08 Specs - California Air National Guard 2271 500kW Generator Data.pdf
PDF 5 MB Posted
- Attached to
- Emergency Generator Repair
- Solicitation number
- W50S74-26-Q-A029
- Issued by
-
Department of the Army National Guard
About this file
This document is an Engineering Submittal Package for a 500kW diesel generator set to be delivered to California Air National Guard Building 2271. The package includes detailed specifications, installation drawings, and technical documentation for a Generac SD500 industrial diesel generator system with supporting components.
The primary deliverable is a Generac SD500 stationary emergency-standby rated generator set rated at 500 kW (625 kVA) at 277/480 VAC three-phase 60Hz, powered by a Perkins 15.2L turbocharged/aftercooled diesel engine. The generator features permanent magnet excitation, UL2200 certification, EPA and SCAQMD compliance, and an H-100 digital control panel with dual 4x20 displays and programmable logic controller capabilities. Additional included components are a PSTS Series 800-amp 3-pole automatic transfer switch with ATC-300+ microprocessor-based controller rated for 277/480 VAC three-phase, a 25-inch 1001-gallon double-wall UL142 basetank with external fill/vent and electronic fuel level sender, standard 800-amp main line circuit breaker with 80% thermal-magnetic rating, 21-light remote annunciator panel, 10-amp NFPA-compliant battery charger, 225 AH Group 8D batteries with rack, 2500W 240VAC coolant heater, and remote emergency stop switch. Factory startup services by trained technicians are included Monday-Friday 8:00 AM–5:00 PM, with freight to first destination included and off-loading/rigging by others. The submittal includes comprehensive technical documentation with installation drawings, dimensional data, weight/center of gravity specifications, alternator specifications, circuit breaker options, battery index, control panel diagrams, and noise level testing data.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bldg 2271
Bill of Material – California Air National Guard PDPG192132
Quantity 1 - Generac Industrial Diesel engine-driven generator set with turbocharged/aftercooled 6-cylinder 15.2L engine, consisting of the following features and accessories:
Stationary Emergency-Standby rated 500 kW Rating, wired for 277/480 VAC three phase, 60 Hz Permanent Magnet Excitation
UL2200
EPA Certified
SCAQMD
H-100 Control Panel o Meets NFPA 99 and 110 requirements o Temp Range -40 to 70 degrees C o Digital Microprocessor:
Two 4-line x 20 displays, full system status 3 Phase sensing, +/-0.25% digital voltage regulation RS232, RS485 and Canbus remote ports Waterproof connections All engine sensors are 4-20ma for minimal interference Programmable I/O Built-in PLC for special applications o Engine function monitoring and control:
Full range standby operation; programmable auto crank, Emergency Stop, Auto-Off-
Manual switch Isochronous Governor, +/-0.25% frequency regulation Full system status on all AC output and engine function parameters Service reminders, trending, fault history (alarm log) I2T function for full generator protection Selectable low-speed exercise o 2-wire start controls for any 2-wire transfer switch Level 1 Acoustic Enclosure, Steel – No dBA Given o Industrial Grey Baked-On Powder Coat Finish 25" 1001 Gallon Double-Wall UL142 Basetank o External fill and vent o Mechanical fuel level indicator gauge o Electronic fuel level sender
Standard MLCB, 80% rated thermal-magnetic o 800 Amp
21 Light Annunciator - Surface Battery Charger, 10 Amp, NFPA 110 compliant, installed 225 AH, 1155 CCA Group 8D Batteries, with rack, installed Coolant Heater, 2500W, 240VAC Remote Emergency Stop Switch, Break-Glass, shipped loose
12 Position Load Center, unit mounted 120V GFCI and 240V Outlet Crankcase Oil Heater Engine Run Relay Std set of 3 Manuals Standard 2-Year Limited Warranty
Quantity 1 - PSTS Series Automatic Transfer Switch consisting of the following features and accessories:
800 Amp, 3 Pole, 277/480 VAC three phase Standard Open Transition Contactor-Based Design CSA C22.2 Certified CUL Listed UL1008 Listed NEMA 3R Enclosure ATC-300+ Microprocessor-Based Controller o 2-Line, 32-Character Alphanumeric LCD Display o Front Panel Mimic Diagram with colored LEDs for Source/Load Indication o Standard Features:
Sensing and Programmable Setpoints for both Normal (S1) and Emergency (S2): Under-voltage/Under-frequency, Over-voltage/Over-frequency; Voltage Unbalance Sensing and Phase Reversal for all phases
Adjustable Time Delays: Engine Start, Transfer Normal to Emergency & Emergency to Normal, Engine Cooldown, Emergency Fail
Pushbutton for Bypassing Time Delays on Transfer/Retransfer Test Pushbutton Contacts for Go to Emergency (S2) MODBUS Communication Digital Programmable Plant Exerciser:
Off, 1-Day, 7-Day, 14-Day, 28-Day Intervals Adjustable 0-600 Minutes Run Time Selectable for Load or No Load
Auxiliary Contacts:
Normal (S1) Source Present (2 Form C) Emergency (S2) Source Present (2 Form C) Normal (S1) Position Indication (1 Form C) Emergency (S2) Position Indication (1 Form C) Pre-Transfer Signal Contacts (1 Form C)
32D - Inphase Transfer, default to Time Delay Neutral 41A - 100W Space Heater with Adjustable Thermostat 42 - IBC/CBC Seismic Qualified 2-Year Basic Warranty
Quantity 1 - Start up 500 kW :
Onsite services performed by factory trained technicians, Monday – Friday 8:00 am – 5:00 pm – fuel not included
Freight included to first destination. Off-loading and rigging by others
4 3 2 1
4 3 1
A
B
A
B
DIM X
COG
NOTE 6, SHEET 3
DIM Y
COG
NOTE 6
SHEET 3
DIM Z
COG
NOTE 6, SHEET 3
1709.32 [67.296]
OVERALL
HEIGHT
1803 [71.0]
OVERALL WIDTH
1679 [66.1]
2436 [95.9]
1414 [55.7] 312 WEG
1375 [54.1] 352 WEG
HIGH VOLTAGE
CONNECTION BOX
HEIGHT
434 [17.1]
LOW VOLTAGE
CONNECTION BOX
HEIGHT
942 [37.1]
MLCB
HEIGHT
(NOTE 5)
68 [2.7]
[2.8]
3923 [154.4]
OVERALL LENGTH
950 [37.4]
DIESEL
CONNECTIONS
(NOTE 7)
1472 [58.0]
OIL DRAIN
(NOTE 7)
506 [19.9]
RADIATOR
DRAIN
(NOTE 7)
739 [29.1]
[2.8]
1280 [50.4]
FLEX
CONNECTION
1758 [69.2]
FLEX
CONNECTION
735 [28.9]
CUSTOMER HIGH
VOLTAGE CONN
(NOTE 5)
571 [22.5]
FLEX
CONNECTION
158 [6.2]
1325 [52.2]
EXHAUST
OUTLET
213 [8.4]
AIR DUCT
(NOTE 10)
1373 [54.1]
AIR DUCT
(NOTE 10)
308 [12.1]
AIR DUCT
(NOTE 10)
1170 [46.0]
AIR DUCT
(NOTE 10)
TITLE
OPEN SET
D15.2L SD500, PD450
ISSUE DATE: 03/21/14
SIZE CAGE NO DWG NO 0K1606 REV
B N/A H SCALE 0.030 WT-KG SHEET 1 of 3
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH 1/3 REV H WINDCHILL VERSION H.2
DIMENSIONS ARE IN MILLIMETERS [INCHES]
NOTES:
1. CONTROL PANEL, (OPTIONAL BATTERY CHARGER INSIDE).
2. 120V, 20A GFCI & 250V, 15A OUTLET (OPTIONAL).
3. CONNECTION POINTS FOR CONTROL WIRES PROVIDED IN THE LOW
VOLTAGE CONNECTION BOX (USE LOW VOLTAGE STUB-UP AREA).
