10-EXHIBIT - 1 HHPO Chiller Scope Outline.pdf
PDF 4 MB Posted
- Attached to
- CHILLER REPLACEMENT FOR HHPO
- Solicitation number
- PROJ-25-131
- Issued by
- Volusia County, Florida
About this file
This document is a comprehensive submittal package for a chiller replacement project for Halifax Health Port Orange Campus, prepared by Johnson Controls for a York YVAA Air-Cooled Chiller (Model YVAA0273). The project involves replacing Air-Cooled Chiller 2, located in the chiller yard at 1041 Dunlawton Ave, Port Orange, FL 32127, with a new 200-nominal ton, R-513A refrigerant chiller. The chiller will be a turnkey replacement with specific requirements including a Trane or York YVAA unit with variable speed drives, high efficiency, 460V/60Hz/3 phase power, and a ten-year parts, labor, and refrigerant warranty. The project includes comprehensive installation components such as chilled water piping, accessories, supports, insulation, permits, commissioning, and associated electrical and control work.
The submittal package includes detailed technical specifications, performance data, warranty information, installation guidelines, and compliance certifications. The chiller is designed to meet ASHRAE 90.1 standards, AHRI certification requirements, and includes advanced features like low ambient temperature control, variable speed fans, microchannel coil technology, and BACnet interface capabilities. The unit's performance data indicates a net cooling capacity of 207 tons, an Energy Efficiency Ratio (EER) of 10.84, and the ability to operate efficiently across various load conditions. The total project cost is not explicitly stated, but the comprehensive technical requirements and extended warranty suggest a high-value, mission-critical infrastructure replacement for the healthcare facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date: 8/7/25
HHPO Chiller Replacement
Outline of Scope of work:
The scope of the work shall include but not limited to:
Replacement of Air-cooled Chiller 2, located in the Chiller yard for the Halifax Health Port Orange Campus, 1041 Dunlawton Ave, Port Orange FL 32127. This system serves the hospital.
Contractor shall provide a turnkey all-inclusive proposal/bid not limited to the following:
o Contractor is responsible for conducting due diligence to ensure the replacement fits within the existing space.
o Basis of design is Trane; approved alternate is York YVAA Chiller; bidders may submit an equal alternate for review and approval. Design data for both Trane and York are attached for bidder’s reference.
o See reference design parameters for Chiller selection:
- RTAF air-cooled screw chiller
- Unit startup
- 200 nominal tons
- 60 hertz
- 460V/60Hz/3 phase
- High efficiency
- Standard noise
- UL listed
- ASME pressure vessel code
- Refrigerant charge R-513A
- AHRI certified
- ASHRAE 90.1 all versions up to 2022
- Made to Order 115-270T
- Circuit Breaker with ASME
- Standard cooling
- 2 pass evaporator
- Water
- Grooved pipe
- Factory installed flow switch water
- Factory insulation- 1.5 inch
- Standard ambient
- Coated Condenser coils
- BYGOLD Coating Cabinet & Casings
- Variable speed fans
- Oil cooler
- Variable speed compressors
- Single point unit power connection
- Circuit breaker with high fault rated control panel
- High amp short circuit rating
- 115V Convenience Outlet
- BACnet interface
- Architectural louvered panels
- Elastomeric isolators
- Ten (10) year Parts, Labor & Refrigerant warranty o Chilled Water Piping o Accessories such as valves o Supports (piping & ductwork) o Insulation minimum of R19 with aluminum jacketing sealed air and watertight. (include reinsulating existing and new lines that serve this unit) o Temporary chiller owner will provide.
o Demolition o Access panels o Vibration isolation o Permits o Commissioning o Structural support, if needed o Hoisting & rigging o O&M o Include sales tax in base bid for Chiller but the Chiller will most likely be an OPO.
o Associated electrical work o Associated plumbing o Associated low voltage work o ICRA o System controls (Siemens) full status and adjustment points o Patching and painting
Cleanliness is imperative and all contractors onsite must pass a background check and be badged.
Unit Overview Chiller Model RTAF air-cooled screw chiller
Unit Nominal Tonnage 200 nominal tons
Unit efficiency High efficiency
Refrigeration Capacity 182.3 tons
Cooling Efficiency 9.949 EER (Btu/W-h)
IPLV.IP 16.44 EER (Btu/W-h)
NPLV.IP 16.24 EER (Btu/W-h)
Unit Voltage 460.V/60.Hz/3 phase
Refrigerant Type Refrigerant charge R-513A
Agency Listing UL listed
Pressure Vessel Code ASME pressure vessel code
ASHRAE 90.1 Compliance ASHRAE 90.1 all versions up to
Model Number RTAF200EU**HXUA1N21X2NXC
CCV1HBPBXXXAA1XXXX0
Evaporator Information
Evaporator Application
Standard cooling
Fluid Temperatures
Evaporator Leaving 42.00 F
Evaporator Entering 54.00 F
Fluid Properties
Fluid Type Water
Freeze Point 32.00 F
Flow Rate
Design Flow 363.0 gpm
Min Flow 202.0 gpm
Fluid Pressure Drop
Design PD 9.69 ft H2O
Min PD 3.01 ft H2O
Construction Features
Configuration 2 pass evaporator
Fouling Factor
0.000100 hr-sq ft-deg F/ Btu
Condenser Information Unit Application Standard ambient
Ambient Air Temp. 95.0 F Condenser Coil Option Coated Long Life
Alloy Aluminum Coil
Auxiliary Items Oil cooler
Fan Type Variable speed fans
Number of Fans 14
Unit Electrical
Unit
Unit Voltage 460.V/60.Hz/3 phase
Frequency 60 hertz
Compressor Starter Variable speed compressors
Total Power 219.9 kW
Compressor Power 200.4 kW
Fan Power 18.76 kW
Incoming Power Line Conn. Type Single point unit power
Power Line Conn. Type Circuit breaker-high fault
Short Circuit Current Option High amp rating
Short Circuit Current Rating 65000 A
RLA
Condenser Fan RLA (each) 2.50 A
RLA/AFD input - Compressor 1A 164.00 A
RLA/AFD input - Compressor 2A 136.00 A
MCA
Single Point Power MCA 383 A
MOP
Single Point Power MOP 500 A
Physical Information
Dimensions
Length 318 in
Width 87 in
Height 94 in
Weights
Operating Weight 11502 lb
Shipping Weight 11319 lb
Refrigerant Charge Oil Charge
Circuit 1 134.3 lb 1.96 gal
Circuit 2 129.4 lb 1.96 gal
Job Name: Halifax Health Port Orange 200 Ton Chiller
Unit Tag: CH-1
Prepared For: Quantity: 1
2025/08/05 13:59:53 Page 1 of 2
REFERENCE DATA SHEET
Unit Acoustics
A-Weighted Sound Power Sound Pressure*
100% 103 dBA 74 dBA
75% 96 dBA 68 dBA
50% 94 dBA 66 dBA
25% 91 dBA 63 dBA
Note: In Accordance with AHRI 370 *Note: at 30 feet in free field
Unit Sound Package
Standard noise
Warranty Standard Warranty
Information for LEED Projects Refrigerant (R-513A) - ckt 1 134.3 lb
Refrigerant (R-513A) - ckt 2 129.4 lb
Rated Capacity (AHRI) 188.9 tons
Rated Efficiency (AHRI) 10.13 EER (Btu/W-h)
IPLV 16.44 EER (Btu/W-h)
Refrigeration Capacity 182.3 tons
Cooling Efficiency 9.949 EER (Btu/W-h)
Compress Power 200.4 kW
Fan Motor Power 18.76 kW
ASHRAE 90.1 all versions up to 2022
This product meets the minimum efficiency requirements of ASHRAE Standard 90.1 and CANS/CSA C743 for all versions (which are based on AHRI standard rating conditions) and, therefore, also meets the LEED "Minimum Energy Performance" prerequisite in the Energy and Atmosphere section.
