1-RFQ Reference Drawings 13MAR2026pdf.pdf
PDF 23 MB Posted
- Attached to
- Tanner Reservoir Valve Replacement
- Solicitation number
- 513800052
- Issued by
- Utah
About this file
This is a reference drawings document prepared by Advanced Engineering and Environmental Services, LLC for the Salt Lake City Department of Public Utilities regarding the Tanner Reservoir Valve Replacement project. The project involves significant improvements to water infrastructure at two locations: the existing Tanner Turnout Vault and a new Big Cottonwood Conduit (BCC) Isolation Vault along Wasatch Boulevard in Salt Lake City, Utah. The scope of work includes installation of two new 18-inch high-performance butterfly valves, a new Siemens SITRANS MAG 5100W flow meter, vault ventilation systems, electrical infrastructure, and telemetry equipment at the Tanner vault; construction of a new isolation vault with a 72-inch high-performance butterfly valve, two access manways, two air-vacuum valves, an 8-inch ductile iron drain pipe with discharge structure, and a dual body combination air valve; and replacement of approximately 100 linear feet of 72-inch prestressed concrete cylinder pipe (PCCP) with welded steel pipe (WSP). The estimated construction cost is approximately $2.5 million, with preliminary drawings indicating the parcel address as 6080 South Wasatch Boulevard.
The drawings provided are preliminary and not for construction, bearing the date of May 2, 2025. The documentation includes detailed civil, structural, and electrical plans with specifications for concrete construction (6500 PSI, 28-day compressive strength), reinforcing steel (ASTM A615, Grade 60), and seismic design criteria per ASCE 7-16 for Salt Lake City (Seismic Design Category D, Risk Category IV). The structural design incorporates lateral earth pressure assumptions of 60 pounds per cubic foot and net allowable bearing pressure of 2,000 PSF. Electrical components include a solar power package with a control panel, battery bank, solar panels, flow control panel, wireless telemetry system with radioline I/O modules, and grounding systems. The contractor is responsible for field verification of existing conditions, excavation planning sealed by a licensed Utah engineer, concrete mix design submissions, special inspections per IBC standards, and coordination with all trades to ensure a complete, operable system prior to completion.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2-RFQ Reference Specifications 13MAR2026.pdf | ||
| 3-Request For Qualifications 13MAR2026.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S A L T
L A K E
C I T Y
TANNER RESERVOIR VAULT REPLACEMENT
FOR R
EFERENCE O
NLY
ATTACHMENT A
© 2025 Microsoft Corporation © 2025 Maxar ©CNES (2025) Distribution Airbus DS
Ad va nc ed
En g i nee r i ng and
PRELIM
IN
ARY
Env ironmental Services, LLC
NOT FOR
CONSTRUCTIO
N
GENERAL NOTES
FOR R
EFERENCE O
SD
va nc ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i r onmental Services, LLC
NOT FOR
CONSTRUCTIO
NFOR R
Ad va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
NFOR R
PARCEL ADDRESS:
6080 S WASATCH BLVD
72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W
W
W
69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W
W
W
W
W
69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W
72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W
72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W
W
W
W
W
W
W
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
OHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHE
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W
GGGGGGGGGGGGGGGGGGG
OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE
WASATCH BLVD
SALT LAKE AQUEDUCT (69" RCP)
BIG COTTONWOOD CONDUIT (72" PCCP)
TO TANNER
RESERVOIR (18" DIP)
EXISTING TANNER
TURNOUT VAULT EXISTING BFV 18" VALVE
OUTSIDE OF VAULT
EXISTING BFV 18"
VALVE INSIDE VAULT
EXISTING FENCE
RIGHT OF WAY
OVERHEAD ELECTRICAL
LINES
EXISTING METER
INSIDE VAULT
CONSTRUCTION LIMITS
Ad va nc ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i r onmental Services, LLC
NOT FOR
CONSTRUCTIO
N
HTRON
Scale in Feet
FOR R
W
W
W
W
W
W
W
W
12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W
W
W
72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W
12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 WSD
SD
R/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/W
R/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/W
72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W
69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W 69 W
72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W
72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W
GGGGGGGGGG
GGGGGGGGGGG
OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE
OHE OHE OHE OHE OHE
WASATCH BLVD
SALT LAKE AQUEDUCT (69" RCP)
TO
LC
AT
E
C R
EE
K
EXISTING FENCE
BIG COTTONWOOD CONDUIT (72" PCCP)
APPROXIMATE TOLCATE
CREEK ALIGNMENT
EXISTING TOLCATE
TURNOUT VAULT
EXISTING 12" BFV
VALVE OUTSIDE VAULT
EXISTING 12" BFV
VALVE OUTSIDE VAULT
EXISTING METER
INSIDE VAULT
30" RCP CULVERT
Ad va nc ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i r onmental Services, LLC
NOT FOR
CONSTRUCTIO
N
HTRON
Scale in Feet
DEMOLITION NOTES
CUT AND REMOVE EXISTING 72" PCCP.
+/- 12' WIDE ASPHALT SAW CUT AND WORK
LIMITS. SEE DETAIL 255/C505
GENERAL NOTES
1.
WORK AREAS SHOWN ARE APPROXIMATE.
PRIOR TO DETERMINING FINAL DEMO AND
REPLACEMENT LIMITS, CONTRACTOR SHALL
FIELD VERIFY LOCATION AND ALIGNMENT OF
EXISTING 72" PCCP, PIPE MATERIAL, SIZE,
JOINT LOCATIONS, AND JOINT
CONFIGURATIONS.
FOR R
va nc ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i r onmental Services, LLC
NOT FOR
CONSTRUCTIO
N
DEMOLITION NOTES
REMOVE EXISTING FL x FL 18" BFV. SALVAGE
VALVE AND RETURN TO OWNER.
REMOVE EXISTING INLINE TURBINE METER.
REMOVE EXISTING FL x FL 18" DIP.
EXISTING VAULT, CLEAN EXISTING GROUND,
PROTECT IN PLACE.
REMOVE EXISTING LADDER RUNGS.
CONNECT NEW PIPE TO EXISTING FL x FL 18"
DIP.
N
H
R O
T
C103
EXISTING TANNER VAULT DEMOLITION
NO SCALE
N
H
R O
T
C103
EXISTING TANNER VAULT DEMOLITION
NO SCALE
FOR R
72 W 72 W 72 W 72 W 72 W 72 W 72 W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W72 W
W
W
18 W
18 W
72 W 72 W 72 W 72 W 72 W 72 W 72 W
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
OHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHE
72 W 72 W 72 W 72 W 72 W 72 W 72 W
GGGGGGGGGGGGGGG
5'-6"
5' -6
W W
Ad va nc ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i r onmental Services, LLC
NOT FOR
CONSTRUCTIO
N
HTRON
Scale in Feet
0 5
CONSTRUCTION NOTES
NOTE: REFER TO DETAILS ON SHEET C502.
REMOVE AND REPLACE BURIED 18" BFV.
CUT BACK EXISTING SLOPE TO EXPOSE
CONCRETE LID. CLEAR DEBRIS AND
VEGETATION AS NEEDED.
REMOVE TREE.
INSTALL CONCRETE PAD WITH CONCRETE
RETAINING WALL FOR SOLAR PANEL
ELECTRICAL. SEE DETAIL 2/S503.
INSTALL TIMBER AND GRAVEL ACCESS
STAIRWAY IN EXISTING SLOPE PER DETAIL
XX/S5XXX.
INSTALL CHAINLINK FENCE AND SINGLE SWING
GATE PER DETAIL XX/CXXX (APWA DETAIL 831).
FOR R
12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W
W
W
W
W
72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W
12 W 12 W
SD
SD
SD
SD
R/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/W
72 W 72 W 72 W72 W 72 W 72 W72 W 72 W 72 W
GGGGGGG
GGGGGGGGGGG
WASATCH BLVD
SDSDSDSD
LAT:1556100.1341
LON: 7404649.9732
0+00
1+00
2+00
BP
: 0
+0 0.
PI
: 0
+5 0.
PI
: 1
+1 0.
PI
: 1
+7 0.
PI
: 1
+7 4.
W W W W W W W W W
8" GV
STA = 0+04.69
SD
SD
SD
SD
8" PVC
EXISTING 30" CULVERT
EXISTING TOLCATE
TURNOUT VAULT
EG
W TOP
STA
EXISTING GRADE
4811.72 4813.87 -6.43 -6.59 1+00 2+00
1.51% 1.62%
1.95% 2.30%
30" RCP CULVERT
EXISTING TOLCATE
TURNOUT VAULTNEW ISOLATION VAULT
(MATCH EXISTING GRADE)
TRANSITION FITTING #1
NEW 72" WELDED STEEL PIPEEXISTING 72" PCCP
TRANSITION FITTING #2
EXISTING 72" PCCP
Ad va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
N
HTRON
Scale in Feet
0 10
CONSTRUCTION NOTES
1. MAINTAIN MIN. OF 5 FT OF COVER ABOVE
PIPELINE.
TRANSITION TO EXISTING PCCP. SEE
DETAIL 3/C508 AND 4/C508 FOR TRANSITION
FITTINGS #1 & 2.
INSTALL NEW 72" WSP RJ PIPE. SEE DETAIL
1/C501 AND 2/C502.
INSTALL NEW 72" DO BFV.
INSTALL NEW BCC ISOLATION VAULT. SEE
DETAIL 1/C501 AND 2/C502.
GENERAL NOTES
1. WORK AREAS SHOWN ARE APPROXIMATE.
PRIOR TO DETERMINING FINAL DEMO AND
REPLACEMENT LIMITS. CONTRACTOR SHALL
FIELD VERIFY LOCATION AND ALIGNMENT OF
EXISTING 72" PCCP, PIPE MATERIAL, SIZE,
JOINT LOCATIONS, AND JOINT
CONFIGURATIONS.
2. MAINTAIN MIN. OF 5 FT OF COVER ABOVE
PIPELINE.