4. BATTERY (24 VOLT NEGATIVE GROUND SYSTEM).
5. MAIN LINE CIRCUIT BREAKER (MLCB), AC LOAD LEADS.
(DIMENSIONS MAY VARY DUE TO UNIT CONFIGURATION)
6. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
7. ENGINE SERVICE CONNECTIONS:
INLET NATURA GAS = N/A
INLET DIESEL = 1/2" NPT FEMALE COUPLING
RETURN DIESEL = 1/2" NPT FEMALE COUPLING
OIL DRAIN = 1/2" NPT FEMALE COUPLING
RADIATOR DRAIN = 1/2" NPT FEMALE COUPLING
FLEX PIPE OUTLET = 6" I.D. PIPE
EXHAUST OUTLET = 5" I.D. SAE FLANGE (TURB O CONNECTION)
***** SEE GENERATOR SIZING GUIDE FOR FUEL PIPE SIZING TO SUIT APPLICATION *****
8. AUXILARY AC CONNECTION FOR UNIT OPTIONS ARE LOCATED IN HIGH VOLTAGE
CONNECTION BOX, UNLESS AN OPTIONAL LOAD CENTER IS INSTALLED.
9. EXHAUST PIPES MAY BE ROTATED TO ALLOW MUFFLER TO POINT OUT TO THE
RIGHT OR LEFT SIDE OF GENERATOR. (MAY NOT APPLY TO ALL UNITS)
10. GENERATOR SET MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS
AVAILABLE AND DISCHARGE AIR FROM THE RADIATOR IS NOT RECIRCULATED.
11. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION
AND RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
12. INSTALL EXHAUST BLANKETS ALONG THIS LINE
13. CONNECT THE OPEN SET EXHAUST PER NFPA 37
14. BOLTS OR STUDS USED TO MOUNT UNIT TO PAD, OR BASE TANK, SHALL BE 5/8"-11 GRADE 5.
USE STANDARD SAE TORQUE SPECS. (FOR INSTALLATION OF FUEL TANK
TO PAD REFER TO INSTALL DRAWING OF THE BASE TANK)
ADDITIONAL NOTES:
FOR WEIGHT AND CENTER OF GRAVITY DATA SEE NOTE 6, AND SHEET 3.
OUTLET LOCATION
(NOTE 2)
LIFTING EYE
(4 PLACES)
51 X 80 SLOT
[2.0 X 3.15]
NOTE 1
LOW VOLTAGE
CONNECTION BOX
(NOTE 3)
NOTE 4
ALT AIR OUT
ALT AIR OUT
OPTIONAL
LOAD CENTER
SECONDARY HIGH VOLTAGE
CONNECTION BOX
(OPTIONAL)
SEE NOTE 12 & 13
FUEL
INLET
FUEL
RETURN
A
B
A
B
DIM X
COG
DIM Y
COG
DIM Z
COG
296 [11.7]
1660 [65.4]
1800 [70.9]
OVERALL WIDTH
[69.0]
[78.8]
2032 [80.0]
OVERALL
HEIGHT
6285 [247.5]
OVERALL LENGTH
R746 [29.4] TYP
DOOR SWING
R766 [30.2] TYP
DOOR SWING
3952 [155.6]
1021 [40.2]3923 [154.4]1322 [52.1]
294 [11.6]
1660 [65.4]
1679 [66.1]
TITLE
L1A ENCLOSURE
D15.2L SD/MD 500 & SB/MB 500
PD/WD 450 & PB/WB 450
ISSUE DATE: 03/21/14
SIZE CAGE NO DWG NO 0K1606B REV
B N/A D SCALE 0.030 WT-KG SHEET 1 of 1
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH 1/1 REV D WINDCHILL VERSION D.1
FOR ALL STUB-UP, WEIGHT, AND COG DETAILS, SEE
CORRESPONDING OPEN SET DRAWING PER UNIT CONFIGURATION.
DIMENSIONS ARE IN MILLIMETERS [INCHES]
AIR INTAKE TYPICAL
INTAKE AIR
DISCHARGE AIR
(RADIATOR & EXHAUST)
AIRAIRAIRAIR
AIR
AIR
AIR
AIR AIR AIR AIR
A
B
A
B
16.7 [.66]
MOUNTING HOLES
(12 PLACES)
(SEE NOTE 14)
99 [3.9] TYP
745 [29.3] TYP
1490 [58.7] TYP
2235 [88.0] TYP
2980 [117.3] TYP
3725 [146.7] TYP
1791 [70.5]
OVERALL WIDTH
1630 [64.2]
1547 [60.9]
3923 [154.4]
OVERALL LENGTH
[13.8]
[15.7]
267.4 [10.5]
62 [2.4]
635.5 [25.0]
[13.8] 125.6 [4.9]
40 [1.6]
95.1 [3.7]
598 [23.5]
OPEN AREA
FOR STUB-UP
410 [16.1]278 [10.9]
RECOMMENDED ELECTRICAL STUB-UP
(HIGH VOLTAGE STUB-UP)
AC LOAD LEAD CONDUIT FOR
PERMANENT MAGNET EXCITATION
CONNECTION BOX
(LOW VOLTAGE STUB-UP)
TITLE
STUB-UP VIEW
D15.2L SD500, PD450
ISSUE DATE: 03/21/14
SIZE CAGE NO DWG NO 0K1606 REV
B N/A H SCALE 0.060 WT-KG SHEET 2 of 3
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH 2/3 REV H WINDCHILL VERSION H.2
PRIMARY HIGH VOLTAGE
STUB-UP AREA
W/ GLAND PLATE
PRIMARY CB CONNECTION
BOX OPENING
LOW VOLTAGE STUB-UP AREA
BASETANK MOUNTED
(SEE NOTE 3)
SECONDARY CB CONNECTION
BOX OPENING (OPTIONAL)
SECONDARY HIGH VOLTAGE
STUB-UP AREA (OPTIONAL)
LOW VOLTAGE STUB-UP
AREA SURFACE MOUNTED
(SEE NOTE 3)
DIMENSIONS ARE IN MILLIMETERS [INCHES]
A
B
A
B
[23.66]
STUB-UP
[24.76]
STUB-UP
448.9 [17.67]
STUB-UP
448.9 [17.67]
STUB-UP
99.1 [3.90]
TYP
745 [29.33]
TYP
1490 [58.66]
TYP
2234.9 [87.99] TYP
2979.9 [117.32] TYP
3724.9 [146.65] TYP
4645 [182.88] TYP
5565.1 [219.10] TYP
1173.7 [46.21]
1421.3 [55.96]
1970 [77.56]
2544.8 [100.19]
5384.8 [212.00]
5435.6 [214.00] TYP
5638.8 [222.00]
510.8 [20.11]
663.2 [26.11]
917.2 [36.11]
1171.2 [46.11]
1425.2 [56.11]
TYP
1056.7 [41.60]
TYP
1456.7 [57.35]
[25.00]
5791.2 [228.00] 1629.4 [64.15]
TYP
24.9 [.98]
TYP
1679.2 [66.11]
190.5 [7.50]
SH 1/1 REV
I/N TANK FITTING DESCRIPTION
1 1/2" NPT COUPLING FUEL RETURN
2 1/2" NPT COUPLING FUEL SUPPLY
3 2" NPT FEMALE FUEL FILL
4 FUEL LEVEL
5 2" NPT FEMALE VENT
6 6" NPT WELD FLANGE EMERGENCY VENT (OUTER)
7 BASIN ALARM
8 6" NPT WELD FLANGE EMERGENCY VENT (INNER)
9 2" NPT FEMALE SPARE PORT
10 FUEL SENDER
TANK P/N 0K0187
TOTAL TANK CAPACITY 3916 [1035]
USABLE TANK CAPACITY 3790 [1001]
DRY WEIGHT [EST] 1429 [3150]
SH 1/1 REV G
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
TITLE
INSTALL HGRP EXT BASETANKS G22
ISSUE DATE: 11/20/12
SIZE CAGE NO DWG NO 0K1837A REV
B G SCALE 0.030 WT-KG SHEET 1 of 1
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2012
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
CAPACITY SHOWN: LITER [GALLONS]
WEIGHT SHOWN: KILOGRAMS [POUNDS]
LENGTH SHOWN: MM [INCH]
UL #142 / ULC-S601 LISTED
NOTES:
1. MOUNTING BOLTS/STUDS FOR BASETANK TO CONCRETE
PAD SHALL BE 3/4-10 GRADE 5. (USE STANDARD SAE
TORQUE SPECS.)