The LEED Green Building Rating System™, developed by the U.S. Green Building Council, provides indepenent, third-party verification that a building project meets green building and performance measures.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Trane Select Assist Version Number: 297
Data Generation Date: 8/5/2025
Job Name: Halifax Health Port Orange 200 Ton Chiller
Unit Tag: CH-1
Prepared For: Quantity: 1
2025/08/05 13:59:53 Page 2 of 2
EQUIPMENT SUBMITTAL FOR APPROVAL
PROJECT: HALIFAX PORT ORANGE CHILLER REPLACEMENT
LOCATION:
Air-Cooled Chiller
EQUIPMENT YVAA Chiller
UNIT TAGS CH-1
QUANTITY 1
SOLD TO:
CONSULTING ENGINEER:
PREPARED BY:
DATE:
Thursday, 03 July 2025
REVISION:
REFERENCE DATA SHEET
TABLE OF CONTENTS
(YVAA - Air-Cooled Chiller)
BOM Data
Performance Ratings
Unit Drawings
Wiring Diagrams
Pressure Relief Devices
Unit Specifications Text
Attachments
Receiving/Rigging
Additional Data Sheets
Lead Time Report
Statement of Compliance
Local Standards
Product Spec. Text
IOM Information
Startup Checklist
Warranties
Submittal Approval Page
BOM Data
Product Type: YVAA - Air-Cooled Chiller
Unit Tags: CH-1
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT
Rating Engine Version: REV.v9_28b.idd Version: SN25.06a Generated: 2025/07/03 at 11:56
Unit Name: CH-1 CHL.2025-07.001 Page 3 of 63
BID DATE: 07/03/2025 LAST ADDEDNUM: None
PROJECT: HALIFAX PORT ORANGE CHILLER
REPLACEMENT
NOTE(S)
TO: Interested Bidders
BILL OF MATERIAL
ITEM QTY TAGS DESCRIPTION
I 1 (1)CH-1
DIRECT EXPANSION - AIR COOLED SCREW CHILLER
EQUIPMENT DESCRIPTIONS
EQUIPMENT PROPOSAL
Items Included
● Provide Model YVAA0273DG46BH Qty: 1
● Refrigerant Type: R-513A
● Power: 460/3/60.0 Application
● Power Connection: SP Circuit Breaker w/ Lockable Handle
● Starter Type: Standard VSD
● TEAO Fan Motors
● Low Sound Fans With Variable Speed Control
● 1 1/2 Inch Double Thickness Insulation of Evaporator
● Post-Coated Microchannel Coils (Environment Guard Premium)
● Suction Service Valve
● Refrigerant Warranty: 126 Month (2-10 Year)
● Entire Unit Parts Only Warranty: 126 Month (2-10 Year) (Months are from date of shipment/Years are from date of start up, whichever expires first)
● Entire Unit Labor Only Warranty: 126 Month (2-10 Year) (Months are from date of shipment/Years are from date of start up, whichever expires first)
● Control Transformer
● Additional Compressor Enclosure Sound Kit (Level 1 Reduction)
● Discharge Pressure Readout Kit ASME Pressure Vessel Codes
● Flow Switches One Thermal Dispersion Switch
● Low Ambient Kit Additional Compressor Enclosure Sound Kit (Level 1
Reduction)
● Suction Service Valve
● End Louver (End Hail Guard) Encl Panels (Factory)
● Silent Night Sound / Load Limiting Control Option
Unit Name: CH-1 CHL.2025-07.001 Page 4 of 63
Items Included but Installed by Others
Items NOT Included
● Hauling or Rigging Equipment Into Place.
Unit Name: CH-1 CHL.2025-07.001 Page 5 of 63
Performance Ratings
Unit Name: CH-1 CHL.2025-07.001 Page 6 of 63
Full Load - Design
PIN
YVAA0273DG V46BHVBXXX SANLXXTX57 42XDSXXS16 1X1DXGA2BN XV9RNXGXXX XXXSXX0000
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90
Unit
Model No. YVAA0273
Number of Compressors 2
Compressor Type VSD Screw - Semi Hermetic
Number of Compressor Circuits 2
Capacity Control 10% - 100%
Refrigerant R-513A
Performance Data
Net Cooling Capacity [tons.R] 207.0
Total Input Power [kW] 229.2
EER [Btu/W.h] 10.84
NPLV.IP [Btu/W.h] 18.06
A-Weighted Sound Power [dB(A)] 98.0
Electrical Data
Nominal Voltage / Voltage Limits 460/3/60.0 / 414V - 508V
Compressor kW (each circuit) 105.0 / 104.1
Compressor RLA (each circuit) [A] 189.2 / 189.2
Fan QTY (each circuit) 7 / 7
Fan FLA (each circuit) [A] 44.0 / 44.0
Min. Circuit Ampacity [A] 477.0
Max. Fuse / CB Rating [A] 600.0
Unit Short Circuit Withstand [kA] 65 kA@480V
Wires Per Phase 2
Wire Range (Lug Size) #1 -500 kcmil
Displacement Power Factor 0.95
Control kVA 2.000
Performance Impacting Options
End User Application Data Center / Process Duty
Compressor Style Standard Part Load Efficiency
Condenser Coil Post-Coated Microchannel Coils (Environment Guard Premium)
Fan Low Sound Fans With Variable Speed Control
Sound Attenuation Additional Compressor Enclosure Sound Kit (Level 1 Reduction)
Weight & Dimensional Data
Shipping Weight [lbs] 17890
Operating Weight [lbs] 18718
Refrigerant Charge [lbs] 267 / 267
Length [in] 335.2
Width [in] 88.3
Height [in] 94.6
Performance Report Performance Specification
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT Unit Tag: CH-1 Qty.: 1 Model: YVAA0273
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT
Unit Name: CH-1 CHL.2025-07.001 Page 7 of 63
Heat Exchanger Performance
Evaporator Condenser (Air Cooled)
Heat Exchanger Type Hybrid Falling Film Ambient Air Temperature* [ºF] 95.0
Entering Fluid Temperature* [ºF] 56.00 Altitude* [ft] 0.00
Leaving Fluid Temperature* [ºF] 42.00 Condensing Temperature [ºF] 119.10 / 118.65
Flow Rate [USGPM] 353.9 Number of Fans (Circuit 1 / Circuit 2) 7 / 7
Fouling Factor* [h ft2 F/Btu] 0.000100 Total Air Flow [cfm] 166219
Fluid Type* Water Total Fan Power [kW] 20.13
Passes* 2
Pressure Drop [ft H2O] 6.82
Fluid Volume [USGAL] 71.1
