1-METRO Northline MPD Site Development BCE Plan Set (COH APPROVED).pdf

PDF 27 MB Posted

Attached to
8030 ½ Fulton Site Development Project
Solicitation number
IFB 2026000012
Issued by
Harris County, Texas

About this file

This is a City of Houston approved Building Civil & Electrical (BCE) Plan Set for the 1-METRO Northline MPD Site Development project located at 8030½ Fulton Street in Houston, Texas. The comprehensive plan set includes landscape design, tree protection protocols, fencing specifications, electrical infrastructure, and technology/security systems for the multi-phase development. The project requires extensive site development work including tree preservation with certified arborist monitoring, installation of perimeter fencing with automated vehicle access gates, landscape plantings totaling 7 live oak trees, 4 Texas red oak trees, 790 square feet of dwarf wax myrtle shrubs, and 6,300 square feet of St. Augustine sod. Electrical infrastructure specifications detail a 1000-amp, 120/208V three-phase service with multiple load centers, distribution panels for two future trailers, lighting fixtures at six pole locations, and associated electrical equipment racks with concrete maintenance pads. The plans indicate City of Houston compliance review dated April 22, 2026, with approval stamps throughout the 40+ sheet document.

The technology and security systems include comprehensive communications infrastructure with fiber optic cables, multiple pullboxes and handholes, five CCTV camera locations with specific mounting and power specifications, access control systems with card readers at vehicle gates, induction loop detection systems for gate operation, and security enclosure installations. Directional drilling is specified for underground conduit installation with detailed bore profiles and fluid specifications. All materials, labor, and construction methods must comply with current National Electrical Code, City Building Code requirements, and manufacturer specifications. The project requires contractor coordination with multiple disciplines including arborists, electricians, gate operators, and technology vendors, with specific shop drawing submissions and pre-construction approvals mandated throughout. Cost details and contract award information are not included in these technical plan documents.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3/5/26

03/23/26

03/23/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all applicable codes, ordinances and regulations. 04/22/26

SHEET 2 OF 46

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 3 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 4 OF 46

03/23/26

03/23/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 5 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 6 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 7 OF 46

03/23/26

03/23/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 8 OF 46

03/23/26

03/23/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 8A OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 9 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 10 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 11 OF 46

03/23/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 12 OF 46

03/23/26

03/23/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 13 OF 46

03/23/26

3/5/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 14 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 15 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 16 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 17 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 19 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all applicable codes, ordinances and regulations. 04/22/26

GB-2

GB-1

SHEET 20 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

SHEET 21 OF 46

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

LIMIT LANDSCAPE SCOPE OF WORK

L I M

I T L

A N

D S C

A P

E S

C O

P E O

F W

O R

K

L I M

I T L

A N

D S C

A P

E S

C O

P E O

F W

O R

K

10 11 12 13 14 15

ROOT PRUNING, TYP.

TREE PROTECTION FENCE, TYP.

25'-0"

MIN.

NO LANDSCAPE

TREATMENT IN THIS AREA.

FINISH TO BE PROVIDED

BY TEMPORARY BUILDING

INSTALLER.

LIMIT LANDSCAPE SCOPE OF WORK

LEGEND

TREE NUMBER

EXISTING TREES TO REMAIN

EXISTING TREES TO BE REMOVED

TREE PROTECTION FENCING

RE: DETAIL 1/L200

ROOT PRUNING WITH

6” WIDE, 2’ DEEP TRENCH

RE: DETAIL 2/L200

3" HARDWOOD MULCH

2500 Summer Street, Suite 3228 Houston Texas 77007

P: 713.337.5830 www.asakurarobinson.com

KEIJI ASAKURA

T

R

R E

L A

P

E G

S

D

N

C A

R

E A

I S ET

T

A

S

ET

O F

T C

E

TI

H C

D

X

A S

E

11.19.2025

TREE PROTECTION NOTES :

1. IT IS CRUCIAL THAT TREE PROTECTION FENCES MUST BE ERECTED PRIOR TO THE BEGINNING OF ANY SITE DEMOLITION.

2. THE TREE PROTECTION FENCE SHALL BE T-POSTS AT 8'-0" O.C. W/ 4' HT. BRIGHT ORANGE, LIGHT WEIGHT, REUSABLE MESH SAFETY FENCING MADE OF HIGH DENSITY POLYETHYLENE WITH 1

1/2" X 3" SIZE MESH OR SIMILAR MATERIAL.

3. PROTECTION FENCE SHALL BE PLACED AROUND CRITICAL ROOT ZONE OF ALL TREES TO REMAIN.

4. UNDER NO CIRCUMSTANCES, SHOULD A CONTRACTOR DRIVE OR PARK MACHINERY ON TREE ROOTS OR UNDER THE DRIPLINE.

5. AVOID DISTURBING ROOTS IN CRITICAL ROOT ZONE. IF ROOT CUTTING IS NECESSARY OR ANY ROOTS ARE DAMAGED, THEY SHALL BE CUT CLEANLY WITH THE APPROPRIATE PRUNING SHEARS

OR PRUNING SAWS A FEW INCHES ON THE SIDE CLOSER TO THE TRUNK. ANY EXPOSED OR PRUNED TREE ROOTS MUST BE COVERED IMMEDIATELY WITH DIRT AND MULCH TO PREVENT ROOTS

FROM DRYING OUT.

6. NO STORAGE OR CONCRETE DUMPING IS PERMITTED ON TREE ROOTS AND/OR UNDER DRIPLINE.

7. NO BUILDING MATERIALS ARE TO BE STACKED OR STOCKPILED WITHIN THE DRIPLINE OR WITHIN 6 FEET OF ANY TREE TO BE PRESERVED, WHICHEVER DISTANCE IS GREATER.

8. TOPSOIL SHALL NOT BE STOCKPILED WITHIN THE DRIP LINE OR WITHIN 6 FEET OF ANY TREE TO BE PRESERVED, WHICHEVER DISTANCE IS GREATER.

9. TREE BOARDING SHALL BE USED AS SHOWN ON PLAN AND IF WORK IS REQUIRED WITHIN FENCING.

10. ANY UNDERSTORY CLEARING WITHIN SIX FEET OF EXISTING TREE TRUNKS SHOULD BE DONE BY HAND.

11. CONTRACTORS ARE REQUIRED TO HIRE A CERTIFIED ARBORIST TO MONITOR AND ASSIST WITH FIELD LAYOUT (EXACT LOCATIONS OF FENCING, ROOT PRUNING, AND ZERO CURB CUTBACK) OF

THE TREE PRESERVATION PROGRAM DURING DEMOLITION AND CONSTRUCTION TO ENSURE TREE PROTECTION PROCEDURES AND TECHNIQUES ARE PRACTICED AS SPECIFIED TO ADDRESS

CONCERNS AND CONDITIONS WHICH OCCUR IN THE FIELD. AT A MINIMUM, THE INDIVIDUAL RESPONSIBLE FOR MONITORING AND FIELD LAYOUT OF THE TREE PROTECTION SHALL HAVE A

MINIMUM OF 5 YEARS OF EXPERIENCE AS A CONSULTANT, AND SHALL NOT BE AFFILIATED WITH A TREE CARE CONTRACTOR IN THE HARRIS COUNTY AREA. QUALIFICATIONS OF THE SELECTED

CERTIFIED ARBORIST SHALL BE SUBMITTED FOR REVIEW AND APPROVAL BY THE LANDSCAPE ARCHITECT.

12. ROOT PRUNING CUT LIMITS SHOWN ON PLANS ARE APPROXIMATE, AND WILL NEED TO FIELD VERIFIED ONCE ROOTS ARE VISIBLE. ALL ROOT PRUNING OVER 1" IN DIAMETER SHALL BE DONE

UNDER APPROVAL FROM CITY FORESTER AND PROJECT ARBORIST.

L100 TREE PROTECTION PLAN

TREE PROTECTION PLAN

SCALE: 1"=20'

LANDSCAPE ANALYSIS FORM

(PLEASE ATTACH TO PERMIT SITE PLAN)

CITY OF HOUSTON

DEPARTMENT OF PLANNING & DEVELOPMENT

Commercial (Staff may create an artificial lot)

1. TREE AND SHRUB PLANTING REQUIREMENTS

A. STREET TREES: Sec. 33-126 (a)

Length of property line in lineal feet as measured along each street separately.

STREET NAME LINEAR TREE EQUIVALENT EX. STREET NEW STREET TOTAL

FEET REQUIRED CREDITS* TREES TO REMAIN TREES

FULTON STREET 140 5 3 0 3 6

JULIA STREET 243 8 4 1 4 9

TOTAL STREET TREES REQUIRED 13

TOTAL STREET TREES PROPOSED 7

EQUIVALENT CREDITS* 8

DEFICIT / NET +2

B. PARKING LOT TREES: Sec. 33-127 (a)

50% of parking lot trees must be large trees. Each parking space must be within 120' of a tree.

TREE PLANTING REQUIREMENTS FOR PARKING LOT: 1 tree / 10 parking spaces

TOTAL NUMBER OF PROPOSED # OF SPACES TREE EQUIVALENT LARGE TREES SMALL TREES TOTAL TREES

PARKING SPACES REQUIREMENT CREDITS* PLANTED

C. PARKING LOT SHRUBS: Sec. 33-127 (b) 75% of the shrubs must be planted along the perimeter of the parking lot.

(Shrubs are required for new and/or the expanded portion of parking lot)

SHRUB REQUIREMENTS: 10 shrubs / 1 street tree

STREET TREE PLANTING REQUIREMENT REQUIREMENT TOTAL SHRUB PLANTED

13 130 152

D. LANDSCAPE BUFFER: Sec. 33-128 (1) Wood, concrete masonry opaque screening fence. (min. 6')

Sec. 33-128(2) Evergreen Screening.