LOW VOLTAGE STUB-UP
HIGH VOLTAGE STUB-UP
8 6
A
B
A
B
STD ENCLOSURE, STEEL
WEIGHT CENTER OF GRAVITY
DIM "X"
CENTER OF GRAVITY
DIM "Y"
CENTER OF GRAVITY
DIM "Z"
4,329 kg [9,544 lbs] 2138 [84.2] 718 [28.3] 797 [31.4]
4,429 kg [9,764 lbs] 2099 [82.6] 714 [28.1] 797 [31.4]
5,321 kg [11,731 lbs] 1884 [74.2] 685 [27.0] 794 [31.3]
5,028 kg [11,085 lbs] 1938 [76.3] 693 [27.3] 795 [31.3] 4,679 kg [10,315 lbs] 2041 [80.4] 704 [27.7] 796 [31.3] 5,255 kg [11,585 lbs] 1895 [74.6] 687 [27.0] 794 [31.3]
MODEL VOLTAGE WEIGHT CENTER OF GRAVITY
DIM X
CENTER OF GRAVITY
DIM Y
CENTER OF GRAVITY
DIM Z
SD/MD 500, PD/WD 450 480V 3,807 kg [8,393 lbs] 1952 [76.9] 642 [25.3] 837 [33.0] SD/MD 500, PD/WD 450 480V UPSIZED ALT. (642kw)
3,907 kg [8,614 lbs] 1912 [75.3] 639 [25.2] 837 [33.0]
SD500, PD450 208V & 240V
SD/MD 500, PD/WD 450 480V UPSIZED ALT. (832kw) 4,799 kg [10,580 lbs] 1709 [67.3] 622 [24.5] 837 [33.0]
SD500, PD450 208V & 240V UPSIZED ALT (723kw) SD500, PD450 208V & 240V UPSIZED ALT (689kw) 4,506 kg [9,934 lbs] 1758 [69.2] 627 [24.7] 837 [33.0]
SD/MD 500, PD/WD 450 600V 4,157 kg [9,165 lbs] 1859 [73.2] 634 [25.0] 837 [33.0] SD/MD 500, PD/WD 450 600V UPSIZED ALT. (800kw) 4,733 kg [10,435 lbs] 1720 [67.7] 623 [24.5] 837 [33.0]
L1A ENCLOSURE, STEEL
STD ENCLOSURE, ALUMINUM
OPEN SET
L2A ENCLOSURE, STEEL
WEIGHT CENTER OF GRAVITY
DIM "X"
CENTER OF GRAVITY
DIM "Y"
CENTER OF GRAVITY
DIM "Z"
4,525 kg [9,976 lbs] 2057 [81.0] 736 [29.0] 801 [31.5]
4,625 kg [10,196 lbs] 2022 [79.6] 782 [30.8] 800 [31.5]
5,517 kg [12,163 lbs] 1828 [72.0] 701 [27.6] 797 [31.4]
5,224 kg [11,517 lbs] 1877 [73.9] 710 [28.0] 798 [31.4] 4,875 kg [10,747 lbs] 1971 [77.6] 722 [28.4] 799 [31.5] 5,451 kg [12,017 lbs] 1839 [72.4] 703 [27.7] 797 [31.4]
WEIGHT CENTER OF GRAVITY
DIM "X"
CENTER OF GRAVITY
DIM "Y"
CENTER OF GRAVITY
DIM "Z"
4,590 kg [10,119 lbs] 2158 [85.0] 823 [32.4] 799 [31.5]
4,690 kg [10,340 lbs] 2121 [83.5] 816 [32.1] 798 [31.4]
5,582 kg [12,306 lbs] 1913 [75.3] 771 [30.4] 796 [31.3]
5,289 kg [11,660 lbs] 1966 [77.4] 784 [30.9] 796 [31.3] 4,940 kg [10,891 lbs] 2065 [81.3] 801 [31.5] 797 [31.4] 5,516 kg [12,161 lbs] 1924 [75.7] 773 [30.4] 796 [31.3]
L1A ENCLOSURE, ALUMINUM
L2A ENCLOSURE, ALUMINUM
TITLE
WEIGHT & CENTER OF GRAVITY
D15.2L SD500, PD450
ISSUE DATE: 03/21/14
SIZE CAGE NO DWG NO 0K1606 REV
B N/A H SCALE 0.060 WT-KG SHEET 3 of 3
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH 3/3 REV H WINDCHILL VERSION H.2
MODEL VOLTAGE WEIGHT CENTER OF GRAVITY
DIM X
CENTER OF GRAVITY
DIM Y
CENTER OF GRAVITY
DIM Z
SD/MD 500, PD/WD 450 480V 4,822 kg [10,631 lbs] 2215 [87.2] 771 [30.4] 802 [31.6] SD/MD 500, PD/WD 450 480V UPSIZED ALT. (642kw)
4,922 kg [10,851 lbs] 2178 [85.7] 766 [30.2] 801 [31.5]
SD500, PD450 208V & 240V
SD/MD 500, PD/WD 450 480V UPSIZED ALT. (832kw) 5,814 kg [12,818 lbs] 1969 [77.5] 731 [28.8] 798 [31.4]
SD500, PD450 208V & 240V UPSIZED ALT (723kw) SD500, PD450 208V & 240V UPSIZED ALT (689kw) 5,521 kg [12,172 lbs] 2023 [79.6] 741 [29.2] 799 [31.5]
SD/MD 500, PD/WD 450 600V 5,172 kg [11,402 lbs] 2122 [83.5] 755 [29.7] 800 [31.5] SD/MD 500, PD/WD 450 600V UPSIZED ALT. (800kw) 5,748 kg [12,672 lbs] 1981 [78.0] 733 [28.9] 798 [31.4]
MODEL VOLTAGE WEIGHT CENTER OF GRAVITY
DIM X
CENTER OF GRAVITY
DIM Y
CENTER OF GRAVITY
DIM Z
SD/MD 500, PD/WD 450 480V 5,278 kg [11,636 lbs] 2048 [80.6] 803 [31.6] 809 [31.9] SD/MD 500, PD/WD 450 480V UPSIZED ALT. (642kw)
5,378 kg [11,856 lbs] 2019 [79.5] 797 [31.4] 808 [31.8]
SD500, PD450 208V & 240V
SD/MD 500, PD/WD 450 480V UPSIZED ALT. (832kw) 6,270 kg [13,823 lbs] 1851 [72.8] 760 [29.9] 804 [31.7]
SD500, PD450 208V & 240V UPSIZED ALT (723kw) SD500, PD450 208V & 240V UPSIZED ALT (689kw) 5,977 kg [13,177 lbs] 1894 [74.6] 771 [30.4] 805 [31.7]
SD/MD 500, PD/WD 450 600V 5,628 kg [12,407 lbs] 1976 [77.8] 786 [30.9] 807 [31.8] SD/MD 500, PD/WD 450 600V UPSIZED ALT. (800kw) 6,204 kg [13,677 lbs] 1861 [73.3] 763 [30.0] 805 [31.7]
MODEL VOLTAGE WEIGHT CENTER OF GRAVITY
DIM X
CENTER OF GRAVITY
DIM Y
CENTER OF GRAVITY
DIM Z
SD/MD 500, PD/WD 450 480V 5,431 kg [11,973 lbs] 2244 [88.3] 966 [38.0] 805 [31.7] SD/MD 500, PD/WD 450 480V UPSIZED ALT. (642kw)
5,531 kg [12,194 lbs] 2211 [87.0] 958 [37.7] 804 [31.7]
SD500, PD450 208V & 240V
SD/MD 500, PD/WD 450 480V UPSIZED ALT. (832kw) 6,423 kg [14,160 lbs] 2019 [79.5] 897 [35.3] 801 [31.5]
SD500, PD450 208V & 240V UPSIZED ALT (723kw) SD500, PD450 208V & 240V UPSIZED ALT (689kw) 6,130 kg [13,514 lbs] 2070 [81.5] 915 [36.0] 802 [31.6]
SD/MD 500, PD/WD 450 600V 5,781 kg [12,745 lbs] 2160 [85.0] 939 [37.0] 803 [31.6] SD/MD 500, PD/WD 450 600V UPSIZED ALT. (800kw) 6,357 kg [14,015 lbs] 2030 [79.9] 901 [35.5] 801 [31.5]
NOTE:
CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS
SD500 | 15.2L | 500 kW
INDUSTRIAL DIESEL GENERATOR SET
EPA Cer tified Stationary Emergency
SP
EC
S
HE
ET
Powering Ahead
For over 50 years, Generac has provided innovative design and superior manufacturing.
