALL PENETRATIONS THROUGH ACOUSTICAL PARTITIONS.
RENOVATION RELATED NOTES DELETE OR COMBINE THESE NOTES WITH ABOVE BASED ON PROJECT SCOPE.
1. ALIGN FACE OF NEW GYPSUM BOARD PARTITION/BARRIER WITH THE FACE OF EXISTING WALL OR COLUMN
ENCASEMENT.
2. PATCH AND REPAIR ANY EXISTING CONSTRUCTION TO MATCH ADJACENT EXISTING QUALITY OF WORK. REFER TO
FINISH SCHEDULE.
ADDITIONAL NOTES THAT CAN BE ADDED BASED ON PROJECT NEEDS.
1. LOCATIONS WHERE SCHEDULED PARTITION TOP TRACK ATTACHES TO CEILING GRID; SHIM WITH ATTACHMENTS AT
48" MINIMUM INTERVALS.
2. THE FOLLOWING LIST OF ROOMS (IF USED) TO HAVE THEIR PERIMETER PARTITIONS INSULATED WITH SOUND
ATTENUATION BATTS:
a. TOILET ROOMS
b. OFFICES
c. ANTE ROOM
d. CLEAN ROOM
GENERAL NOTES FOR FLOOR PLANS:
1. COMPLY WITH THE FOLLOWING NOTES IN THIS SET OF DRAWINGS WHICH ALSO APPLY TO THE REFLECTED CEILING PLANS:
A. "GENERAL NOTES" ON THIS SHEET
B. "GENERAL NOTES FOR DEMOLITION PLANS" ON THIS SHEET
C. "GENERAL NOTES FOR NEW CONSTRUCTION AND DIMENSION PLANS" ON THIS SHEET
2. CAREFULLY STUDY AND COMPARE THE REFLECTED CEILING PLANS WITH: ELECTRICAL'S LIGHTING, SYSTEMS AND COMMUNICATIONS DRAWINGS; MECHANICAL'S SUPPLY, RETURN AND EXHAUST DRAWINGS; AND FIRE PROTECTION'S DRAWINGS IF APPLICABLE. IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY ERROR, INCONSISTENCY OR OMISSION
THAT IS DISCOVERED.
3. SEE ELECTRICAL, COMMUNICATION, SECURITY AND FIRE PROTECTION DRAWINGS FOR LOCATIONS OF CEILING MOUNTED SMOKE DETECTORS, COMMUNICATION DEVICES, FIRE ALARM DEVICES, SECURITY DEVICES, ETC.
4. CEILING MOUNTED EXIT LIGHTS ARE SHOWN ON THE REFLECTED CEILING PLANS. SEE THE ELECTRICAL DRAWINGS FOR LOCATIONS OF WALL MOUNTED EXIT LIGHTS. (NOTE: THE BOTTOM OF EXIT LIGHTS SHALL BE A MINIMUM OF 7'-0" CLEAR AFF.)
5. SPRINKLER HEADS:
A. THE SPRINKLER HEADS ARE NOT SHOWN ON THE REFLECTED CEILING PLANS. REFER TO FIRE PROTECTION DRAWINGS
FOR ADDITIONAL INFORMATION.
B. RELOCATE AND/OR INSTALL SUFFICIENT HEADS IN ALL SPACES TO PROVIDE COMPLETE (100%) AUTOMATIC
SPRINKLER COVERAGE AS DEFINED IN NFPA STANDARD 13, - FIRE SUPPRESSION AND AS SHOWN ON THE FIRE PROTECTION
DRAWINGS.
C. NEITHER SPRINKLER HEADS OR CONCEALED SPRINKLER HEAD COVERS ARE ALLOWED TO BE PAINTED. VERIFY THAT
ANY SPRINKLER HEADS THAT ARE ACCIDENTALLY PAINTED ARE REMOVED FROM THE SITE AND REPLACED WITH NEW ONES.
6. ADVISE THE OWNER AND TENANTS THAT AN 18 INCH MINIMUM VERTICAL CLEARANCE SHALL BE MAINTAINED BETWEEN THE BOTTOM OF THE EXTENDED (DROP DOWN) SPRINKLER HEADS AND THE TOP OF ANY FILES, SHELVING, EQUIPMENT, LOCKERS, ETC., (WHETHER CONTRACTOR OR OWNER FURNISHED). ADVISE THE OWNER AND TENANTS THAT ITEMS SHALL NOT BE PLACED OR STORED ON TOP OF SHELVING SO THAT THIS CODE REQUIRED 18 INCH MINIMUM VERTICAL CLEARANCE
WILL BE MAINTAINED.
7. WHERE EXISTING LAY-IN CEILING GRIDS ARE REMOVED AND RE-INSTALLED, TAKE CARE NOT TO DAMAGE THE GRID. ANY DAMAGED GRID SHALL BE REPLACED WITH NEW MATERIAL. THESE NEW MATERIALS SHALL MATCH THE EXISTING IN A UNIFORM MANNER FOR COLOR, TEXTURE, PATTERN, ETC. IF UNIFORMITY CANNOT BE ACHIEVED, REPLACE THE ENTIRE CEILING WITHIN THAT SPACE WITH NEW MATERIAL. PROVIDE NEW MATERIAL AS APPROVED BY BOTH OWNER AND
ARCHITECT IN WRITING.
8. THE "LIMITS OF CONSTRUCTION" LINES SHOWN ON THE REFLECTED CEILING PLANS APPLY ONLY TO THE LIMITS OF THE ARCHITECTURAL NEW CONSTRUCTION AND RENOVATION. SEE THE OTHER DISCIPLINES' DRAWINGS FOR THE LIMITS OF THE
NEW CONSTRUCTION AND RENOVATION FOR THEIR DISCIPLINE.
9. SEE THE INTERIOR DESIGN DRAWINGS FOR THE PAINT SPECIFICATIONS AND COLORS OF PAINTED CEILINGS AND INTERIOR SOFFITS. HORIZONTAL SURFACES OF SOFFITS SHALL BE PAINTED THE SAME COLOR AS THE VERTICAL SURFACES, UNLESS
NOTED OTHERWISE.