A 6' high wood, concrete masonry opaque screening fence or 15' wide evergreen planting strip along total length of line adjacent to existing single family residential, or limit of expansion adjacent to existing single family. (Site plan must show land use on all sides of property)

CREDIT WORKSHEET: Sec. 33-123 (a) Tree planting equivalency credits

STREET PARKING

1. Number of proposed trees exceeding 4" in caliper 7 . Each 4" tree is (1) credit. 7 --

2. Depositing of monies with Parks and Recreation Department. $500 per tree.

Proposed credits cannot exceed 30% of tree planting requirement above. Amount to be deposited:

Proposed Credits x $500.00 = $ -- --

3. Preservation of on-site trees, per the following schedule in caliper:

minimum 4" - 6" 2 trees x greater than 6" but less than 12" 3 trees x

12" and greater 4 trees x

Total number of tree credits for this option trees. 0 0

4. Credit for preserving existing right of way street trees

1 0

5. Proposed total number of tree credits (to receive credit, documentation must be provided in conformance with Section 33-123). 8 0

43 43 4 0 2 0 4

SHEET 22 OF 46

DDERDDERDDDDDEREEERERRERDDERDDERRDERRDERDDERERERRDDDDERDDEERERRRDDDDDERDDDDERERRERDDDDDDDEERRDDDDDEERRRDDDERDDDERDDDDERERRDDDDDD RDDDDDDDDERDDDDDDD RDDDERDE THETTHTTTHTTTTTHETHETHHTHEHTHHHEHEEHEETTTTHETTTHETTHETHTTHEHHTHEHEHHHETHEEEEEHEHETTTTTTTTTHETTTHHHHHHHEHHEEEEEEEEETHETHETTTHETTTTTTTHEHHEHHHHHHEEEEETHETHEETHETTTTHETTTTTHHEHTHEEEEEETTTTTTTHTHHHHHHHEEEEEETHETHETTHETHTTHHHTHEHHHTHHETHEETHEEETHEEETTHTHTTHETTTHHHHHEHHHHHHEEEEEETTTTTTHHHHHHHHHEEEEEEEEETTTTHETTHHHHHHEEEEETTTTHHHHHEEEEEEETHHHHHHHTHEEEEEEEETHETHETTHTTTHHHEHEHHEETTTHTTHHEEE DDDDDDDDRIPDDRIPRIRRIRIPPPPIPDRIPLIPLLPLLLLDRIPLDRDRIDRIPLDDDDDDRIPDRIPPIPPPDRIPLRIPLLLDRIPLLLDRIPLDDDDRIPDDDRIPRIPRRRRRRRRRRRIPLDRIIRIPIIIIPPRIPPPPPPLLDRIPLLLDRIDRIPLDRIPDDRIDRIPDDDRDRRDRIPLRDRIRDRIPLRIPLDRIPRIIPRIPPPLLLRIPLDDDDRRRRRIRIRIPIPRIPPPPLLLLDDDDDDRRRRRRRIPRDRIPLIRIPIIIPIIPPDRIPPPPLLIPLRIPLDDDDRIRIPRRRRIPIPIIIPPPPPDRIPLDDRIPDRIDDRIPDRIPRIPDRIPRRRRIPIIIPPPDRIPPPLDRIPLDDRDDRRRIPRRIIPPPPPDDDRRIPRRIIIPPPPDDDDDRRRIPPPPPDDDRRRIPPPPPPDRIPPDRIDDRIDDRDRIPLDDRRRRIIPPPLDRDDDRIPRRIPLRRIPLIPLIP IINIININE.INNNNNE.IIINE.NNNNNNNE.IINENNNNNEINNNE..NNNINNE.INE.NNNNNNENNNE.NNNNNNNNNNNNNNNNNNNN .NNNN .IIINNNN .IIIINNNNN

E DADADAMDAMDDDADAAAAAAAMAAAAMAMMMMMMDAMMMAMMMMDDDADDDAAAAAAAAMMMMMAMMMMMMMDAMDDDDDAAAMDAMAAAMAMAMAMMMMMAMMMMMMDADDAMAAAMMMMMMDDDAMAAAADAAAAAAAAAMMDAAAAAAAAMAAAAAAAAAAAMMAAAAAAAAMMAAAAAMMMAMAAMAMAAAAMMMMAAAAAAAAAMMMMMAAAAAAAMMAAAMMMMAGED,AGED,AAGEDAGEDAGED,AGED,AGED,GAGED,GAGEDGEDGAGED,EDEEEEEDAGED,EEAGEDGEDDGEDGEDAGEDDDDAGAGEDGGAGEDGEEDDGEDGEDEDAAGAGEAGEDAGAGEGEGGGEGGGEEDAGEDAAAAGAGEGGEDAGED,GEDGGEDEAGEAAAGEDAAAAGAGGGGEEEEAAAGAAAAGGGAGEGEDEEEEEEAAAGEDAGEDAAAGGGEEDEEEEEDDDDDDDEDGED,GED,AGEDAAGAGEAAAGED,AGGGGEDGGEEDDDDAGEDAAAAAAGEGGGEDEAGED,EEDDDDDAAAAGGEAGEDEDDDAGEAAAGEAGGGGEDGEEEEEDEAAAAGGGGGAGEDAGEDDD,,,AAGAGEEEAGEDAAAAAAAGEDGGEEEEDAGEDDDDDAAAAAAGEEEDDDDDDDDDDDDD THEYTHEYTHEYTTTTTTHEYTHTHEYHHTHEYTHEYTHEYHEEHEETHEEYEYHEEYYHEYYTHEYHEYTHEYTTTTTHEYTTHEYTTTHEYHTHEEEEEHEHETHEYEYHEYTHEYYYYYTHEYTTTTTTHETHEYTHEYHHHEHHETHEEETHEETHEYYEYYYYYTTTHTTTHEYTHEYTHHHHHHEHEYYYHEYYYYYTHEYTTHTHEYTHHHTHH YYYYYTTTTTHHHHHTHHH YTHEYHEYYYYYTHTTHHEYHHHHEYYYYYYHEYTTTTTTHEHTHEHHHHHHEYYYYYYYTTTHTHEHHHHHEYYYYYYYT EEEYYYYYYYHHEEYYYYYYHEYHEYTHHHEHEEYYYHEYYYYTHETTHHHHHEEYYYYYYTHHHHEEEEEYYYTHEYYYYYTHHHTHHHHTHEEYYYYYY SSSSHSS

ROOTS TS MTSTTTS MTS MTS MSSSSSSS MSSS MS MMMMMMMMMMMMMMMMTS MTTS MTTSSSSSSS MMMMMMMMMMMMTTTTSTTSSSS MS MSSSSS MMMMMMMMMMMTTTTSSSSSS MMS MMMMTS MSSSSSS MMMMMMMSSS MSSSS MMMS MMMSSSSSS MMMMMSS MS MMMMMMMSSS MMMMMMMMSS MMMMMMS MMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMUSTUSTUST BUUUUSTSSUST BUSSTTTTTTTUST BTUSTUSTTT BUST BUST BT BBBUST BBBUSTUUUUSSSSUSTTTTTTUSTUSTUSTTUST BT BBBST BBBUST BUUUUUST USUUSSSSST BSSSTTTTTTTUSTSTUST BBBBBT BST BBBUST BUUUUSSSSTTTUSTSTUSTST BBBBBST BBBUSTST BTTUST BUSTUST BST BBBBST BUUSUUUUUSSSSSSTSTTUSTUST BBBBBBBUSUUST BSTTTTTUST BBBBBUST BTTSTTTTTTTT BBBBBBBUST BUUUUUUUUSSSSST BUSSSSSTTTTTTTTUST BT BST BUST BBUSUUUSSSSSSSTUSTTTTTT BBBBBBUUUUUUUSSSSSSTTTTTT BBBBUUUUUSSSSSSTTTT BUUUUUSSSSSTTTTUUUUSSSSSTTTTTTUUUUSSSSTTTTTT EEEEEEEEEEE COVEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

2500 Summer Street, Suite 3228 Houston Texas 77007

P: 713.337.5830 www.asakurarobinson.com

KEIJI ASAKURA

T

R

R E

L A

P

E G

S

D

N

C A

R

E A

I S ET

T

A

S

ET

O F

T C

E

TI

H C

D

X

A S

E

11.19.2025

L200 TREE PROTECTION DETAILS

TREE PROTECTION DETAILS

SCALE: NTS

ROOT PRUNING DETAILS

SCALE: NTS

TREE BOARDING DETAILS

SCALE: NTS

SHEET 23 OF 46

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

L I M

I T L

A N

D S C

A P

E S

C O

P E O

F W

O R

K

L I M

I T L

A N

D S

C A

P E S

C O

P E O

F W

O R

K

16'-0"

/2

O .C

7'-6 1/2"

V.I.F

/2

O .C

T Y P

/4

.C

V .I

.F

8'-0 1/2"

O.C, TYP.

6" O.C, TYP.

O .C

T Y P

O .C

V .I

.F

O .C

T Y P

4'-10 3/4" O.C, V.I.F

4'-0"

O.C, V.I.F

4'-0 1/2"

O.C, V.I.F

8'-0 1/2"

O.C, TYP.

8'-0 1/2"

O.C, TYP.

'-3

" O .C

T Y P

5'-6 1/2"

O.C, V.I.F

TYP.

/4

O

.C V .I

F

/2

O .C

GATE OPERATOR

AUTOMATIC

DRIVEWAY SLIDING

GATE (ENTRY ONLY)

AUTOMATIC

DRIVEWAY SLIDING

GATE (EXIT ONLY)

GATE OPERATOR

PERIMETER FENCE

FROM R.O.W TO

CENTERLINE OF

FENCE

PRELIM KEYPAD LOCATION.

RE: MEP FOR EXACT

LOCATION AND

SPECIFICATIONS

8'-0 1/2"

E Q

E Q

10 1/2", O.C, TYP.

'-0

T Y P

4' -9

/2

O .C

V

.I .F

NOTE: V.I.F = VERIFY IN FIELD

CONTRACTOR TO CLOSE ANY GAPS FROM EXISTING PERIMETER CHAIN

LINK FENCE TO NEW FENCE UTILIZING CHAIN LINK TO MATCH

EXISTING. CONTRACTOR TO PROVIDE SHOP DRAWING INDICATION

PROPOSED SOLUTION.

WOOD FENCE,

RE: 4/L400

2500 Summer Street, Suite 3228 Houston Texas 77007

P: 713.337.5830 www.asakurarobinson.com

KEIJI ASAKURA

T

R

R E

L A

P

E G

S

D

N

C A

R

E A

I S ET

T

A

S

ET

O F

T C

E

TI

H C

D

X

A S

E

11.19.2025

L300 FENCING PLAN & DETAILS

FR VEHICLE ACCESS GATE -1

FENCING PLAN

SCALE: 1"=20'

ACCESS GATE NOTES:

- CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING ALL REQUIRED

EMERGENCY ACCESS ELEMENTS FOR BOTH DRIVEWAY SLIDING GATES.

THESE WILL INCLUDE, BUT ARE NOT LIMITED TO KNOX GATE & KEY

SWITCHES.

- CONTRACTOR SHALL COMPLY WITH ALL LOCAL PERMITTING & FIRE

MARSHAL CODE REQUIREMENTS.

- CONTRACTOR SHALL SUPPLY ANY SHOP DRAWINGS NECESSARY TO

OBTAIN ALL ACCESS GATE PERMITS.

PEDESTRIAN GATE - DETAIL

SCALE:NTS

DRIVEWAY GATE - DETAIL

SCALE:NTS

SHEET 24 OF 46

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

6' O.C. TYP. 6' O.C. TYP.