Generac ensures superior quality by designing and manufacturing most of its generator components, including alternators, enclosures and base tanks, control systems and communications software.
Generac gensets utilize a wide variety of options, configurations and arrangements, allowing us to meet the standby power needs of practically every application.
Generac searched globally to ensure the most reliable engines power our generators. We choose only engines that have already been proven in heavy-duty industrial applications under adverse conditions.
Generac is committed to ensuring our customers’ service support continues after their generator purchase.
Codes and Standards Generac products are designed to the following standards:
UL2200, UL508, UL142, UL489
NFPA 37, 70, 99, 110
NEC700, 701, 702, 708
ISO 3046, 7637, 8528, 9001
NEMA ICS10, MG1, 250, ICS6, AB1
ANSI C62.41
IBC 2009, CBC 2010, IBC 2012,
ASCE 7-05, ASCE 7-10, ICC-ES AC-
156 (2012)
Image used for illustration purposes only
Standby Power Rating 500 kW, 625 kVA, 60 Hz
Prime Power Rating* 450 kW, 563 kVA, 60 Hz
*EPA Certified Prime ratings are not available in the US or its Territories *Built in the USA using domestic and foreign parts
EPA Cer tified Stationary Emergency
SP
EC
S
HE
ET
CONTROL SYSTEM
Control Panel
• Digital H Control Panel - Dual 4x20 Display
• Programmable Crank Limiter
• 7-Day Programmable Exerciser
• Special Applications Programmable PLC
• RS-232/485
• All-Phase Sensing DVR
• Full System Status
• Utility Monitoring
• 2-Wire Start Compatible
• Power Output (kW)
• Power Factor
• kW Hours, Total & Last Run
• Real/Reactive/Apparent Power
• All Phase AC Voltage
• All Phase Currents
• Oil Pressure
• Coolant Temperature
• Coolant Level
• Engine Speed
• Battery Voltage
• Frequency
• Date/Time Fault History (Event Log)
• Isochronous Governor Control
• Waterproof/Sealed Connectors
• Audible Alarms and Shutdowns
• Not in Auto (Flashing Light)
• Auto/Off/Manual Switch
• E-Stop (Red Mushroom-Type)
• NFPA110 Level I and II (Programmable)
• Customizable Alarms, Warnings, and Events
• Modbus protocol
• Predictive Maintenance Algorithm
• Sealed Boards
• Password Parameter Adjustment Protection
• Single Point Ground
• 15 Channel Data Logging
• 0.2 msec High Speed Data Logging
• Alarm Information Automatically Comes Up On the
Display
Alarms
• Oil Pressure (Pre-Programmable Low Pressure Shutdown)• Coolant Temperature (Pre-Programmed High Temp Shutdown)• Coolant Level (Pre-Programmed Low Level Shut-down)• Low Fuel Alarm
• Engine Speed (Pre-Programmed Over Speed Shut-down)• Battery Voltage Warning
• Alarms & Warnings Time and Date Stamped
• Alarms & Warnings for Transient and Steady State
Conditions• Snap Shots of Key Operation Parameters During Alarms & Warnings• Alarms and Warnings Spelled Out (No Alarm Codes)
STANDARD OPTIONS
ENGINE SYSTEM
• Oil Drain Extension
• Air Cleaner
• Fan Guard
• Stainless Steel Flexible Exhaust Connection
• Critical Exhaust Silencer (Enclosed Only)
• Factory Filled Oil & Coolant
• Radiator Duct Adapter (Open Set Only)
Fuel System
• Primary Fuel Filter
Cooling System
• Closed Coolant Recovery System
• UV/Ozone Resistant Hoses
• Factory-Installed Radiator
• 50/50 Ethylene Glycol Antifreeze
• Radiator Drain Extension
• 120 VAC Coolant Heater
Electrical System
• Battery Charging Alternator
• Battery Cables
• Battery Tray
• Rubber-Booted Engine Electrical Connections
• Solenoid Activated Starter Motor
ALTERNATOR SYSTEM
• UL2200 GENprotect™
• Class H Insulation Material
• Vented Rotor
• 2/3 Pitch
• Skewed Stator
• Amortisseur Winding
• Permanent Magnet Excitation
• Sealed Bearings
• Full Load Capacity Alternator
• Protective Thermal Switch
GENERATOR SET
• Rust-Proof Fasteners with Nylon Washer to Protect Finish• High Performance Sound-Absorbing Material
• Gasketed Doors
• Air Discharge Hoods for Radiator-Upward Pointing
• Stainless Steel Lift off Door Hinges
• Stainless Steel Lockable Handles
• Rhino Coat™ - Textured Polyester Powder Coat
ENCLOSURE (if selected)
• Rust-Proof Fasteners with Nylon Washers to Protect Finish• High Performance Sound-Absorbing Material (L1 & L2)• Gasketed Doors
• Stamped Air-Intake Louvers
• Air Discharge Hoods for Radiator-Upward Pointing
• Stainless Steel Lift Off Door Hinges
• Stainless Steel Lockable Handles
• Rhino Coat™ - Textured Polyester Powder Coat
TANK (if selected)
• UL 142
• Double Wall
• Vents
• Sloped Top
• Sloped Bottom
• Factory Pressure Tested (2 psi)
• Rupture Basin Alarm
• Fuel Level
• Check Valve in Supply and Return Lines
• Rhino Coat™ - Textured Polyester Powder Coat
• Stainless Hardware
EPA Cer tified Stationary Emergency
SP
EC
S
HE
ET
Standby - Applicable for a varying emergency load for the duration of a utility power outage with no overload capability.
Prime - Applicable for supplying power to a varying load in lieu of utility for an unlimited amount of running time. A 10% overload capacity is available for 1 out of every 12 hours. The Prime Power option is only available on International applications. Power ratings in accordance with ISO 8528-1, Second Edition.
