1.02 38DJ266202_00_A01.pdf
PDF 208 KB Posted
- Solicitation number
- N6264926Q0556
About this file
This is a Job Specification for preservation work on the USS TRIPOLI (LHA-7), a naval vessel. The work involves cleaning and preservation of the bilge area in Fire Pump and Refrigerant Machinery Room 6-45-0-E, totaling 1,000 square feet designated as a "Critical Coated Area." The anticipated award date is September 11, 2026, with a production completion date of December 18, 2026. The period of performance runs from October 7, 2026, through January 29, 2027, with the work being performed at Sasebo. The preparing activity is SASEBO, and work authorization is managed through the SRF-JRMC Detachment.
The scope requires removal and reinstallation of existing floor deck plates with new corrosion-resistant steel (CRES) fasteners, chasing and tapping exposed thread areas, and high-pressure cleaning and gas-freeing of bilge spaces using portable air-driven pumps. Environmental controls include ventilation of harmful vapors to the exterior, waste liquid disposal to government-provided conveyance with spill containment measures, and periodic inspections of piping and hose alignment. Cleaning and preservation must comply with SSPC standards (SP-11, SP-WJ-2/L, SP-3, SP-2, and SP-1 depending on surface accessibility), with subsequent application of bilge red coating. Non-ferrous piping requires solvent cleaning and bilge red coating. Government-furnished materials include 350 CRES machine screws with nylon locking strips (5/16"-18UNC-2A, 3/4 inch) and 4 tubes of antiseize compound. A Marine Chemist certificate is required prior to work commencement.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation - N6264926Q0556.pdf | ||
| 1.02 38DJ266202_01_A02.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ship/HULL NO. Ship/HULL NAME ICN: Rev: Key Op:
LHA-7 USS TRIPOLI JON. 380J266202 AOl
TITLE:
Bilge Area in Fire Pump and Refrigerant Machinery Room 6-45-0-E; preserve
JOB SPECIFICATION
Anticipated Award Date: Production Completion Date: PREPARING ACTIVITY:
SASEBOPOP Start Date: POP End Date:
PREPARED BY:
T.SATO
CODE
H_ST
DATE
6/09/2026
APPROVED BY: f)
S.MURAKAMI
CODE
S225
CONCURRED BY:
S.MOROOKA L411
CODE
S231
ASSIST PLANNER'S NAME: CODE
ASSIST PLANNER'S NAME: CODE
ASSIST PLANNER'S NAME: CODE
DESCRIPTION:
JSN(S): EAO5-1375 CASREP #
S/F CONTACT: OBJIO MM2 I HANNA MMC CWP # CCNS # LHA7-002-27
Approved by S300/S900
D. PERKINS/Pro Date:
c Manager
Avi: 7J1
LWC:
Work Completed
S/Force: Rate:
Ship Supt: Date:
Date:
SRF CONTROL NO.:________________________
WORK CERTIFICATION SIGNATURES
COMPLETION OF WORK REVIEW: BADGE NO.: SHOP/CODE: PHONE: DATE:
Sakura.Yamaguchi.ja Typewritten Text 09/11/2026
Sakura.Yamaguchi.ja Typewritten Text 10/07/2026
Sakura.Yamaguchi.ja Typewritten Text 12/18/2026
Sakura.Yamaguchi.ja Typewritten Text 01/29/2027
Sakura.Yamaguchi.ja Typewritten Text 1301401348
Ship/HULL NO. Ship/HULL NAME ICN: Rev: Key Op:
LHA-7 USS TRIPOLI j 38DJ266202 AOl
TITLE:
Bilge Area in Fire Pump and Refrigerant Machinery Room 6-45-O-E; preserve
1. SCOPE:
1.1 Title: Bilge Area in Fire Pump and Refrigerant Machinery Room 6-45-0- 5; preserve
1.2 Location of Work:
1.2.1 Fire Pump and Refrigerant Machinery Room (6-45-0-5)
"CRITICAL COATED AREA"
1.3 Identification:
1.3.1 A Total of (1,000 SF) of Bilge Area in Fire Pump and
Refrigerant Machinery Room, Located in 1.2.1
2. REFERENCES:
2.1 Standard Items (FY27)
2.2 622-7569310 Rev B, Floor Plates, Grating and Handrails MDL 1
2.3 803-1340709 Rev C, Floor Plating and Grating in Machinery Spaces, Installation of
2.4 501-6924906 Rev G, Detail Arrangement FWD Fire Pump/Refrigerant Machinery Room
2.5 142-7563484 Rev C, Structural ASSY 104 lB to 2ND PLATF 30" FWD FR 41 to 30" FWD FR 49 MDL 1
3. REQUIREMENTS:
3.1 Remove each existing floor deck plate located in 1.2.1 for preservation work. Upon completion of the work, install them with each new CRES fastener where missing or damaged, using 2.2 and 2.3 for guidance.