Evaporating Temperature [ºF] 39.55
Minimum Flow Rate [USGPM] 300.0
Maximum Flow Rate [USGPM] 1170
* Designates user specified input
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org. Auxiliary components included in total KW - Oil heaters, Chiller controls. Auxiliary power is already included in the compressor and fan power
Part Load Performance (Based on Standard AHRI Unloading)
Percent Load Ambient [ºF] Capacity [tons.R] Power Input [kW] Unit Efficiency [Btu/W.h]
100.0 95.0 207.0 229.2 10.84
75.0 80.1 155.2 125.8 14.80
50.0 65.1 103.5 61.69 20.13
25.0 55.0 51.75 27.89 22.26
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT Unit Tag: CH-1 Qty.: 1 Model: YVAA0273
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT
Unit Name: CH-1 CHL.2025-07.001 Page 8 of 63
Sound Power Levels (In Accordance with AHRI 370)
Percent Load Ambient [ºF] Octave Band Center Frequency [Hz]
LWA
63 125 250 500 1000 2000 4000 8000
100.0 95.0 97.0 97.0 98.0 97.0 93.0 88.0 84.0 79.0 98.0
75.0 80.1 93.0 94.0 93.0 93.0 89.0 84.0 80.0 75.0 94.0
50.0 65.1 89.0 90.0 89.0 90.0 86.0 80.0 76.0 71.0 91.0
25.0 55.0 87.0 87.0 87.0 87.0 83.0 77.0 73.0 68.0 88.0
Note:Unit is equipped with Additional Compressor Enclosure Sound Kit (Level 1 Reduction) and Low Sound Fans With Variable Speed Control.
Measurement of sound pressure used to obtain the sound power data presented is based on AHRI-370.
Air-cooled chillers are rated in terms of sound power not sound pressure. Johnson Controls provides estimates of sound pressure, but this is not the rating metric.
For an air-cooled chiller, sound pressure calculated from sound power varies depending on how the chiller is assumed to behave, i.e. the radiation model. In other words, determining sound pressure from sound power requires making assumptions that result in different answers at a given distance from the chiller. The environment also influences sound pressure in the field installation. Sound pressure estimation radiation models pertaining to air-cooled chillers include the ‘traditional’ hemispherical model, parallelepiped model and equivalent hemispherical model.
Regarding sound power, Johnson Controls references tolerance limits based on ASHRAE guidelines. These are +/- 6dB in the 63Hz octave band, +/- 4dB in all other octave bands and +/- 3dB for the overall dBA.
Tolerance limits are based on uncertainties associated with:
1. Measurement Test Procedure
2. Repeatability
3. Production / Manufacturing Variability
Standard deviation associated with air-cooled chiller sound data is a measure of spread i.e. it indicates the range of probability of sound levels. Note that for operating conditions other than AHRI’s Standard Rating Condition, higher levels of uncertainty can be expected.
Lead times for factory performance testing depend on test laboratory availability. Please confirm with Johnson Controls Customer Service.
Performance at AHRI Conditions
Evaporator Condenser
EFT [ºF] 54.00 Ambient Temp. [ºF] 95.0
LFT [ºF] 44.00 Altitude [ft] 0.00
Flow Rate [USGPM] 495.4 Performance
Pressure Drop [ft H2O] 12.4 EER [Btu/W.h] 11.19
Fluid Type Water IPLV.IP [Btu/W.h] 18.73
Fouling Factor [h ft2 F/Btu] 0.000100 Net Cooling Capacity [tons.R] 207.0
Fluid Volume [USGAL] 71.1
Note:Unit rated at design condition capacity.
Part Load Performance (Based on AHRI 550/590 - 2023 (IP))
Percent Load Ambient [ºF] Capacity [tons.R] Power Input [kW] Unit Efficiency [Btu/W.h]
100.0 95.0 207.0 222.0 11.19
75.0 80.0 155.3 121.5 15.33
50.0 65.0 103.5 59.43 20.90
25.0 55.0 51.75 26.87 23.11
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT Unit Tag: CH-1 Qty.: 1 Model: YVAA0273
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT
Unit Name: CH-1 CHL.2025-07.001 Page 9 of 63
Notes:
Country of Origin:Mexico
Min DSD (Factory Purpose/Use Only):91.0 psig
Displacement Power Factor refers to compressor only. Unit Power Factor depends on fan option selected. Calculated value is available by request.
Use Copper Conductors only
Minimum and maximum evaporator flow information are for full load ratings with Water.
Evaporator Passes:2, Condenser Type:N, Fan Type:V
Compliant with ASHRAE 90.1 - 2010,2013,2016,2019,2022.
Compliant with IECC - 2012,2015,2018.
The product image shown is for illustrative purposes only and is not representative of selected options.
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT Unit Tag: CH-1 Qty.: 1 Model: YVAA0273
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT
Unit Name: CH-1 CHL.2025-07.001 Page 10 of 63
Unit Drawings
Unit Name: CH-1 CHL.2025-07.001 Page 11 of 63
PRODUCT DRAWING
MODEL:
NOT FOR CONSTRUCTION
Project Name:
Location:
Engineer:
Contractor:
For:
Sold To:
Cust Purch Order#:
Contract#:
UNIT
TAG:
Date:
Rev. Date:
Form No.:
Dwg. Lev.:
Dwg. Scale: NTS
YORK YVAA Air Cooled Screw Chiller
YVAA 0273
HALIFAX PORT ORANGE CHILLER REPLACEMENT
San Antonio 6
CH-1
May 26, 2020 July 03, 2025
201.28-EG1
[3.00]
[1.50]
[10.35]
[80.98]
[160.77]
[200.98]
[301.32]
[85.80]
[47.48]
[14.11]
[12.35]
[60.28]
[48.34]
[60.19]
[83.28]
[59.10]
[88.30]
[94.60]
[60.00]
[5.00]
[2.95]
[49.22]
[43.98]
[22.52]
[65.71]
[72.28]
[3.04] n15.9 MM [5/8"]
MOUNTING HOLES (TYP.)