CONFIGURABLE OPTIONS
ENGINE SYSTEM
Block Heater (Coolant)
Crankcase Heater (Oil)
Critical Grade Silencers
Fan and Belt Guard (Optional)
Flexible Fuel Lines Included with Base Tank
Stone Guard (Open Set Only)
ELECTRICAL SYSTEM
Battery 10A UL Battery Charger Battery Warmer
ALTERNATOR SYSTEM
Alternator Upsizing Anti-Condensation Heater
CIRCUIT BREAKER OPTIONS
Main Line Circuit Breaker 2nd Main Line Circuit Breaker Shunt Trip and Auxiliary Contact Electronic Trip Breakers
GENERATOR SET
Gen-Link Communications Software (English Only) 8 Position Load Center Alarm Horn Extended Factory Testing 2 Year Extended Warranty 5 Year Warranty 5 Year Extended Warranty 7 Year Extended Warranty 10 Year Extended Warranty
ENCLOSURE
Standard Enclosure (Weather)
Level 1 Sound Attenuation
Level 2 Sound Attenuation
Steel Enclosure
Aluminum Enclosure
IBC Seismic Certification
180 MPH Wind Kit
AC/DC Enclosure Lighting Kit
CONTROL SYSTEM
21-Light Remote Annunciator
Ground Fault Indication and Protection Functions
Engine Run Relay 10A (1-NO, 1- NC)
120 VAC GFCI outlet
Oil Temperature Indication
Remote Relay Panel (8 or 16)
Remote E-Stop (Break Glass-Type, Surface Mount)
Remote E-Stop (Red Mushroom-Type, Surface Mount)
Remote E-Stop (Red Mushroom-Type, Flush Mount)
Remote Communication - Modem
TANKS (Size On Last Page)
Electronic Fuel Level
Mechanical Fuel Level
ENGINEERED OPTIONS
ENGINE SYSTEM
Fluid Containment Pans Coolant Heater Ball Valves
ALTERNATOR SYSTEM
3rd Breaker Systems Unit Mounted Load Banks
CONTROL SYSTEM
Spare Inputs (x4) / Outputs (x4) - H Panel Only
GENERATOR SET
Special Testing
Battery Box
ENCLOSURE
Motorized Dampers
Intrusion Alert Door Switch
Customer Color
TANKS
Overfill Protection Valve
UL 2085 Tank
ULC S-601 Tank
Stainless Steel Tank
Special Fuel Tanks
Vent Extensions
5 Gallon Spill Containment Box
Dealer Supplied AHJ Requirements
RATING DEFINITIONS
EPA Cer tified Stationary Emergency
SP
EC
S
HE
ET
General
Make Perkins
Cylinder # 6
Type In-Line
Displacement - L (cu in) 15.2 (927.56)
Bore - mm (in) 137 (5.39)
Stroke - mm (in) 171 (6.73)
Compression Ratio 16.0:1
Intake Air Method Turbocharged/Aftercooled
Cylinder Head Type 4-Valve
Piston Type Aluminum
Crankshaft Type I-Beam Section
Engine Governing
Governor Electronic Isochronous
Frequency Regulation (Steady State) ±0.25%
Lubrication System
Oil Pump Type Gear
Oil Filter Type Full Flow
Crankcase Capacity - L (qts) 45 (47.55)
Cooling System
Cooling System Type Closed Recovery
Water Pump Type Centrifugal Type, Belt-Driven
Fan Type Pusher
Fan Speed (rpm) 1658
Fan Diameter - mm (in) 927 (36.5)
Coolant Heater Wattage 1500
Coolant Heater Standard Voltage 120 V
Fuel System
Fuel Type Ultra Low Sulfur Diesel #2
Carburetor ASTM
Fuel Filtering (microns) Primary 10 - Secondary 2
Fuel Inject Pump Make Electronic
Injector Type MEUI
Engine Type Pre-Combustion
Fuel Supply Line - mm (in) 12.7 (0.5) NPT
Fuel Return Line - mm (in) 12.7 (0.5) NPT
Engine Electrical System
System Voltage 24 VDC
Battery Charger Alternator Standard
Battery Size See Battery Index
0161970SBY
Battery Voltage (2) 12 VDC
Ground Polarity Negative
APPLICATION AND ENGINEERING DATA
ENGINE SPECIFICATIONS
ALTERNATOR SPECIFICATIONS
Standard Model WEG
Poles 4
Field Type Revolving
Insulation Class - Rotor H
Insulation Class - Stator H
Total Harmonic Distortion <3%
Telephone Interference Factor (TIF) <50
Standard Excitation Permanent Magnet
Bearings Single Sealed Cartridge
Coupling Direct, Flexible Disc
Prototype Short Circuit Test Yes
Voltage Regulator Type Full Digital
Number of Sensed Phases All
Regulation Accuracy (Steady State) ±0.25%
EPA Cer tified Stationary Emergency
SP
EC
S
HE
ET
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.
Please consult a Generac Power Systems Industrial Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528 and DIN6271 standards.
POWER RATINGS
Standby Three-Phase 120/208 VAC @0.8pf 500 kW Amps: 1735
Three-Phase 120/240 VAC @0.8pf 500 kW Amps: 1504
Three-Phase 277/480 VAC @0.8pf 500 kW Amps: 752
Three-Phase 346/600 VAC @0.8pf 500 kW Amps: 601
STARTING CAPABILITIES (sKVA) sKVA vs. Voltage Dip
480 VAC 208/240 VAC
Alternator kW 10% 15% 20% 25% 30% 35% Alternator kW 10% 15% 20% 25% 30% 35%
Standard 500 457 686 914 1143 1371 1600 Standard 500 429 643 857 1071 1286 1500
Upsize 1 642 471 707 943 1179 1414 1650 Upsize 1 689 543 814 1086 1357 1629 1900
Upsize 2 832 757 1136 1514 1893 2271 2650 Upsize 2 723 571 857 1143 1429 1714 2000
FUEL CONSUMPTION RATES*
Diesel - gph (lph) Fuel Pump Lift - ft (m) Percent Load Standby
12 (3.7) 25% 10.5 (39.7)
50% 19.5 (73.8)
Total Fuel Pump Flow (Combustion + Return) gph (lph) 75% 23.7 (89.7)
121 (457) 100% 31.2 (118.1)
* Fuel supply installation must accommodate fuel consumption rates at 100% load.
COOLING
Standby
Coolant Flow per Minute gpm (lpm) 114.1 (432)
Coolant System Capacity gal (L) 264 (999)
Heat Rejection to Coolant BTU/hr 1,198,080
Inlet Air cfm (m3/min) 30,582 (866)
Max. Operating Ambient Temperature (Before Derate) °F (°C) 104 (40)
Maximum Radiator Backpressure in H2O 0.50
COMBUSTION AIR REQUIREMENTS
Standby
Flow at Rated Power cfm (m3/min) 1483 (42)
ENGINE EXHAUST
Standby Standby
Rated Engine Speed rpm 1800 Exhaust Flow (Rated Output) cfm (m3/min) 3400 (96)
Horsepower at Rated kW** hp 835 Max. Backpressure (Post Silencer) in Hg (Kpa) 2.01 (6.8)
Piston Speed ft/min 2020 Exhaust Temp (Rated Output - Post Silencer) °F (°C) 1022 (550)
BMEP psi 366 Exhaust Outlet Size (Open Set) mm (in) 127 (5)
OPERATING DATA
EPA Cer tified Stationary Emergency
SP
EC
S
HE
ET
YOUR FACTORY RECOGNIZED GENERAC INDUSTRIAL DEALER
Specification characteristics may change without notice. Dimensions and weights are for preliminary purposes only. Please consult a Generac Power Systems Industrial Dealer for detailed installation drawings.
* All measurements are approximate and for estimation purposes only.
Part No 0197160SBY Rev. D 09/21/15
Generac Power Systems, Inc. | P.O.Box 8 | Waukesha, WI 53189 P: (262) 544-4811 ©2016 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
L
W
H
L
L
L
W
W
H
H
H
W
DIMENSIONS AND WEIGHTS*
OPEN SET (Includes Exhaust Flex)
Run Time Hours
Usable Capacity Gal (L)
L x W x H (in (mm) Weight lbs (kg)
No Tank - 154.4 (3923) x 71 (1803) x 67 (1702) 10580 (4799)
10 334 158.5 (4026) x 71 (1803) x 81 (2057) 12255 (5559)
32 1001 158.5 (4026) x 71 (1803) x 103 (2616) 13180 (6228)
32 1001 228 (5791) x 71 (1803) x 103 (2616) 13730 (6228)
64 2002 290 (7366) x 71 (1803) x 103 (2616) 15430 (6999)
STANDARD ENCLOSURE
Run Time Hours
Usable Capacity Gal (L)
L x W x H (in (mm) Weight lbs (kg) Enclosure Only
Steel Aluminum
No Tank - 207.4 (5268) x 71 (1803) x 80 (2032)
(907)
(394)
10 334 207.4 (5268) x 71 (1803) x 94 (2388)
32 1001 207.4 (5268) x 71 (1803) x 116 (2946)
32 1001 228 (5791) x 71 (1803) x 105 (2667)
64 2002 290 (7366) x 71 (1803) x 116 (2946)
LEVEL 1 ACOUSTIC ENCLOSURE
Run Time Hours
Usable Capacity Gal (L)
L x W x H (in (mm) Weight lbs (kg) Enclosure Only
Steel Aluminum
No Tank - 247.5 (6285) x 71 (1803) x 80 (2032)
(1262)
(586)
10 334 247.5 (6285) x 71 (1803) x 94 (2388)
32 1001 247.5 (6285) x 71 (1803) x 116 (2946)
32 1001 247.5 (6285) x 71 (1803) x 105 (2667)
64 2002 290 (7366) x 71 (1803) x 116 (2946)
LEVEL 2 ACOUSTIC ENCLOSURE
Run Time Hours
Usable Capacity Gal (L)
L x W x H (in (mm) Weight lbs (kg) Enclosure Only
Steel Aluminum
No Tank - 207.4 (5268) x 71 (1803) x 114 (2899)
(1510)
(692)
10 334 207.4 (5268) x 71 (1803) x 128 (3251)
32 1001 207.4 (5268) x 71 (1803) x 150 (3810)
32 1001 228 (5791) x 71 (1803) x 139 (3531)
64 2002 290 (7366) x 71 (1803) x 150 (3810)
GE
NE
RA
TO
R
CO
NT
RO
LS
Part No. 0191120SSD Rev. / /1
Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53187 P: (262) 544-4811 © 2015 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
CONTROL INTERCONNECTIONS
H-PANEL, CCI
GTS TRANSFER SWITCH
RB3
HTS TRANSFER SWITCH
R
LOW VOLTAGE CONNECTION PANEL
SPARE OUTPUTS NOTE 1 + 3
NOTE 4
NOTE 5
NOTES:
SPARE OUTPUTS ARE STANDARD ON INDUSTRIAL
PRODUCT ONLY. GENLINK™ REQUIRED FOR
PROGRAMMING. CONTACTS RATED
TB4 MAX WIRE SIZE: #10 AWG, RECOMMENDED
TIGHTENING TORQUE: 14 LB-IN
TB1, TB2 & RB3 MAX WIRE SIZE: #14 AWG
RECOMMENDED TIGHTENING TORQUE: 12 LB-IN
REFER TO H-PANEL MANUAL FOR INSTRUCTIONS
ON ENABLING HTS TRANSFER SWITCH. REFER TO
HTS TRANSFER SWITCH MANUAL FOR DIP SWITCH
SETTINGS FOR MULTIPLE HTS APPLICATIONS.
