This document is a solicitation from the Office of the Federal Public Defender, District of Kansas, requesting quotations for the procurement of furniture for their existing office space in Kansas City, Kansas. The solicitation includes general project requirements such as delivery, installation, debris removal, and insurance coverage. Offerors are required to provide an itemized price quotation, including per item pricing, total cost, manufacturer specifications, and all associated freight, delivery, and installation costs. The award will be made to the lowest priced offeror that meets the technical requirements, with a desired delivery and installation completion date of Tuesday, September 6, 2024. All offers must be received by 5:00 P.M. CST on Thursday, July 18, 2024. The contracting agency is the Administrative Office of the U.S. Courts.

View the file

Other files

File Type Posted
KCK.2024.06 RFQ_SOW.pdf PDF
KCK.2024.06 RFQ_VendorInfoSheet.pdf PDF
KCK.2024.06 Furniture_List.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. DO NOT SCALE DRAWINGS. USE FIGURED DIMENSIONS ONLY, VERIFY

ALL DIMENSION PRIOR TO START OF WORK. IN THE EVENT OF

DISCREPANCY, NOTIFY C.O.R. AND OBTAIN RESOLUTION BEFORE

PROCEEDING."

2. NOTIFY THE C.O.R. OF ANY AND ALL DISCREPANCIES BETWEEN

EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS BEFORE

PROCEEDING WITH THAT PORTION OF WORK. FAILURE TO NOTIFY THE

C.O.R. WILL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY TO

PERFORM THE WORK AS INTENDED BY THE CONTRACT DOCUMENTS.

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK ARISING FROM

SUCH FAILURE TO COORDINATE DISCREPANCIES TO THE

SATISFACTION OF THE C.O.R.."

3. WHERE EXISTING CONSTRUCTION AND GRIDS ARE INDICATED,

CONTRACTOR SHALL VERIFY EXISTING DIMENSIONED GRIDS PRIOR TO

PERFORMING LAYOUT WORK REQUIRED FOR INSTALLATION OF NEW

WORK."

4. VERIFY EXISTING DIMENSIONS, CONDITIONS AND CLEARANCES PRIOR

TO THE SUBMITTAL OF SHOP DRAWINGS"

5. ALL SLEEVES, OPENINGS, ETC. FOR CONDUIT, PIPES, DUCTS, ETC.

(OUTSIDE OF RATED CHASES) THROUGH FLOOR SLABS AND RATED

PARTITIONS ARE TO BE FIRE SEALED IN ACCORDANCE WITH FIRE

RATED ASSEMBLY DESIGNS, APPLICABLE CODES AND FIRE MARSHAL'S

REQUIREMENTS."

6. PROVIDE A MINIMUM OF 3/4"" FIRE-RETARDANT TREATED WOOD

BLOCKING OR 18 GA. MINIMUM STEEL PLATE BLOCKING AS REQUIRED

WITHIN STEEL STUD FRAMED PARTITIONS FOR SECURE AND PROPER

ATTACHMENT OF NEW WORK, INCLUDING BUT NOT LIMITED TO A/V

EQUIPMENT, MILLWORK, VISUAL DISPLAY SURFACES, SIGNAGE, AND

FURNISHINGS WHERE INDICATED ON PLANS."

7. WHERE WORK OCCURS IN AREAS WITH EXISTING FINISHES TO REMAIN,

REFINISH DISTURBED AREAS TO MATCH EXISTING FINISHES AND

MATERIALS UNLESS NOTED OR DIRECTED OTHERWISE."

8. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL

DIMENSIONS, ELEVATIONS, AND DETAIL SHOWN ON THE DRAWINGS.

ANY DISCREPANCIES WHICH WILL PREVENT THE ACCOMPLISHMENT OF

INTENT SHOWN ON DRAWINGS SHALL BE BROUGHT TO THE IMMEDIATE

ATTENTION OF THE C.O.R.. INDICATED CONDITIONS ARE NOT

INTENDED AS REPRESENTATIONS OR WARRANTIES OF ACCURACY. IT

IS EXPRESSLY UNDERSTOOD THAT THE GOVERNMENT WILL NOT BE

RESPONSIBLE FOR INTERPRETATIONS OR CONCLUSIONS DRAWN BY

THE CONTRACTOR."

9. WHERE CONDUIT, PIPES, DUCTS, ETC. ARE INDICATED TO BE

INSTALLED IN EXISTING WALLS AND NO FURRING IS SHOWN, THE

WALLS SHALL BE NEATLY CHASED, CONDUITS, ETC. INSTALLED, AND

WALLS PATCHED TO MATCH EXISTING. IN AREAS OF NEW PARTITIONS

WHERE CONDUITS, DUCTS, PIPING, ETC, PASS THROUGH FINISHED

SPACES, ROUTE WITHIN PARTITION CONSTRUCTION."