SECTION B-B
POWER ENTRY
254 MM WIDE X 330 MM
HIGH
(10.00" WIDE X 13.00 HIGH)
SECTION A-A
CONTROL ENTRY
76 MM WIDE X 292 MM
HIGH
(3.00" WIDE X 11.50" HIGH)
B B
AA
[17.25]
[43.98]
[43.98]
[43.98]
[43.98]
[43.98]
OUT
IN
[42.92]
[15.27]
[26.69]
[44.18]
[335.19]
NOZZLE LEGEND
EVAPORATOR INLET LEFT END 2 PASS 6 DIA. (150Psig DWP) EVAPORATOR OUTLET LEFT END 2 PASS 6 DIA. (150Psig DWP)
Victaulic Grooved Nozzles (per ANSI / AWWA C-606)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE
FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR
AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION
AND EASE OF MAINTENANCE. SITE
RESTRICTIONS MAY COMPROMISE
MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE
AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT
CONTROLS WILL OPTIMIZE OPERATION
WITHOUT NUISANCE HIGH PRESSURE
SAFETY CUTOUT; HOWEVER, THE SYSTEM
DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. ACCESS TO
THE UNIT CONTROL CENTER ASSUMES
THE UNIT IS NO HIGHER THAN ON
SPRING ISOLATORS. RECOMMENDED
MINIMUM CLEARANCES: SIDE TO WALL - 6';
REAR TO WALL - 6'; CONTROL PANEL
TO WALL - 4'; TOP - NO
OBSTRUCTIONS ALLOWED; DISTANCE
BETWEEN ADJACENT UNITS - 10';
NO MORE THAN ONE ADJACENT WALL
MAY BE HIGHER THAN THE UNIT.
2. WEIGHT AND CENTER OF GRAVITY -
REFER TO AVM REPORT.
3. WATER CONNECTIONS ARE GROOVED
FOR VICTAULIC CONNECTION.
4. DIMENSIONS IN mm [INCHES].
Wiring Diagrams
FORM 201.28-EG1 (721)
JOHNSON CONTROLS 75
Power wiring
STANDARD
CONTROL
TRANSFORMER
UNIT CONTROLS
EVAPORATOR HEATER
FAN
CONTACTORS
GR
D
LINE
REACTOR
FIELD PROVIDED
UNIT POWER
SUPPLY
SEE NOTE 1
UNIT MOUNTED ELECTRONICS
INVERTER
INVERTER
TERMINAL BLOCK
(CIRCUIT BREAKER - OPT)
(NON-FUSED DISCONNECT
SWITCH - OPT)
COMPRESSOR
SYSTEM #1
COMPRESSOR
SYSTEM #2
SINGLE POINT WIRING
LD18588
JOHNSON CONTROLS 77
SYS. No. 1
ALARM
CONTACTS
SYS. No. 2
ALARM
CONTACTS
CHILLER
RUN
EVAP. PUMP
START
SIGNAL
SYS. No. 1 RUN PERM
SYS. No. 2 RUN PERM
FLOW SWITCH (-SF)
PRINT (PNT)
LEGEND
TERMINAL BLOCK FOR CUSTOMER CONNECTIONS
TERMINAL BLOCK FOR YORK CONNECTIONS
WIRING AND COMPONENTS BY YORK
OPTIONAL EQUIPMENT
WIRING AND/OR COMPONENTS BY OTHERS
RELAY
BOARD
No. 2
RELAY
BOARD
No. 1
CONTROL
BOARD
Customer control wiring
LD18590
JOHNSON CONTROLS
Control wiring
LD19417 LD19418
JOHNSON CONTROLS 79
LD19417
Control wiring (cont'd)
LD19418
PIN
YVAA0273DG V46BHVBXXX SANLXXTX57 42XDSXXS16 1X1DXGA2BN XV9RNXGXXX XXXSXX
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90
AVM Data
LOCATION X Distance [in] Y Distance [in] JCI PART NUMBER SAP NUMBER COLOUR Operating Weights [lb]
R1 10.4 1.3 029-25335-001 434002 Charcoal 632
R2 81.0 1.3 029-25335-004 434005 Charcoal 2591
R3 160.8 1.3 029-25335-002 434004 Brick Red 1638
R4 201.0 1.3 029-25335-004 434005 Charcoal 2885
R5 301.3 1.3 029-25335-002 434004 Brick Red 1638
L1 10.4 87.1 029-25335-001 434002 Charcoal 589
L2 81.0 87.1 029-25335-004 434005 Charcoal 2420
L3 160.8 87.1 029-25335-004 434005 Charcoal 1809
L4 201.0 87.1 029-25335-004 434005 Charcoal 2753
L5 301.3 87.1 029-25335-004 434005 Charcoal 1809
Weight Data
Total Weight [lb] Centre of Gravity [in]
Shipping Weight [lb] 17890 Xg [in] 175.3
Operating Weights [lb] 18718 Yg [in] 46.2
All values are de-rated by 15% apart from those which have part number. (029-25334-013 and 029-25336-014: 0% de-rated), (029-25335-004: 10% de-rated), (029-25335-001 and 029-25335-003: 25% de-rated)
YVAA Air-Cooled VSD Screw Chiller AVM Report
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT Unit Tag: CH-1 Qty.: 1 Model: YVAA0273
Project Name: HALIFAX PORT ORANGE CHILLER REPLACEMENT
Unit Name: CH-1 CHL.2025-07.001 Page 18 of 63
Pressure Relief Devices
Unit Name: CH-1 CHL.2025-07.001 Page 19 of 63
Unit Specifications Text
Unit Name: CH-1 CHL.2025-07.001 Page 20 of 63
Air Cooled Screw Liquid Chiller - YORK YVAA R-513A 50Hz & 60Hz
I. GENERAL
a. GENERAL REQUIREMENTS
i. The requirements of this Section shall conform to the general provisions of the Contract, including General and Supplementary Conditions, Conditions of the Contract, and Contract Drawings.
b. SCOPE
i. Provide Microprocessor controlled, twin-screw com¬pressor, air-cooled, liquid chillers of the scheduled capacities as shown and indicated on the Drawings, including but not limited to:
1. Chiller package
2. Charge of refrigerant and oil
3. Electrical power and control connections
4. Chilled liquid connections
5. Manufacturer start-up
c. QUALITY ASSURANCE
i. Products shall be Designed, Tested, Rated and Certified in accordance with, and Installed in compliance with applicable sections of the following Standards and Codes:
1. AHRI 550/590 – Water Chilling Packages Using the Vapor Compression Cycle
2. AHRI 370 – Sound Rating of Large Outdoor Refrigerating and Air-Conditioning Equipment
3. ANSI/ASHRAE 15 – Safety Code for Mechanical Refrigeration
4. ANSI/ASHRAE 34 – Number Designation and Safety Classification of Refrigerants
5. ASHRAE 90.1 – Energy Standard for Buildings Except Low-Rise Residential Buildings
6. ANSI/NFPA 70 – National Electrical Code (N.E.C.)
7. ASME Boiler and Pressure Vessel Code, Section VIII, Division 1
8. OSHA – Occupational Safety and Health Act
9. Manufactured in facility registered to ISO 9001
10. Conform to Intertek Testing Services for construction of chillers and provide ETL/cETL Listed Mark
ii. Factory Run Test: Chiller shall be pressure-tested, evacuated and fully charged with refrigerant and oil, and shall be factory operational run tested with water flowing through the vessel.
iii. Chiller manufacturer shall have a factory trained and supported service organization.
iv. Warranty: Manufacturer shall Warrant all equipment and material of its manufacture against defects in workmanship and material for a period of eighteen (18) months from date of shipment or twelve (12) months from date of start-up, whichever occurs first.
d. DELIVERY AND HANDLING
i. Unit shall be delivered to job site fully assembled with all interconnecting refrigerant piping and internal wiring ready for field installation and charged with refrigerant and oil by the Manufacturer.
ii. Provide protective covering over vulnerable components for unit protection during shipment. Fit nozzles and open ends with plastic enclosures.
iii. Unit shall be stored and handled per Manufacturer’s instructions.