CONNECT THE RS485 OVERALL SHIELD AT
GENSET CONNECTION TERMINAL ONLY.
NOTE 5
125A
LOAD CENTER
TB1 TB2
HIGH VOLTAGE CONNECTION PANEL
NOTE 2
NOTE 3
NOTE 3
TB4
120/240 VAC
UTILITY SUPPLY
(BY CUSTOMER)
VERIFY COMPONENT
RATINGS FOR PROPER
SUPPLY VOLTAGE
TO BE PROVIDED.
NE
RA
TO
R
CO
NT
RO
LS
21 LIGHT REMOTE ANNUNCIATOR AND
REMOTE RELAY PANELS
The remote Annunciator Panel provides remote monitoring and annunciation of up to 18 generator parameters using LED’s located on the annunciator keypad. It also provides two system level warnings which are System Ready and Communications OK.
The Relay panel has up to 8 selectable functions on form A relays, and multiple relay panels can be connected for all 18 generator parameters.
The specific faults can be selected using either the DIP switches located on the annunciator circuit board or through a computer via the RS232 connection on the circuit board. All relays are energized on power up and open during a fault condition.
Communication is via a RS485 serial data link and power is supplied by the generator battery (+12 VDC or +24 VDC)
The remote Annunciator Panel complies with NFPA 99 and NFPA 110.
Environmental Specifications:
Operating Temperature ............................................................................................................................................. -25 ºC to 60 ºC Humidity ...................................................................................................................................................0 to 95% Non Condensing Power Supply .....................................................................................................................Generator Battery, +12 or +24 Volts DC Power Usage...............................................................................................................................................................6 watts typical Communication Line ..............................................................................................RS485 fully isolated twisted pair cable with shield Maximum Cable Length ...................................................................................................................................................... 4000 feet Relay Output ...................................................... One NO contact (Energized when annunciator is powered and no faults are present) Relay Contact Rating ................................................................................................................................................. 30 VDC, 1 amp Enclosure Rating .................................................................................................................................................................. NEMA 1 Alarm Horn (Remote Annunciator Panels Only) .........................................................................................................90 dB @ 10 cm
Model 0054650 Gray Remote Annunciator Panel without Relays Model 0054660 Gray Remote Relay Panel without LED’s and Keypad (Relay’s only) Model 0054640 Gray Remote Annunciator Panel with 8 Relays Model 0056370 Tan Flush Mount Enclosure w/o Annunciator Model 0066950 Gray Flush Mount Enclosure w/o Annunciator
Description:
Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53187 P: (262) 544-4811 © 2018 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
GE
NE
RA
TO
R
CO
NT
RO
LS
Part No. 0604160SSD Rev. D 4/27/18
21 LIGHT REMOTE ANNUNCIATOR AND
REMOTE RELAY PANELS
Function Color Alarm Latched Pre-Low Oil Pressure Yellow Yes Yes Pre-High Water Temp Yellow Yes Yes Pre Low Water Temp Yellow Yes Yes Pre-Low Fuel Yellow Yes Yes Battery Chrg AC Fail Yellow Yes No Low Battery Voltage Yellow Yes No High Battery Voltage Yellow No No Not in Auto Red Yes No RPM Sensor Loss Red Yes Yes Overcrank Red Yes Yes Over speed Red Yes Yes Low Oil Pressure Red Yes Yes Hi Water Temp Red Yes Yes Lo Water Level Red Yes Yes Emergency Stop Red Yes No Gen Running Yellow No No Gen Power (ATS) Yellow No No Line Power (ATS) Green No No Systems Ready Green Yes No Communications OK Green Yes No Spare Green No No
Spare Keypad Switch Can be used to implement a remote start function (Model 05464 only)
Surface Mount Annunciator
The 21 Light Annunciator can mount to a flat surface with connections through the
0.812 Dia knockout on the back surface
or through 0.812 knockouts on sides as shown.
Flush Mount Annunciator
This Flush Mount Box is recessed into the wall opening and the surface mount annunciator mounts to the
(4) 4 mm screw holes on the back surface. After wire connections are made the front annunciator cover is attached.
1.649.06
0.86
0.812 Dia. 4.53
0.812 Dia.
Both Sides
11.42
10.24
7.09
8.27
9.64 Outside
Four mounting holes for 21 Light Annunciator 4-mm -0.7 Female Thread
1.57 Thru
2.32
1.93
R0.59 Both Sides
0.87
1.42
6.49
Cut Rough Opening 6.75” x 9.88”
5.8
P: (262) 544-4811 © 2019 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
Bulletin No. 0175540SSB Rev. E 12/05/18
ALTERNATOR DATA SHEET
K0500124Y23
Hz
A
LT
ER
NA
TO
R
DA
TA
General Characteristics
Voltages (V) 380, 208/240, 480 Number of Leads 12
Frequency (Hz) 60 Winding Type Reconnectable
Phases 3 Air Flow (cfm) 5106
Speed (rpm) 1800 Total Harmonic Distortion (%) <5
Excitation System PMG Largest Single Harmonic Value (%) <3.5
Insulation Class H Telephone Interference Factor (TIF) <50
Winding Pitch 2/3 Reference Part Number OH9457, OJ9643, GTA312AIIB
Ratings at 0.8 pf based on 40 C Ambient
Voltage (V) kW kVA kW kVA kW kVA kW kVA
380 326 408 374 467 408 510 446 558
208/240 377 472 432 541 472 590 504 631
480 400 500 458 573 500 625 534 668
Reactance Base Data at 480V, 625 kVA, 1800 RPM, 60 Hz, 3 Phase
Description Value
Stator Resistance, Line to Neutral, High Wye 0.007
1.721
15.26
0.1518
1.1064
Xd, Direct Axis Synchronous Reactance (p.u.) 3.62
X2, Negative Sequence Reactance (p.u.) 0.221
X0, Zero Sequence Reactance (p.u.) 0.023
X’d, Direct Axis Transient Reactance (p.u.) 0.289
X”d, Direct Axis Subtransient Reactance (p.u.) 0.227
Xq, Quadrature Axis Synchronous Reactance (p.u.) 1.291
T’d, Direct Axis Transient Short Circuit Time Constant (s)
1.10
Description Value
T”d, Direct Axis Subtransient Short Circuit Time Constant (s)
0.0019
T’do, Direct Axis Transient Open Circuit Time Constant (s)
1.399
Ta, Short Circuit Time Constant of Armature Winding (s)
0.021
Phase Sequence CCW-NDE T1, T2, T3
Voltage Balance, L-L or L-N (%) Contact Factory
Deviation Factor (%) Contact Factory
High Wye Connection, Sustained 3-Phase Short Circuit Current (%) - PMG only
Contact Factory
X/R Contact Factory
Short Circuit Ratio 0.28
Heat Rejection (BTU/hr) - 100% Rated Load, 480V, 0.8pf, 120oC Temp. Rise
158,487
Reference: Mil-STD-705B All Ratings are Nominal
P: (262) 544-4811 © 2019 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
Bulletin No. 0175540SSB Rev. E 01/23/19
ALTERNATOR DATA SHEET
K0500124Y23
Hz
A
LT
ER
NA
TO
R
DA
TA
skVA
10% 15% 20% 25% 30%
480V @ 0.3PF 240 360 520 700 900
480V @ 0.6PF 260 410 590 800 1020
208/240V @ 0.3PF 160 280 380 520 650
208/240V @ 0.6PF 190 300 430 570 730
380V @ 0.3PF 140 220 320 420 540
380V @ 0.6PF 160 240 360 480 620
Efficiencies
480V @ 0.8 PF 480V @ 1.0 PF 208/240V @
0.8PF
208/240V @
1.0 PF
380V 0.8PF 380V 1.0PF
25% Rated Power* 86.3 89.0 86.7 89.3 85.9 86.7
50% Rated Power* 90.8 92.8 90.6 92.6 90.1 92.2
75% Rated Power* 91.7 93.6 91.1 93.1 90.7 92.7
100% Rated Power* 91.5 93.6 90.7 92.8 90.3 92.4
*Rated Power value is rating kVA at 125°C Winding Temp Rise
LOG LOG Decrement Curves
Time [s]
Sh or t-c irc ui t c ur re nt [A m ax im um ti m e s
3 Phase short-circuit current decrement curve. At no load and rated speed (connection Y 60Hz ) 480 V
10000
0.001 0.010 0.100 1.000 10.000
Phase to neutral (1-phase L-N) short-circuit
Three-phase symmetrical short circuit
Phase to phase (2-phase L-L) short-circuit Three-phase asymmetrical short circuit
EN
CL
OS
UR
E
GENERATOR ENCLOSURES
DESCRIPTION
GENERAC POWER SYSTEMS’ generator enclosures provide year-round weather protection for your power equipment. Engineered with functionality and value in mind, the enclosure design benefits are unique in that the enclosures utilize dimensionally matched components for either a weather protective configuration or a sound attenuated/acoustic configuration. With common components used between design, modification and on-site upgrades can be accomplished with ease.