11 1/2"

1x6 RED CEDAR PICKET

4x4 TREATED PINE POST

4-2x4 TREATED PINE

STRINGERS

2x12 RED CEDAR

BASE BOARD

FINISH GRADE,

SLOPE AWAY

FROM FOOTING

CONCRETE

FOOTING

NOTES:

1. CONTRACTOR TO SUBMIT SHOP DRAWINGS FOR APPROVAL PRIOR TO FABRICATION.

2. ALL HARDWARE TO BE PRE-FINISHED.

3. ALL FENCE SUPPORT MEMBERS SHALL BE TREATED PINE. ALL PICKETS TO BE RED CEDAR.

4. APPLY 2 COATS OF BEHR PREMIUM® SEMI-TRANSPARENT WATERPROOFING STAIN & SEALER TO PICKETS AT STAINED WOOD

FENCE. PREPARATION & APPLICATION PER PRODUCT'S GUIDELINE. CONTRACTOR TO SUBMIT COLOR SAMPLE (CEDAR ST-146, CHESTNUT ST-110, TUGBOAT ST-141) FOR APPROVAL PRIOR TO APPLICATION.

1" CHAMFER,

TYP.

2500 Summer Street, Suite 3228 Houston Texas 77007

P: 713.337.5830 www.asakurarobinson.com

KEIJI ASAKURA

T

R

R E

L A

P

E G

S

D

N

C A

R

E A

I S ET

T

A

S

ET

O F

T C

E

TI

H C

D

X

A S

E

11.19.2025

L400 FENCING DETAILS

FR VEHICLE ACCESS GATE -2

PERIMETER FENCE - DETAIL

SCALE:NTS

GATE OPERATOR - SECTION/ELEVATION DETAIL

SCALE:NTS

GATE OPERATOR - PLAN DETAIL

SCALE:NTS

MODEL: SD15 MODEL: SD15

PERIMETER FENCE - DETAIL

OPERATOR NOTES:

- GATE OPERATOR TO INCLUDE FIRE AND EMERGENCY ACCESS LOCK BOX WITH CABLE

MANUAL RELEASE.

- CONTRACTOR TO COORDINATE WITH GATE OPERATOR MANUFACTURER.

6' .H WOOD FENCE

SCALE:12"=1'-0"

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

L I M

I T L

A N

D S C

A P

E S

C O

P E O

F W

O R

K

L I M

I T L

A N

D S C

A P

E S

C O

P E O

F W

O R

K

SOD, TYP.

LIVE OAK, TYP.

DWARF WAX MYRTLE, TYP.

DWARF WAX MYRTLE, TYP.

TEXAS RED OAK, TYP.

STEEL EDGE, TYP.

14X6 FOOT VISIBILITY BUFFER

14X6 FOOT VISIBILITY BUFFER

LIMIT LANDSCAPE SCOPE OF WORK

LEGEND

EXISTING TREES

LIVE OAK

DWARF WAX MYRTLE

STEEL EDGING

RE: DETAIL 4/L500

SOD

TEXAS RED OAK

EQUAL

3" MULCH, SLOPE FOR

POSITIVE DRAINAGE

FROM BASE OF PLANT

PREPARED SOIL

MIX

UNDISTURBED

SUBGRADE

ROTOTILL OR SPADE BED @

FINISHED GRADE TO A DEPTH

OF 6", ADD SOIL MIXTURE TO

BRING BED TO 3" ABOVE FINISH

GRADE, WATER ADDED TO SETTLE

THE MIXTURE TO 2" ABOVE

FINISH GRADE

GROUNDCOVER - SEE PLANTING

SCHEDULE FOR SIZE & SPACING

SHRUB OR GROUNDCOVER LAYOUT

REFER TO PLANTING PLAN

SPACING

PER PLAN

VARIES

EQUALEQUAL

SPACING PLANTS/SF

6" O.C. 4.61

8" O.C. 2.60

9" O.C. 1.78

10" O.C. 1.66

12" O.C. 1.15

18" O.C. 0.50

24" O.C. 0.28

30" O.C. 0.18

36" O.C. 0.12

48" O.C. 0.07

STEEL EDGE - SET 3"

ABOVE FINISH GRADE

PROVIDE GAPS ON

SLOPE TO ALLOW BEDS

TO DRAIN

1 2

M A X

V A R

IE

S

T Y P

STEEL EDGING SHALL BE

INSTALLED BETWEEN

ALL GRASS AND PLANTING

BEDS

STEEL SPIKE @ 24" O.C. TYP.

PLANTING BED W/ PREPARED SOIL MIX

3" MULCH

4" - 14 GA. STEEL EDGING W/

BLACK PROTECTIVE COATING OR

APPROVED EQUAL

GRASS

M

IN

M

A X

M

IN

M

A X

6"

MIN.

NOTE:

FOR 200 GAL. TREE,

10' METAL T-POST

MAY BE REQUIRED FOR

EXTRA SUPPORT

3- 8' METAL T-POSTS W/ UV

RESISTANT MOLDED WHITE

VINYL CAP. ALL POLES TO BE

INSTALLED @ SAME HT. &

STAKE SHALL CLEAR ROOT

BALL BY 3-6"

MIN.& INTO GROUND @ 3' MIN.

2" MULCH, SLOPE FOR

POSITIVE DRAINAGE

FROM BASE OF PLANT

SCARIFY SIDES &

BOTTOM OF PIT

PREPARED SOIL MIX

UNDISTURBED SUBGRADE

12 GA. GUY

WIRES

1/2" X 12" NON-STRETCH

FABRIC W/ GROMMETS

SAUCER RING

4"-5" HT.

2% TYP.

2X-3X DIA. OF ROOTBALL

WRAP-AROUND TRUNK

PROTECTION

ROOT FLARE OF TREE VISIBLE

TREEDIAPER® TD48R, ROUND

SHAPE

2500 Summer Street, Suite 3228 Houston Texas 77007

P: 713.337.5830 www.asakurarobinson.com

KEIJI ASAKURA

T

R

R E

L A

P

E G

S

D

N

C A

R

E A

I S ET

T

A

S

ET

O F

T C

E

TI

H C

D

X

A S

E

11.19.2025

L500 PLANTING PLAN

TREE PLANTING DETAIL

SHRUB PLANTING DETAIL

SCALE: 38 "=1'-0"

STEEL EDGING DETAIL

SCALE: 38"=1'-0"

PLANTING PLAN

SCALE: 1"=20'

SCALE: 38 "=1'-0"

PLANTING SCHEDULE

QTY

COMMON NAME/BOTANICAL

NAME

CALIPER /

CONT.SIZE

HEIGHT SPREAD COMMENTS

TREES

7 EA

LIVE OAK

Quercus virginiana

4" CAL. 14'-16' 8' - 10' SINGLE TRUNK W/ STRONG

CENTRAL LEADER. FULL,

WELL-BRANCHED

4 EA

TEXAS RED OAK

Quercus buckleyi

30 GAL 8'-10' 6' - 7' SINGLE TRUNK W/ STRONG

CENTRAL LEADER. FULL,

WELL-BRANCHED

SHRUBS

790 SF

DWARF WAX MYRTLE

Myrica pusilla

3 GAL 18" - 20" 18" - 24" CONTAINER GROWN, FULL &

WELL ROOTED, PLANTED 24"

O.C., TRIANGULATED

SPACING

SOD

6,300

SF

ST. AUGUSTINE

Stenotaphrum secundatum

NA NA NA SOLID SOD, AS SHOWN PER

PLAN

PLANTING NOTES :

1. CONTRACTOR SHALL BE RESPONSIBLE FOR BECOMING FAMILIAR WITH ALL UNDERGROUND UTILITIES, PIPES AND

STRUCTURES. CONTRACTOR SHALL TAKE SOLE RESPONSIBILITY FOR ANY COST INCURRED DUE TO DAMAGE OF

THESE UTILITIES.

2. CONTRACTOR SHALL NOT WILLFULLY PROCEED WITH CONSTRUCTION AS DESIGNED WHEN IT IS OBVIOUS THAT

UNKNOWN OBSTRUCTIONS AND/OR GRADE DIFFERENCES EXIST THAT MAY NOT HAVE BEEN KNOWN DURING THE

DESIGN. SUCH CONDITIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE LANDSCAPE

ARCHITECT AND THE OWNER'S AUTHORIZED REPRESENTATIVE.

3. CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR NECESSARY REVISIONS DUE TO FAILURE TO GIVE SUCH

NOTIFICATION.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY COORDINATION WITH SUBCONTRACTORS AS REQUIRED TO

ACCOMPLISH PLANTING.

5. CONTRACTOR SHALL NOTIFY OWNER'S AUTHORIZED REPRESENTATIVE 72 HOURS (WEEKENDS NOT INCLUDED)

PRIOR TO COMMENCEMENT OF WORK TO COORDINATE PROJECT OBSERVATION SCHEDULE.

6. IF CONFLICTS ARISE BETWEEN SIZE OF AREAS ON PLANS OR LAYOUT OF PLANS, CONTRACTOR SHALL CONTACT

LANDSCAPE ARCHITECT FOR RESOLUTION. FAILURE TO MAKE SUCH CONFLICTS KNOWN TO LANDSCAPE

ARCHITECT WILL RESULT IN CONTRACTOR'S LIABILITY TO RELOCATE THE MATERIAL.

7. PROTECT ALL EXISTING TREES TO REMAIN. CONTRACTOR SHALL REPLACE ANY TREES DAMAGED DURING

CONSTRUCTION. CONTRACTOR SHALL PROVIDE FENCING, IF NECESSARY, AT THE TREE DRIP LINE TO PROTECT

TRUNK AND ROOTS AND TO PREVENT COMPACTION FROM VEHICLE TRAFFIC OR MATERIAL STORAGE BELOW TREES.

8. CONTRACTOR SHALL PROVIDE FOR THE FEEDING, WATERING, AND GENERAL MAINTENANCE OF TREES TO KEEP

THEM IN A HEALTHY CONDITION DURING CONSTRUCTION DURATION.

9. CONTRACTOR SHALL SUBMIT PHOTOS/PDFS OF REPRESENTATIVE TREES, SHRUBS, GRASSES, GROUNDCOVERS, AND VINES SHOWN ON THE PLANTING PLAN AND SCHEDULE, WITH INDICATION OF SPECIES, HEIGHT, WIDTH, AND CALIPER/CONTAINER SIZE. IF A NURSERY VISIT IS REQUIRED, THE CONTRACTOR WILL ARRANGE TO HAVE

THE PARTICULAR NURSERIES PREPARED TO SHOW PLANT MATERIAL. SHOULD CONTRACTOR INSTALL PLANT

MATERIAL INFERIOR TO INDUSTRY STANDARD OR DRAWING SPECIFICATIONS, IT IS AT CONTRACTOR'S RISK. ALL

SUBMITTALS ARE TO BE APPROVED PRIOR TO PLANTING. NO UNAPPROVED MATERIAL IS TO BE INSTALLED.

10. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FURNISH PLANT MATERIALS FREE OF PESTS AND DISEASES.

PRE-SELECTED OR "TAGGED" MATERIAL MUST BE INSPECTED BY CONTRACTOR AND CERTIFIED PEST AND DISEASE

FREE. IT IS THE CONTRACTOR'S OBLIGATION TO GUARANTEE ALL PLANT MATERIALS PER THE SPECIFICATIONS.

TAGS PLACED BY THE LANDSCAPE ARCHITECT MUST REMAIN ON MATERIAL THROUGHOUT THE DURATION OF

CONSTRUCTION.

11. CONTRACTOR SHALL STAKE ALL FINAL TREE LOCATIONS AND PLANTING BED LIMITS IN THE FIELD FOR APPROVAL

BY LANDSCAPE ARCHITECT PRIOR TO INSTALLATION.

12. STEEL EDGING SHALL BE PLACED BETWEEN ALL SHRUB BEDS AND TURF AREAS, AS WELL AS BETWEEN GRAVEL

BED AND PLANTING BEDS.

13. UPON INSTALLATION, ALL TREE MATERIALS SHALL BE STAKED BY THE METHOD INDICATED IN THE

SPECIFICATIONS AND PLANTING DETAILS.

14. IF REQUESTED BY OWNER, CONTRACTOR SHALL INSTALL DEEP ROOT BARRIERS AT ALL TREES WITHIN 5'-0" OF

CONCRETE WALKWAYS, STRUCTURES, WALLS, CURBS, ETC.

15. ALL PLANTS SHALL BE TRIANGULARLY SPACED, UNLESS OTHERWISE INDICATED.

16. ALL PLANTING BEDS SHALL RECEIVE A MINIMUM OF 3" OF APPROVED SHREDDED MULCH.

17. CONTRACTOR SHALL FINE GRADE ALL DISTURBED AREAS TO PROVIDE FOR PROPER DRAINAGE.

SHEET 26 OF 46

CONT.SIZE

4" C4"4"4""" CA" CA4" CACCCCCC" CA4"4444"" C"" CACCCCCCCA4444""" CA" CACC4" CAA444" C4444"""" CC4" CAAA44444" CA444""""" CCCCCACA444"""" CCCA44444 CA444 CC444444 C4 CCA44444 CA4444 CACC444 CCA44 C444 CCA44444444 CCAA444444 CCAAL.L.LLLLLLLLLLLLL..LLLLLLL.LL 1411111111111111

30 GA30330 GA30 GA30 GA330 GA30 GA0 GA0 G0 GAGGGGGAGAG30 G0 GGAAA30 GAAA30 GAAAA30 GA33330 GA30 GAGG0 GG0 GAGAG0 GAA30 GA0 GAAA0 GAAA3333033 GA30 GAGGAGGAGGAG0 GA0 GA0 GA30 GA30 GAAA33330 GA3330 GAGGGGGGGAAAAAA33300 GA30 GGGGGAAAA30030 GGGGGAAA3333300 GGGAGGGAAAAAAAAA330 G30 30 GA333330 GA000 GAGGGGAAAAAA33333333300 GGGGAAAGAAAA3333333000 GGGAAAAAA330 GAGAAAAAAA330000 GAAAAAA33000000 GAAAAGA333333000 GAAAAA3330 GGAAAALLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLL 8

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE

OE OE

OE OE OE OE OE OE OE OE OE

OE OE OE OE OE OE OE OE OE OE OE

OE OE OE OE OE OE OE OE OE OE OE OE OE OE OE

E

OE OE OE OE OE OE OE OE OE OE OE OE OE

O E

O E

O E

O E

ABOVE GROUND

AT&T BOX

D B

D B

D B

D B

DB DB DB DB DB

DB

PANEL "LA-1"

RE: 2/E-503

PB-2

PB-3

GATE OPERATOR

GATE OPERATOR

PB-5

PB-4

A

A

B

B

(1) 2"C W/ 2#12, 1#12G (NORTH LIGHTS)

(1) 2"C W/ 2#12, 1#12G (NORTH GATE)

(1) 2"C W/ 2#12, 1#12G (SECURITY ENCLOSURE)

(2) 4" C W/ (8) 250KCMIL, #2G (TRL-1)

(2) 4" C W/ (8) 250KCMIL, #2G (TRL-2)

(1) 2"C W/ 2#12, 1#12G (SOUTH LIGHTS)

(1) 2"C W/ 2#12, 1#12G (EAST GATE)

2#12, 1#12G (SOUTH LIGHTS)

2#12, 1#12G (EAST GATE

OPERATOR)

2#12, 1#12G (SOUTH LIGHTS)

(1) 2"C W/ 2#12, 1#12G (NORTH LIGHTS)

(1) 2"C W/ 2#12, 1#12G (SECURITY ENCLOSURE)

(1) 2"C W/ 2#12, 1#12G

(NORTH GATE OPERATOR)

2#12, 1#12G (SOUTH LIGHTS)

2#12, 1#12G (SOUTH LIGHTS)

(4) 4" C W/ (12) 400KCMIL, 2/0G

(1) 2"C W/ 2#12, 1#12G

(NORTH LIGHTS)

B

C

2#1, 1#6G (TRAILER 2 PANEL A)

2#1, 1#6G (TRAILER 2 PANEL B)

2#1, 1#6G (TRAILER 2 PANEL C)

2#1, 1#6G (TRAILER 2 PANEL D)

(2) 3/0, 1#4G (TRAILER 2 PANEL E)

PB-1

FUTURE

TRAILER 2

(COMPLETED

BY OTHERS)

FUTURE

TRAILER 1

(COMPLETED

BY OTHERS)

(1) 2"C W/ 2#12, 1#12G (NORTH LIGHTS)

(1) 2"C W/ 2#12, 1#12G (SECURITY ENCLOSURE)

(1) 2"C W/ 2#12, 1#12G (SECURITY ENCLOSURE)

P-1

P-2

P-3 P-4

P-5

P-6

F U L T O N

S T R E E T

2#1, 1#6G (TRAILER 2 PANEL A)

2#1, 1#6G (TRAILER 2 PANEL B)

2#1, 1#6G (TRAILER 2 PANEL C)

(2) 3/0, 1#4G (TRAILER 2 PANEL D)

PANEL "TR-2"

RE: 2/E-506

PANEL "TR-1"

RE: 2/E-505

4 2

2 2

(2) 4" C W/ (8) 250KCMIL, #2G (TRL-1)

(1) 2"C W/ 2#12, 1#12G (SOUTH LIGHTS)

(1) 2"C W/ 2#12, 1#12G (EAST GATE)

(2) 4" C W/ (8) 250KCMIL, #2G (TRL-1)

(1) 2"C W/ 2#12, 1#12G (SOUTH LIGHTS)

(1) 2"C W/ 2#12, 1#12G (EAST GATE)

(2) 4" C W/ (8) 250KCMIL, #2G (TRL-1)

JULIA STREET

0 20' 40'10'

HORIZONTAL SCALE 1"=20'

N

1. REFER TO E-501 FOR LIGHT FIXTURE SCHEDULE.

2. REFER TO T SERIES FOR TECHNOLOGY PLAN SHEETS.

3. SHADED LINEWORK IS BY OTHER DISCIPLINES AND

SHOWN FOR REFERENCE ONLY.

GENERAL NOTES

PB1

PROPOSED LIGHT POLE AND FIXTURE. LETTER SUBSCRIPT DENOTES TYPE.

RE: E506 FOR SCHEDULE

ELECTRICAL SYMBOLS LEGEND

A

PROPOSED ELECTRICAL PULLBOX. SUBSCRIPT DENOTES ID.

DB PROPOSED ELECTRICAL DUCT BANK

INDICATES QUANTITY OF 2" DUCTS

2" SCHEDULE 40 PVC CONDUIT UNLESS OTHERWISE NOTED

KEYED NOTES

TERMINATE CIRCUIT AT LOAD CENTER WITHIN

PREFABRICATED TRAILER. COORDINATE EXACT TIE

IN LOCATION ON SITE OR WITH MANUFACTURER.

INDICATES QUANTITY OF 4" DUCTS

SHEET 27 OF 46

APPROVED

ELECTRICAL PLAN

Plans and specifications to be in accordance with current national

Electric Code and City Building

Code. This plan shall be kept on job for Inspectors. Seperate

Permit for Electrical required.

Joplin Ford 04/20/26

ANNNNND NDNNNNNNDNDND DDND NDNDNNNNNNNDDDDDNNNNNNNDNNDDDDDDDNNNNNNDNNDDDNDDDDDDDDNNNNNNDNDND NDNDDDDDDDDDNNNNNNNNDDNDNDDNDDDDDDNNNNNNNDDDDDDDNDNNNNNNDNDDDDDDDDNDNNNNNNDDDNDDDNNNNNNNNNDDDNNNNNNNNDDDNDNNNNNNNNNDDDNDDDDNNNNNDDDDDNNNNNNDDDNNDDDDDNNNNDDDDNNNNNNDNNDDDNNNNNNNDDDDDNNNNNDDDDDFIXFFFIFIXFIXXFFIXIXFIXFIXFIXFIXFIIXXXFFIXXXXXXFIXXXXXXXXXXXIXFIXFIXIXXXXXXXFIXIIXXXFIIIFIXXXXXXXFIXXXXXFIXIIIXXXXXXIXIXXXXXIXIIXXXXFIIIXXXXFFIXIIXXXXXXXFFIIIXXXIXXXXXXXXXIXXFIIXXXXXXFIXXF XTUUTURUTUTURRTURTURTURTUTURRRRTUTUTURRRRRRRRT RRRRTURTURRRRTUTUUUTUTURRRRRRRTUTTTUTUTUURTTUTUTUUTURTTUTUTURRTUUUURTTTTUUURTURRTUUUTURTURTTTUURTURRRTUTTTTTUURRTUTUTUTURRRRRRRRTUTTUTUUUTURRTUUUUUUURRRRUUUURRRRRRRRRRRRRUURRRRRRRRRURRRRRRRRREEEEE.EEEEEEEEE.E.EEEEEEEEEE.EEEEEEE.EEEEEEEEE.EEEEEEEEE.EEEEEEEEEEEE..EEEEEE....EEEE...EEEE. LLLLELLELEELLLLLLLLLLLLLLLLLLLLLEELLLLLLLLLLLELLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLELLLLLLLLLLELLLLELLELLLLLLLLLLLLLLLELLLLLLLLELLLLLLEELLLLLEELLLLLLLEELLLEE

PULLULLULLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLBOXBOXBOBOXBOXBBBBOXBBOXBOXBOXOOOXOXBOXBOXBOXBOXOXBOOXBOXBOXOXXBOXXBOXBOBOBOXBBBOXOOOOBOXBOXBOXOOOOBOXBOXBOXXXXBOXBOBBBOXOBOOOOOOBOBOXOOOXBOXBOXXXXXBOXBOXBOBBBOXOOOOOOOBOXBOXOOBOOOOBOXOOXXXXXXXXXXXXXBBOOOOOOXBOXXXXXXXBOXBOOOOOOXXXOXBOXXXXBOBOBBOOOOOOOOXOXXXXXBBOXBOOOOOXOBOXXXXXXBOOXOOOOOXXXBBOOOOXXOXXBBOOXOOOOXXXXBBBOOOOXXXBOXBBBBBOBBOOOOOXBOXXXBBBBBOXOOOOOOXXXXXXXBBBBBBBOBOXOOOOOOOXXXXBBBBBBBBOBOOXXXXBOBBBBBBBBOOOOOOXBBBBBBBBBOOX. S. S. SSSSSSSSSSSSSSSSSSSSSS. S. SSSSS. SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS SSSSS. SSSSSSSSSSSSSSSSSSSSSSSSSSSSS... SSSSSSSSS. SSSSSS.. S. S. SSSSSSS.. SSSSSSSSUUBUUUBUUUUUUBUBBUBBUBBBUBUBUBSUUUUUUUUUBBBBUUUUUUUUUUBBUBBBUUUUUUUUUUBBBBUBBUUUUUUUBBBUBUUUUUUUUUBBUUUUUUUUUBUBUUUUUUUUUBUBUUUUUUBUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUU C

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

NET

36''

12"

FINISHED GRADE

2" CLEAR

24''

3500 PSI

CONCRETE

LIGHT POLE. RE: E-506 FOR LIGHT FIXTURE SCHEDULE

WIRING ACCESS. PROVIDE INTERIOR GROUNDING LUG

ACCESSIBLE FROM OPENING. PROVIDE STAINLESS

STEEL COVER WITH STAINLESS STEEL SCREWS.

FULL BASE COVER: MATCH MATERIAL OF POLE, EXCEPT

WHERE POLE IS CONCRETE, BASE COVER SHALL BE

STAINLESS STEEL.

CONNECT CONDUITS TO GROUNDING LUG AND

GROUNDING CONDUCTOR TO GROUND ROD.

PROVIDE BOTTOM NUT FOR LEVELING AND DOUBLE NUTS

ON TOP.

NO. 4 STEEL REINFORCING TIES ON 12" CENTERS.

CHAMFER EDGES ON BASE.

1" RIGID GALVANIZED CONDUIT.

RIGID GALVANIZED STEEL CONDUIT 12" PAST EDGE OF

CONCRETE BASE. PROVIDE CONDUIT TO PVC DUCT

ADAPTER. SEE PLANS FOR NUMBER REQUIRED.

GALVANIZED STEEL ANCHOR BOLTS, AS REQUIRED BY

MANUFACTURER FURNISHING POLE. ANCHOR BOLTS

SHALL BE SET VERTICAL.

EIGHT NO. 4 STEEL REINFORCING RODS.

THERMOWELD CONNECTOR.

3/4 " X 10'-0" COPPER CLAD STEEL GROUND ROD.

NO. 6 BARE STRANDED COPPER GROUND WIRE.

CONNECT TO GROUND ROD, CONDUITS,

REINFORCEMENT BARS AND GROUNDING LUG.

12' DEPTH FOR 35'H LIGHT POLE, OR 7' DEPTH FOR 20'H

LIGHT POLE. LIGHT POLE FOUNDATION CONSTRUCTED TO

WITHSTAND WINDSPEED OF 134 MPH.

POLE BASE NOTES:

SCALE:

LIGHT POLE BASE DETAIL

N.T.S.

E-501

T O

N O R T H

L

IG

H T S

CR

C

C

A

H

HA1-14

L A -1

LA1-16

TIME

SWITCH TS-1

T O

S O U T H

L

IG

H T S

TIME SWITCH TS-1

MICROPROCESSOR BASED,

PROGRAMMABLE 7 DAY WITH

365-DAY CALENDAR, DAYLIGHT

SAVINGS CHANGEOVER, LEAP

YEAR CORRECTED, LCD DISPLAY,

120V INPUT WITH MIN. 72 HOUR

BATTERY BACKUP. MAINTAINED

CONTACT OUTPUT. NEMA 3R

SURFACE MOUNTED ENCLOSURE.

SET TIME CONTROL FOR

PHOTOCELL-ON, 12AM-OFF M-F OR

AS DIRECTED BY OWNER.

PHOTOCELL

CONDUIT MOUNTED WITH

ADJUSTABLE LIGHT LEVEL,

TIME DELAY. 120V INPUT,

WEATHERPROOF HOUSING.

LOCATE AT TOP OF THE

RACK. ORIENT TO NORTH

CONTACTOR C-1

MECHANICALLY HELD, ELECTRICALLY OPERATED

WITH INTERPOSING CONTROL RELAY FOR 2-WIRE

CONTROL. 120V COIL, 20A, 208V, CONTACTS.

NEMA 3R ENCLOSURE WITH H-O-A IN COVER.

SCALE:

CONTACTOR CONTROL DIAGRAM

N.T.S.

E-501

L A -3

L A -5

L A -7

NOTES:

TYPE MANUFACTURER/DESCRIPTION

WATTSNO.

VOLTAGE

LAMPS

MOUNTING NOTES

LIGHT FIXTURE SCHEDULE

A

1. PROVIDE 20' VALMONT SQUARE NON-TAPERED STEEL POLE WITH NO PAINT FINISH, WITH ANCHOR BASE. (VALMONT #DS330-600W350-D1-GV-GV-FBC-AB OR APPROVED EQUAL).

2. PROVIDE 35' VALMONT SQUARE NON-TAPERED STEEL POLE WITH NO PAINT FINISH, WITH ANCHOR BASE. (VALMONT #DS330-600W350-D5-GV-GV-FBC-AB OR APPROVED EQUAL).

3. PROVIDE 35' VALMONT SQUARE NON-TAPERED STEEL POLE WITH NO PAINT FINISH, WITH ANCHOR BASE. (VALMONT #DS330-600W350-D6-GV-GV-FBC-AB OR APPROVED EQUAL).

4. FURNISH WITH LIGHT ENGINE AND SQUARE POLE UNIVERSAL MOUNTING ADAPTER HARDWARE. COORDINATE EXACT MANUFACTURER AND MODEL NUMBER WITH OWNER.

5. LIGHT POLE MUST BE RATED TO WITHSTAND A WINDSPEED OF 134 MPH.

B

1 1, 4, 5480V 179W POLE MOUNT

LITHONIA AREA LIGHT - 1 FIXTURE TYPE II MEDIUM

LITHONIA LIGHTING #DSX2 LED P2 50K T2M HVOLT

2480V POLE MOUNT

LITHONIA AREA LIGHT - 2 FIXTURES TYPE II MEDIUM

LITHONIA LIGHTING #DSX2 LED P2 50K T2M HVOLT

179W 2, 4, 5

C 3480V POLE MOUNT

LITHONIA AREA LIGHT - 3 FIXTURES TYPE II MEDIUM

LITHONIA LIGHTING #DSX2 LED P2 50K T2M HVOLT

179W 3, 4, 5

METRO - ELECTRICAL PULLBOX LOCATIONS

PULLBOX ID NORTHING EASTING

DETAIL

REFERNCE

KEYNOTES

PB-1 3117409.73 13868606.10 2/E501

PB-2 3117569.00 13868608.61 2/E501

PB-3 3117565.33 13868679.22 2/E501

PB-4 3117562.47 13868734.14 2/E501

PB-5 3117401.84 13868717.83 2/E501

METRO - ELECTRICAL LIGHT POLE LOCATIONS

LIGHT POLE ID NORTHING EASTING LUMINARE TYPE KEYNOTES

P-1 3117409.05 13868619.20 A

P-2 3117537.29 13868612.64 B

P-3 3117420.93 13868668.73 C

P-4 3117534.58 13868677.62 B

P-5 3117408.04 13868719.97 B

P-6 3117563.54 13868738.75 A

SHEET 28 OF 46

APPROVED

ELECTRICAL PLAN

Plans and specifications to be in accordance with current national

Electric Code and City Building

Code. This plan shall be kept on job for Inspectors. Seperate

Permit for Electrical required.

Joplin Ford 04/20/26

EASEAEASEEASEASEASEASAASEASEASAEASEASEEAEEASAAEAASEASEEAAAEASEASAASEEEEAASSSSEEEASAAASSSASSSEAAEASSSASSEASAASASASSSSSSEEAAASSSASASSEAASSSEASEAAAAAAAAASSASSSSSEAAAAASASSSSSASSEASAAASAASSSSASASSSEASAAAAAAAASSSSSSSSSAAAASAASSSAAAAAAASASASAAASSSSSSSSSAAAAAAAASSSSSSSAAASAAAASSAASSEAAAASAASAASSSTITTTINITIINNNNNINTININTINTITINTINNTINTITINNNNININTINNNTINNNNNIINNNNNNNIINTINNNNNTTITITINTTINTININNTTINTTTIITITTTIIITINTTTTTIIIINNTTTTTIINNNTTIIINNNNNNNTINNNNNNTTTTTIITTIIINNNNNNTTNNNNNNNNNNTNNNNNNNNNTTTTITTTTTIINNNNNNNNNNGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG

13868619 20

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

KEYED NOTES FOR DUCT SECTIONS UNDER PAVEMENT

1 INSTALL CONDUIT SPACERS EVERY 5'.

FINAL FINISHED GRADE. WHERE GRADE IS IN

TURF, ADD MIN 4" SEEDING AND TOPSOILING -

PAYMENT IS INCIDENTAL TO DUCT BANK LINE ITEM

3" 3"

8 3/8"

/8

DETECTABLE WARNING

TAPE

M

IN

C O V E R

U N D E R

P A V E M E N T

TYP.

/8

2"

12.75"

3" 3"

2 3/8" 2 3/8"

DETECTABLE WARNING

TAPE

TYP.

M

IN

C O V E R

U N D E R

P A V E M E N T

SCALE:

2 WAY - 2" DUCT BANK

N.T.S.

E-502 SCALE:

1 WAY - 2" DUCT BANK

N.T.S.