FOR R
W
12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W 12 W
W
W
72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W 72 W
12 W 12 W 12 W 12 W 12 W
SD
SD
SD
R/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/W
R/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/WR/W
72 W 72 W 72 W 72 W 72 W 72 W 72 W
72 W 72 W 72 W 72 W 72 W 72 W 72 W
72 W 72 W 72 W 72 W 72 W 72 W 72 W
GGGGGGGGGGGGGGGGGG
OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE
WASATCH BLVD
SDSDSD
D
45 DEG BEND
45 DEG BEND
8" PVC
8" STEEL BLOWOFF & DISSIPATION
STRUCTURE
STA 1+59.51 - 0.03' (R)
RIM: 4798.46
0+
1+
1+7 1.06
8" STEEL
8" STEEL x PVC ADAPTOR
STA = 0+07.98
W W W W W W
BP: 0+00.00
EP: 1+71.06
PI: 0+69.60
PI: 0+75.34
PI: 1+59.51
PI: 0+08.48
8" GV
STA = 0+04.69
8" GV
STA = 1+51.13
8" STEEL x PVC ADAPTOR
STA = 1+46.73
SD
SD
SD
8" PVC
90 DEG BEND
EXISTING 30" CULVERT
EXISTING TOLCATE
TURNOUT VAULT
EG
TOP
STA
4811.64 4810.58
0+00 1+00 -13.18 -15.13
8" PVC
8" STEEL
12" WATER
10" GAS
8" S
TE
EL
x P
VC
A
D
AP
TO
R
ST
A
0+
.9
EXISTING GRADE
-1.65% 8" STEEL
8" S
TE
EL
x P
VC
A
D
AP
TO
R
ST
A
1+
.7
8"
G V
ST
A
1+
.1
BL
O
W O
FF
D
IS
SI
PA
TI
O
N
ST
R U
C
TU
R E
ST
A
1+
.5
8" G
V
ST
A
0+
.6
NEW ISOLATION VAULT
Ad va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
N
HTRON
Scale in Feet
0 10
CONSTRUCTION NOTES
INSTALL 8" VAULT DRAIN.SEE DETAIL 1/C501
AND 2/C501.
INSTALL BLOWOFF AND DISSIPATION
STRUCTURE. SEE DETAIL 4/C501.
CONNECT DRAIN TO VAULT AS SHOWN IN
DETAIL 1/C501, 2/C501, AND 3/C501.
FOR R
C501
C501
FLOW
FLOW
22'-3" 26'-3"
6' -0
4'-0"
0' -8
.4
3' -0
'-0
'-0
3'-4"
2'-0"
0'-8"1'-4"
1' -4
8" WSP
C/L EL 4794'
CONCRETE BLOCK, PROVIDE 2 SQ FT
HORIZONTAL AND VERTICAL BEARING AREA
8"X8" STL TEE WITH DISH HEAD
STRUCTURAL FILL,
SEE SECTION 32 05 16
NON-WOVEN GEOTEXTILE FABRIC
18" THICK LAYER RIPRAP D50 = 12"
NON-WOVEN GEOTEXTILE FABRIC
RIPRAP D50 = 12"
12'
1'
2'
EL 4795.00
EL 4796.50±
1 1/2" SST GRATING
#4 MESH RODENT SCREEN
8" STEEL TEE WITH BLIND FLANGE
8.5'
5'
2' MIN
7'
PAINT IN ACCORDANCE WITH SECTION 09 96 00
RESTORE TOP OF BANK TO
PRECONSTRUCTION GRADE
EL 4796.00 ±
2'
8" STL PUMPING WELL
CONTINUES TO VAULT
DRAIN CONNECTION
CONCRETE COLLAR
6" AROUND PIPE
5'-0"
1'-0" TYP RIPRAP BANK
6' -0
PLAN VIEW
PROFILE VIEW
FLOW FLOW
5' -0
2' -0
1' -6
1' -6
4'
-0
'-6
0' -8
0'-6"
Ad va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
N
TOLCATE 72" BUTTERFLY VALVE VAULT PROFILE VIEW2
C501
CONSTRUCTION NOTES
INSTALL CAST-IN-PLACE CONCRETE VAULT.
FURNISH AND INSTALL 72" DOUBLE OFFSET
BUTTERFLY VALVE.
FURNISH AND INSTALL 30" HINGED MANWAY.
INSTALL GALVANIZED STEEL FIXED LADDER
W/ RUNG EXTENSION ATTACHED TO LID. SEE
DETAIL 4/C506 AND 2/C507.
INSTALL 8" STEEL VAULT DRAIN. SEE DETAIL
3/C501 FOR SECTION VIEW AND 3/C506 FOR
FLOOR PENETRATION.
WALL/FLOOR PENETRATION SEE DETAIL
3/C506.
INSTALL TRANSITION FITTING SEE DETAILS
3/C508, 4/C508, AND 5/C508.
INSTALL 6" COMBINATION AIR-VAC VALVE. SEE
DETAIL 1/C506.
CLSM FILL TO NATIVE SOIL.
6" MIN. OF TYPE A3 VAULT BASE.
(2) CONTINUOUS ROWS OF 1" RX-101
WATERSTOP (TYPICAL AT ALL VAULT JOINTS).
INSTALL PLASTIC MUSHROOM VENT. SEE
DETAIL 1/C507.
INSTALL 8" STEEL x PVC ADAPATOR.
INSTALL 8" GATE VALVE.
INSTALL REMOVABLE CONCRETE ROOF
PANEL. SEE DETAIL 2/S502.
INSTALL CONCRETE PIPE SUPPORT. SEE
DETAIL 1/C509.
INSTALL VAULT SUMP. SEE DETAIL 3/S502.
TOLCATE VAULT BLOWOFF AND DISSIPATION STRUCTURE DETAIL4
C501 SCALE: NONE
TOLCATE 72" BUTTERFLY VALVE VAULT PLAN VIEW1
C501
8 8
2.5' 2.5' 5'0'
2.5' 2.5' 5'0'
TOLCATE VAULT DRAIN SECTION VIEW3
C501
2.5' 2.5' 5'0'
6 13
STRUCTURAL FILL TO NATIVE SOIL
FOR R
1' -0
8'-0"
10'-0"
8' -0
'-0
FLOW FLOW
SET VALVE BOX 14"
BELOW PAVED
SURFACE DROP LID MARKED
"WATER"
CONCRETE COLLAR
MIN. 24" TOP
SECTION
4"
BUTTERFLY
VALVE
DUCTILE IRON
PIPE
BEDDING CONCRETE
BLOCK
JOINT
RESTRAINER
VALVE BOX
ADAPTOR
18"
VALVE
BOX
3" CLEAR
COVER
#4 REBAR
4" CONCRETE
COLLAR
3" C
LE
AR
C O
VE
R
ELEVATION
PLAN
#4 REBAR
8'-0"
10'-0"
5' -0
7' -0
0' -8
.4
C502
FLOWFLOW
Ad va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
N
TANNER 18" BUTTERFLY VALVE VAULT PROFILE VIEW2
C502
CONSTRUCTION NOTES
EXISTING VAULT. PROTECT IN PLACE.
REMOVE EXISTING 18" BUTTERFLY VAVLE
AND REPLACE WITH 18' FL DOUBLE OFFSET
BUTTERFLY VALVE W. MANUAL ACTUATOR
& STEM EXTENDED TO OPERATE FROM
SURFACE.
CONNECT NEW BURIED VALVE TO EXISTING
PIPE. USE RESTRAINED FLANGE ADAPTER,
ROMAC OR EQUIVALENT.
REMOVE AND REPLACE CLASS 52 18"
DUCTILE IRON PIPE. CONTRACTOR TO
VERIFY SIZE OF SPOOL NEEDED.
REMOVE AND REPLACE EXISTING METER
WITH SIEMENS SITRANS MAG 5100W
FLOWMETER MODEL 7ME6520.
TIE-IN LOCATION. TIE INTO EXISTING
FLANGED PIPE.
INSTALL MUSHROOM HIGH VENT. SEE
DETAIL 1/C507.
INSTALL MUSHROOM LOW VENT. SEE
DETAIL 1/C507.
REPLACE PRECAST CONCRETE ROOF WITH
CAST IRON MANHOLE RING AND COVER.
INSTALL GALVANIZED STEEL FIXED LADDER
W/ RUNG EXTENSION ATTACHED TO LID.
SEE DETAIL 4/C506 AND 2/C507.
BURIED BUTTERFLY VALVE COLLAR AND SETTING3
C502 SCALE: NONE
1.25' 1.25' 2.5'0'
TANNER 18" BUTTERFLY VALVE VAULT PLAN VIEW1
C502
1.25' 1.25' 2.5'0'
FOR R
n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
NFOR R
n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
NFOR R
NOT USED
va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
NFOR R
ISOLATI0N VALVE
VALVE SIZES 3" AND SMALLER SHALL HAVE FULL
SIZE NPT INLETS AND OUTLETS EQUAL TO THE
NOMINAL VALVE SIZE. VALVE SIZES 4" AND
LARGER SHALL HAVE BOLTED FLANGE INLETS
AND PLAIN OUTLETS AND PROTECTIVE HOODS TO
PREVENT DEBRIS FROM ENTERING THE VALVE
DUAL BODY COMBINATION AIR VALVE (SIZED
PIPE SIZE AND FLOW RATES)
TAP PIPING SYSTEM AT HIGH POINT FOR AIR
VALVE INLET PIPE (VERIFY SIZE)
LARGE WATER LINE (VERIFY
SIZE AND FLOW RATES)
PIPE PENETRATION NOTES:
RECOMMENDED BY MECHANICAL
SLEEVE DIAMETER AS
MIN. SCH 20 PIPE SLEEVE
SEAL MANUFACTURER
EXTERIOR SURFACE
SEE NOTE #4
SEEP RING (CENTERED)
SEE NOTE #3EXPOSED FACE
INTERIOR OR
PENETRATING FLOORS
EXTEND SLEEVE WHEN
FLOOR PENETRATIONS
FOR UPPER LEVEL
ROD AND MASTIC SEALANT
FILL WITH BACKER
MODULAR SEAL
4''
1. ALL STEEL SLEEVES TO BE HOT DIP GALVANIZED AFTER FABRICATION.
2. INSULATION SHALL NOT EXTEND THROUGH SLEEVES, UNLESS OTHER-WISE SPECIFIED
3. SEEP RING TO HAVE OUTSIDE DIA. 4" GREATER THAN SLEEVE DIA.
4. SEAL WITH MASTIC SEALANT WHERE WALL IS EXPOSED TO LIQUID OR EARTH
5. ALL PIPE PENETRATIONS ARE SHOWN FOR CAST-IN-PLACE.
1. DIMENSION "A" CORRESPONDS TO THE COMPLETED JOINT OVERLAP AFTER WELDING
DIMENSION "A" SHALL BE THE GREATER OF 3" OR 5t, MINIMUM FOR STANDARD JOINTS. FOR
SPECIAL TEMPERATURE CONTROL JOINTS, THE DIMENSION "A" JOINT OVERLAP SHALL BE
INCREASED BY 3 INCHES AS FURTHER DISCUSSED IN NOTE 3.
2. FOR STANDARD JOINTS THE MINIMUM DIMENSION "B" SHALL BE AS REQUIRED TO PROVIDE
THE MINIMUM OVERLAP DIMENSION "A" AND MAINTAIN THE INDICATED HOLDBACK FOR THE
WELD.
3. FOR SPECIAL TEMPERATURE CONTROL JOINTS, THE MINIMUM DIMENSION "B" SHALL BE
INCREASED BY AT LEAST 3 INCHES. AT THE TIME OF INSTALLATION AND PRIOR TO WELDING, THE SPIGOT SHALL BE INSERTED INTO THE LENGTHENED BELL TO PROVIDE "A" PLUS 3
INCHES MINIMUM JOINT OVERLAP. SEE SPECIFICATIONS SECTION 33 11 13 FOR SPECIAL
TEMPERATURE CONTROL JOINT WELDING REQUIREMENTS.