10. RECESSED CAN LIGHT FIXTURES:
A. THE RECESSED CAN LIGHT FIXTURES SHALL BE CENTERED IN GYPSUM BOARD SOFFITS, U.N.O
B. THE RECESSED CAN LIGHT FIXTURES SHALL BE CENTERED IN THE CEILING TILE, U.N.O.
C. RECESSED CAN LIGHT FIXTURES IN A SERIES SHALL BE ALIGNED AND EQUALLY SPACED, U.N.O.
GENERAL NOTES FOR REFLECTED CEILING PLANS:
1. ALL WORK SHALL CONFORM TO ALL APPLICABLE CODES, STANDARDS AND GOVERNING AUTHORITIES.
2. REFER TO ARCHITECTURAL, INTERIOR DESIGN, MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL DRAWINGS FOR
COORDINATION OF WORK.
3. NOTES APPEAR ON A NUMBER OF DRAWINGS FOR DIFFERENT SYSTEMS AND MATERIALS. REFERENCE ALL ISSUED CONTRACT DOCUMENTS TO APPLY APPLICABLE NOTES, SYMBOLS AND ABBREVIATIONS TO BUILDING COMPONENTS.
4. DO NOT SCALE THE DRAWINGS.
5. VISIT THE SITE AND BECOME KNOWLEDGEABLE OF CONDITIONS. INVESTIGATE, VERIFY AND BE RESPONSIBLE FOR ALL THE REQUIREMENTS OF THE PROJECT AND NOTIFY THE OWNER AND ARCHITECT OF ANY EXISTING CONDITIONS REQUIRING
INFORMATION BEFORE PROCEEDING WITH ANY WORK.
6. PROTECT ALL EXISTING SITE ELEMENTS FROM DAMAGE DUE TO ALTERATION AND CONSTRUCTION OPERATIONS AND THEY
SHALL REPAIR OR REPLACE ELEMENTS DAMAGED DURING THE PROJECT.
7. ANY UTILITY SHUT-OFFS AS REQUIRED FOR COMPLETION OF THE WORK SUCH AS ELECTRICAL, GAS, WATER, SEWER, STEAM, ETC., MUST BE SCHEDULED WITH THE OWNER, ARCHITECT AND UTILITY COMPANY PRIOR TO COMMENCING WORK.
8. DETAILS SHOWN ARE INTENDED TO BE INDICATIVE OF THE PROFILES AND TYPE OF DETAILING REQUIRED FOR THE WORK.
DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE SHOWN.
9. UNLESS NOTED OTHERWISE, ALL FASTENERS AND FASTENING DEVICES ARE TO BE CONCEALED IN ALL FINISHED SPACES.
10. ANY PIPING, DUCTS, CONDUITS, ETC. THAT PENETRATE FIRE RATED FLOOR SLABS AND WALLS SHALL BE INSTALLED IN A MANNER THAT WILL PRESERVE THE FIRE INTEGRITY OF THE FLOOR OR WALL. FIRE STOP RATINGS SHALL MATCH RATINGS OF FLOORS OR WALLS WHERE PENETRATIONS OCCUR. PROVIDE FIRE DAMPERS IN DUCTS PENETRATING FIRE-RATED WALLS AND
FLOORS TO MEET THE APPLICABLE BUILDING CODES.
11. ALL JOINTS OF ANY ELEMENT OF CONSTRUCTION WHICH ARE REQUIRED TO HAVE A FIRE RESISTANCE RATING SHALL BE INSTALLED PER THE MANUFACTURER'S PUBLISHED TESTED ASSEMBLIES, SHALL BE TIGHT AND SHALL PREVENT THE PASSAGE
OF SMOKE AND FLAME.
12. WHERE THE FIRE RATINGS OF WALLS ARE NOTED ON THE DRAWINGS, THE FIRE RATING SHALL APPLY TO THE ENTIRE PERIMETER ENCLOSURE OF THE ROOM OR SPACE FOR THE FULL LENGTH AND HEIGHT OF AREAS BEING SEPARATED, EXTENDING TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK.
13. PROVIDE FIRE STOPS TO SEPARATE WALL CAVITIES FROM HORIZONTAL PLENUM AREAS AND BETWEEN FLOORS TO CLOSE OPENINGS. FIRE RATING OF STOPS SHALL MATCH THE FIRE RATING OF VERTICAL SEPARATION OR FLOOR CONSTRUCTION, WHICHEVER IS GREATER.
14. CONSTRUCTION AROUND CABINETS, PANELS AND BOXES RECESSED IN FIRE -RATED FLOOR, WALL AND CEILING
ASSEMBLIES SHALL MAINTAIN THE FIRE-RATING NOTED IN THE DRAWINGS.
15. OPENINGS IN WALL, CEILING, FLOOR AND ROOF ASSEMBLIES SHALL BE SEALED WITH PENETRATION SEALANT SYSTEMS
THAT MEET OR EXCEED THE REQUIRED FIRE RATINGS.
16. ALL DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER BY GASKETS OR COATINGS OR BOTH TO
AVOID GALVANIC CORROSION ACTION.
17. PATCH FIREPROOFING TO MATCH EXISTING.
18. SEE MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL DRAWINGS TO DETERMINE QUANTITIES OF DIFFUSERS, GRILLES, LIGHT FIXTURES, SPRINKLER HEADS, ETC.
19. PIPE AND COLUMN FURRING SHALL BE HELD AS CLOSE TO THE PIPING AND/OR COLUMNS AS POSSIBLE, UNLESS NOTED
OTHERWISE.
20. THE EXTENT OF THE WORK SHOWN ON THE PLANS AND DETAILS REFLECTS THE BEST JUDGMENT OF THE ARCHITECT/ENGINEER. FAMILIARIZE HIM/HERSELF WITH THE EXISTING CONDITIONS AND ADVISE THE ARCHITECT, IN WRITING, OF ANY SITUATION THAT WOULD NOT ALLOW HIM/HER TO PROCEED ON THE BASIS OF THESE DOCUMENTS.
21. THE ARCHITECT/ENGINEER'S SELECTION OF MATERIALS AND DETAILS DOES NOT RELIEVE THE CONTRACTOR FROM VERIFYING WITH THE MATERIAL SUPPLIERS THAT THE PROPOSED MATERIALS ARE CORRECT AND PROPER FOR THE INTENDED
APPLICATION AND USE.