E-502

3500 PSI CONCRETE

(TYP). REFER TO CIVIL

SPECIFICATIONS

WARNING TAPE

M

IN

C O V E R

3" MIN

3" MIN

3" MIN3" MIN

THRU 1/4" SLEVE

SOIL THAT WILL PASS

4" PVC CONDUIT

DIRECT BURIED (TYP)

3" MIN (TYP)

COMPACTED SOIL

(SEE SPECIFICATIONS)

UNDISTURBED SOIL

3" MIN (TYP)

4" PVC CONDUIT

DIRECT BURIED (TYP)

WARNING TAPE

M

IN

C O V E R

3" MIN

3" MIN

3" MIN3" MIN

THRU 1/4" SLEVE

SOIL THAT WILL PASS

COMPACTED SOIL

(SEE SPECIFICATIONS)

UNDISTURBED SOIL

3" MIN (TYP)

2" PVC CONDUIT

DIRECT BURIED

M

IN

C O V E R

WARNING TAPE

THRU 1/4" SLEVE

SOIL THAT WILL PASS

3" MIN

3" MIN

3" MIN3" MIN

COMPACTED SOIL

(SEE SPECIFICATIONS)

UNDISTURBED SOIL

SCALE:

4-WAY, 4"C DIRECT BURIED

N.T.S.

E-502

TYPICAL CONDUIT TRENCH DETAIL

SCALE:

1-WAY, 2"C DIRECT BURIED

N.T.S.

E-502

TYPICAL CONDUIT TRENCH DETAIL

SCALE:

2-WAY, 4"C DIRECT BURIED

N.T.S.

E-502

TYPICAL CONDUIT TRENCH DETAIL

WARNING TAPE

M

IN

C O V E R

3" MIN

3" MIN

3" MIN3" MIN

THRU 1/4" SLEVE

SOIL THAT WILL PASS

2" PVC CONDUIT

DIRECT BURIED (TYP)

3" MIN (TYP)

COMPACTED SOIL

(SEE SPECIFICATIONS)

UNDISTURBED SOIL

3" MIN (TYP)

SCALE:

4-WAY, (2) 2"C, (2) 4"C DIRECT BURIED

N.T.S.

E-502

TYPICAL CONDUIT TRENCH DETAIL

WARNING TAPE

M

IN

C O V E R

3" MIN

3" MIN

3" MIN

THRU 1/4" SLEVE

SOIL THAT WILL PASS

4" PVC CONDUIT

DIRECT BURIED (TYP)

3" MIN (TYP)

COMPACTED SOIL

(SEE SPECIFICATIONS)

UNDISTURBED SOIL

3" MIN (TYP)

3" MINTHRU 1/4" SLEVE

SOIL THAT WILL PASS

SCALE:

6-WAY, (2) 2"C, (4) 4"C DIRECT BURIED

N.T.S.

E-502

TYPICAL CONDUIT TRENCH DETAIL

SHEET 29 OF 46

APPROVED

ELECTRICAL PLAN

Plans and specifications to be in accordance with current national

Electric Code and City Building

Code. This plan shall be kept on job for Inspectors. Seperate

Permit for Electrical required.

Joplin Ford 04/20/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

INCOMING POWER

FLOOR TYPE

FLANGE (TYP)

STAINLESS STEEL B-LINE OR EQ.

PROVIDE END CAPS (TYP. ALL

SUPPORTS)

PROVIDE 2" RGS

SUPPORT POSTS

(TYP FOR 2)

TURF

ELEVATION VIEW - FRONT OF RACK

10' x 3/4" COPPER-CLAD

STEEL GROUND ROD (TYP)

12" (TYP)

EXOTHERMIC

WELD (TYP)

EXOTHERMIC BOND TO RACK,

18" ABV GRADE (TYP)1" PVC WITH #4/0

BARE COPPER

GROUND

1" PVC WITH #4/0

BARE COPPER

GROUND

NOTE: ALL CONDUITS ABOVE

GRADE TO BE RGS UON. ALL

CONDUIT BELOW GRADE TO

BE SCH. 40 PVC UON.

ELECTRICAL CURRENT TRANSFORMER (CT).

COORDINATE WITH CENTERPOINT ENERGY

CT

6"X6"X36" SS WRWY W/ HINGED COVER

LIGHTING

CONTACTOR

PHOTOCELL

2"

3" TYP ALL SIDES

84"

98"

TO PB-1

TO PB-2

DISCONNECT

SWITCH "DS-1"

1"

4" 4"

(4) 2"

TO HANDICAP LIGHTS

30"

(4) 4"

LOAD

CENTER

"LA-1"

DS-1 2"

(4) 4"

(2) 2"

(4) 4"

(4) 4"

98"

#4 BARS SPACED

12" OC ALL WAYS

48"

CONCRETE SLAB. FINISH

SLAB TOP SMOOTH AND

LEVEL 1" ABOVE GRADE

UTILITY METER

DISCONNECT SWITCH "SW1"

LOAD CENTER "LA-1"

4"H X 3' X 8' REINF. CONC.

MAINT. PAD USE #4 BARS AT

12"OC ALL WAYS

1/2 "x4" DEEP (FULL PAD DEPTH)

EXP. JOINT, TYP.

3/4" CHAMBER

SCALE:

ELECTRICAL EQUIPMENT RACK PLANVIEW

N.T.S.

E-503

SCALE:

ELECTRICAL EQUIPMENT RACK

N.T.S.

E-503 SHEET 30 OF 46

APPROVED

ELECTRICAL PLAN

Plans and specifications to be in accordance with current national

Electric Code and City Building

Code. This plan shall be kept on job for Inspectors. Seperate

Permit for Electrical required.

Joplin Ford 04/20/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

LOAD DESCRIPTION

CONNECTED LOAD

KVA

NORTH LIGHTING CKT 0.54

UTILITY LOAD ANALYSIS

DEMAND LOAD

KVA

0.68

269.75 KVA / 360V = 749.30A @ 208V

1000 A SERVICE EXCEEDS NEC REQUIREMENTS

CKT CKT BKR.KVA LOAD DESCRIPTION WIRE* C"BKR.KVALOAD DESCRIPTION WIRE* C"

VOLTAGE: 120/208V 3 4 W AIC: REMARKS:*

SURFACE

NEMA 1

FLUSH

NEMA 3R

MAINS:

LUGS:

AMPS

SUB - FEED

1000 MLO MCB

FEED - THRU

PANEL:

LA-1

KVA CONNECTED LOAD

KVA DEMAND

AMPS DEMAND @ 208V

PHASE A PHASE B PHASE C

10,000

* ALL BRANCH CIRCUITS ARE 2 #12, 1 #12G THWN CU IN 2"C (UON)

SOUTH LIGHTING CKT 1.45 1.82

NORTH GATE OPERATOR 0.75 0.75

EAST GATE OPERATOR 0.75 0.94

TRAILER NO. 1 119.60

TRAILER NO. 2 145.60

SURFACE GRADE

120/208V,3-PHASE, 1000A

ELECTRICAL SERVICE.

COORDINATE WITH CENTERPOINT

ENERGY

DS

-1

2#12, #12G (SOUTH LIGHTS)

1000A, 3P, NEMA

3R DISCONNECT

SWITCH "DS-1"

2#12, #12G (NORTH LIGHTS)

METER

CT

ELECT

PANEL

"LA-1"

LIGHTING

CONTACTOR

2#12, #12G (NORTH GATE OPERATOR)

2#12, #12G (EAST GATE OPERATOR)

PHOTOCELL

1/0 BARE

COPPER

GROUND

1/0 BARE COPPER

GROUND

(4) 4"C W/ (12) 400

KCMIL (3A, 3B, 3C, 3N),

2/0G. GROUP PHASES

TOGETHER IN SAME

CONDUIT

NORTH LIGHTS .27

.27

SOUTH LIGHTS .72

.72

NORTH GATE OPER. .37

.37

EAST GATE OPER. .37

.37

TRAILER NO.1 (6), 250

KCMIL

#2 G

39.8

39.8

39.8

48.5

SECURITY ENCLOSURE

87.53 KVA 94.98 KVA 87.62 KVA

87.89 KVA 95.16 KVA 88.18 KVA

422.55 A 457.50 A 423.94 A

2#12, #12G (SECURITY ENCLOSURE)

269.05SUB-TOTAL LOAD 269.75

.36

SECURITY ENCLOSURE 0.36 0.36

119.60

145.60

TRAILER NO.2

48.5

48.5 #2 G

(4) 4"C W/ (12) 400 KCMIL

(2A, 2B, 2C, 2N), 2/0G.

GROUP PHASES

TOGETHER IN SAME

CONDUIT

LIGHTING CONTROLS

TIME SWITCH (TS-1)

SPACE

CKT CKT BKR.KVA LOAD DESCRIPTION WIRE C"BKR.KVALOAD DESCRIPTION WIREC"

VOLTAGE: 120/208V 3 4 W AIC: REMARKS:*

SURFACE

NEMA 1

FLUSH

NEMA 3R

MAINS:

LUGS:

AMPS

SUB - FEED

450 MLO MCB

FEED - THRU

PANEL:

TRL-1

KVA CONNECTED LOAD

KVA DEMAND

AMPS DEMAND @ 208V

PHASE A PHASE B PHASE C

10,000

2#1, #6G

(2) 3/0, #6G

20.8

20.8

46.80 KVA 46.80 KVA 26.00 KVA

225.00 A 225.00 A 125.00 A

TRAILER 1 PANEL A

TRAILER 1 PANEL B

TRAILER 1 PANEL C

TRAILER 1 PANEL D

SPARE

CKT CKT BKR.KVA LOAD DESCRIPTION WIRE C"BKR.KVALOAD DESCRIPTION WIREC"

VOLTAGE: 120/208V 3 4 W AIC: REMARKS:*

SURFACE

NEMA 1

FLUSH

NEMA 3R

MAINS:

LUGS:

AMPS

SUB - FEED

500 MLO MCB

FEED - THRU

PANEL:

TRL-2

KVA CONNECTED LOAD

KVA DEMAND

AMPS DEMAND @ 208V

PHASE A PHASE B PHASE C

10,000

2#1, #6G

59.80 KVA 39.00 KVA 46.80 KVA

287.50 A 187.50 A 225.00 A

TRAILER 2 PANEL A

TRAILER 2 PANEL B

TRAILER 2 PANEL C

TRAILER 2 PANEL D

SPARE

TRAILER 2 PANEL E

20.8

20.8

46.80 KVA 46.80 KVA 26.00 KVA

59.80 KVA 39.00 KVA 46.80 KVA

(2) 3/0, #4G

2#1, #6G

2#1, #6G

2#1, #6G

2#1, #6G

2#1, #6G

(6), 250

KCMIL

ELECT

PANEL

"TRL-1"

ELECT

PANEL

"TRL-2"

DS-2

(2) 4"C W/ (8) 250 KCMIL

(2A, 2B, 2C, 2N), #2G. (2) 4"C W/ (8) 250 KCMIL

(2A, 2B, 2C, 2N), #2G.