4. FILLET WELDS FOR BELL AND SPIGOT LAP JOINTS SHOWN FILLET WELDS ON OTHER JOINTS
SIMILAR.
5. FOR ALL PIPE 30" DIAMETER OR LARGER, CONTRACTOR SHALL CONDUCT AN AIR/SOAP
SOLUTION LEAK TEST AT 40 PSI AIR PRESSURE IN ADDITION TO DYE PENETRANT OR
MAGNETIC PARTICLE TESTING PERFORMED BY THE ENGINEER. IF LEAKS ARE DETECTED,
REPAIR AND RETEST THE WELDS UNTIL THERE ARE NOT DEFECTS. PLUG HOLES WITH
THREADED OR WELDED PLUG AT COMPLETION OF TEST AND COAT AS SHOWN. TAP HOLES
MAY BE ON INSIDE OR OUTSIDE OF JOINT.
6. THE JOINTS SHALL BE FABRICATED AND INSTALLED TO BE WITHIN THE TOLERANCES
INDICATED. THE TOLERANCE REQUIREMENTS SHALL APPLY TO BOTH WELDS AND TO BOTH
STRAIGHT AND DEFLECTED JOINTS.
7. FOR ALL PIPE DIAMETER SMALLER THAN 30", SINGLE LAP JOINTS SHALL BE INSIDE OR
OUTSIDE AT C0NTRACTORS OPTI0N. IF WELDED FROM THE INSIDE, AN ADDITIONAL HEAT
SHRINK SLEEVE WILL BE REQUIRED. REFER TO SECTION 33 11 13 FOR SPECIAL
REQUIREMENTS.
8. LININGS AND COATINGS ARE NOT SHOWN FOR CLARITY.
NOTES
SEE NOTE 7
LINING AND COATING NOT SHOWN FOR CLARITY
B
NOTE 2 AND 3
1"A
NOTE 1 MIN
SEE NOTE 7
1t
1"t t 16
1"
JOINT COATING SEE NOTE 8
(HEAT SHRINK SLEEVE 3" MIN
OVERLAP PIPE COATING EACH
SIDE) SEE NOTE 3
POINT OF TANGENCY
OF BELL RADIUS (LAP
JOINT)
3/4" NPT TAP FOR
AIR/SOAP TEST
SEE NOTE 5
FILL BOLLARD WITH CONCRETE
ROUND TOP OF CONCRETE
REFLECTIVE STRIP
6" SCH, 40 GALV, STEEL PIPE
PROVIDE YELLOW HDPE BOLLARD SLEEVE
SLOPE TO DRAIN
CORED OR DRILLED HOLE
FILLED WITH CONCRETE(4) 1/2" DIA. X 4"
HEADED ANCHORS
@ 90 DEC (2 PLACES)
6" 5'
-0
3' -6
6" 2'
-6
1'-8" ø
Ad va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
N
C506
DUAL BODY COMBINATION AIR VALVE DETAIL
SCALE: NONE
C506
CONCRETE BOLLARD DETAIL
SCALE: NONE
C506
VAULT DRAIN FLOOR PENETRATION DETAIL
SCALE: NONE
C506
LAP JOINT WELD
SCALE: NONE
FOR R
MUSHROOM STYLE
VENT CAP WITH NO. 4
SST WIRE MESH
MUSHROOM STYLE
VENT CAP WITH NO
4 SST WIRE MESH
FLANGED
PLATE
ANCHOR
BOLTS
ROOF LINE
CORE HOLE FOR
VENT PIPEROOF LINE
CORE HOLE FOR
VENT PIPE
ANCHOR
BOLTS
FLANGED
PLATE
6" GALV. STL PIPE
2'- 6"
M
IN
1'- 0"
A
BO
VE
F
LO
O
R
LOW VENT HIGH VENT
6" GALV. STL PIPE
6" SCH 90 PVC PIPE
6" SCH 80 PVC PIPE
PRESSURE GAUGE
1/2" STAINLESS STEEL BALL VALVE
TAP PIPE FOR 1/2" NPT
STAINLESS NIPPLE
72" PIPE
8" 8"8"
3" 2"
3"
2'-0"
8"
1/ 2"
1' -0
1'
-0
1' -0
1'-4"
1/2" GALVANIZED STEEL BASE PLATE
3" x 1/2" GALVANIZED STEEL RAIL
GALVANIZED STEEL
4-ROW TRACTION TREAD
LADDER RUNG
1/2" x 5-1/2" HILTI
KWIK BOLT TZ ANCHOR
BOLT (TYPICAL)
1'-4"
7" M
IN
GALVANIZED STEEL HATCH FRAME
3'-0"
CLEAR OPENING
3'-0" MINIMUM
CLEAR OPENING
1/
2"
2"
3" x 1/2" GALVANIZED STEEL RAIL
GALVANIZED STEEL
4-ROW TRACTION TREAD
LADDER RUNG
5/8" STAINLESS STEEL ADHESIVE
ANCHOR BOLT, 5" EMBEDMENT
1'-4" 7"
MIN
FLOOR, GRATING, OR FLOOR GROUT
6"
2-1/2" x 1/4" GALVANIZED STEEL BRACKETS
SPACE @ 4'-0" ON CENTER MAX
EQ
U
AL
S
PA
C
ES
F
U
LL
L
EN
G
TH
" M
AX
EQ
U
AL
S
PA
C
ES
F
U
LL
L
EN
G
TH
" M
AX
EDGE OF CONCRETE DECK
(VARIES)
3'-0"
CLEAR OPENING
1/
2"
3-RUNG HANDHOLD
FIXED LADDER
3' -0
STRUCTURE DECK
2 1/2"
1/
2"
3-RUNG HANDHOLD
SEE NOTE 1.
36" WIDE x MINIMUM 1/16" THICK
GALVANIZED STEEL DEFLECTOR
PLATE BOLTED TO TOP SLAB IF
SPACE BETWEEN CENTERLINE
OF LADDER AND OPENING IS
LESS THAN 2'-6"
60°
NOTES:
1. 3-RUNG HANDHOLD IS NOT NEEDED IF A TELESCOPING LADDER-UP SAFETY POST
HANDHOLD WILL BE INSTALLED. REFER TO VAULT / STRUCTURAL DETAILS.
SEE NOTE 1
Ad va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
N
C507
MUSHROOM AIR VENT DETAIL
SCALE: NONE
C507
C507
PRESSURE GAUGE DETAIL
SCALE: NONE
LADDER DETAIL
SCALE: NONE
FOR R
100% U.T. OF
10% OF
PRIOR TO BACKFILLING AND LINING PIPE,
INSTALL "t" THK CURVED BUTT STRAP COUPON
PASSHOLES
t
TYP
t
WSP CYL ID LINING &
COATING NOT
SHOWN FOR
CLARITY
2" CORPORATION STOP
3"x2" BRASS
REDUCING FLANGE
3"
MIN
TYPE A
100% UT OF 10%
OF OUTLETS
COAT W/ JOINT PROTECTION
MATERIALS AS SPECIFIED
FILL PASSHOLE RECESS W/
SPECIFIED LINING AFTER JOINT
COMPLETION
t
SEE
NOTE 3
UT
6" MAX FLAT THREADED OUTLET. SUPPLY THREADED
STEEL PLUG TO CLOSE AFTER USE. SEAL WELD IN
PLACE, PATCH LINING & COATING AS SPECIFIED
NOTES:
1. LINE AND COAT TEST HEAD AND PLAIN END
WITH 3 MILS MIN RUST INHIBITING PRIMER.
2. MINIMUM 8" HOLDBACK REQUIRED AFTER
TEST HEAD CUT OFF.
3.
LINING & COATING
NOT SHOWN FOR
CLARITY
TYPE B
INSIDE OF WSP WALL
OR BUTT STRAP
FILL RECESS W/ SPECIFIED
LINING AFTER JOINT COMPLETE
4.
WALL THICKNESS "t" SHALL BE THE SAME AS
THE ADJOINING PIPE.
EXCEPT FOR WELDING ON OUTLETS, ALL WELDS
ON FABRICATED TEST HEADS SHALL BE FULL
PENETRATION BUTT WELDS. ALL BUTT WELDS
SHALL BE 100% RADIOGRAPHY TESTED.
CONTRACTOR TO SELECT
VALVE & PIPING SIZE
NEEDED FOR DRAINING AND
FILLING PIPE, 12" MAX
BLIND FLANGE
ISOLATION GATE OR
PLUG VALVE
STEEL TEST HEAD
t t TYP
6" MAX
UT
COAT WITH HEAT SHRINK
SLEEVE AFTER WELDING,
SEE DETAIL 7 / C501
12"
LINING AND COATING
AS SPECIFIED
HOLD-
BACK
(NOTE 2)
FABRICATED TEST
HEAD, SEE NOTE 4
TWO SINGLE LAP WELDS
SEE DETAIL 1 / C501 , TYP
3 " FLG STEEL OUTLET t t
PI
PE
I.
D
C
YL
IN
D
ER
I.
D
5. ALL PIPING, VALVES AND FITTINGS SHALL BE
RATED AT PRESSURE CLASS OF MAIN PIPE.
TRANSITION #1 BELL x FL DETAIL 4/C508
TRANSITION #2 SPIGOT x FL DETAIL 5/C508
X"-XX"
PCCP TO STEEL BELL x FL TRANSITION #1 PCCP TO STEEL SPIGOT x FL TRANSITION #2
BUTT STRAP (SEE DETAIL XX/C5XX)
32 LB ANODE 32 LB ANODE
32 LB ANODE 32 LB ANODE
FL INSULATED KIT FL INSULATED KIT
72" STEEL PIPE
(W/ POLY WRAP OR EPOXY PAINT)
NOTE:
1. VAULT NOT SHOWN FOR CLARITY.
2. ALL STEEL PIPE TO BE LAP OR WELDED.
GROUND
POTENTIAL TEST STATION
(SEE DETAIL XX/C5XX)
WIRE ATTACHMENT
(SEE DETAIL XX/C5XX)
1.66 FT
2.05 FT
Ad va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
N
C508
TEST HEAD DETAIL
SCALE: NONE
C508
WSP PASSHOLE DETAIL
SCALE: NONE
C508
TRANSITION FITTINGS / CATHODIC PROTECTION DETAIL
SCALE: NONE
C508
PCCP TO STEEL (SPIGOT x FL) TRANSITION DETAIL
SCALE: NONE
C508
PCCP TO STEEL (BELL x FL) TRANSITION DETAIL
SCALE: NONE
FOR R
DRILL 3/4"Ø HOLE, FILL WITH EPOXY GROUT,
CONCRETE FLOOR
CONCRETE PIPE SUPPORT
3/4" CHAMFER ALL EDGES (TYPICAL)
CONCRETE PIPE SUPPORT
VERIFY PIPE SIZE
AND INSERT #5 DOWEL (TYPICAL)
3" (TYPICAL)
8" (V
ER
IF
Y)
6"
120°
Ad va n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
N
C509
CONCRETE PIPE SUPPORT DETAIL
SCALE: NONE
FOR R
PR
ELI
M
IN
AR
Y
Ad va n c e d
En g i nee r i ng and
Env i ronmentalServices,LLC
N O
T F O
R
C O N
STR
U C
TIO
N
SAL
T L
A K E
C I T Y
S C A L E
B A R
IS
O N E
IN
C H
O N
R
IG
IN
A L
D R A W
IN
G
D E S
IG
N E D
B Y
D R A W N
B Y
C H E C K E D
B Y
A P P R O V E D
B Y
D A T E
E W O
N O
A C C O U N T
N O
DRAWING NO.