22. CONCRETE FILLS ABOVE STRUCTURAL SLABS SHALL BE REINFORCED. REFER TO STRUCTURAL DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
23. UNLESS NOTED OTHERWISE, WHERE AN ARCHITECTURAL FINISHED FLOOR IS TO BE PROVIDED (REQUIRING A DEPRESSED STRUCTURAL SLAB), THE FLOOR ELEVATIONS ARE TO TOP OF FINISHED FLOOR. WHERE AN ARCHITECTURAL FINISHED FLOOR IS INTENDED FOR SURFACE APPLICATION, THE FLOOR ELEVATIONS ARE TO TOP OF STRUCTURAL SLAB. REFER TO STRUCTURAL
DRAWINGS FOR LOCATION OF DEPRESSED SLABS.
24. UNLESS NOTED OTHERWISE, CONCRETE PAD WITH REINFORCING SHALL BE INSTALLED UNDER ALL FLOOR MOUNTED MECHANICAL AND ELECTRICAL EQUIPMENT. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION DRAWINGS FOR THE EXTENT OF EQUIPMENT PADS. COORDINATE THE SIZE, THICKNESS AND LOCATION OF THE CONCRETE PADS
WITH THE EQUIPMENT INSTALLER.
25. AT THOSE PLACES WHERE MATERIALS ARE APPLIED TO, OR ARE IN DIRECT CONTACT WITH WORK INSTALLED BY ANOTHER SUBCONTRACTOR, COMMENCEMENT OF WORK IMPLIES THE ACCEPTANCE OF THE SUBSTRATE AND EXISTING CONDITIONS AS
SUITABLE FOR THE APPLICATION INTENDED.
26. CONSTRUCTION OF NEW HORIZONTAL SURFACES SHALL BE LEVEL AND FLAT AND NEW VERTICAL SURFACES SHALL BE
CONSTRUCTED TO BE PLUMB, UNLESS NOTED OTHERWISE.
27. WHERE NOT INDICATED, PROVIDE BLOCKING IN WALLS, SOFFITS, AND CEILINGS RECEIVING SIGNAGE, COAT HOOKS, LOCKERS, MARKER BOARDS, AND OTHER MOUNTED ITEMS, ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.
28. CONTINUOUS PERIMETER FIRE SAFING BETWEEN FLOORS SHALL BE PROVIDED AND COORDINATED WITH THE EXTERIOR WALL SYSTEMS AND ASSEMBLIES. THE FIRE SAFING'S RATING SHALL MATCH OR EXCEED THAT OF THE FLOOR CONSTRUCTION
RATING.
29. CONFIRM AND FIELD VERIFY DIMENSIONS TO COORDINATE WITH OWNER PROVIDED EQUIPMENT AND FURNISHINGS.
30. SUBSTITUTIONS OF MATERIALS MAY OCCUR IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, AND ONLY IF AUTHORIZED
BY THE ARCHITECT.
31. PERFORM FIELD VERIFICATION OF ALL THE EXISTING CONDITIONS ON THE SITE AND SHALL VERIFY THE LOCATION OF ALL EXISTING UTILITIES AND SHALL COMPARE THE INFORMATION TO THE CONTRACT DOCUMENTS PRIOR TO THE COMMENCEMENT
OF ALL WORK. IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES.
32. ALL CONTRACTOR PROVIDED MATERIALS SHALL BE NEW AND DELIVERED AND INSTALLED IN GOOD CONDITION AND
WITHOUT ANY DEFECTS.
33. ANY WORK NOT CONFORMING TO THESE SPECIFICATIONS WILL BE REJECTED. THE ARCHITECT OR THE OWNER MAY REJECT THE WORK. REJECTED WORK WILL BE REMOVED AND REPLACED AT NO ADDITIONAL COST TO THE OWNER.
34. CONTRACT DOCUMENTS ARE INCLUSIVE OF ALL DISCIPLINES DRAWINGS AND SPECIFICATIONS. ENSURE COORDINATION
ACROSS ALL DRAWINGS.
35. DELEGATED DESIGN SUBMITTALS SHALL BE SUBMITTED TO THE BUILDING OFFICIAL AND THE ARCHITECT AND SHALL BE REVIEWED PRIOR TO INSTALLATION. ALL DELEGATED DESIGN SUBMITTALS SHALL BE SIGNED AND SEALED BY A LICENSED
PROFFESSIONAL ENGINEER REGISTERED IN THE STATE OF FLORIDA.
GENERAL PROJECT NOTES:
A
B
C
D
54321
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
SEAL:
/2
/2
:4 :4
A
M A u to d e s k D o c s /2
H a lif a x P o rt
O ra n g e P h a rm a c y R e n o v a ti o n
/H a lif a x P o rt
O ra n g e
P h a rm a c y
R e n o v a ti o n n d
F lo o r_
A R
.r v t
CONSTRUCTION DOCUMENTS
RS&H
MW
1041 DUNLAWTON AVE,
PORT ORANGE, FL 32127
2ND FLOOR PHARMACY
RENOVATION
20070225000
06/23/2025
RS&H
G004
GENERAL PROJECT
NOTES
© 2025 RS&H, INC
Copyright © 2025. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
407-893-5800 Fax 407-264-6624
301 E. Pine Street, Suite 350 Orlando, Florida 32801 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956 *
DROP CEILING SOFFIT
G.I. (SOUTH) SIDE
RESP. (NORTH) SIDE
SC-2C
SC-2A SC-2B
S
S
S
S S
S
ELEV #1
ELEV #2ELEV #3
down up
AREA OF WORK
EXERCISE
AREA
HYDROTHERAPY
CLEAN
HOLDING
TOILET
SOILED
HOLDING
DRESSING
STRESS LABCONTROL ROOM
NUCLEAR MEDICINE SCAN PASSAGE
TOILET OFFICE
E - CORRIDOR
STAIR
ELECT.DOSING
ATRIUM BELOW
FIRE DOOR
MECHANICAL MECHANICAL MECHANICAL
W - CORRIDOR
STAIR
ELECT.
STAIR
MED GAS
O2 STORAGE
CORRIDOR
CLEAN ROOM
NARCOTICS
E X
IT
T
R A
V E
L D
IS
T
A N
C E
'-0
ANTE ROOM
PHARMACY
1045 SF
PICK-UP
N - CORRIDOR
FE
CODE ANALYSIS
AREA OF WORK
FIRE PROTECTION
THE BUILDING IS FULLY SPRINKLERED PER NFPA 13. SEE FIRE SPRINKLER NOTES, SHEET G004.
THE BUILDING WILL CONTAIN (OR CONTAINS) A FIRE ALARM SYSTEM CONSISTING OF
HORN/STROBES PER NFPA 72.
PORTABLE FIRE EXTINGUISHERS WILL BE PROVIDED PER NFPA 10.