The enclosure design offers several benefits over the “standard enclosures” of other manufacturers. Generac’s enclosures have been created with the goal of maximizing the customer’s product performance satisfaction while maintaining the functionality of reducing exterior noise levels and discouraging product tampering.
Although others may require a “premium” for a self-enclosed exhaust system, rugged steel panel construction or protective polyethylene washers under all exterior panel fasteners, Generac includes these and several other features on every enclosure configuration. Be sure to compare. Generac Enclosures offer additional design enhancement extras that other “standard enclosures” do not.
EN
CL
OS
UR
E
GENERATOR ENCLOSURES
Post-Free Twin Doors Provide Large, Unobstructed Service Access
Gasket-Free, Interconnected Roof Panel Joint Drip-Free, Maintenance-Free
Heavy Gauge, Stainless Steel, Partial Pin Hinges with Nylon Spacers Durable, Corrosion-Free, Removable Doors
Lockable Turn and Tuck Stainless Steel Latch Handle Corrosion-Free, Non- Protruding and Secure
Dense, Closed-Cell Foam Insulation with Reflective Silver Mylar Layer Improved Sound Attenuation Without Damaging Effects From Radiant Heat Exposure
Two-Point Door Latch System Ensures Proper Seal Preventing Water Ingress and Sound Egress
P: (262) 544-4811 © 2016 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
EN
CL
OS
UR
E
Doc No. 0163180SBY Rev. D 02/27/18
GENERATOR ENCLOSURES
FEATURES: BENEFITS:
Dimensional matching of acoustic and non-acoustic enclosure designs
Reduces variation in fuel tank pricing, inventory; removes need to change out fuel tank or retrofit
Standardized enclosure components * Ease of retrofit or upgrade to acoustic system; reduced parts inventory, costs
Enclosure mounted directly to unit baseframe Simplified delivery and installation with enclosure and unit in single component design
Electrostatically painted panels Maximum protection from weather elements
12 or 14 gauge steel based on kW rating Maximum sound attenuation, protection and product life
Aluminum Enclosure optional Prevents corrosion in coastal regions
Stainless steel door latch and hinge hardware Provides extended component life; maximum protection against rusting
Stainless steel door latch strike plate Maximum protection against enclosure paint damage from door latch pin
Door hinges utilize slip-pin design Provides quick door removal for full-unit access
Polyethylene gasketing under door hinges Additional protection for enclosure paint finish
Keyed door latches Protection for equipment and personnel
Large removable access doors Ease of maintenance
Relocation of access doors Provides improved access to MLCB on all units
Redesigned door gasketing Improved sealing quality from sound and weather elements
Weather resistant aluminum roof design with drip ledge Provides optimum moisture/rain runoff from unit
Cabled and gasketed radiator access cover Provides improved radiator access and additional protection from weather elements
Acoustic roof panels manufactured with mechanical retention pins Increased acoustic foam retention within unit
Polyethylene washers under all panel fasteners Additional paint finish protection from stainless steel fastener
Internally fastened enclosure panels (where possible) Provides streamlined unit appearance
Additional roof panel stiffener Added overall compartment rigidity and acoustic foam panel retention
Self-enclosed exhaust system Provides safe unit operation; no enclosure hot spots; streamlined unit appearance
Discharge air duct has been designed with minimal fasteners Ease of removal and access to exhaust system
Stainless steel exhaust band clamps Provides extended component life; ensures proper exhaust seal
Drain holes within air ducts Enables maximum water run-off
Rodent-proof, tamper proof enclosure design Safety and security for personnel and equipment
Redesigned baseframe lifting lugs Ease of unit relocation; prevents compartment damage from lifting straps
150mph wind kit options Meets locally enforced wind requirements
* Consult Generac Power Systems, Inc. for installation drawings for specific configurations and dimensions.
P: (262) 544-4811 © 2015 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
AL
TE
RN
AT
OR
C
IR
CU
IT
B
RE
AK
ER
Part No. 0189370SSD Rev. C 11/08/16
EATON CIRCUIT BREAKER DATA
STANDARD (80% RATED) THERMAL-MAGNETIC
AMPS VOLTS ACCESSORIES EATON PART No. SERIES FRAME GENERAC PART No.
350 600 No Accessories KG3350
C K-Frame
0H9320TA00
Shunt Trip & Aux. Contacts KG3350A12S43 0H9320TAB0
400 600 No Accessories KG3400
C K-Frame
0H9321TA00
Shunt Trip & Aux. Contacts KG3400A12S43 0H9321TAB0
450 600 No Accessories LG3450
C L-Frame
0H9322TA00
Shunt Trip & Aux. Contacts LG3450A12S03 0H9322TAB0
500 600 No Accessories LG3500
C L-Frame
0H9323TA00
Shunt Trip & Aux. Contacts LG3500A12S03 0H9323TAB0
600 600 No Accessories LG3600
C L-Frame
0H9324TA00
Shunt Trip & Aux. Contacts LG3600A12S03 0H9324TAB0
700 600 No Accessories MDL3700
C M-Frame
0H9325TA00
Shunt Trip & Aux. Contacts MDL3700A06S02 0H9325TAB0
800 600 No Accessories MDL3800
C M-Frame
0H9326TA00
Shunt Trip & Aux. Contacts MDL3800A06S02 0H9326TAB0
900* 600 No Accessories NG3900
C N-Frame
0H9327TA00
Shunt Trip & Aux. Contacts NG3900A12S03 0H9327TAB0
1000* 600 No Accessories NG31000
C N-Frame
0H9328TA00
Shunt Trip & Aux. Contacts NG31000A12S03 0H9328TAB0
1200* 600 No Accessories NG31200
C N-Frame
0H9329TA00
Shunt Trip & Aux. Contacts NG31200A12S03 0H9329TAB0
1400* 600 No Accessories RGH316033MY22
G RG-Frame
0H9360EAN0
Shunt Trip & Aux. Contacts RGH316033MA12S21Y22 0H9360EANB
1600* 600 No Accessories RGH316033MY22
G RG-Frame
0H9361EAN0
Shunt Trip & Aux. Contacts RGH316033MA12S21Y22 0H9361EANB
2000* 600 No Accessories RGH320033M
G RG-Frame
0H9367EAN0
Shunt Trip & Aux. Contacts RGH320033MA12S21 0H9367EANB
2500* 600 No Accessories RGH325033M
G RG-Frame
0H9368EAN0
Shunt Trip & Aux. Contacts RGH325033MA12S21 0H9368EANB
*LS-type electronic trip breaker equipped with RMS 310+ trip unit.