SHEET OF
S A L T
L A K E
C
IT
Y
D E P A R T M E N T
O F
P U B L
IC
U T
IL
IT
IE
S
0-
V E
R I F
Y
S
C A
L E
W S
\S a lt L a k e C it y D e p t o f P u b lic
U ti lit ie s \1
-2
-0
\C
A D
D w g s \0
-S tr u c tu ra l\R e v it \S
L C
D P
U B
C C
T A
N N
E R
T U
R N
O U
T S
R
.r v t
/3
/2
:5 :5
P
M
K D
E
P A
J
K D
E
S001
G E N E R A L
N O T E S
M A
Y
P A
J
20 30
S L C D P U
B C C
T A N N E R
T U R N O U T
IM
P R O V E M E N T S
2. SEE GENERAL NOTES & SPECS FOR ADDITIONAL REQUIREMENTS
1. ALL SPECIAL INSPECTION IN ACCORDANCE WITH CURRENT IBC
PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE
SUBGRADE AND VERIFY THAT SITE HAS BEEN
PREPARED PROPERLY
X
VERIFY USE OF PROPER MATERIALS, DENSITIES AND
LIFT THICKNESS DURING PLACEMENT AND COMPACTION
OF COMPACTED FILL
X
PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS
X
VERIFY EXCAVATIONS ARE EXTENDED TO PROPER
DEPTH AND HAVE REACHED PROPER MATERIAL
X
VERIFY MATERIAL BELOW SHALLOW FOUNDATIONS ARE
ADEQUATE TO ACHIEVE DESIGN BEARING CAPACITY
X
VERIFICATION & INSPECTION CONTINUOUS PERIODIC
REQUIRED SPECIAL INSPECTION OF SOILS
1, 2
1. SEE GENERAL NOTES & SPECS FOR ADDITIONAL REQUIREMENTS
REINFORCING BARS ASTM A615, GRADE 60,
DEFORMED
REINFORCING STEEL
CONCRETE 6500 PSI
28 DAY COMPRESSIVE STRENGTH f'c
CONCRETE
MATERIAL STRENGTHS
2. SEE GENERAL NOTES & SPECS FOR ADDITIONAL REQUIREMENTS
1. ALL SPECIAL INSPECTION IN ACCORDANCE WITH CURRENT IBC AND ACI STANDARDS
INSPECTION OF FORMWORK FOR SHAPE, LOCATION
AND DIMENSIONS PRIOR TO CONCRETE POUR
X
VERIFICATION IN-SITU CONCRETE STRENGTH, PRIOR TO
STRESSING OF TENDONS IN POST-TENSIONED
CONCRETE AND PRIOR TO REMOVAL OF SHORES AND
FORMS FROM BEAMS AND STRUCTURAL SLABS
X
INSPECT ERECTION OF PRECAST CONCRETE MEMBERS X
b. GROUTING OF BONDED PRESTRESSING
TENDONS
X
a. APPLICATION OF PRESTRESSING FORCED; AND X
INSPECTION OF PRESTRESSED CONCRETE FOR:
VERIFY MAINTENANCE OF SPECIFIED CURING
TEMPERATURE AND TECHNIQUES
X
INSPECTION OF CONCRETE AND SHOTCRETE
PLACEMENT FOR PROPER APPLICATION TECHNIQUES
X
PRIOR TO CONCRETE PLACEMENT, FABRICATE
SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP
AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE
X
VERIFYING USE OF REQUIRED DESIGN MIX X
b. MECHANICAL ANCHORS AND ADHESIVE
ANCHORS NOT DEFINED ABOVE
X
a. ADHESIVE ANCHORS INSTALLED IN
HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION
LOADS
X
INSPECTION OF ANCHORS POST-INSTALLED IN
HARDENED CONCRETE MEMBERS
X
INSPECTION OF ANCHORS CAST INTO CONCRETE X
c. INSPECT ALL OTHER WELDS X
b. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM
5/16"; AND
X
a. VERIFY WELDABILITY OF REINFORCING BARS
OTHER THAN ASTM A 706
X
REINFORCING BAR WELDING:
INSPECTION OF REINFORCEMENT, INCLUDING
PRESTRESSING TENDONS, AND VERIFY PLACEMENT
X
VERIFICATION & INSPECTION CONTINUOUS PERIODIC
REQUIRED SPECIAL INSPECTION OF CONCRETE CONSTRUCTION
1, 2
1. HORIZONTAL BARS WITH MORE THAN 12" DEPTH OF CONCRETE CAST BELOW THEM
#9 7'-7" 5'-10" 5'-10" 4'-6"
#8 6'-8" 5'-2" 5'-2" 3'-11"
#7 5'-10" 4'-6" 4'-6" 3'-6"
#6 4'-0" 3'-1" 3'-1" 2'-5"
#5 3'-4" 2'-7" 2'-7" 2'-0"
#4 2'-8" 2'-1" 2'-1" 1'-7"
#3 2'-0" 1'-7" 1'-7" 1'-3"
BAR SIZE TOP BARS
OTHER BARS TOP BARS
OTHER BARS
MINIMUM LAP SPLICE LENGTH ("Ls") MINIMUM DEVELOPMENT LENGTH ("Ld")
REINFORCING STEEL LAP SPLICE AND DEVELOPMENT LENGTH
SCHEDULE
SLAB ON GRADE / SLAB ON METAL DECK CENTERED
PRIMARY REINFORCEMENT, TIES, STIRRUPS, SPIRALS 1 1/2
BEAMS, COLUMNS:
No. 11 BAR AND SMALLER 3/4
No. 14 AND No. 18 BARS 1 1/2
SLABS, WALLS, JOISTS:
NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
No. 5 BAR AND SMALLER 1 1/2
No. 6 THROUGH No. 18 BARS 2
EXPOSED TO EARTH OR WEATHER:
CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3
UNLESS NOTED OTHERWISE ON DRAWINGS COVER (in)
ACI 318 - STRUCTURAL CONCRETE
CAST IN PLACE CONCRETE (NON-PRESTRESSED) COVER
LATERAL EARTH PRESSURE (AT REST) (ASSUMED) 60 PCF
NET ALLOWABLE BEARING PRESSURE (ASSUMED) 2000 PSF
FOUNDATIONS
Sd1 N/A
SPECTRAL DESIGN RESPONSE COEFFICIENT Sds 1.068g
S1 0.496g
SPECTRAL RESPONSE ACCELERATION Ss 1.335g
SITE CLASS E
IMPORTANCE FACTOR Ie 1.00
SEISMIC FORCE RESISTING SYSTEM N/A
SEISMIC DESIGN CATEGORY D
SEISMIC DESIGN ASCE 7-16
DESIGN MINIMUM SNOW LOAD 55 PSF
IMPORTANCE FACTOR Is 1.20
MAIN ROOF GROUND SNOW LOAD Pg 45 PSF
SNOW LOAD ASCE 7-16, CHAP 7
RAIN INTENSITY (24-HR) 1.87 INCH/HR
RAIN INTENSITY (15-MIN) 4.49 INCH/HR
RAIN LOADS IBC CHAP 16, SECTION 1603.1.9
FLOOR 200 PSF
ROOF HS20 32 K AXLE
WALL PIPE THRUST LOADING (EACH) __ KIP
LIVE LOADS
ROOF DEAD 15 PSF
DEAD LOADS (SUPERIMPOSED)
OCCUPANCY BUILDING RISK CATEGORY IV
(IN ADDITION TO THOSE INDICATED ON PLANS & DETAILS)
DESIGN CRITERIA AND LOADS
CAST-IN-PLACE CONCRETE - SPEC 03 30 00
1. A CONCRETE MIX DESIGN FOR EACH UNIQUE COMBINATION OF STRENGTH,
APPLICATION, COARSE AGGREGATE GRADATION, AND WATER CEMENT RATIO
SPECIFIED SHALL BE PREPARED BY THE SUPPLIER OR AN INDEPENDENT TESTING
LABORATORY AND BE SUBMITTED FOR REVIEW PRIOR TO CASTING ANY CONCRETE.
2. UNLESS NOTED OTHERWISE, MAXIMUM AGGREGATE SIZE SHALL BE 1 INCH,
MAXIMUM WATER: CEMENT RATIO OF 0.40, AIR CONTENT NOT TO EXCEED 3%
ENTRAPPED AT TROWEL FINISHED SLABS, AND AT APPLICATIONS EXPOSED TO
FREEZE/THAW CYCLES PROVIDE 6% AIR ENTRAINMENT.
3. ALL FORMWORK SHALL BE DESIGNED, ERECTED, SUPPORTED, BRACED AND
MAINTAINED ACCORDING TO ACI 347, “RECOMMENDED STANDARD PRACTICE FOR
CONCRETE FORMWORK”.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN,
CONSTRUCTION, AND SAFETY OF ALL FORMWORK.
5. ALL EXPOSED EDGES OF CONCRETE SHALL BE CHAMFERED 3/4" WHERE NOT
SPECIFICALLY SHOWN ON THE ARCHITECTURAL OR STRUCTURAL DRAWINGS.
6. UNLESS OTHERWISE NOTED, TOLERANCES FOR CONCRETE FORMWORK SHALL
CONFORM TO ACI STANDARD 117, “STANDARD TOLERANCES FOR CONCRETE
CONSTRUCTION AND MATERIALS”. TOLERANCES IN PLACING REINFORCEMENT
SHALL BE:
A. +/- 3/8 INCH FOR MEMBERS WITH DEPTH </= 10 INCHES
B. +/- 1/2 INCH FOR MEMBERS WITH DEPTH > 10 INCHES
7. DO NOT USE ADMIXTURES CONTAINING CALCIUM CHLORIDE.
8. ALL WATER TO ACHIEVE CONCRETE BATCHING MUST BE ADDED DURING THE
BATCH AT THE PLANT. THE ADDITION OF WATER TO THE A BATCH ON SITE WILL
NOT BE PERMITTED.
9. CONCRETE CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF ACI 301
“STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE” AND ACI 318 “BUILDING
CODE REQUIREMENTS FOR REINFORCED CONCRETE.” CONFORM TO THE
REQUIREMENTS OF ACI 305 “HOT WEATHER CONCRETING” OR ACI 306 “COLD
WEATHER CONCRETING” WHEN WEATHER CONDITIONS DICTATE.