G.C. SHALL PROVIDE FIRE EXTINGUISHERS DURING CONSTRUCTION PER 2010 FFPC.
MEANS OF EGRESS (FBC)
MAXIMUM TRAVEL DISTANCE (TABLE 1017.2)
GROUP I-2/ INSTITUTIONAL - 200 FT
MAXIMUM DEAD-END CORRIDOR (1020.4)
GROUP I - 20 FT
MAXIMUM COMMON PATH OF TRAVEL 75 FT
EGRESS STAIR WIDTH (FBC 1005.3.1) - .3" PER OCCUPANT
EGRESS WIDTH PER PERSON (FBC 1005.3.2) - .2" PER OCCUPANT
MINIMUM CORRIDOR WIDTH (FBC1020.2) 44" (96" REQ'D FOR BED MOVEMENT AREAS)
THE GENERAL SCOPE OF THE PROJECT CONSISTS OF APPROXIMATELY 164 SQUARE FEET OF
RENOVATIONS TO AN EXISTING I.V ROOM TO MEET THE REQUIREMENTS OF USP 797 WISH INCLUDES CLEAN
& ANTE ROOMS. THE DESIGN WILL SUPPORT THE USE OF EPIC IV SYSTEM.
CODE ANALYSIS
APPLICABLE CODES
2023 FLORIDA BUILDING CODE (FBC): BUILDING (6TH EDITION)
2023 FLORIDA BUILDING CODE (FBC): EXISTING BUILDING (6TH EDITION)
2023 FLORIDA BUILDING CODE (FBC): MECHANICAL (6TH EDITION)
2023 FLORIDA BUILDING CODE (FBC): PLUMBING (6TH EDITION)
2023 FLORIDA BUILDING CODE (FBC): ACCESSIBILITY (6TH EDITION)
2020 NATIONAL ELECTRICAL CODE
2023 FLORIDA FIRE PREVENTION CODE
2019 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 110, EMERGENCY & STANDBY POWER
2021 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 101, LIFE SAFETY CODE
2021 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 99, HEALTH CARE FACILITIES CODE
2019 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 72, FIRE ALARM
2020 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 70, ELECTRICAL
2019 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 13, SPRINKLERSGUIDELINES FOR THE DESIGN AND
UNITED STATES PHARMACOPEIA (USP) CHAPTERS 797 & 800
APPLICABLE CODES - AHCA
GUIDELINES FOR THE DESIGN AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT FACILITIES 2022
EDITION.
F.A.C. 69A-60 F.A.C. 69A-3.012
OCCUPANCY CLASSIFICATION (FBC/LSC)
INSTITUTIONAL GROUP I-2 (FBC 308)
BUILDING DATA
TOTAL GROSS BUILDING SQUARE FOOTAGE: ~ 24,864 SF
NUMBER OF FLOORS: 5
HEIGHT OF BUILDING: EXISTING
ALLOWED PER CODE: 180'-0" IN CODE + 20' FOR AUTOMATIC SPRINKLER
SPRINKLERED: YES
PROJECT DESCRIPTION
2ND LEVEL I-2 INSTITUTIONAL OCCUPANT LOAD FACTOR = 120 OCCUPANTS / SF
AREA OF WORK 164 SF
OCCUPANT LOAD FACTOR 120 OCCUPANTS / SF
TOTAL OCCUPANT LOAD 2 OCCUPANTS
PLUMBING FIXTURE COUNT (IPC)
WATER CLOSETS:
LAVATORIES:
EXISTING (NO CHANGE)
EXISTING (NO CHANGE)
CODE ANALYSIS
SMOKE COMPARTMENTS & EGRESS WIDTH
SMOKE
COMPARTMENT
ZONE
COMPARTMENT
GROSS FLOOR
AREA (SF)
SF PER
OCCUPANT
OCCUPANT
LOAD
EXIT CAPACITY
REQUIRED
DOOR
(0.2)
STAIR
(0.3)
EXIT WIDTH
PROVIDED
(STAIRS)
SC-2A 4,070 240 17 3" 5" 48"
DRINKING FOUNTAINS:
SERVICE SINKS:
EXISTING (NO CHANGE)
EXISTING (NO CHANGE)
(EXISTING; NO CHANGE)
TYPE IB, SPRINKLERED PER TABLE 601
NON BEARING INTERIOR WALLS AND PARTITIONS ARE NOT REQUIRED TO BE FIRE RATED.
CONSTRUCTION CLASSIFICATION (FBC)
SC-2B 16,469 240 69 14" 20" 48"
SC-2C 2,575 240 11 2" 3" 48"
SYMBOL LEGEND
LIFE SAFETY LEGEND
FIRE EXTINGUISHER
ETD 60' - 0"
CPT 20' - 0"
EXIT SIGN WITH DIRECTIONAL ARROW
NEW CONSTRUCTION
34"
FE
OUTSIDE SCOPE OF PROJECT
EXISTING CONSTRUCTION TO REMAIN
1-HOUR FIRE RATED PARTITION
1-HOUR FIRE/SMOKE RATED PARTITION
2-HOUR FIRE RATED PARTITION
TRAVEL DISTANCE TO EXIT
EXIT SIGN
COMMON PATH OF TRAVEL DISTANCE
DOORWAY EXIT WIDTH
NOTE: ALL CORRIDOR WALLS ARE SMOKE TIGHT
PARTITION LEGEND
GENERAL NOTES
1. THE LIFE SAFETY PLANS ARE "DIAGRAMMATIC ONLY". THEIR PURPOSE IS SOLELY TO REPRESENT THE
LIFE SAFETYCOMPONENTS FOR THE PROJECT (AS INCLUDED IN THE CONSTRUCTION DOCUMENTS
PREPARED BY THE ARCHITECT,ELECTRICAL ENGINEER, ETC.). USE THE CONSTRUCTION DOCUMENTS (NOT THE LIFE SAFETY PLANS) FOR THE IMPLEMENTATION OF THE REQUIRED LIFE SAFETY COMPONENTS INTO
THE PROJECT.
2. ADVISE THE ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY LIFE SAFETY COMPONENT THAT IS SHOWN ON THE LIFE SAFETY PLANS BUT HAVE NOT BEEN INCLUDED IN THE CONSTRUCTION DOCUMENTS
PREPARED BY THE ARCHITECT, ELECTRICAL ENGINEER, ETC.