3.1.1 Chase and tap each exposed thread area for existing floor plate supports.
3.2 Provide each portable air driven bilge pump, high pressure pump with each necessary nozzle, suction hose, and required equipment to high pressure clean and gas-free each bilge space listed in 1.3.1.
3.2.1 Ventilate, empty, clean, and maintain each bilge space listed in 1.3.1 throughout the work item performance period.
3.2.1.1 Ensure that each harmful vapor, fume, and mist is
ventilated to the exterior of the vessel.
3.2.1.2 Remove and dispose of waste liquid that is not being
stored for reuse to a Government provided waste liquid conveyance. (See 4.2)
2,-
Shi /HULL NO. Shi IHULL NAME ICN: Rev: Key Op:
LHA-7 USS TRIPOLI JON: 38DJ266202 AOl
TITLE:
Bilge Area in Fire Pump and Refrigerant Machinery Room 6 -45-O-E; preserve
3.2.1.3 Contact the SRF-JRMC Detachment Sasebo ESH Division, Environmental Branch, S106.3 prior to transfer of waste liquid to the conveyance.
3.2.1.4 Provide watches and following spill kits (absorbent
pads, booms, etc. for oil or chemical spill containment) at each affected area where waste liquid is being transferred to ensure that each liquid is not released to any shipboard compartment or the sea. In case of a spill, take immediate action to contain the spill, and contact Sl06.3.
3.2.1.5 Identify each transfer hoses to the conveyance by
affixing the company's name and space location pumping from on each hose.
3.2.1.6 Establish and maintain communication between the
pumping station and the conveyance when the waste liquid is being transferred.
CV) "INSPECT PIPING ND HOSE ALIGNNT"
3.2.1.7 Inspect alignment of each piping, hose, and valves in the flow path prior to the start of pumping, purging, or flushing.
3.2.1.8 Accomplish a periodic walkthrough of all piping, hose, and valve alignments for leaks at least once an hour.
3.2.1.9 Pumping after sunset is not authorized unless
approved by SUPERVISOR.
3.3 Accomplish a visual inspection of each bilge area listed in 1.3.1 to determine the preservation area, using 2.4 and 2.5 for guidance.
(v) "REPORT"
3.3.1 Submit one legible copy of a report listing the results of the requirement of 3.3 to SUPERVISOR.
(v) "REPORT"
3.4 Submit one legible copy of Marine Chemist certificate to SUPERVISOR including certified location.
3.5 Accomplish the requirements of 009-032 of 2.1, including Table 3, One system out of Line 9 or 10, Columns A (SSPC-SP-ll or SSPC-SP WJ-2/L), B and H, or Line 13 Columns A and B for each bilge area listed in 1.3.1 as determined in 3.3, using manufacturer's instruction for guidance.
3.5.1 Power tool clean each narrow area to SSPC-SP-3 where power tool in 3.5 cannot reach.
3.5.1.1 Hand tool clean each narrow area to SSPC-SP-2 where
power tool in 3.5.1 cannot reach.
Shi /HULL NO. Shi /HULL NAME ICN: Rev: Key Op:
LHA-7 USS TRIPOLI JON: 38DJ266202 AOl
TITLE:
Bilge Area in Fire Pump and Refrigerant Machinery Room 6-45-O-E; preserve
3.5.2 Solvent clean each narrow area to SSPC-SP-1 where hand tool in
3.5.1.1 cannot reach.
3.5.2.1 Apply one coat of bilge red to each narrow area.
3.5.3 Roughen and wipe off, solvent clean each surface of non-ferrous piping.
3.5.3.1 Apply one coat of bilge red to non-ferrous piping.
3.6 Accomplish the requirements of 009-032 of 2.1 for cleaning and preservation of each new and disturbed surface to match surrounding areas.
4. NOTES:
4.1 Initial Condition - The bilge in fire pump and refrigerant machinery room was in need preservation.
4.2 The SUPERVISOR will provide a waste liquid conveyance to accumulate waste liquids in bilge for work being accomplished for SRF-JRMC availabilities.
5. GOVERNNT FURNISHED MATERIAL (GFM):
5.1 Government Furnished Materials.
MATERIAl I IT
MATERIAL LIST
M
QTY
ITEM PC REF / STOCK HAZ DOG REQD/ PARA
NO. NO NO C DESCRIPTION NUMBER MAT NO. UNIT NO.
001 M SCREW MACHINE, PAN HEAD, NYLON 9Z 5305 N 350/EA 3.1
LOCKING STRIP, 5/16"-18UNC-2A, 3/4 INCH SA21 00953
LG, CRES 316/NYLON, MIL-DTL-18240F
002 M ANTISEIZE COMPOUND, 8 OZ/TU, A-A-
9B 8030 Y
4/TU
3.1
59313 002921102