10. OPENINGS IN CONCRETE SHALL BE REINFORCED AS NOTED IN THE STANDARD
DETAILS.
11. SEE STANDARD DETAILS FOR CORNER BAR REINFORCING AT WALL CORNERS.
12. PROVIDE DOWELS TO SUPPORTING MEMBER WITH BARS SIZED AND SPACED TO
MATCH TYPICAL VERTICAL REINFORCING. DOWELS SHALL HAVE STANDARD HOOKS
EMBEDDED INTO SUPPORTING CONCRETE WITH LAP SPLICE TO VERTICAL
REINFORCING, UNLESS NOTED OTHERWISE.
13. ALL EMBEDDED ELEMENTS, INCLUDING BUT NOT LIMITED TO REINFORCING
DOWELS, WATERSTOPS, EMBEDMENT PLATES, AND ANCHOR BOLTS, MUST BE HELD
RIGIDLY AND ACCURATELY IN PLACE, AND PROTECTED AGAINST DISPLACEMENT
BEFORE AND DURING PLACEMENT OF CONCRETE. WET SETTING OF EMBEDDED
ELEMENTS WILL NOT BE PERMITTED.
REINFORCING STEEL - SPEC 03 20 00
1. LAP SPLICES OF DEFORMED BARS SHALL BE CLASS B, SEE REINFORCING SPLICE
AND DEVELOPMENT TABLE FOR LENGTHS, UNLESS OTHERWISE NOTED.
2. REINFORCING STEEL SHALL NOT BE WELDED.
3. ALL REINFORCING STEEL SHALL BE SUPPORTED ON STANDARD ACCESSORIES,
HELD RIGIDLY AND ACCURATELY IN PLACE, AND PROTECTED AGAINST
DISPLACEMENT BEFORE AND DURING PLACEMENT OF CONCRETE. SUPPORTING
ACCESSORY LEGS THAT REST ON CONCRETE SURFACES THAT WILL BE EXPOSED IN
THE FINISHED STRUCTURE SHALL BE FABRICATED OF STAINLESS STEEL.
4. DOWELS AND OTHER MISCELLANEOUS STEEL EMBEDDED ITEMS SHALL BE
LOCATED AND HELD IN SPECIFIED POSITION PRIOR TO PLACEMENT OF CONCRETE
AND SHALL NOT BE PUSHED INTO CONCRETE FOLLOWING CONCRETE POUR.
FOUNDATIONS
1. FOOTINGS HAVE BEEN DESIGNED FOR THE ALLOWABLE SOIL BEARING PRESSURE
INDICATED WITHIN THE DESIGN CRITERIA AND LOADS TABLE AND SHALL BE FIELD
VERIFIED, WHEN ASSUMED VALUES ARE NOTED, WITH THE PROJECT
GEOTECHNICAL ENGINEER.
2. PROJECT GEOTECHNICAL ENGINEER SHALL INSPECT ALL SUBGRADES AND
PREPARED SOIL BEARING SURFACES PRIOR TO PLACEMENT OF FOUNDATIONS.
3. FOUNDATIONS, WHERE PRESENT, SHALL BEAR ON EITHER COMPETENT NATIVE
SOIL OR COMPACTED STRUCTURAL FILL.
4. RETAINING WALLS HAVE BEEN DESIGNED FOR THE LISTED LATERAL EARTH
PRESSURE AND SURCHARGE, ASSUMING A WELL GRADED AND DRAINED
CONDITION.
5. PLACE ALL BACKFILL ACCORDING TO PROJECT SPECIFICATIONS. BRACE ALL WALLS
AS REQUIRED PRIOR TO AND DURING THE PLACEMENT OF BACKFILL AND UNTIL
SUPPORT FOR THE WALLS ARE IN PLACE.
6. STRUCTURAL ENGINEER FILL SHALL BE USED AS SPECIFIED MEETING THE
FOLLOWING REQUIREMENTS:
A. P200 < 12% B. P40 < 25%
C. SOIL CLASSIFICATIONS SP, SW, GP, OR DUAL SYMBOL CLASSIFICATIONS WITH
NON-PLASTIC FINE MATERIALS
D. SUBMIT ASTM D2487 SOIL CLASSIFICATION TEST DATA FOR APPROVAL OF
EACH PROPOSED MATERIAL
7. COMPACT ALL BACKFILL UNDER FOOTINGS TO THE FOLLOWING REQUIREMENTS:
A. MINIMUM COMPACTION TO 98% OF ASTM D698
B. SOIL WATER CONTENT OF -4% TO 0% OF ASTM D698 OPTIMUM WATER
CONTENT
8. BACKFILL ALONG FOUNDATION WALLS, AND WITHIN THE BUILDING AREA
FOUNDATION WALLS, MEETING THE FOLLOWING REQUIREMENTS:
A. MINIMUM COMPACTION OF 98% OF ASTM D698
B. SOIL WATER CONTENT OF -4% TO 0% FOR GRANULAR NON-COHESIVE SOILS
AND -3% TO +3% FOR COHESIVE SOILS
C. BACKFILL WITH SALVAGED EXISTING SOILS OR IMPORTED SOILS FREE OF
ORGANIC MATTER, FROZEN SOIL, OR DEBRIS AND WITH A LIQUID LIMIT BELOW
D. STRUCTURAL ENGINEER FILL MAY BE USED PER CONTRACTOR OPTION
9. PROTECT ALL FOUNDATIONS FROM THE ACTION OF WATER AND FREEZING.
10. CONTRACTOR SHALL SUBMIT AN EXCAVATION PLAN, INCLUDING DESIGN
CALCULATIONS, PREPARED AND SEALED BY A PROFESSIONAL ENGINEER LICENCED
IN THE STATE OF UTAH.
GENERAL REQUIREMENTS
1. REFER TO CIVIL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR
ADDITIONAL INFORMATION RELATED TO: DIMENSIONS, ELEVATIONS, SLOPES, DOOR
AND WINDOW OPENINGS, NON-BEARING WALLS, STAIRS, FINISHES, DRAINS,
WATERPROOFING, RAILINGS, MECHANICAL UNIT LOCATIONS, INSERTS, EMBEDDED
ITEMS, ANCHORAGES, AND OTHER NON-STRUCTURAL ITEMS
2. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR: COORDINATING DETAILS,
ACCURACY OF THE WORK, VERIFICATION OF ALL QUANTITIES AND DIMENSIONS,
SELECTING FABRICATION PROCESSES, MEANS AND METHODS OF CONSTRUCTION,
AND FOR PERFORMING THE WORK IN A SAFE AND SECURE MANNER
3. STRENGTH AND STABILITY OF THE STRUCTURE DURING CONSTRUCTION SHALL BE
THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PROVIDE TEMPORARY
SHORING, BRACING AND OTHER ELEMENTS REQUIRED TO MAINTAIN STABILITY
UNTIL THE STRUCTURE IS COMPLETE
4. DISCREPANCIES WITHIN THE CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO
THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE
WORK
5. GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS,
AND CONDITIONS AT THE SITE, INCLUDING FOUNDATIONS. CONFLICTS BETWEEN
THE DRAWINGS AND ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH THE WORK.
6. NO STRUCTURAL MEMBER SHALL BE CUT OR NOTCHED OR OTHERWISE REDUCED
IN STRENGTH UNLESS APPROVED BY THE ENGINEER OF RECORD.
7. CONSTRUCTION OBSERVATION BY THE STRUCTURAL ENGINEER IS FOR GENERAL
CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS. GENERAL CONTRACTOR
SHALL BE RESPONSIBLE FOR PERFORMING ALL WORK IN COMPLIANCE WITH THE
CONTRACT DOCUMENTS.
8. PROTECT EXISTING CONSTRUCTION FROM DAMAGE DURING CONSTRUCTION OF
NEW ADDITIONS. MAKE NO CUTS OR ALTERATIONS TO EXISTING CONSTRUCTION,
OTHER THAN THOSE SHOWN ON THE DRAWINGS, WITHOUT THE APPROVAL OF THE
ENGINEER. PATCHING SHALL MATCH THAT OF WORK PREVIOUSLY COMPLETED.
9. GENERAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND PRODUCT DATA TO
ENGINEER OF RECORD FOR REVIEW OF GENERAL CONFORMANCE WITH CONTRACT
DOCUMENTS. ALL SUBMITTALS SHALL BE REVIEWED AND STAMPED BY THE
GENERAL CONTRACTOR PRIOR TO SUBMISSION. SUBMITTALS ARE REQUIRED FOR:
EXCAVATION PLAN, CONCRETE MIX DESIGNS AND REINFORCING STEEL.
10. SPECIAL INSPECTIONS SHALL BE PROVIDED BY AN INDEPENDENT TESTING AND
INSPECTION AGENCY PER CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE
AND AS NOTED WITHIN THE CONTRACT DOCUMENTS. REPORTS DOCUMENTING THE
RESULTS OF THE TESTING AND INSPECTIONS SHALL BE SUBMITTED FOR REVIEW
AND RECORD.
POST-INSTALLED ANCHORS
1. POST INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE
DRAWINGS. CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ENGINEER OF
RECORD PRIOR TO USING POST INSTALLED ANCHORS FOR MISSING OR MISPLACED
ANCHORS.
2. CARE SHALL BE TAKEN TO AVOID CONFLICTS WITH EXISTING REINFORCING WHEN
DRILLING HOLES. HOLES SHALL BE DRILLED AND CLEANED PER THE
MANUFACTURER’S INSTRUCTIONS. ANCHORS SHALL BE INSTALLED PER THE
MANUFACTURER’S INSTALLATION INSTRUCTIONS AT NOT LESS THAN MINIMUM EDGE
DISTANCES AND/OR SPACING INDICATED WITHIN THE LITERATURE.
STRUCTURAL CODES AND STANDARDS
THE GOVERNING STRUCTURAL DESIGN CODES AND STANDARDS ARE TAKEN FROM IBC
2021.
CODES AND STANDARDS NOT LISTED HEREIN ARE NOT APPLICABLE TO THE SCOPE OF
THE DESIGN.
1. AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) 7-16 MINIMUM DESIGN LOADS FOR
BUILDING AND OTHER STRUCTURES
2. AMERICAN CONCRETE INSTITUTE (ACI) 318-19 BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE
3. ACI 315-99 DETAILS AND DETAILING OF CONCRETE REINFORCEMENT
4. AMERICAN WELDING SOCIETY (AWS) D1.1/D1.1M:2015 STRUCTURAL WELDING CODE -
STEEL
N O
D
A T
E
FOR R
PLAN NOTES
1. MATCH ROOF ELEVATION WITH GRADING
CONSTRUCTION NOTES
1. 18" MAT SLAB REINFORCED WITH #7 @ 12" O/C EACH WAY
TOP AND BOTTOM - INSTALL NORTH/SOUTH RUNNING
BARS W/ 3" CLEAR TOP AND BOTTOM
2. 18" ROOF SLAB REINFORCED WITH #7 @ 12" O/C EACH
WAY TOP AND #7 @ 6" O/C EACH WAY BOTTOM - INSTALL
PLAN N/S RUNNING BARS W/ 2" CLEAR TOP AND 1-1/2"
CLEAR BOTTOM HS-20 RATED
3. SUMP IN MAT SLAB -SLOPE FLOOR TOWARDS DRAIN 1/8"
/FT -PROVIDE 1" GRATING OVER COVER
4. CONTRACTOR TO PROVIDE #5 BENT REBAR FOR RIGGING
POINTS FOR LIFTING CENTER SECTION OF ROOF SLAB -
VERIFY QUANITY AND LOCATION
5. BACKERROD AND SEALANT BETWEEN PANELS
6. PIPE PENETRATION SEE DETAIL
7. LADDER SEE CIVIL
8. FLOOR PENETRATION- FIELD ADJUST BARS TO AVOID
CUTTING
9. AT REMOVABLE 5'-0" WIDE PANEL PROVIDE BOND
BREAKER AT TOP OF WALL AND OMIT TYPICAL TOP OF
WALL DOWELS. PROVIDE A HYDROPHILLIC WATERSTOP
10. 8" x 8" CONCRETE CURB AND FLOOR HATCH -SEE STD
DETAIL COORDINATE HATCH SIZING WITH CIVIL
11. CONCRETE PIPE SUPPORT SEE CIVIL SHEETS
/ 1 S502
S301
S301
2'-0" 22'-3" 2'-0"
6" 26'-3" 6"
27'-3"
12 12
S301
S301
MAT SLAB
PROJECTION ABOVE
2'-0" 22'-3" 2'-0"
S301
S301
2 2
10'-7" 1/2" GAP
W/ VALVE SIZE
5'-0" VERIFY 1/2" GAP 10'-7"
5 5
PR
ELI
M
IN
AR
Y
Ad va n c e d
En g i nee r i ng and
Env i ronmentalServices,LLC
N O
T F O
R
C O N
STR
U C
TIO
N
SAL
T L
A K E
C I T Y
S C A L E
B A R
IS
O N E
IN
C H
IG
IN
A L
D R A W
IN
G
D E S
IG
N E D
B Y
D R A W N
B Y
C H E C K E D
B Y
A P P R O V E D
B Y
D A T E
E W O
N O
A C C O U N T
N O
DRAWING NO.
SHEET OF
S A L T
L A K E
C
IT
Y
D E P A R T M E N T
O F
P U B L
IC
U T
IL
IT
IE
S
0-
V E
R I F
Y
S
C A
L E
W S
\S a lt L a k e C it y D e p t o f P u b lic
U ti lit ie s \1
-2
-0
\C
A D
D w g s \0
-S tr u c tu ra l\R e v it \S
L C
D P
U B
C C
T A
N N
E R
T U
R N
O U
T S
R
.r v t
/3
/2
:5 :5
P
M
A s in di ca te d
K D
E
P A
J
K D
E
S101
I S O L A T I O N
V A U L T
P L A N S
M A
Y
P A
J
21 30
S L C D P U
B C C
T A N N E R
T U R N O U T
IM
P R O V E M E N T S
S101
2 FOUNDATION PLAN
S101
3 GRADE LEVEL PLAN
S101
1 FOUNDATION KEY PLAN
12" 0 1' 2' 3' 4' 5' 6' 7'
12" 0 1' 2' 3' 4' 5' 6' 7'
P
L
A
N
N
O R
T H
P
L A
N
N
O R
T H
12" 0 1' 2' 3' 4' 5' 6' 7'
P
L A
N
N
O R
T H
N
O R
T H
N
O R
T H
N
O R
T H
N O
D
A T
E
FOR R
4812.00'
FFE
4793.50'
BO KEY
4799.00'
TFE
S501
2'-0"
PIPE SEE CIVIL
FLOW
S502
S501
STRUCTURAL
ENGINEERED
BACKFILL 98%
COMPACTION
UNDISTURBED
NATIVE SOIL
STRUCTURAL
ENGINEERED
BACKFILL 98%
COMPACTION
UNDISTURBED
NATIVE SOIL
UNDISTURBED
NATIVE SOIL
LADDER SEE
CIVIL
HATCH SEE
CIVIL
4812.00'
FFE
4799.00'
TFE
S501
S501
OPP
STRUCTURAL
ENGINEERED
BACKFILL 98%
COMPACTION
UNDISTURBED
NATIVE SOIL
STRUCTURAL
ENGINEERED
BACKFILL 98%
COMPACTION
UNDISTURBED
NATIVE SOIL
PR
ELI
M
IN
AR
Y
Ad va n c e d
En g i nee r i ng and
Env i ronmentalServices,LLC
N O
T F O
R
C O N
STR
U C
TIO
N
SAL
T L
A K E
C I T Y
S C A L E
B A R
IS
O N E
IN
C H
IG
IN
A L
D R A W
IN
G
D E S
IG
N E D
B Y
D R A W N
B Y
C H E C K E D
B Y
A P P R O V E D
B Y
D A T E
E W O
N O
A C C O U N T
N O
DRAWING NO.
SHEET OF
S A L T
L A K E
C
IT
Y
D E P A R T M E N T
O F
P U B L
IC
U T
IL
IT
IE
S
0-
V E
R I F
Y
S
C A
L E
W S
\S a lt L a k e C it y D e p t o f P u b lic
U ti lit ie s \1
-2
-0
\C
A D
D w g s \0
-S tr u c tu ra l\R e v it \S
L C
D P
U B
C C
T A
N N
E R
T U
R N
O U
T S
R
.r v t
/3
/2
:5 :5
P
M
3/ 8"
'-0
K D
E
P A
J
K D
E
S301
I S O L A T
IO
N
V A U L T
S E C T
IO
N S
M A
Y
P A
J
22 30
S L C D P U
B C C
T A N N E R
T U R N O U T
IM
P R O V E M E N T S
S301
1 VAULT SECTION 1
S301
2 VAULT SECTION 2
12" 0 1' 2' 3' 4' 5' 6' 7'
12" 0 1' 2' 3' 4' 5' 6' 7'
N O
D
A T
E
FOR R
4793.50'
BO KEY
4799.00'
TFE
#7 AT 12" O/C VERT
EACH FACE
#7 AT 12" O/C HORIZ
EACH FACE
CONCRETE SLAB
SEE PLAN
MAT SLAB SEE PLAN
#7 AT 12" O/C HORIZ
OUTSIDE FACE
6" PVC WATERSTOP
DOWEL - MATCH
WALL VERT SIZE &
SPACING - UNLESS
NOTED OTHERWISE
2'-0"
2" CLR
MODIFIED
REINFORCING
AREA ABOVE PIPE
SEE DETAIL
OUTSIDE FACE
/ 1 S502
MODIFIED
REINFORCING
AREA BELOW PIPE
SEE DETAIL
OUTSIDE FACE
/ 1 S502
PIPE BEYOND
LOCATION SEE CIVIL
CHAMFER EDGE
6"
2" CLR
FLOW
2'-0"
MATCH VERT
REINFORCING ABOVE
HYDROPHILLIC
WATERSTOP
4812.00'
FFE
4799.00'
TFE
#7 AT 12" O/C VERT
OUTSIDE FACE
#7 AT 12" O/C VERT
INSIDE FACE
#7 AT 12" O/C HORIZ
OUTSIDE FACE
#7 AT 12" O/C HORIZ
INSIDE FACE
CONCRETE SLAB
SEE PLAN
MAT SLAB SEE PLAN
6" PVC WATERSTOP
CHAMFER EDGE
6"
1'-6"
HYDROPHILLIC
WATERSTOP
C L R
/2
C L
R
4812.00'
FFE
4793.50'
BO KEY
4799.00'
TFE
#7 AT 12" O/C VERT
EACH FACE
#7 AT 12" O/C VERT
OUTSIDE FACE
#7 AT 12" O/C HORIZ
EACH FACE
CONCRETE SLAB
SEE PLAN
MAT SLAB SEE PLAN
MATCH VERT
REINFORCING ABOVE
#7 AT 12" O/C HORIZ
EACH FACE
6" PVC WATERSTOP
DOWEL - MATCH
WALL VERT SIZE &
SPACING - UNLESS
NOTED OTHERWISE
2'-0"
2"
MODIFIED
REINFORCING
AREA ABOVE PIPE
SEE DETAIL
INSIDE FACE
/ 1 S502
MODIFIED
REINFORCING
AREA BELOW PIPE
SEE DETAIL
INSIDE FACE
/ 1 S502
PIPE BEYOND
LOCATION SEE CIVIL
CHAMFER EDGE
2" CLR
FLOW
2'-0"
6"
HYDROPHILLIC
WATERSTOP
C L
R
/2
C
L R
S501
1 WALL SECTION
S501
3 WALL SECTION
PR
ELI
M
IN
AR
Y
Ad va n c e d
En g i nee r i ng and
Env i ronmentalServices,LLC
N O
T F O
R
C O N
STR
U C
TIO
N
SAL
T L
A K E
C I T Y
S C A L E
B A R
IS
O N E
IN
C H
IG
IN
A L
D R A W
IN
G
D E S
IG
N E D
B Y
D R A W N
B Y
C H E C K E D
B Y
A P P R O V E D
B Y
D A T E
E W O
N O
A C C O U N T
N O
DRAWING NO.