3. FIELD VERIFY THAT THE REQUIRED VISIBILITY FOR EACH INDIVIDUALLY INSTALLED EXIT LIGHT IS NOT IN ANY WAY DIMINISHED DUE TO VISUAL INTERFERENCE CAUSED BY ANY OTHER LIGHT FIXTURE, DEVICE, SIGN, ETC. (COORDINATE WITH THE ARCHITECT'S REFLECTED CEILING PLANS, THE ELECTRICAL
DRAWINGS, THE GRAPHICS DRAWINGS, ETC.)
4. EACH "WALL/PARTITION/BARRIER" CLASSIFICATION IN RED LETTERS ABOVE THE FINISH CEILING ON EACH SIDE OF ALL FIRE WALLS, RATED FIRE BARRIERS, RATED SMOKE BARRIERS, NON-RATED SMOKE
PARTITIONS, ETC.
SCALE: = 1'-0"
A
B
C
D
54321
3/32"
0 8 16 248
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
SEAL:
/1
/2
:3
:2
A
M A u to d e s k D o c s /2
H a lif a x P o rt
O ra n g e P h a rm a c y R e n o v a ti o n
/H a lif a x P o rt
O ra n g e
P h a rm a c y
R e n o v a ti o n n d
F lo o r_
A R
.r v t
CONSTRUCTION DOCUMENTS
MV
MW
1041 DUNLAWTON AVE,
PORT ORANGE, FL 32127
2ND FLOOR PHARMACY
RENOVATION
20070225000
06/23/2025
RS&H
G101
OVERALL 2ND FLOOR
LIFE SAFETY PLAN
© 2025 RS&H, INC
Copyright © 2025. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
407-893-5800 Fax 407-264-6624
301 E. Pine Street, Suite 350 Orlando, Florida 32801 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956 *
5620 * LCC000210 * GB238
SCALE: 3/32" = 1'-0"
A1
OVERALL 2ND FLOOR LIFE SAFETY PLAN
KEY PLAN:
A
SOILED
HOLDING
EXERCISE
AREA
HYDROTHERAPYCLEAN ROOM
F2-A
F3-D
1'
1'
A3-D
A401D1
D2
D3
D4
LWR
LWR
MS
A401C1 C2
MS
E-2
E-1
2F 2F F2-A.1
A3-D
1F
1F
3F
1' - 0"
4"1'
" F2-A.1
F2-A
F2-A
5F
4F
ANTE ROOM
5F
5F
3'
4' - 6"
A4
A501
1' - 0"
8' - 0" 1' - 2"
LWR
OFFICE
PHARMACY
MS
HYDROTHERAPY
SOILED
HOLDING
I.V. ROOM
EXERCISE
AREAPHARMACY
1D 2D
3D
4D 5D
5D
6D
7D
S
MS
M
EXIT
NAM
C O
N T
R A
C T
O R
E N
T R
A N
C E
CONSTRUCTION
ANTE ROOM
OFFICE
2D
SOILED
HOLDING
EXERCISE
AREA
HYDROTHERAPY
CLEAN ROOM
ACT1 8'-0" AFF
ANTE ROOM
OFFICE
PHARMACY
PARTITION LEGEND
DEMOLITION PLAN LEGEND
REMOVE EXISTING CONSTRUCTION
EXISTING CONSTRUCTION TO REMAIN
AREA NOT IN CONTRACT (NIC) U.N.O.
INSTALL TEMPORARY FIRE RETARDANT DUST BARRIER
WALL BEFORE BEGINNING DEMOLITION &
CONSTRUCTION -SEE DETAIL A4/A501
PATH OF CONTRACTOR ACCESS FROM EXTERIOR DOOR TO ENTRY
DOOR OF CONSTRUCTION ANTE ROOM. PROVIDE STICKY MATTS
ON BOTH SIDES OF ANTE ROOM DOOR.
S.M. STICKY MAT, INSTALL AT ALL CONSTRUCTION ENTRANCES
N.A.M.
PROVIDE HEPA-FILTERED NEGATIVE AIR HVAC UNIT -DISCHARGE
FILTERED AIR THRU TEMPORARY DUST BARRIER WALL
FIRE RETARDANT PLASTIC MEMBRANE DUST BARRIER
W/ ZIPPER ACCESS DOOR
NOTE: SEE GENERAL NOTES ON SHEET G004
DEMOLITION PLAN KEYNOTES
REMOVE EXISTING FLOORING & WALL BASE.
PREPARE EXISTING SLAB TO RECEIVE NEW FLOOR FINISHES.
REMOVE EXISTING CEILING, SOFFIT, AND ALL CEILING DEVICES.
TURN OVER EXISTING CEILING DEVICES TO OWNER FOR REUSE/STORAGE.
CORE DRILL EXISTING SLAB TO ACCOMMODATE SANITARY PIPING PENETRATIONS
LOCATIONS, SEE FLOOR PLAN AND PLUMBING PLAN.
REMOVE EXISTING DOOR & FRAME AND PORTION OF EXISTING WALL AS
REQUIRED TO INSTALL NEW DOOR AND FRAME. TURN OVER EXISTING DOOR
AND DOOR HARDWARE TO OWNER FOR REUSE/STORAGE.
REMOVE EXISTING PLUMBING FIXTURE AND ACCESORIES
AND SALVAGE FOR REUSE.
REMOVE EXISTING MILLWORK.
SALVAGE EXISTING EQUIPMENT AND PROTECT DURING CONSTRUCTION.
PREPARE FOR REINSTALLATION.
1D
2D
3D
4D
5D
6D
7D
PARTITION LEGEND
FLOOR PLAN LEGEND & SHEET NOTES
NOTE: REFER TO PARTITION TAGS ON PLANS AND PARTITION TYPE DETAILS.
(ALL PARTITION TO BE A3-D UNLESS NOTED OTHERWISE)
SEE GENERAL NOTES ON SHEET G004
EXISTING CONSTRUCTION TO REMAIN
AREA NOT IN CONTRACT (NIC) U.N.O.
NON-RATED WALL SYSTEM
A3-D PARTITION TAG, SEE TYPE ON SHEET A501
LWR
IN-WALL LOW WALL RETURN GRILLE.
REFER TO MECH. DRAWINGS
MS MOTION SENSOR ACTUATORS
1F
2F
3F
FLOOR PLAN KEYNOTES
PATCH AND REPAIR AFFECTED GYPSUM WALL BOARD SURFACES AND
FINISHES AS REQUIRED FOR AN UNDETECTABLE REPAIR.