DS-3

2#1, #6G (TRAILER 1 PANEL A)

2#1, #6G (TRAILER 1 PANEL B)

2#1, #6G (TRAILER 1 PANEL C)

(2) 3/0, #6G (TRAILER 1 PANEL D)

2#1, #6G (TRAILER 2 PANEL A)

2#1, #6G (TRAILER 2 PANEL A)

2#1, #6G (TRAILER 2 PANEL A)

2#1, #6G (TRAILER 2 PANEL A)

(2) 3/0, #6G (TRAILER 2 PANEL D)

600A/3P/450AF NEMA

3R DISCONNECT

SWITCH "DS-2"

600A/3P/500AF NEMA

3R DISCONNECT

SWITCH "DS-3"

#4 BARE

COPPER

GROUND

#4 BARE

COPPER

GROUND

SHEET 31 OF 46

APPROVED

ELECTRICAL PLAN

Plans and specifications to be in accordance with current national

Electric Code and City Building

Code. This plan shall be kept on job for Inspectors. Seperate

Permit for Electrical required.

Joplin Ford 04/20/26

YYYYY YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY YYYYYYYYYYYYYYYYYYYYYYYYYYYYYY YYYYYYYYYYYYYYYYYY YYYYYYYYYY YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY LLLLLLLLLLLLOLOOOLOLOLOOLOLOOOOOLLOLOLLLLLLLOLOOOLOOOLOOOOLOOLOLLLLLOLOOOLOLOOOOLOLLOLOLLLLLLLLOLOOOLOOOOOOOLLLLLLLLLLLOLOLOLOOLOOLOOLOOLLOLLLLOLOOOOOOLOOOLLLLLLLLLLOOLOLOOOOLOLOOOOLLLLLLLLOOOOOOOOOLLLLLOOLOLLLLLLLLLLOOOOLLLLLOOOOOLLOOLLLLLOOOOLOLLLLLLLLOLLLLLLLLLLLLLLOOOOOLLLLLLLOLOOLLLLLOOLLLOOOLLLLOLLOLLLLLLLLLLOLLOLOOOOLLLOOOOOOLLOOOOOOLLOOOOOOLLOOOOOOOLOOOOLOOOOOOOOADADADAAAAADADDDADADDADADDDDDDDADADDDADAAAADADAADADADADDDDDDDDDDADDADAAAAADAAADDDDADADDDDDDAAAAADAADADAAADDDDDDDADAAAADAAAAAAAAAADDDDDDDDDAAAADAAAAAAAAAAAADADADADADDDDAAAAAAAAAAAADAAAADDDDAAAAAAAAAAAAAADDDDDDAAAAAADAAAAAAAADADDDAAAAAAAAAADADDADAAAAAAAAADAAAAADDDDADAAADAAAAADAAAADADAADAAAAAAAAAADDAAAAAAAAAAADAAAAAAAAAADAAADAAAAAAAAAAADAADAAAAAADDDDDDDDDAADDDDDAADDADDDDAADDDADADDDDDDDDDAADDDDDDDDDDAADDDDAAADDADAADDAADAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAANNNNNNNNNNNNNNNNNN

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

POWER FROM PANEL

"LA-1"

FLOOR TYPE

FLANGE (TYP)

STAINLESS STEEL B-LINE OR EQ.

PROVIDE END CAPS (TYP. ALL

SUPPORTS)

PROVIDE 2" RGS

SUPPORT POSTS

(TYP FOR 2)

TURF

ELEVATION VIEW - FRONT OF RACK

10' x 3/4" COPPER-CLAD

STEEL GROUND ROD (TYP)

12" (TYP)

EXOTHERMIC

WELD (TYP)

EXOTHERMIC BOND TO RACK,

18" ABV GRADE (TYP)1" PVC WITH #4/0

BARE COPPER

GROUND

1" PVC WITH #4/0

BARE COPPER

GROUND

NOTE: ALL CONDUITS ABOVE

GRADE TO BE RGS UON. ALL

CONDUIT BELOW GRADE TO

BE SCH. 40 PVC UON.

LOAD

CENTER

"TRL - 1"

3" TYP ALL SIDES

60"

74"

TO TRAILER 1

30"

DS-2

2"

(2) 4" (4) 2"(4) 4"

74"

#4 BARS SPACED

12" OC ALL WAYS

48"

CONCRETE SLAB. FINISH

SLAB TOP SMOOTH AND

LEVEL 1" ABOVE GRADE

DISCONNECT SWITCH

"DS-2"

LOAD CENTER "TRL-1"

4"H X 3' X 8' REINF. CONC.

MAINT. PAD USE #4 BARS AT

12"OC ALL WAYS

1/2 "x4" DEEP (FULL PAD DEPTH)

EXP. JOINT, TYP.

3/4" CHAMBER

SCALE:

ELECTRICAL EQUIPMENT RACK "TRL-1" PLANVIEW

N.T.S.

E-505

SCALE:

ELECTRICAL EQUIPMENT RACK "TRL-1"

N.T.S.

E-505

SHEET 31A OF 46

APPROVED

ELECTRICAL PLAN

Plans and specifications to be in accordance with current national

Electric Code and City Building

Code. This plan shall be kept on job for Inspectors. Seperate

Permit for Electrical required.

Joplin Ford 04/20/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

POWER FROM PANEL

"LA-1"

FLOOR TYPE

FLANGE (TYP)

STAINLESS STEEL B-LINE OR EQ.

PROVIDE END CAPS (TYP. ALL

SUPPORTS)

PROVIDE 2" RGS

SUPPORT POSTS

(TYP FOR 2)

TURF

ELEVATION VIEW - FRONT OF RACK

10' x 3/4" COPPER-CLAD

STEEL GROUND ROD (TYP)

12" (TYP)

EXOTHERMIC

WELD (TYP)

EXOTHERMIC BOND TO RACK,

18" ABV GRADE (TYP)

1" PVC WITH #4/0

BARE COPPER

GROUND

1" PVC WITH #4/0

BARE COPPER

GROUND

NOTE: ALL CONDUITS ABOVE

GRADE TO BE RGS UON. ALL

CONDUIT BELOW GRADE TO

BE SCH. 40 PVC UON.

3" TYP ALL SIDES

60"

TO TRAILER 2

30"

DS-3

2"

(2) 4" (5) 2"

74"

(4) 4"

LOAD

CENTER

"TRL - 1"

74"

#4 BARS SPACED

12" OC ALL WAYS

48"

CONCRETE SLAB. FINISH

SLAB TOP SMOOTH AND

LEVEL 1" ABOVE GRADE

DISCONNECT SWITCH

"DS-3"

LOAD CENTER "TRL-2"

4"H X 3' X 8' REINF. CONC.

MAINT. PAD USE #4 BARS AT

12"OC ALL WAYS

1/2 "x4" DEEP (FULL PAD DEPTH)

EXP. JOINT, TYP.

3/4" CHAMBER

SCALE:

ELECTRICAL EQUIPMENT RACK "TRL-2" PLANVIEW

N.T.S.

E-506

SCALE:

ELECTRICAL EQUIPMENT RACK "TRL-2"

N.T.S.

E-506

SHEET 31B OF 46

APPROVED

ELECTRICAL PLAN

Plans and specifications to be in accordance with current national

Electric Code and City Building

Code. This plan shall be kept on job for Inspectors. Seperate

Permit for Electrical required.

Joplin Ford 04/20/26

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

CAM-01

DB DB DB DB DB DB DB

DB DB DB DB

CAM-05

CAM-04

CAM-02

CAM-03

HH-2

GATE OPERATOR

GATE OPERATOR

PB-T5

FUTURE

TRAILER 2

(COMPLETED

BY OTHERS)

FUTURE

TRAILER 1

(COMPLETED

BY OTHERS)

CAMERA POLE

(3) 2"C:

(1) 2"C W/ 1" PVC INNERDUCT W/

FSM-NC-SH-NL>TRAILER 1

(1) 2"C W/ 1" PVC INNERDUCT W/

FSM-NC-SH-NL>TRAILER 2

(1) 2"C EMPTY W/ PULLWIRE

1"C EMPTY W/ PULLWIRE

(4) 2"C:

(1) 2"C W/ 1" PVC INNERDUCT W/

FSM-NC-SH-NL>SEC ENCL 1

(3) 2"C EMPTY W/ PULLWIRE

(3) 2"C EMPTY W/ PULLWIRE

(1) 1"C EMPTY W/ PULLWIRE

METRO SECURITY

ENCLOSURE

RE: 2/T-504

JULIA STREET

F U L T O N S T R E E T

2"C EMPTY W/ PULLWIRE

2"C EMPTY W/ PULLWIRE4

HH-3

D B

1"C EMPTY W/ PULLWIRE

(2) 4" C

(1) 4"C W/ (3) 1" PVC INNERDUCT

INNERDUCT 1: FSM-NC-SH-NL>SEC ENCL 1

INNERDUCT 2: FSM-NC-SH-NL>TRAILER 1

INNERDUCT 3: FSM-NC-SH-NL>TRAILER 2

(1) 4"C EMPTY W/ PULLWIRE

(2) 4" C:

(1) 4"C W/ (3) 1" PVC INNERDUCT

INNERDUCT 1: FSM-NC-SH-NL>SEC ENCL 1

INNERDUCT 2: FSM-NC-SH-NL>TRAILER 1

INNERDUCT 3: FSM-NC-SH-NL>TRAILER 2

(1) 4"C EMPTY W/ PULLWIRE

MATCH LINE ~ T-202

ENTRANCE GATE ENLARGED VIEW

RE:1/T-301

EXIT GATE ENLARGED VIEW

RE:2/T-301

1. REFER TO T-500 FOR TECHNOLOGY DETAILS.

2. REFER TO E-200 SERIES FOR ELECTRICAL PLAN

SHEETS.

GENERAL NOTES

PROVIDE NEW CAMERA POLE FOR INSTALLATION OF

CAMERA. POLE SHALL BE SAME MODEL AS LIGHT POLE.

REFER TO 1/ E-501 FOR LIGHT POLE DETAILS AND

FOUNDATION REQUIREMENTS.

PROPOSED CCTV CAMERA LOCATION. RE: 4/T-501 FOR

ROUGH-IN DETAIL.

PROVIDE 100' SLACK COIL FIBER CABLES FOR FUTURE

TRAILERS IN PULLBOX NOTED. FIBER CABLES TO BE

EXTENDED AND TERMINATED BY METRO IT IN FUTURE

TRAILER PROJECT.