SHEET OF
S A L T
L A K E
C
IT
Y
D E P A R T M E N T
O F
P U B L
IC
U T
IL
IT
IE
S
0-
V E
R I F
Y
S
C A
L E
W S
\S a lt L a k e C it y D e p t o f P u b lic
U ti lit ie s \1
-2
-0
\C
A D
D w g s \0
-S tr u c tu ra l\R e v it \S
L C
D P
U B
C C
T A
N N
E R
T U
R N
O U
T S
R
.r v t
/3
/2
:5 :5
P
M
3/ 4"
'-0
K D
E
P A
J
K D
E
S501
I S O L A T
IO
N
V A U L T
D E T A I L S
M A
Y
P A
J
23 30
S L C D P U
B C C
T A N N E R
T U R N O U T
IM
P R O V E M E N T S
S501
2 WALL SECTION
12" 6" 0 1' 2' 3' 12" 6" 0 1' 2' 3' 12" 6" 0 1' 2' 3'
N O
D
A T
E
FOR R
4793.50'
BO KEY
4799.00'
TFE
CONCRETE WALL -
TYPICAL REINFORCING
NOT SHOWN FOR
CLARITY -CUT BARS
AS REQUIRED AROUND
PIPE
CONCRETE SLAB-SEE
PLAN -REINFORCING
NOT SHOWN FOR
CLARITY
CONCRETE KEY-SEE
PLAN -REINFORCING
NOT SHOWN FOR
CLARITY
(5) #7 HORIZ @ 4" o/c
EACH FACE ABOVE
(5) #7 HORIZ @ 4" o/c
EACH FACE BELOW
(5) #7 VERT @ 4" o/c EACH
FACE EACH SIDE OF
OPENING - PROVIDE 90 DEG
HOOK INTO ROOF SLAB
S E
E S
C H
E D
U L E
L A
P S
P L
IC
E
L s
(3) #7 x 10'-0" @ 4" o/c
DIAGONAL BARS -
EACH CORNER
ADDITIONAL DOWELS TO
MATCH ADDITIONAL
REINFORCING
NOTE: ADDITIONAL REINFORCING
REQUIRED EACH FACE OF WALL
S E
E S
C H
E D
U L E
L A
P S
P L
IC
E
L s
' M A
X
M
IN
CORNER DETAILINTERSECTING WALL
90 DEG HK
STD ACI CORNER BARS TO
MATCH HORZ BAR
SIZE & SPACING
EXTEND TO OUTSIDE
FACE TYPICAL
CONSTRUCTION
JOINT SEE TYPICAL
ALTERNATE
CONSTRUCTION
JOINT LOCN WHERE
WATERSTOP NOT
REQUIRED
S E
E S
C H
E D
U L E
L A
P S
P L
IC
E
L s
' M A
X
M
IN
90 DEG HK
STD ACI
PVC WATER STOP
WHERE REQD
SEE SPECS
S E
E S
C H
E D
U L E
D E
V E
L O
P M
E N
T L
E N
G T
H
L d
90 DEG HK
STD ACI
FOOTING OR SLAB
SEE DETAIL
S E
E S
C H
E D
U L E
D E
V E
L O
P M
E N
T L
E N
G T
H
L d
DOWEL - MATCH
WALL VERT SIZE &
SPACING - UNLESS
NOTED OTHERWISE
SLAB - SEE DETAIL
90 DEG HK
STD ACI
S E
E D
E T
A
IL
S T
O P
B A
R C
O V
E R
U N
O
C
L R
BACKER ROD AND
SEALANT SEE
SPECIFICATIONS
GAP
1/2" +/-
BACKER ROD AND
SEALANT SEE
SPECIFICATIONS
OPEN
3'-0" TYP
SEE SCHEDULE
LAP SPLICE (Ls)
(2) #5 DIAG. BAR ALL SIDES
OF OPENING TOP & BOTTOM
OF SLAB (TOP ONLY @
SLABS 8" THICK OR LESS)
SQUARE OPENING
(SOME CASES) SEE
MECH'L, ELEC'L, &
PROCESS DRAWINGS
FOR ALL OPENINGS
PLACE HALF OF TOTAL NUMBER
OF BARS CUT (MIN. 2 BARS)
TOP & BOTTOM ON EACH SIDE
OF OPENING (SIZE TO MATCH
SIZE OF BARS CUT) LENGTH OF
BARS TO MATCH TYPICAL SLAB
REINFORCEMENT
PROVIDE (2) - #6's OR HALF
OF CUT BARS (WHICHEVER
IS GREATER) BOTH SIDES OF
OPENING TOP & BOTTOM
NOTE: MAT SLAB BARS ONLY
NEED TO EXTEND LAP SPLICE
LENGTH PAST FACE OF
OPENING - SEE SCHEDULE
*** TYPICAL WALL REINFORCING
NOT SHOWN - CUT AS REQ'D @
OPENING
S L
A B
S P
A N
S
E E
P L
A N
S
C H
E D
U L
E
PR
ELI
M
IN
AR
Y
Ad va n c e d
En g i nee r i ng and
Env i ronmentalServices,LLC
N O
T F O
R
C O N
STR
U C
TIO
N
SAL
T L
A K E
C I T Y
S C A L E
B A R
IS
O N E
IN
C H
IG
IN
A L
D R A W
IN
G
D E S
IG
N E D
B Y
D R A W N
B Y
C H E C K E D
B Y
A P P R O V E D
B Y
D A T E
E W O
N O
A C C O U N T
N O
DRAWING NO.
SHEET OF
S A L T
L A K E
C
IT
Y
D E P A R T M E N T
O F
P U B L
IC
U T
IL
IT
IE
S
0-
V E
R I F
Y
S
C A
L E
W S
\S a lt L a k e C it y D e p t o f P u b lic
U ti lit ie s \1
-2
-0
\C
A D
D w g s \0
-S tr u c tu ra l\R e v it \S
L C
D P
U B
C C
T A
N N
E R
T U
R N
O U
T S
R
.r v t
/3
/2
:5 :5
P
M
A s in di ca te d
K D
E
P A
J
K D
E
S502
I S O L A T
IO
N
V A U L T
D E T A I L S
M A
Y
P A
J
24 30
S L C D P U
B C C
T A N N E R
T U R N O U T
IM
P R O V E M E N T S
S502
1 ADDITIONAL REINFORCING AROUND OPENING
NO SCALES502
4 WALL CORNER DETAIL
0 1' 2' 3' 4' 5'12"
NO SCALES502
5 WALL DOWEL DETAIL
NO SCALES502
2 REMOVABLE PANEL SECTION
NO SCALES502
6 STANDARD FLOOR OPENING
N O
D
A T
E
FOR R
2" TALL x 3/4"
THICK ANCHOR
RING AROUND
PERIMETER
1/4
1/4
1/4
1/4
3/4"
STEEL PIPE-SEE
CIVIL
CONCRETE WALL
2'-0"
M A
X
TOW
SEE CIVIL (VARIES)
CHAMFER EDGES
GRADE (VARIES) -
SEE CIVIL
#5 HORIZONTAL
MATCH SLOPE
OF WALL
1'-0"
#5 HORIZONTAL AT
12" o/c -EACH FACE
#5 VERTICAL AT 16"
o/c -EACH FACE
2" CLR
#5 AT 16" O/C
EACH WAY TOP
AND BOTTOM
GRADE
SEE CIVIL
RECOMPACTED
NATURAL GRADED
TO 95%
18" GRANULAR FILL
UNDER CONCRETE
COMPACTED TO 95%
RETAINING WALL FOR
ELECTRICAL
EQUIPMENT- SEE CIVIL
FOR DIMENSIONS AND
ELEVATIONS
HINGED MANWAY -
SEE CIVL
1/2" REINFORCING
PLATE EXTENDING
6" BEYOND MANWAY
OUTLET TEE 1/2
CJP TYP
PIPE SEE CIVIL
PR
ELI
M
IN
AR
Y
Ad va n c e d
En g i nee r i ng and
Env i ronmentalServices,LLC
N O
T F O
R
C O N
STR
U C
TIO
N
SAL
T L
A K E
C I T Y
S C A L E
B A R
IS
O N E
IN
C H
IG
IN
A L
D R A W
IN
G
D E S
IG
N E D
B Y
D R A W N
B Y
C H E C K E D
B Y
A P P R O V E D
B Y
D A T E
E W O
N O
A C C O U N T
N O
DRAWING NO.
SHEET OF
S A L T
L A K E
C
IT
Y
D E P A R T M E N T
O F
P U B L
IC
U T
IL
IT
IE
S
0-
V E
R I F
Y
S
C A
L E
W S
\S a lt L a k e C it y D e p t o f P u b lic
U ti lit ie s \1
-2
-0
\C
A D
D w g s \0
-S tr u c tu ra l\R e v it \S
L C
D P
U B
C C
T A
N N
E R
T U
R N
O U
T S
R
.r v t
/3
/2
:5 :5
P
M
3/ 4"
'-0
K D
E
P A
J
K D
E
S503
I S O L A T
IO
N
V A U L T
P
IP
E
D E T A I L S
M A
Y
P A
J
25 30
S L C D P U
B C C
T A N N E R
T U R N O U T
IM
P R O V E M E N T S
NO SCALES503
1 ANCHOR RING DETAIL
S503
2 TYPICAL RETAINING WALL SECTION
12" 6" 0 1' 2' 3'
N O
D
A T
E
NO SCALES503
3 MANWAY COLLAR DETAIL
FOR R
n c ed
En g i nee r i ng and
PRELIM
IN
ARY
Env i ronmental Services, LLC
NOT FOR
CONSTRUCTIO
N
ONE-LINE DIAGRAM AND SCHEMATIC SYMBOLS
PRESS TO TEST LAMP
(LETTER DENOTES COLOR)
OPERATING COIL (LETTER OR
NUMBER DENOTES DEVICE)
RTM
52 M
ENERGIZED TIMER
CONTROL (N.C., N.O.)
DE-ENERGIZED TIMER
CONTROL (N.C., N.O.)
TEMPERATURE SWITCH (N.C., N.O.)
FLOW SWITCH (N.C., N.O.)
LIQUID LEVEL SWITCH (N.C., N.O.)
R
OFF
RUN
AUTO
30A FUSE (NUMBER DENOTES
RATING)
SELECTOR SWITCH
CIRCUIT BREAKER
MAGNETIC TRIP
THERMAL TRIP
RUNNING TIME METER
CONTACT (N.C., N.O.)
PRESSURE SWITCH (N.C., N.O.)
LIMIT SWITCH (N.C., N.O.)