II. PRODUCTS
Unit Name: CH-1 CHL.2025-07.001 Page 21 of 63
a. MANUFACTURERS
i. The design shown on the Drawings is based on YORK model YVAA chiller manufactured by Johnson Controls / YORK. Alternate equipment will be acceptable if the manufacturer’s equipment meets the scheduled performance and complies with these specifications. If equipment manufactured by a manufacturer other than that scheduled is utilized, then the Mechanical Contractor shall be responsible for coordinating with the General Contractor and all affected Subcontractors to insure proper provisions for installation of the furnished unit. This coordination shall include, but not be limited to, the following:
1. Structural supports for units.
2. Piping size and connection/header locations.
3. Electrical power requirements and wire/conduit and overcurrent protection sizes.
4. Chiller physical size on plant layout.
5. Site noise considerations.
ii. The Mechanical Contractor shall be responsible for all costs incurred by the General Contractor, Subcontractors, and Consultants to modify the building provisions to accept the furnished alternate equipment.
iii. The equipment manufacturer must specialize in the design and manufacture of the products specified and shall have a minimum of five
(5) years of experience in supplying variable speed driven compressor technology on the type of equipment and refrigerant specified.
b. GENERAL
i. Description: Furnish, Install, and Commission factory assembled, charged, and operational run tested air-cooled screw compressor chiller as specified herein and shown on the Drawings. Chiller shall include, but is not limited to: a complete system with multiple independent refrigerant circuits, semi hermetic twin screw compressors, shell and tube hybrid falling film type evaporator, air-cooled condenser, R-513A refrigerant, lubrication system, interconnecting wiring, safety and operating controls including capacity controller, control center, motor starting components, and special features as specified herein or required for safe, automatic operation.
ii. Operating Characteristics:
1. Provide low and high ambient temperature control options as required to ensure unit is capable of starting and operating from
0°F to 125°F (-23°C to 52°C) ambient temperature.
2. Provide capacity control system capable of reducing unit capacity to 10% of full load for 2 compressor units. Compressor shall start in unloaded condition. Hot gas bypass shall not be acceptable to meet specified minimum load.
iii. Cabinet: Unit panels, structural elements, control boxes and heavy gauge structural base shall be constructed of painted galvanized steel. All exposed sheet steel shall be coated with baked on powder paint to meet 500-hour salt spray test in accordance with the ASTM B117 standard.
iv. Shipping: Unit shall ship in one piece and shall require installer to provide only a single evaporator inlet and outlet pipe connection. If providing chiller model that ships in multiple pieces, bid shall include all the material and field labor costs for factory authorized personnel to install a trim kit to connect the pieces as well as all interconnecting piping and wiring.
c. COMPRESSORS
i. Compressors: Shall be direct drive, semi hermetic, rotary twin-screw type, including: muffler, temperature actuated ‘off-cycle’ heater, rain-tight terminal box, discharge shut-off service valve, suction shut-off service valve for each compressor and precision machined cast iron housing. Design working pressure of entire compressor, suction to discharge, shall be 350 psig (24 barg) or higher. Compressor shall be U.L. Recognized.
ii. Compressor Motors: Refrigerant suction-gas cooled accessible hermetic compressor motor, full suction gas flow through 0.006”
(0.1524 mm) maximum mesh screen, with inher-ent internal thermal overload protection and external current overload on all three phases.
iii. Balancing Requirements: All rotating parts shall be statically and dynamically balanced.
iv. Lubrication System: External oil separators with no moving parts, 450 psig (31 barg) design working pressure, and ETL listing shall be provided on the chiller. Refrigerant system differential pressure shall provide oil flow through service replaceable, 0.5 micron, full flow, cartridge type oil filter internal to compressor. Filter bypass, less restrictive media, or oil pump not acceptable.
v. Capacity Control: Compressors shall start at minimum load. Provide Microprocessor control to command compressor capacity to balance compressor capacity with cooling load.
d. REFRIGERANT CIRCUIT COMPONENTS
i. Refrigerant: R-513A. Classified as Safety Group A1 according to ASHRAE 34.
Unit Name: CH-1 CHL.2025-07.001 Page 22 of 63
ii. Equipment supplied shall comply with LEED Energy & Atmosphere Credit 4, Enhanced Refrigerant Management.
iii. Each independent refrigerant circuit shall incorporate all components necessary for the designed operation including: liquid line shut-off valve with charging port, low side pressure relief device, removable core filter-drier and sight glass with moisture indicator.
iv. Chiller manufacturer shall provide an independent circuit for each compressor to provide maximum redundancy during chiller operation. If equipment does not have independent circuits per compressor, manufacturer shall provide owner one spare compressor of each unique size.
v. Discharge lines shall be provided with manual compressor shut-off service valves.
e. HEAT EXCHANGERS
i. Evaporator:
1. Evaporator shall be shell and tube, hybrid falling film type with 2 pass arrangement to optimize efficiency and refrigerant charge. Tubes shall be high-efficiency, internally and externally enhanced type copper tubes with 0.035” (0.89 mm) minimum wall thickness at all intermediate tube supports to provide maximum tube wall thickness at the support area. Each tube shall be roller expanded into the tube sheets providing a leak proof seal, and be individually replaceable. Independent refrigerant circuits shall be provided per compressor.
2. Constructed, tested, and stamped in accordance with applicable sections of ASME pressure vessel code for minimum 235 psig
(16 barg) refrigerant side design working pressure and 150 psig (10 barg) liquid side design working pressure.
3. Water boxes shall be removable to permit tube cleaning and replacement. Water boxes shall include liquid nozzle connections suitable for ANSI/AWWA C-606 couplings, welding, or flanges.
4. Provide vent and drain fittings.
5. Provide thermostatically controlled shell heaters to assist in preventing freeze damage.
6. Connection location: Chilled liquid inlet and outlet nozzle connections are located at rear (opposite control panel) end of unit.
ii. Air-cooled Condenser:
1. Condenser coils shall be microchannel type, parallel flow aluminum alloy tubes metallurgically brazed as one piece to enhanced aluminum alloy fins. Waterside economizer coil shall be tube and fin type with 3/8 diameter tube for low pressure drop and to avoid clogging. If microchannel economizer coils are provided, contractor is responsible to provide wye-strainer properly sized to avoid economizer coil clogging. Condenser coils shall be designed for 350 psig (24 barg) or higher working pressure.