PROVIDE BLACK-OUT FILM ON COVERED PORTION OF WINDOW AND INSTALL
FRICTION FIT RIGID INSULATION IN EXISTING WINDOW FRAME.
NEW STAINLESS STEEL KNEE OPERATED SCRUB SINK WITH EYEWASH.
REFER TO PLUMBING DRAWINGS.
RED-LINE OF DEMARCATION; 2" WIDE, INTEGRAL, WELDED WITH ADJACENT
SEAMLESS VINYL FLOOR FINISH.
EXTEND METAL STUD FRAMING, BATT INSULATION, AND GYPSUM WALL
BOARD ABOVE CEILING TO DECK, PER DETAIL A3-D.1/A501
4F
5F
FIXTURE LEGEND
CEILING PLAN LEGEND & SHEET NOTES
2' x 2' LED LIGHT FIXTURE;
SEE ELECTRICAL
EXIT SIGN;
SEE ELECTRICAL
2' x 4' FAN FILTER UNIT, SEE MECHANICAL
CEILING TYPES LEGEND
ACT1
(ALL CEILING 8'-0" A.F.F. UNLESS NOTED OTHERWISE)
AREA NOT IN CONTRACT
(NIC) U.N.O.
NOTE: SEE GENERAL NOTES ON SHEET G004
2' x 2' SUSPENDED SCRUBABBLE ACOUSTICAL CEILING TILE
SYSTEM W/ GASKETED GRID - PROVIDE CONTINUOS CLEAR
SEALANT BETWEEN PERIMETER OF TILES & GRID.
2' x 2' EMERGENCY
LED LIGHT FIXTURE;
SEE ELECTRICAL
SCALE: = 1'-0"
A
B
C
D
54321
0 4 84
1/4"
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
SEAL:
/1
/2
:4 :3
A
M A u to d e s k D o c s /2
H a lif a x P o rt
O ra n g e P h a rm a c y R e n o v a ti o n
/H a lif a x P o rt
O ra n g e
P h a rm a c y
R e n o v a ti o n n d
F lo o r_
A R
.r v t
CONSTRUCTION DOCUMENTS
MV
MW
1041 DUNLAWTON AVE,
PORT ORANGE, FL 32127
2ND FLOOR PHARMACY
RENOVATION
20070225000
06/23/2025
RS&H
A102
ENLARGED 2ND
FLOOR DEMOLITION
PLAN, FLOOR PLAN,
REFLECTED CEILING
PLAN AND NOTES
© 2025 RS&H, INC
Copyright © 2025. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
407-893-5800 Fax 407-264-6624
301 E. Pine Street, Suite 350 Orlando, Florida 32801 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956 *
5620 * LCC000210 * GB238
SCALE: 1/4" = 1'-0"
D3
ENLARGED 2ND FLOOR PLAN
SCALE: 1/4" = 1'-0"
D5
ENLARGED 2ND REFLECTED CEILING PLAN
SCALE: 1/4" = 1'-0"
D1
ENLARGED 2ND FLOOR DEMOLITION PLAN
KEY PLAN:
A
EQUIPMENT SCHEDULE
Type Mark Description Vendor Model Comments
Furnished by / Installed by
E-1 REFRIGERATOR OFCI
E-2 LAMINAR FLOW HOOD OFCI
3'
CL
SCRUB SINK W/
EYEWASH. REFER
TO PLUMBING
INTEGRAL BASE
AS SCHEDULED
BOBRICK MIRROR:
MODEL 781
TEMPERED GLASS
24" x 60" . PROVIDE
BLOCKING BEHIND
WALL
MS
STAINLESS STEEL IN-WALL LOW
WALL RETURN GRILLE BEYOND.
SEE MECH. DRAWINGS
9"
LWR
MOTION
SENSORM1
E-1 E-2
3'
MOTION
SENSOR
CL
INTEGRAL BASE
AS SCHEDULED
MS
LWR
MS
SCRUB SINK W/EYEWASH.
REFER TO PLUMBING
9"
STAINLESS STEEL IN-WALL
LOW WALL RETURN GRILLE.
SEE MECH. DRAWINGS
INTEGRAL BASE
AS SCHEDULED
LWR
3'
MOTION
SENSOR
CL
MS
2'
SCRUB SINK W/EYEWASH.
REFER TO PLUMBING
LWR
INTEGRAL BASE
AS SCHEDULED
LWR
9" 9"
STAINLESS STEEL IN-WALL
LOW WALL RETURN GRILLE.
SEE MECH. DRAWINGS
PT1SD1
STAINLESS STEEL IN-WALL
LOW WALL RETURN GRILLE.
SEE MECH. DRAWINGS
LWR
E-2
INTEGRAL BASE
AS SCHEDULED
INTEGRAL BASE
AS SCHEDULED
MS
INTERIOR ELEVATION NOTES
1. FOR EQUIPMENT INFORMATION, REFER TO EQUIPMENT SCHEDULE ON
SHEET A102.
2. LOW WALL RETURNS ARE DEPICTED ON THE ELEVATIONS AS "LWR".
REFER TO MECHANICAL DRAWINGS.
3. WALL MOUNTED ACCESSORIES ARE "OFCI" OWNER PROVIDED
CONTRACTOR INSTALLED. LOCATIONS TO BE COORDINATED WITH THE
OWNER DURING CONSTRUCTION.