DISCONNECT SWITCH
ELECTRICAL ABBREVIATIONS
A AMPERES F&I FURNISH AND INSTALL LIT LEVEL INDICATING TRANSMITTER SCP SUPERVISORY CONTROL PANEL AC ABOVE COUNTER (VERIFY HEIGHT) FCV FLOW CONTROL VALVE LMF LIQUID-TIGHT METALLIC CORE FLEXIBLE CONDUIT SCADA SUPERVISORY CONTROL AND DATA ACQUISITION
ACK ACKNOWLEDGE FE FLOW ELEMENT LSH LEVEL SWITCH HIGH SE SERVICE ENTRANCE
AE ANALYZER ELEMENT FIT FLOW INDICATING TRANSMITTER LSHH LEVEL SWITCH HIGH HIGH SEC SECOND OR SECONDARY
AI ANALOG INPUT FS FLOW SWITCH LSL LEVEL SWITCH LOW SIG SIGNAL
AIT ANALYZER INDICATION TRANSMITTER FU FUSE OR FUSIBLE LSLL LEVEL SWITCH LOW LOW SOL Vv SOLENOID VALVE
A.F.F. ABOVE FINISHED FLOOR SP SINGLE POLE
AM AMMETER GC GENERAL CONTRACTOR M MOTOR STARTER OPERATING COIL SPECS SPECIFICATIONS ANN ANNUNCIATOR GDE GAS DETECT ELEMENT MAX MAXIMUM SSNR ''SOFT START'' NON-REVERSING SWITCH AO ANALOG OUTPUT GFI GROUND FAULT INTERRUPTER MCM THOUSAND CIRCULAR MILS SSR SW ''SOFT START'' REVERSING SWITCH AWG AMERICAN WIRE GAGE GND GROUND MCP MOTOR CIRCUIT PROTECTOR SUSE SUITABLE FOR USE AS SERVICE ENTRANCE
GRS GALVANIZED RIGID STEEL CONDUIT MECH MECHANICAL
BKR BREAKER MFR MANUFACTURER TD TIME DELAY
BLDG BUILDING HD HEAVY DUTY MH METAL HALIDE TEMP TEMPERATURE
HH HANDHOLE MIN MINUTE OR MINIMUM TIT TEMPERATURE INDICATING TRANSMITTER
CKT CIRCUIT H/R HAND/REMOTE MTD MOUNTED TS MOTOR THERMAL SWITCH
℄ CENTER LINE HOA HAND-OFF-AUTO TSTAT THERMOSTAT
CONTR CONTRACTOR HOL HAND-OFF-LOCAL NF NON-FUSED
CP CONTROL PANEL HP HORSEPOWER NC NORMALLY CLOSED UH UNIT HEATER
CPT CONTROL POWER TRANSFORMER HPS HIGH PRESSURE SODIUM NO NORMALLY OPEN
CS CONTROL STATION HS HAND SWITCH NTC NOT CONNECTED V VOLTS
CT CURRENT TRANSFORMER HTR HEATER VFD VARIABLE FREQUENCY DRIVE
HZ HERTZ (CYCLES / SECOND) OL(S) OVERLOAD RELAY CONTACT(S) VM VOLTMETER
DE DUAL ELEMENT VS VOLTMETER SWITCH
DI DIGITAL INPUT IMC INTERMEDIATE METAL CONDUIT PF POWER FACTOR Vv VALVE
DISC DISCONNECT PIT PRESSURE INDICATING TRANSMITTER
DO DIGITAL OUTPUT JB JUNCTION BOX PLC PROGRAMMABLE LOGIC CONTROLLER W WATTS OR WIRE
DP DAMP PROOF PSH PRESSURE SWITCH HIGH W/ WITH
KVA KILOVOLT-AMPERES PSL PRESSURE SWITCH LOW WW WIREWAY
EC ELECTRICAL CONTRACTOR KVAR KILOVOLT-AMPERES REACTIVE PTT PUSH TO TEST WP WEATHERPROOF
ELEC ELECTRICAL KW KILOWATTS PVC POLYVINYLCHLORIDE CONDUIT
EMT ELECTRICAL METALLIC TUBING XFMR TRANSFORMER
EXP EXPLOSION PROOF REQ'D REQUIRED
EQUIP EQUIPMENT RS RIGID STEEL CONDUIT ZC POSITION CONTROLLER
RTD RESISTANCE TEMPERATURE DETECTOR ZI POSITION INDICATOR
RTM RUNNING TIME METER ZSC POSITION SWITCH CLOSED
RTR REMOTE TEST / RESET ZSO POSITION SWITCH OPENED
GENERAL NOTES
1. AE2S ELECTRICAL DRAWINGS ARE INTENDED TO BE
REPRODUCED IN COLOR. AE2S ASSUMES NO LIABILITY
FOR CONTRACTORS CHOOSING TO REPRODUCE THESE
DRAWINGS IN BLACK AND WHITE OR AT A SCALE WHICH
REDUCES LEGIBILITY.
2. PLANT MUST REMAIN IN VIRTUALLY CONTINUOUS
OPERATION DURING CONSTRUCTION. COORDINATE
SEQUENCING, SWITCHOVERS, AND SHORT DOWNTIME
PERIODS WITH LOCAL UTILITY COMPANY, THE OWNER,
AND THE ENGINEER DURING CONSTRUCTION.
3. COORDINATE THE INSTALLATION OF ALL BELOW-GRADE
AND CAST-IN-PLACE CIRCUITRY WITH OTHER TRADES.
4. CONTRACTOR SHALL RETURN ALL DISTURBED
SURFACES AND SOILS TO ORIGINAL OR
PRE-CONSTRUCTION CONDITION UNLESS
SPECIFICALLY INDICATED OTHERWISE.
5. CONTRACTOR SHALL LOCATE OR SHALL HAVE THE
SERVING UTILITIES LOCATE ALL UNDERGROUND CABLE,
CONDUITS, PIPING, UTILITIES, ETC., PRIOR TO
COMMENCING CONSTRUCTION (UNDERGROUND
EXCAVATION). CONTRACTOR SHALL BE RESPONSIBLE
FOR THE REPAIR OF ANY DAMAGES DUE TO
CONSTRUCTION ACTIVITIES.
6. EXISTING AND / OR NEW UNDERGROUND CONDUITS,
DUCTBANK, AND OTHER CIRCUITRY SHOWN ON THE
PLANS ARE INTENDED TO BE DIAGRAMMATIC IN
NATURE. CONTRACTOR IS RESPONSIBLE FOR FIELD
CONFIRMING ALL CIRCUITRY AND ROUTING.
7. CORE DRILL EXISTING STRUCTURES AS REQUIRED FOR
NEW CONDUIT INSTALLATIONS. PATCH AROUND
PENETRATIONS WITH NON-SHRINK GROUT AND PAINT
TO MATCH SURROUNDING SURFACES WHERE
APPLICABLE.
8. PLUG ALL UNUSED OPENINGS IN PANELS / EQUIPMENT
LEFT BY REMOVALS. CUT OFF ALL ABANDONED
CONDUITS FLUSH WITH SURFACES AND FILL WITH
NON-SHRINK GROUT.
9. REFER TO EXISTING ELECTRICAL DRAWINGS FOR SITE
PLAN DETAILS / CIRCUITRY.
10. SCHEDULE 80 PVC CONDUIT IS ALLOWED
UNDERGROUND FOR NON-VFD AND NON-SIGNAL
CIRCUITS. TRANSITION TO RIGID STEEL CONDUIT
BEFORE EXPOSING ABOVE GRADE.
11. FIELD CONFIRM CONDUIT ROUTING. DO NOT ROUTE
CONDUIT ON BUILDING EXTERIOR UNLESS NOTED
OTHERWISE.
12. WHERE THE PLANS CALL FOR DISCONNECTION AND
REMOVAL OF CIRCUITRY (CABLE AND CONDUIT),
COMPLETE CONDUIT REMOVAL MAY NOT BE PRACTICAL
DUE TO THE LIMITS OF OTHER CONSTRUCTION. IN
SUCH CASES, THE CONTRACTOR SHALL DISCONNECT
AND REMOVE ALL CIRCUITRY FROM CONDUITS THAT
ARE TO BE DEMOLISHED, SHALL REMOVE THE
CONDUITS TO 18'' MINIMUM BELOW GRADE, AND SHALL
BE ALLOWED TO CUT OFF THE CONDUITS AND
ABANDON IN PLACE. THIS APPROACH SHALL ONLY BE
USED WHERE LARGE SCALE EXCAVATION DUE TO
OTHER CONSTRUCTION ACTIVITIES IS NOT PLANNED IN
AN AREA. ALL SUCH CONDUIT ABANDONMENT IN PLACE
SHALL BE CONFIRMED WITH THE ENGINEER PRIOR TO
DOING SO.
13. SEE ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND
PROCESS DRAWINGS FOR EXACT EQUIPMENT, PIPING,
AND BUILDING LAYOUTS.
14. ALL CONDUCTORS ARE TO BE COPPER.
15. PROVIDE AS-BUILT DRAWINGS. DRAWINGS SHALL BE
NEAT AND LEGIBLE.
16. COORDINATE ELECTRICAL WORK WITH OTHER TRADES.
17. PROVIDE PANEL SCHEDULES FOR ALL NEW AND / OR
MODIFIED PANELS. SCHEDULES SHALL BE TYPED.
18. ANY ELECTRICAL BOX THAT BECOMES ABANDONED
DURING THE COURSE OF THE PROJECT SHALL HAVE A
BLANK COVERPLATE.
19. VERIFY LOCATION OF ALL FLOOR OUTLETS WITH
ARCHITECT PRIOR TO ROUGH-IN.
20. WHERE OTHER ELECTRICAL DEVICES ARE LOCATED
ADJACENT TO LIGHT SWITCHES, MOUNT ALL DEVICES
AT THE SAME CENTER LINE ELEVATION. WHERE
ELECTRICAL DEVICES ARE NOT LOCATED ADJACENT TO
LIGHT SWITCHES, MOUNT DEVICES AT 48'' A.F.F.
UNLESS NOTED OTHERWISE.
21. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN
FIELD PRIOR TO COMMENCEMENT OF WORK.
22. FINAL CONNECTIONS TO EQUIPMENT SHALL BE PER
MANUFACTURER'S APPROVED WIRING DIAGRAMS,
DETAILS, AND INSTRUCTIONS. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO PROVIDE
MATERIALS AND EQUIPMENT COMPATIBLE WITH
EQUIPMENT ACTUALLY SUPPLIED.
23. ALL EMPTY RACEWAY SYSTEMS SHALL HAVE A
PULLWIRE OR EQUAL AND SHALL BE IDENTIFIED AT ALL
JUNCTION, PULL, AND TERMINATION POINTS USING
PERMANENT METALLIC TAGS. TAG SHALL INDICATE
INTENDED USE OF CONDUIT, ORIGINATION, AND
TERMINATION POINTS OF EACH INDIVIDUAL CONDUIT.
24. IT IS THE INTENT OF THESE DRAWINGS AND
SPECIFICATIONS TO ESTABLISH A STANDARD OF
QUALITY. THE ENGINEER RESERVES THE RIGHT TO
APPROVE METHODS AND MATERIALS NOT REFLECTED
HEREIN.
25. CONTRACTOR SHALL VISIT SITE PRIOR TO BID AND
VERIFY THAT CONDITIONS ARE AS INDICATED.
CONTRACTOR SHALL INCLUDE IN THEIR BID THE COSTS
REQUIRED TO MAKE HIS WORK MEET EXISTING
CONDITIONS.
26. WORK SHALL BE PERFORMED IN A WORKMANLIKE
MANNER TO THE SATISFACTION OF THE ARCHITECT /
ENGINEER.
27. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM
TO THE LATEST EDITIONS OF LOCAL, STATE, AND
NATIONAL CODES AND ORDINANCES.
28. VERIFY THAT EXACT LOCATION OF EQUIPMENT TO BE
FURNISHED BY OTHERS PRIOR TO ROUGH-IN.
29. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION.
IF TESTS SHOW THAT WORK IS DEFECTIVE,
CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY
AT NO COST TO OWNER.
30. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND
READY FOR CONTINUOUS OPERATION. LIGHTS,
SWITCHES, RECEPTACLES, MOTORS, ETC., SHALL BE
CONNECTED AND OPERABLE.
31. ALL CONDUIT IS TO BE RIGID STEEL WITH CAST 'FS'
STYLE BOXES. MAKE FINAL EQUIPMENT CONNECTIONS
USING LIQUID-TIGHT METALLIC FLEX.
32. ALL LIGHTING AND RECEPTACLE CIRCUITRY
CONDUCTOR QUANTITY AND CONDUIT IS THE
RESPONSIBILITY OF THE CONTRACTOR. LIGHTING
CIRCUITRY IS TO BE A MINIMUM OF #12AWG COPPER IN
3/4'' CONDUIT, QUANTITY AS REQUIRED.
33. ALL CABLE CONNECTIONS SHALL BE…