Economizer coils shall be designed for 150 psig (10.3 barg) or higher. Economizer and condenser coils shall be post-coated with an electro-deposited and baked flexible epoxy coating that is finished with a polyurethane UV resistant top-coat suitable for highly corrosive applications. Manufacturer shall provide standard five (5) year parts warranty against corrosion when used in accordance with manufacturer’s application recommendations.
2. Unit shall include End Hail Guard: Louvered steel panels on rear of unit (opposite end of control panel), painted to match unit panels.
3. Low Sound Fans with Variable Speed Drives. All fans shall be powered by VSDs. Fans shall provide vertical air discharge from extended orifices. Fans shall be composed of corrosion resistant aluminum hub and glass-fiber-reinforced polypropylene composite blades molded into a low-noise airfoil section. Fan impeller shall be dynamically balanced for vibration-free operation. Fan guards of heavy gauge, PVC (polyvinyl chloride) coated or galvanized steel.
4. Fan Motors: High efficiency, direct drive, 3-phase, insulation class “F”, current protected, Totally Enclosed Air-Over (TEAO), with double sealed, permanently-lubricated ball bearings. Open Drip Proof (ODP) fan motors will not be acceptable.
f. INSULATION
i. Material: Closed-cell, flexible, UV protected, thermal insulation complying with ASTM C 534 Type 2 (Sheet) for preformed flexible elastomeric cellular thermal insulation in sheet and tubular form.
ii. Thickness: 1-1/2” (38mm).
iii. Thermal conductivity: 0.26 (BTU/HR-Ft2-°F/in) maximum at 75°F mean temperature.
iv. Factory-applied insulation over cold surfaces of liquid chiller components including evaporator shell, water boxes, and suction line.
Liquid nozzles shall be insulated by Contractor after pipe installation.
v. Adhesive: As recommended by insulation manufacturer and applied to 100 percent of insulation contact surface including all seams and joints.
Unit Name: CH-1 CHL.2025-07.001 Page 23 of 63
g. ACOUSTICAL DATA
i. Provide acoustical sound power or sound pressure level data in decibels (dB) at the scheduled eight (8) octave band center frequencies.
A-weighted sound data alone is not acceptable.
ii. Provide all sound power or sound pressure level data at 100%, 75%, 50%, and 25% load.
iii. Supplied equipment shall not exceed scheduled sound power or sound pressure level data at any load point. The mechanical
Contractor shall be responsible for any additional costs associated with equipment deviation.
iv. Acoustical performance ratings shall be in accordance with AHRI Standard 370.
v. Provide optional control input to limit sound output of the chiller based on time of day. Shall be programmable at the chiller panel or controlled remotely via signal (4-20 mA or 0-10VDC) from BAS system. Chillers without this feature shall be provided with the necessary sound attenuation to meet the scheduled sound performance data at all load points.
h. POWER AND ELECTRICAL REQUIREMENTS
i. Power/Control Panel:
1. Factory installed and wired NEMA 3R, powder painted steel cabinets with tool lockable, hinged, latched, and gasket sealed outer doors equipped with wind struts for safer servicing. Provide main power connection(s), compressor starters and fan motor contactors, current overloads, and factory wiring.
2. Panel shall include control display access door.
ii. Single Point Power:
1. Provide single point power connection to chiller, shall be 3 phase of scheduled voltage.
2. Single Point Circuit Breaker: A unit-mounted Circuit Breaker with external lockable handle shall be provided at the point of incoming single point connection for field connection, interconnecting wiring to the compressors, and isolating the power voltage for servicing. Incoming power wiring must comply with local codes. Circuit breaker shall be sized to provide the motor branch circuit protection, short circuit protection and ground fault protection for the motor branch-circuit conductors, the motor control apparatus and the motors.
iii. Control Transformer: Power panel shall be supplied with a factory mounted and wired control transformer that will supply all unit control voltage from the main unit power supply. Transformer shall utilize scheduled line voltage on the primary side and provide 115V/1Ø on secondary.
iv. Short Circuit Withstand Rating of the chiller electrical enclosure shall be (380, 400, & 460V: 65,000 Amps). Rating shall be published in accordance with UL508.
v. Motor Starters: Motor starters shall be Variable Frequency Drive type with zero electrical inrush current. Wye-Delta, Solid State, and Across the Line type starters will not be acceptable.
vi. Motor Starters: Motor starters shall be zero electrical inrush current (Variable Frequency Drives) or reduced inrush type (Closed transition Wye-Delta or Solid State) for minimum electrical inrush. Open transition Wye-Delta and Across the Line type starters will not be acceptable.
vii. Motor Starters: Motor starters shall be Variable Frequency Drive type with zero electrical inrush current. Wye-Delta, Solid State, and
Across the Line type starters will not be acceptable.
viii. Power Factor:
1. Provide equipment with power factor correction capacitors as required to maintain a displacement power factor of 95% at all load conditions.
2. The installing contractor is responsible for additional cost to furnish and install power factor correction capacitors if they are not factory mounted and wired.
ix. All exposed power wiring shall be routed through liquid-tight, UV-stabilized, non-metallic conduit.
x. Supplied equipment shall not exceed scheduled Minimum Circuit Ampacity (MCA.) The mechanical Contractor shall be responsible for any additional costs associated with equipment deviation.
i. CONTROLS
i. General:
Unit Name: CH-1 CHL.2025-07.001 Page 24 of 63
1. Provide automatic control of chiller and waterside economizer operation including compressor start/stop and load/unload, anti-recycle timers, condenser fans, evaporator pump, evaporator heater, waterside economizer bypass value, unit alarm contacts and run signal contacts.
2. Provide dry contacts for chilled fluid pump control and evaporator shell heaters to assist in preventing freeze damage due to migration of refrigerant at ambient temperatures below 32°C (0°C).
3. Chiller shall automatically reset to normal chiller operation after power failure.
4. Unit operating software shall be stored in non-volatile memory. Field programmed set points shall be retained in lithium battery backed regulated time clock (RTC) memory for minimum 5 years.
5. Alarm contacts shall be provided to remote alert for any unit or system safety fault.
ii. Display:
1. Provide a touch screen display per chiller that is viewable in both direct sunlight and during nighttime.
2. Display shall be accessible through display access door without opening main control/electrical cabinet doors.
3. Display shall provide a minimum of unit setpoints, status, electrical data, temperature data, pressures, safety lockouts and diagnostics without the use of a coded display.