P: (262) 544-4811 © 2019 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
AL
TE
RN
AT
OR
C
IR
CU
IT
B
RE
AK
ER
Part No. 0192390SSD Rev. I 05/08/19
EATON CIRCUIT BREAKER DATA
LUG INFORMATION
Eaton Series C Circuit Breaker Lugs
Standard Lug
Amps Series Frame Eaton Part # Wire (QTY) Size
15-70 C G - (1) #10-1/0
15-100 C F 3T100FB (1) #14-1/0
125-200 C F 3TA225FD (1) #4-4/0
225 C F 3TA225FDK (1) #6-300MCM
250 C J TA250KB (1) #4-350MCM
300 C K TA350K (1) 250-500MCM
350-400 C K 3TA400K (2) 3/0-250MCM
450-500 C L TA602LD (2) 3/0-350MCM
600 C L 3TA603LDK (2) 400-500MCM
700-800 C M TA800MA2 (3) 3/0-400MCM
900-1000 C N T1200NB3 (4) 4/0-500MCM
1200 C N TA1201NB1 (3) 500-750MCM
Eaton Series G Circuit Breaker Lugs
Amps Series Frame
Standard Lug
Eaton Part # Wire (Qty) Size
50-250 G JG TA250FJ (1) #4-350MCM
300-600 G LG 3TA632LK (2) #2-500MCM
900-1000 G NG T1200NB3 (4) 4/0-500MCM
1200 G NG TA1201NB1 (3) 500-750MCM
1400-1600 G RG T1600RD (4) 1-600MCM
2000 G RG Lugs Not Included
2500 G RG Lugs Not Included
• Warranty by Exide Corp. • Exide e-mail: tbgna@exide.com • 800-782-7848 National Hot line • Dry Batteries Available**
Industrial Spark-Ignited Gensets - Available Batteries
Engine System Voltage Battery Quantity Generac Part #
058208 (Group 24F) 077483 (Group 26) 058665 (Group 27F) 061119 (Group 31) 061104 (Group 8D)
G2.4 12 1 X
G5.4 12 1 X X or D X or D
G6.8 12 1 X or D X or D
G8.0/G9.0 12 1 X or D X or D
G14.2 24 2 X or D
G21.9 24 2 X or D
G25.8 24 2 X or D
G33.9 24 4 X
X = Battery available with electrolyte and installed in genset.
D = Battery available dry and installed in genset.
Industrial Diesel Gensets - Available Batteries
Engine System Voltage Battery Quantity Generac Part #
058665 (Group 27F) 061119 (Group 31)
061104/BT0015A00
(Group 8D)
BT0015A02
(Group 8D)
D2.4 Generac 12 1 X or D X or D
D3.4 Generac 12 1 X or D X or D
D4.5 FPT 12 1 X or D
D6.7 FPT
100 & 130kW
12 1 or 2† X or D
D6.7 FPT
150 & 175kW
12 2† X or D
D8.7 FPT 24 2 X or D
D10.3 FPT 24 2 X or D X or D
D12.9 FPT 24 2 X or D X or D
D12.5 Perkins 24 2 X or D
D15.2 Perkins 24 2 X or D
D16.0 Volvo 24 2 X or D X or D
D18.1 Perkins 24 2 X or D
D33.9 MHI 24 2 X X
D37.1 MHI 24 4 X X
D49.0 MHI 24 4 X X
D65.4 MHI 24 4 X X
X = Battery available with electrolyte and installed in genset.
D = Battery available dry and installed in genset.
† = Single or dual-paralleled battery options are available on 100 & 130kW. Single-battery option not available on 150 & 175kW.
Part Number Group Number* Nominal CCA
@ 0° F Dimensions (inches) Nominal
A B C
058208 24F 525 6.75 10.63 9.00
077483 26 525 6.75 8.25 7.75
058665 27F 700 6.75 12.50 9.00
061119 31 925 6.75 13.00 9.40
061104/
BT0015A00
8D 1155 11.00 20.80 10.00
BT0015A02 8D 1300 11.00 20.80 10.00
All batteries are 12 volt, 6 cell construction, lead calcium type.
For 24 volt systems, batteries are wired in series.
* BCI Group Size reference.
** Add an “A” suffix to the Generac part number for dry batteries, which are shipped without electrolyte.
Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53187 P: (262) 544-4811 © 2016 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
EN
GI
NE
O
PT
IO
NS
Part No. 0161970SBY Rev. G 11/03/17
INDUSTRIAL GENSET
BATTERY INDEX
27F
24F
8D +
A
A
B
C
C
P: (262) 544-4811 © 2019 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
BATTERY CHARGER
2.5A & 10A
Part No.0191900SBY Rev. D 03/11/19
GE
NE
RA
TO
R
CO
NT
RO
LS
The Generac 2.5A 12V and 10A 12/24V battery chargers are designed to work with Generac Industrial Controls to provide the ultimate in automatic battery voltage maintenance.
The 2.5A charger is self-regulating and produces instantaneous output current adjustments to keep the battery charged to an optimum level. Battery voltage is read on the control panel digital display.
The 10A charger has automatic float and equalize control.
It precisely monitors the battery’s voltage and automatically activates the correct charging mode. The charge rate is limited and controlled to efficiently and safely maintain ideal battery levels under varying conditions.
The equalize system uses a control circuit to limit charging current to 10 Amps. When battery voltage drops below a preset level, charging current increases to 5 Amps and then to the 10 Amp charge rate if needed. When the battery reaches maximum charge, the charger switches to float mode to supply just enough current to maintain the battery at or above 13/26 Volts. Battery voltage and charging current are read at the control panel digital display.
Battery Charger shown from inside of Control Panel Enclosure.
Connections are made via an attached harness.
Specifications 2.5A 10A
Nominal Input 120 VAC 120 VAC
Operating AC Line Voltage Range 108 to 132 VAC 108 to 132 VAC
Input AC Line Frequency 50/60 Hz 50/60 Hz
Battery Fuse N/A 15A
Nominal Charge Rate 2.5A 10A
Equalize Voltage 13.8/27.6 Volts
Float Voltage 13.4 Volts 13.0/26.0 Volts
Current @ Equalize to Float Transition 5A
Battery Under-voltage shutdown N/A 11/22 Volts
LED Indicators
AC Line Voltage N/A Green LED
Battery Connected and charging N/A Yellow LED
Battery Current Drain 30 Milliamp 30 Milliamp
AC Line Connection Connector Plug Connector Plug
Battery Connection Connector Plug Connector Plug
Control Connection AC Power Fail Form Relay Form C 2A Rating
CUL Recognized Yes Yes
NFPA 110 Compliant No Yes
AGM Compatible No Yes
P: (262) 544-4811 © 2016 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
EN
GI
NE
Part No. 10000004898 Rev. A 06/23/16
12-POSTION LOAD CENTER
125A
Description
The 12 position 125A Load Center is a unit-mounted distribution panel that is optional equipment on Generac generators that utilize the H-100 Panel, PM-GC, or PM-PC control systems. This main lug load center includes all of the circuit breakers required for the coolant heater, battery charger, and other factory-installed optional AC loads within the generator set, and serves as a convenient connection point for the customer’s utility feed for those AC loads. All breakers are labeled for specific load circuits.
Specifications
• Siemens part number: SW1224L1125
• 125A Main Lug Load Center
• 100,000A IR
• Single Phase, Aluminum Bus
• UL Listed
• NEMA 3R
• Maximum of 12 single pole breakers
• Maximum of 6 two pole 240V Breaker
• Dimensions: 21” L x 14.25” W x 3.88” D
RA
TO
R
CO
NT
RO
LS
Part No. 0K5958 Rev. B 04/14/15
Generac Power Systems, Inc. | P.O.
This is the start of the file's text. The full file is on GovTribe.