4. REFER TO SHEET I101 FOR INFORMATION ON FINISHES AND DETAILS.
A
B
C
D
54321
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
SEAL:
/1
/2
:5 :5
P
M A u to d e s k D o c s /2
H a lif a x P o rt
O ra n g e P h a rm a c y R e n o v a ti o n
/H a lif a x P o rt
O ra n g e
P h a rm a c y
R e n o v a ti o n n d
F lo o r_
A R
.r v t
CONSTRUCTION DOCUMENTS
MV
MW
1041 DUNLAWTON AVE,
PORT ORANGE, FL 32127
2ND FLOOR PHARMACY
RENOVATION
20070225000
06/23/2025
RS&H
A401
INTERIOR
ELEVATIONS AND
DETAILS
© 2025 RS&H, INC
Copyright © 2025. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
407-893-5800 Fax 407-264-6624
301 E. Pine Street, Suite 350 Orlando, Florida 32801 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956 *
5620 * LCC000210 * GB238
SCALE: 3/8" = 1'-0"
D1
ANTE ROOM ELEVATION
SCALE: 3/8" = 1'-0"
D2
CLEAN ROOM / ANTE ROOM ELEVATION
SCALE: 3/8" = 1'-0"
D3
ANTE ROOM ELEVATION
SCALE: 3/8" = 1'-0"
D4
CLEAN ROOM / ANTE ROOM ELEVATION
SCALE: 3/8" = 1'-0"
C2
CLEAN ROOM ELEVATION
SCALE: 3/8" = 1'-0"
C1
CLEAN ROOM ELEVATION
CONT. HEADER TRACK
CEILING AS SCHEDULED
ACOUSTICAL SEALANT AND
BACKER ROD BOTH SIDES
UNDERSIDE OF DECK / STRUCTURE
ONE LAYER GYP. WALL BD. EACH
SIDE ON METAL STUDS
HOLD GYP. WALL BOARD 1/2" AFF, TYPICAL;
BASE AS SCHEDULED
SOUND BATT INSULATION
CONTINUOUS ACOUSTICAL
SEALANT BOTH SIDES OF WALL
BOTTOM TRACK
METAL DECK
PROVIDE FIRE RATED STOP INFILL AT VOIDS
PATCH AND REPAIR FIRE PROOFING AT
DECK AS REQUIRED
PARTITION TYPE AS SCHEDULED
METAL DECK
PARTITION TYPE AS SCHEDULED
PROVIDE FIRE RATED STOP INFILL AT VOIDS
PATCH AND REPAIR FIRE PROOFING AT
DECK AS REQUIRED
METAL DECK
CONTINUOUS SEALANT AND JOINT FILLER
PATCH AND REPAIR FIRE PROOFING AT
DECK AS REQUIRED
PARTITION TYPE AS SCHEDULED
STEEL ANCHORS EACH SIDE OF WALL - REFER
TO STRUCTURE
HEAD DETAIL @ STUD WALL AND MTL DECK
HEAD DETAIL @ STUD WALL AND MTL DECK
HEAD DETAIL @ CMU WALL AND MTL DECK
EXTERIOR WALL,
FOUNDATION OR RATED
PARTITION
NON-RATED PARTITION OR
PARTITION OF LESS RATING
RATED PARTITION
NON-RATED PARTITION OR
PARTITION OF LESS RATING
RATED PARTITION
NON-RATED PARTITION OR
PARTITION OF LESS RATING
RATED PARTITION
NON-RATED PARTITION OR
PARTITION OF LESS RATING
RATED PARTITION
PARTITION TAG
GENERAL PARTITION TYPES NOTES
NOTE: PARTITION TAGS ARE READ LEFT TO RIGHT.
1. THE FIRST SECTION IN THE TAG INDICATES THE WALL TYPE BASED ON THE PRIMARY MATERIAL
OR USE OF THE PARTITION AS REFERENCED IN THE WALL TYPE SCHEDULE'S FIRST TWO
COLUMNS.
2. THE SECOND SECTION IN THE TAG INDICATES THE HEAD CONDITION OF THE WALL:
A = 6" ABOVE CEILING, B = 6" BELOW STRUCTURE, C = TO CEILING, D = TO DECK/STRUCTURE, P = PARTIAL HEIGHT WALL
3. THE LAST SECTION IN THE TAG INDICATES WHETHER THE WALL ASSEMBLY IS FIRE RATED (IF
APPLICABLE) AND IF SO, TO WHAT NUMERICAL HOUR RATING.
B3-A
WALL TYPE
(MATERIAL/USE)
GENERAL NOTES
1. SEE PLANS FOR ALL LOCATIONS OF PARTITION TYPES.
2. PROVIDE WATER-RESISTANT CORE GYPSUM WALL BOARD AT TILED OR WET LOCATIONS,
INCLUDING, BUT NOT LIMITED TO: RESTROOMS, LOCKER ROOMS, SHOWER AREAS, JANITOR
CLOSETS, KITCHEN AREAS.
3. SEE STRUCTURAL DRAWINGS FOR MASONRY WALL SIZE AND CONSTRUCTION.
4. COLUMNS SHOWN W/ ENCLOSURES AS PER DETAILS ON ARCHITECTURAL DRAWINGS. WHERE
COLUMNS INTERSECT PARTITIONS, PROVIDE RATED OR SOUND ATTENUATED PARTITION ACROSS
COLUMN ENCLOSURE, TO MAINTAIN ASSEMBLY RATING.
5. REFER TO SPECIFICATIONS FOR ADDITIONAL WALL BOARD PRODUCT DATA, THICKNESS, AND
ADDITIONAL PERFORMANCE REQUIREMENTS.
6. REFER TO SPECIFICATIONS FOR METAL STUD SPACING AND PERFORMANCE REQUIREMENTS FOR
METAL STUD GAUGES.
7. GYPSUM WALLBOARD ON PARTITIONS REQUIRING A RATING OF ONE-HOUR OR MORE MUST MEET
CONDITIONS STIPULATED BY UL DESIGN NUMBER, WHETHER OR NOT WALL TREATMENT IS
SCHEDULED.
8. FRICTION FIT SOUND ATTENUATION INSULATION SNUG IN PLACE BETWEEN FRAMING USED IN
PARTITIONS.
9. SCHEDULE CONSTRUCTION OF WALLS ACCORDING TO PRIORITY.
• TWO HOUR FIRE & SMOKE WALL PRIORITY 1 (HIGHEST)
• TWO HOUR FIRE WALL PRIORITY 2
• ONE HOUR FIRE & SMOKE WALL PRIORITY 3
• ONE HOUR FIRE WALL PRIORITY 4
• NON-RATED WALL PRIORITY 5 (LOWEST)
HEAD CONDITION
STANDARD PARTITION TAG
RS3-1
WALL TYPE
(MATERIAL/USE)
NUMERICAL HOUR
RATING
RATED PARTITION TAG
UNDERSIDE OF DECK / STRUCTURE
EXISTING PARTITION TO REMAIN.
USE SMOKE RATED SEALANT IN ALL
THROUGH WALL PENETRATIONS
CEILING AS SCHEDULED
HOLD GYP. WALL BOARD 1/2" AFF,
TYPICAL; BASE AS SCHEDULED
CONTINUOUS SMOKE SEALANT
BOTH SIDES OF WALL
CONT. HEADER TRACK
CONTINUOUS SMOKE SEALANT AND
BACKER ROD BOTH SIDES
ONE LAYER GYP. WALL BD.