4. Descriptions in English (or available language options), numeric data in English (or Metric) units.
iii. Security Access: Controlled through YORK Chiller Access Manager which will provide users dynamic access codes so that changes in the control panel can be traced back to a specific user. Users will need to set up an account at www.yorkchilleraccessmanager.com in order to be able to generate access codes. Access levels are defined by different levels of user capability.
iv. Programmable Setpoints (within Manufacturer limits): Display language, chilled liquid cooling mode, local/remote control mode, display units mode, system lead/lag control mode, remote temperature reset, remote current limit, remote sound limit, low ambient temperature cutout enable/disable, leaving chilled liquid setpoint and range, maximum remote temperature reset.
v. Display Data: Chilled liquid leaving and entering temperatures; outside ambient air temperature; lead system; evaporator pump status;
active remote control; compressor suction, discharge, and oil pressures per refrigerant circuit; compressor discharge, motor, and oil temperatures per refrigerant circuit; saturation temperatures per refrigerant circuit; compressor speed; condenser fan status; condenser subcooling temperature; condenser drain valve percentage open; compressor capacity in percentage of Full Load Amps; compressor number of starts; run time; operating hours; evaporator heater status; history data for last ten shutdown faults; history data for last 20 normal (non-fault) shutdowns.
vi. Predictive Control Points: Unit controls shall avoid safety shutdown when operating outside design conditions by optimizing the chiller controls and cooling load output to stay online and avoid safety limits being reached. The system shall monitor the following parameters and maintain the maximum cooling output possible without shutdown of the equipment: motor current, suction pressure, discharge pressure, starter internal ambient temperature, and starter baseplate temperature.
vii. System Safeties: Shall cause individual compressor systems to perform auto-reset shut down if: high discharge pressure or temperature, low suction pressure, low motor current, high/low differential oil pressure, low discharge superheat, high motor temperature, system control voltage.
viii. Unit Safeties: Shall be automatic reset and cause compressors to shut down if: high or low ambient temperature, low leaving chilled liquid temperature, under voltage, flow switch operation. Contractor shall provide flow switch and wiring per chiller manufacturer requirements.
ix. Manufacturer shall provide any controls not listed above, necessary for automatic chiller operation. Mechanical Contractor shall provide field control wiring necessary to interface sensors to the chiller control system.
j. ACCESSORIES AND OPTIONS
i. Some accessories and options supersede standard product features. All options are factory-mounted unless otherwise noted.
ii. CONTROLS OPTIONS:
1. Building Automation System Interface: Chiller to accept BACnet MS/TP, N2 and Modbus protocol from BAS (by others). BACnet to be BACnet Testing Laboratories (BTL) listed and support BACnet Automatic Discovery to eliminate field commissioning of chiller controls.
iii. GENERAL OPTIONS:
1. Vibration Isolation (All Options Field Mounted by Contractor):
a. Provide Elastomeric Isolators.
Unit Name: CH-1 CHL.2025-07.001 Page 25 of 63
2. END USER APPLICATION:
a. Data Center/Process Duty kit is available for any YVAA unit. This application is ideal for Data Center or Process Duty applications which require the unit's full load capacity to be maintained regardless of ambient temperature. This kit requires the use of VSD Fans.
III. EXECUTION
a. INSTALLATION
i. General: Rig and Install in full accordance with Manufacturer’s requirements, Project drawings, and Contract documents.
ii. Location: Locate chiller as indicated on drawings, including cleaning and service maintenance clearance per Manufacturer instructions.
Adjust and level chiller on support structure.
iii. Components: Installing Contractor shall provide and install all auxiliary devices and accessories for fully operational chiller.
iv. Electrical: Coordinate electrical requirements and connections for all power feeds with Electrical Contractor.
v. Controls: Coordinate all control requirements and connections with Controls Contractor.
vi. Finish: Installing Contractor shall paint damaged and abraded factory finish with touch-up paint matching factory finish.
Unit Name: CH-1 CHL.2025-07.001 Page 26 of 63
Attachments
Unit Name: CH-1 CHL.2025-07.001 Page 27 of 63
Receiving/Rigging
Unit Name: CH-1 CHL.2025-07.001 Page 28 of 63
Additional Data Sheets
Unit Name: CH-1 CHL.2025-07.001 Page 29 of 63
Unit Name: CH-1 CHL.2025-07.001 Page 30 of 63
Form Number: 150.12-AD2 (720)
Supersedes: 150.12-AD2 (520)
Application Data
Issue Date: 2020-07-01
Johnson Controls - Confidential
Air-Cooled Chiller Derating due to Airflow Restrictions
Unit Name: CH-1 CHL.2025-07.001 Page 31 of 63
2 Air-Cooled Chiller Derating due to Airflow Restrictions
Johnson Controls - Confidential
Unit Name: CH-1 CHL.2025-07.001 Page 32 of 63
Contents
Introduction Recommended minimum clearances
YVAA
Case 1: Study of two YVAA chillers side by side Case 2: Study of three or more YVAA chillers side by side Case 3: Study of a single chiller surrounded by a fence Case 4: Study of a YVAA chiller surrounded by solid wall
YLAA
Case 1: Study of two YLAA chillers side by side Case 2: Study of three or more YLAA chillers side by side Case 3: Study of a single chiller surrounded by a fence Case 4: Study of a YLAA chiller surrounded by solid wall
Air-Cooled Chiller Derating due to Airflow Restrictions 3
Unit Name: CH-1 CHL.2025-07.001 Page 33 of 63
4 Air-Cooled Chiller Derating due to Airflow Restrictions
Unit Name: CH-1 CHL.2025-07.001 Page 34 of 63
Introduction This report presents different scenarios involving various air restrictions to YORK air-cooled chillers.
These scenarios outline the scope of the chiller’s derating by quantifying the decrease of capacity and the increase of power required on a case by case basis. The following are the tested cases:
• Case 1: Derating of two chillers placed side by side
• Case 2: Derating of three or more chillers in a row (chillers with other chillers on either side and chillers on the end of the row)
• Case 3: Required open area of a fence surrounding a single chiller for negligible derating
• Case 4: Derating of a single chiller surrounded by a solid wall
Johnson Controls has set recommendations for placement of chillers next to each other or next to walls while still allowing adequate airflow to the units. However, some clients may wish to forgo these recommendations at the cost of increased power consumption and loss of capacity. This guide details several common restrictions to airflow and quantifies the derating of efficiency so that the client to make an informed decision on the placement of air-cooled chiller units. Figure 1 shows the recommended minimum clearances for a YVAA chiller. Any deviation from the minimum clearances causes a decrease in performance.
Recommended minimum clearances The recommended clearances for the YVAA units are as follows:
• Side to wall: 6 ft (1.8 m)
• Rear to wall: 6 ft (1.8 m)
• Control panel end to wall: 4 ft (1.2 m)
• Top: no obstructions
• Distance between adjacent units: 10 ft (3 m)
Figure 1: Recommended minimum clearances, m (ft)
5Air-Cooled Chiller Derating due to Airflow Restrictions
Unit Name: CH-1 CHL.2025-07.001 Page 35 of 63
YVAA
Case 1: Study of two YVAA chillers side by side The recommended minimum clearance for two air-cooled chillers placed next to each other is 10 ft (3 m). See the following figure, where D is the distance between adjacent units.