PROVIDE EMPTY DUCT W/ PULLWIRE AND STUB UP TO

TRAILER. FIELD CONFIRM EXACT ROUGH-IN REQUIREMENTS

AND LOCATION PRIOR TO INSTALLATION.

PROVIDE 30' SLACK COIL FIBER CABLES FOR FUTURE NIE

INSTALLATION IN WIREWAY. FIBER CABLES TO BE

EXTENDED AND TERMINATED BY METRO IT ONCE NIE IS

INSTALLED.

KEYED NOTES

0 20' 40'10'

HORIZONTAL SCALE 1"=20'

N

SCALE:

PROPOSED TECHNOLOGY PLAN

1" = 20'

T-201

PB1

CAMERA MOUNTED ON LIGHT POLE. OWNER PROVIDED AND INSTALLED.

RE: T-501 FOR DETAILS

TECHNOLOGY SYMBOLS LEGEND

PROPOSED COMMUNICATIONS PULLBOX. SUBSCRIPT DENOTES ID. RE: T-503

FOR SCHEDULE. RE: 2/E-501 FOR DETAIL.

PROPOSED COMMUNICATIONS DUCT BANK

INDICATES QUANTITY OF 2" DUCTS

2" SCHEDULE 40 PVC CONDUIT UNLESS OTHERWISE NOTED

DB

INSTALL NEW FIBER IN EXISTING DUCT INFRASTRUCTURE

INDICATES QUANTITY OF 4 DUCTS

PROPOSED COMMUNICATIONS HANDHOLE. SUBSCRIPT DENONTES ID.

RE: T-503 FOR INSTALLATION SCHEDULE

HORIZONTAL DIRECTION DRILL RE: 1/T-505

SHEET 32 OF 46

APPROVED

ELECTRICAL PLAN

Plans and specifications to be in accordance with current national

Electric Code and City Building

Code. This plan shall be kept on job for Inspectors. Seperate

Permit for Electrical required.

Joplin Ford 04/20/26

GGGGGGHHTHTHHT HHTHTHTHT HT HTHHTHTHHHT TTHTHTHTTTHHHHHHHTTTHHHHHHTTTHTTHHTHHHHTHTTHTHTTTTTTHHHHHHTTHTTTTHTHTHHTHTHHTT TTHHHHTHHTTTTTTTTHHHHHHHTTTTHTTTTHHHHHHTTTHTHHHHHHHTTTTTTTTTTHHHHHHTTTHTTTTHTHHHTTTHHHHHHHHTTTTTTTTTHHHHHHHTTTTTTTTHHHHHHHTTHHHHHHHTTTHHHHHTTHHHHHTTTTTHHHHHHHHTTTTTT POPOPOLPOLPOLPPPOOPOLOPOPOPOOOPOOPOLPOLPOLPOPOLPPOPOLPOLPPPPPPPPPOOPOOOOLOLPOLOOOLLLLPOLLLOLLLLPPPOPPOLPPPOLPOPPOOOOOPOOOLOLLLLOLPPPPPPOOOOOPOOPOLOPOLOLPOLOLLLPPPOOOOOOOOPOLOOOLPOLPOLOLLLPOLPOLOLPPPPOOOPOOOOOLOPOOPOLLPOLPPPOPOOLOLLLPPPPPPOOOLLOLPPPOLLLPPOLPPPPOLLLPPPOPP LLLLPPPPPPOOOOOLLLLPPOPPOLLLLLPOLLOLPPPPOLOOOOLOLLLLLLLLLPPPPPOOPOOOLLLLLPPPPPOOOOOLLLLLLLOLLLLPPPPPPPOLOOOOOOPOLLLLLLLLPPPOPOOLLLLLLLLLLLLPPPOLPOOLLLLLLLLLPPOOLLLLLLLLEEEEEEEEE. EEEE.EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE.EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE OWOWOOWOWOOOOOOOOWOWOWOWOWOWNOWWOWNOWNWNOOOOOOOWOWOOWOWWWWWWWWWWWWWWOWOWOOOOWOWWWWWWWWNWWWWOWOOOOOWOWWOWWOOOOOOOOWOWWWWWWOWWOOOOWOOWOOWWWOWWWWWWWWWOOOOOWOWOWOOWWOWWWWWWWWWWWWOOOOOOOOWWWWWWWWWOWWWOOOOOOOWWWOWWWOOOOOWWWOWWWWWOWOOWOOWOOOWWOWWWWWWWWWWOOOOOWWWWWWWWWWWWWOOOOOOOWWWWWWWWOOOOOOWOOOOWWWWWOOOWOOOOOOWWWWOWOOWOOOOWOOWWWWWOWWWWWWWWOWOOOOOOOWWWWWWWWWWWWWWWWNOOOOOWWWWWWWWWWOOOWWWNNOOOOOWWWWWWW

TIIIOIIOOOOOOOIIIIOOOOIIIOOOIOOOIOIIOOOOOIIOOOOOOOOOOOOOIIIOOOOIIOOOOOIIOOOOOOIOOOOOOOOIOOOOOOOOIOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOONNNNSNNSNNSSSSNSNSSNNNNNNSSSSSSSSSSSSSNNNNNNSSSSSSNNNNSNNNNSNNNNNSSNNNNNNSNNSNNNSNNNNNNNSNNNNNNSSSNNSNSSSSNNNNSSSSNNNSSSSSSSSNSSSNSNSSSSNNNSSNSSSS PULPULPPPULPUPPULPUPULPULULLLLPULPULPPULPPULULLPULPUPPPPULPPPPPPPPPPPPPUPUPPPPPPUPPPPPUPPPPPPPPPPUPULUUUUUUUUUUUUUUULLLULLLLULPPPPUPPPPUUUUUUUUPUUUUUUUUUULLLLPPUPPPPUUUUUUUUUUUPULULULPUPPPPPPPUPUUPUPUUUUUULLLLLLLLLPUPPPPPPPUUUUUUUUPUUUPUPPPPPPUPPPPUUUUUUUUPPPPPUUUUUUUUUUU LBBBBOBLBOOOOOLBOOOLBLBLBLLLLBBBBBBOBOOOLBOOLLLBLLLBBLBBBBOBOOOOOOOBOBOOBOOOOOLBOBOOOOOBOOOOOOBLBOOOOBOOLBBOOLLLLLLLLBBBOOOLLLLLLLLLBBBBOOLLLLLLLBOLLLLLLBBBOLLLLLLBBBBBOOLLLBBBOLLBLLLLBBBBBBBBBBBB XXXXXXXXXX.X. XXXXXXXXX.XXXXXXXXXXXXXXXXX.XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX

0011111111 FFFF1FF1F11111111FFFFFFFFFFFFF1 11 FF1FFF1FFFFFFFF1 11F1 FFFFFFFFFFFFF1F1 F111FFFFF1FFFFFFF111111FFFFFFFFFFFF1 1F11111FFFFFFFFFFFFFFFFFF1FF1FFFFFFFFFFFFFF FFFFFFFFFFFFFFFFFFFFFFFFOR OR OOOROOROR OOROOORRORROOROROROROORORRRRRRRRRRRRRORRRROROROROROOR OOROORRORRRORRRRRRROR OROROROOOORRRRRRRRROORORRRRRROOROOOROROOORORRRRRROROOOORORORRRROROOOROOOOOORRRRRRROOOROOOOORRRROOOOORRRRRROOOROROOOOOORRRRORROOOOOROORORROR OOOOOORORROROOORORRRRRRRRRRROOOOORRRRRRROR OORRRORRRROOOOOOORRRRRRRRROOOOORRROOOORRRRRRRDETDDETDETDETDETDETDETDETDETDDDDDDEDDETDETDEEEEEEEEEEEETTTDETTDETDEDDDDDDDDDDDDDDDDEEEEDETEEEETTTDETDETTTDDDDDDDDDDDDDDDDEEEEEEDETTTDETDETDETDETTETDETDEDEDDEDDDDDDDEEEEETTDETDEEEDEEEEETTTETEEEEEDEDETDETETTTTEEDEEETETTTTTDETDEEEETETDETTTDETTTDDDDDDEEEEETTTTTTETTTDDDDDDDDETDEEETTDETTTTTDDDDDETEEEDEETTETTTTTTDETDDDDETEETETTTTTTTDDETETTDD TTTDDETDDDETDEEETTDETTTEEETTDETTTDDDDDEETTTTTDDDDDDDDEEETTTTTTTDDDDDDEEEEETTTTTTAAAILAIILAILLAILAILLAAAAAAAIAAAIAILAILLLLLLAILAAAILAAAAAAAAILLLLLLAAAAAAAAAAIAILLLAILLAILAAAAAAIAAAAILLLLAAAAAAAAAAAAIIILLLLLAAAAILAAAAAIAAAAIIILLLLAAAAAIIILLLLAIIILLLAAAAIILLAILAAAAAIIAAAAAILAAAAAAIAAAAAAAAAAAAAIAAAAAIAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA .

City of Houston Texas

REVIEWED FOR COMPLIANCE

25092455

Performance of this review does not relieve the applicant from full responsibility to comply with all

O E

O E

DB

D B

EXISTING METRO COMM MANHOLE

METRO SIGNAL HOUSE

HORIZONTAL DIRECTION DRILL

(50 LF)

HH-1

FSM-NC-SH-NL>SEC ENCL 1

FSM-NC-SH-NL>TRAILER 1

FSM-NC-SH-NL>TRAILER 2

(2) 4" C

(1) 4"C W/ (3) 1" PVC INNERDUCT

INNERDUCT 1: FSM-NC-SH-NL>SEC ENCL 1

INNERDUCT 2: FSM-NC-SH-NL>TRAILER 1

INNERDUCT 3: FSM-NC-SH-NL>TRAILER 2

(1) 4"C EMPTY W/ PULLWIRE

(2) 4" C

(1) 4"C W/ (3) 1" PVC INNERDUCT

INNERDUCT 1: FSM-NC-SH-NL>SEC ENCL 1

INNERDUCT 2: FSM-NC-SH-NL>TRAILER 1

INNERDUCT 3: FSM-NC-SH-NL>TRAILER 2

(1) 4"C EMPTY W/ PULLWIRE

EXISTING METRO

IT DUCTBANK

MATCH LINE ~ T-201

1. REFER TO T-500 FOR TECHNOLOGY DETAILS.

2. REFER TO E-200 SERIES FOR ELECTRICAL PLAN

SHEETS.

3. NEW COMMUNICATION DUCTS TO TERMINATE IN

EXISTING METRO COMM MANHOLE

GENERAL NOTES

0 20' 40'10'

HORIZONTAL SCALE 1"=20'

N

SCALE:

P…