EACH SIDE ON METAL STUDS
BOTTOM TRACK
METAL FRAMING TO
STRUCTURE ABOVE
3-5/8" MTL HEADER, TYP.
ACOUSTIC CEILING
TILE AS SCHEDULED
5/8" GYPSUM WALL BOARD -
FINISH AS SCHEDULED
CORNER REINFORCING, TYP. AT
ALL OUTSIDE CORNERS (TYP.)
SEE: RCP FOR
ELEV.
ACOUSTIC CEILING TILE
AS SCHEDULED
CONT. HEADER TRACK
ACOUSTICAL SEALANT AND
BACKER ROD BOTH SIDES
UNDERSIDE OF DECK / STRUCTURE
CEILING AS SCHEDULED
BRACE AS REQUIRED TO MEET LATERAL
LOAD REQUIREMENTS PER SPECIFICATIONS
UNDERSIDE OF DECK / STRUCTURE
HOLD GYP. WALL BOARD 1/2" AFF, TYPICAL;
BASE AS SCHEDULED
BOTTOM TRACK
CONT. HEADER TRACK
6"
ONE LAYER GYP. WALL BD. ON
2 1/2" FURRING CHANNEL
SOUND BATT INSULATION
CEILING AS SCHEDULED
BRACE AS REQUIRED TO MEET LATERAL
LOAD REQUIREMENTS PER SPECIFICATIONS
UNDERSIDE OF DECK / STRUCTURE
EXISTING WALL TO REMAIN
HOLD GYP. WALL BOARD 1/2" AFF, TYPICAL;
BASE AS SCHEDULED
BOTTOM TRACK
CONT. HEADER TRACK
6"
ONE LAYER GYP. WALL BD. ON
2 1/2" FURRING CHANNEL
SOUND BATT INSULATION
CLOSE CEILING SPACE W/ FIRE
POLYTHENE MEMBRANE
COMPLIANT W/ NFPA 701 TEST
METHOD 2. INSTALLED PER
MFR'S INSTRUCTIONS FOR NFPA
701 COMPLIANCE. EXTEND
MEMBRANE PAST ACOUSTICAL
CEILING AND SEAL ALL
PENETRATIONS
SEAL AROUND ALL PIPE &
DUCT PENETRATIONS.
SECURE ALL TAPE W/ RAM-
TACK IN THE PARTITION &
POLY BARRIER W/ DUCT TAPE
PROVIDE FIRE-RESISTIVE SELF-
CLOSING DOOR IN FIRE RESISTIVE
AND SMOKE GASKETED FRAME BY
ICRA MFR, COMPLIANT WITH NFPA
241, 4.13.4 & NFPA 701. INSTALL
STICKY MATS AT BOTH SIDES OF
DOOR ASSEMBLY EXISTING FLOOR
NON-COMBUSTIBLE, SMOKE
RESISTIVE PRE-FABRICATED
TEMPORARY PARTITION
COMPLIANT WITH NFPA 241;
4.13.4 & NFPA 701
PLASTER TAPE ALL JOINTS,
HIGH TACK SPRAY OR EQUAL
RENOVATED SIDE OCCUPIED SIDE
TEMPORARY (ICRA) PARTITION
NOTE: 'EDGEGUARD' OR EQUAL FIRE RESISTANT PRE-FAB WALL SYSTEM IS ACCEPTABLE
FINISHED CEILING
AS SCHEDULED
PARTITION TYPE
AS SCHEDULED
PROVIDE BLACK-OUT FILM ON
WINDOW AND INSTALL 1" THICK
FRICTION FIT RIGID INSULATION
IN EXISTING WINDOW FRAME
EXISTING EXTERIOR WALL
TO REMAIN
INTERIOREXTERIOR
FINISH FLOOR AS
SCHEDULED
BASE AS SCHEDULED
EXISTING GWB TO REMAIN
8' -0
A
F F
SOUND BATT INSULATION
CONT. HEADER TRACK
4" 6"
1. ALL STUD GAUGES AND LIMITING HEIGHTS IN GYPSUM WALL BOARD REFERENCE SPECIFICATIONS.
2. ALL PARTITIONS CONTAINING PLUMBING OR HAVING AN EXTERIOR FACE TO BE INSULATED.
3. THE FOLLOWING LIST OF ROOMS (IF USED) SHALL HAVE THEIR PERIMETER PARTITIONS INSULATED
USING MINERAL WOOL:
A. ALL ROOMS ENCLOSED WITH RATED PARTITIONS
4. THE FOLLOWING LIST OF ROOMS (IF USED) SHALL HAVE THEIR PERIMETER PARTITIONS INSULATED WITH
SOUND ATTENUATION BATTS AS SPECIFIED:
A. TOILET ROOMS
B. OFFICES
C. EXAM ROOMS
5. ALL RATED PARTITIONS TO EXTEND FROM TOP OF SLAB TO UNDERSIDE OF STRUCTURE. SEAL TOP
AND BOTTOM TYPICAL.
6. ALL INTERIOR ROOF DRAINS AND OVERFLOW DRAINS TO BE WRAPPED CONTINUOUSLY WITH SOUND
ATTENUATION INSULATION.
7. REFER TO PLANS FOR LOCATION OF PARTITION TYPES. "A" IS THE TYPICAL PARTITION TYPE UNLESS
NOTED OTHERWISE.
8. UNDERSIDE OF STRUCTURE INDICATED AT HEAD CONDITION FOR EACH PARTITION TYPE IS
DIAGRAMMATIC ONLY, AND DOES NOT INDICATE EXACT CONSTRUCTION CONDITIONS.
9. INSTALL FRAMING AND GYPSUM WALL BOARD TO OFFSET AROUND STRUCTURAL MEMBERS OR OTHER
OBSTRUCTIONS TO MAINTAIN FIRE RESISTIVE RATINGS.
10. WHERE GYPSUM WALL BOARD EXTENDS TO THE UNDERSIDE OF STRUCTURE, STOP GYPSUM WALL
BOARD ½ BELOW LINE OF STRUCTURE AND SEAL AS REQUIRED.
11. FIRE RESISTANT, RATED PARTITIONS TO BE INSTALLED WITH FIRESTOP SEALANT, UNLESS NOTED
OTHERWISE.
12. NON-RATED PARTITIONS TO BE INSTALLED WITH ACOUSTICAL SEALANT, UNLESS NOTED…
This is the start of the file's text. The full file is on GovTribe.