Figure 2: Diagram of Case 1
Closer placement is achievable, but this causes the power consumption of the unit to increase, and lowers the unit’s capacity. See the following graphs for the respective adjustments to performance.
Figure 3: Capacity ratio derating
LD29342a
0.0
0.5
1.0
1.5
2.0
2.5
3.0
66.577.588.599.510
P er ce nt o f C ap ac ity R at io
D er at e
Distance in Feet Between Two Chillers Side by Side
20 to 26 fan un its
14 to 18 fan un its
8 to 12 fan units
Figure 4: Increase in power
LD29343a
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
66.577.588.599.510
P er ce nt of In cr ea se in
P ow er R eq ui re d
Distance in Feet Between Two Chillers Side by Side
20 to 26 fan units
14 to 18 fan units
8 to 12 fan units
Air-Cooled Chiller Derating due to Airflow Restrictions6
Unit Name: CH-1 CHL.2025-07.001 Page 36 of 63
Case 2: Study of three or more YVAA chillers side by side Similarly to Case 1, the recommended minimum clearance of this configuration is 10 ft (3 m) between each unit. See the following figure, where D is the distance between adjacent units.
Figure 5: Diagram of Case 2
All chillers experience larger derating than Case 1. See the following graphs for the respective adjustments to performance.
Figure 6: Capacity ratio derating in side chillers
LD29345a
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
66.577.588.599.510
P er ce nt o f C ap ac ity R at io
D er at e
Distance in Feet Between Chillers
20 to 26 fan un its
14 to 18 fan un its
8 to 12 fan units
Figure 7: Increase in power in side chillers
LD29346a
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
66.577.588.599.510
P er ce nt of In cr ea se in
P ow er R eq ui re d
Distance in Feet Between Chillers
20 to 26 fan units
14 to 18 fan units
8 to 12 fan units
7Air-Cooled Chiller Derating due to Airflow Restrictions
Unit Name: CH-1 CHL.2025-07.001 Page 37 of 63
Figure 8: Capacity ratio derating in center chiller
LD29347a
0.0
1.0
2.0
3.0
4.0
5.0
6.0
66.577.588.599.510
P er ce nt o f C ap ac ity R at io
D er at e
Distance in Feet Between Chillers
20 to 26 fan un its
14 to 18 fan un its
8 to 12 fan units
Figure 9: Increase in power in center chiller
LD29410a
0.0
1.0
2.0
3.0
4.0
5.0
6.0
66.577.588.599.510
P er ce nt o f I nc re as e in P ow er
R eq ui re d
Distance in Feet Between Chillers
20 to 26 fan un its
14 to 18 fan un its
8 to 12 fan units
Case 3: Study of a single chiller surrounded by a fence Note: Assuming the wall height is the same height as the installed chiller.
In some cases, a customer may want to conceal the chiller with a thin wall or fence. This can be accomplished with a wall that is the same height as the chiller without any negligible derating to capacity or increase in power required. See Figure 26, where D is the distance between the chiller and the wall. See Figure 11 for the necessary percent of openness a wall or a fence requires at varying distances from the chiller.
Note: A chiller may not be accessible for servicing if a wall surrounds the chiller at close distances. A gate or other alterations to the fence may have to be installed.
Air-Cooled Chiller Derating due to Airflow Restrictions8
Unit Name: CH-1 CHL.2025-07.001 Page 38 of 63
Figure 10: Diagram of Case 3
Figure 11: Open area of a fence required for negligible derating of chiller capacity and power
LD29411a
22.533.544.555.56 P
er ce nt o f O pe n F en ce
A re a R eq ui re d
Distance of Chiller to Fence
Case 4: Study of a YVAA chiller surrounded by solid wall An installation of a chiller inside of a pit, or with thick walls around it that are taller than the chiller, causes lower capacity and higher power consumption. See the following figure, where D is the distance between the chiller and the wall. If the wall is the same height as the chiller, the derating is negligible for a distance of 6 ft (1.8 m) or more between the chiller and the walls. See Case 3.
Figure 12: Diagram of Case 4
9Air-Cooled Chiller Derating due to Airflow Restrictions
Unit Name: CH-1 CHL.2025-07.001 Page 39 of 63
An increase of the height of the wall above the chiller’s height causes derating due to restriction of airflow. See the following graphs.
Figure 13: Example of distance (D) and height (H)
Figure 14: Percent of capacity derating with increasing wall height (6 ft from wall)
LD29412a
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
8 8.5 9 9.5 10 10.5 11 11.5 12
P er ce nt of C ap ac ity D er at e
Height of Wall
20 to 26 fan units
14 to 18 fan units
8 to 12 fan units
Figure 15: Percent of power increase with increasing wall height (6 ft from wall)
LD29417a
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8 8.5 9 9.5 10 10.5 11 11.5 12P er ce nt o f P ow er
In cr ea se
R eq ui re d
Height of Wall
20 to 26 fan un its
14 to 18 fan un its
8 to 12 fan units
Air-Cooled Chiller Derating due to Airflow Restrictions10
Unit Name: CH-1 CHL.2025-07.001 Page 40 of 63
Figure 16: Percent of capacity derating with increasing wall height (8 ft from wall)
LD29418a
0.0
0.5
1.0
1.5
2.0
2.5
3.0
8 8.5 9 9.5 10 10.5 11 11.5 12
P er ce nt o f C ap ac ity D er at e
Height of Wall
20 to 26 fan un its
14 to 18 fan un its
8 to 12 fan units
Figure 17: Percent of power increase with increasing wall height (8 ft from wall)
LD29419a
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
8 8.5 9 9.5 10 10.5 11 11.5 12P er ce nt o f P ow er
In cr ea se
R eq ui re d
Height of Wall
20 to 26 fan un its
14 to 18 fan un its
8 to 12 fan units
11Air-Cooled Chiller Derating due to Airflow Restrictions
Unit Name: CH-1 CHL.2025-07.001 Page 41 of 63
YLAA
Case 1: Study of two YLAA chillers side by side The recommended minimum clearance for two air-cooled chillers placed next to each other is 10 ft (3 m). See the following figure, where D is the distance between adjacent units.
Figure 18: Diagram of Case 1
Closer placement is achievable, but this causes the power consumption of the unit to increase, and lowers the unit’s capacity. See graphs for the respective adjustments to performance.
Figure 19: Capacity ratio derating
LD29420a
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
66.577.588.599.510
P er ce nt o f C ap ac ity R at io
D er at e
Distance in Feet Between Two Chillers Side by Side
8 to 12 fan un its
4 to 6 fan un its
Figure 20: Increase in power
LD29421a
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
66.577.588.599.510
P er ce nt o f I nc re as e in P ow er
R eq ui re d
Distance in Feet…
This is the start of the file's text. The full file is on GovTribe.