10. PROTECT AND PRESERVE ALL EXISTING ITEMS TO REMAIN AND REPAIR

AND/OR REPLACE ANY ITEMS DAMAGED DURING THE COURSE OF THE

WORK TO THE SATISFACTION AND APPROVAL OF THE C.O.R. WITHOUT

ADDITIONAL COST TO THE GOVERNMENT."

11. (## ## ##) INDICATES REFERENCED SPECIFICATIONS FOR PRODUCTS

AND MATERIALS SHOWN ON THE DRAWINGS AND SPECIFIED IN THE

PROJECT MANUAL."

GENERAL NOTES - FLOOR PLAN

NEW CONSTRUCTION

EXISTING CONSTRUCTION

X

ROOM NAME

DOOR INDICATION TAG

PARTITION TYPE

WINDOW TYPES

PLAN KEYNOTES

SPOT ELEVATION

DRAWING REVISION

ROOM NAME AND NUMBER

CENTER LINE

MATCH LINE

FLOOR PLAN SYMBOLS

NEW GRID IDENTIFIER

EXISTING GRID IDENTIFIER

OFFICE 200A

OFFICE 200B

OFFICE 200C

OFFICE 200D

OFFICE 200E

OFFICE 200F

OFFICE 201C

S T

O R

A G

E

A

OFFICE 201E

OFFICE 201F

OFFICE 201G

OFFICE 201H

OFFICE 201N

OFFICE 201M

OFFICE 201R

SERVER 201B

STORAGE 201J

INTERVIEW/CONF. 201L

RECEPTION 201T

GALLEY / WORK RM

201K

IT / OFFICE 201D

SM. CONF. 200H

T E

L E

W O

R K

Q

EXPANDED ELEVATOR

LOBBY 207

CORRIDOR 201S

TELEWORK 201P

NO WORK IN

SHADED AREA

NO WORK IN

SHADED AREA

EX207

E X

E X

EX204

E X

EX211

E X

EX27

A

202A

E X

226A

B

A

A

A

230A

219A

E X

215A

EX232

205A

A

A

A

A

GSA 203

A B C D E

G3

G3

G3

G1

G1

G2

G2

G2

G2

G2

G2

G2

G2

G2

G2

G1

G1

G1

G1

G2

G2

G2

G2

G2

G2

COMMON AREA/

CORRIDOR 201

A2

A2

A3

A3

A4

A2

ID211

20' - 0" 40' - 0" 20' - 0" 40' - 0"

208A

SCOPE AREA B

SCOPE AREA A

G2

A2 A2

220A

A9

A9

A9

A9

A9

A10

ID211

ID211 8

2' - 8 1/4"

/2

MIN.

1' - 0"

/2

11' - 9 1/2" 11' - 9 1/2"

ALIGN

A L

IG

N

A L

IG

N

/4

STAIR 1

A13

A13

AREA OF WORK

A B C D E

1. REFER TO PARTITION TYPE SYMBOLS ON FLOOR PLANS.

2. REFER TO CODE PLAN FOR MINIMUM REQUIRED FIRE RATING IN HOURS.

3. PARTITION TYPES DO NOT INDICATE WHICH SIDE FINISH MATERIALS ARE

APPLIED. REFER TO FINISH PLAN.

4. REFER TO THE PROJECT MANUAL FOR MINIMUM GAGE STUDS, RUNNERS,

FURRING CHANNELS, MISC. ANGLES & CLIPS.

5. FIRE RATED WALLS SHALL MAINTAIN FIRE RATING AS SCHEDULED

CONTINUOUSLY TO UNDERSIDE OF SLAB OR ROOF DECK.

6. PARTITIONS ARE DIMENSIONED TO THE FACE OF THE GYPSUM/

VENEER/BACKER BOARD - NOT APPLIED FINISH MATERIAL (i.e. VENEER, CERAMIC TILE, ETC.)

7. COORDINATE THE LOCATION OF FIRE RATED PARTITIONS WITH CODE PLANS.

8. REFER TO STRUCTURAL DRAWINGS FOR DESIGN OF LOAD BEARING

PARTITIONS.

9. HOLD ALL GYPSUM BOARD 1/2"" ABOVE CONCRETE SLAB TO AVOID WICKING

ACTION.

10. CONTRACTOR TO PROVIDE FIRE RETARDANT BLOCKING IN FIRE RATED

WALLS AS NECESSARY TO MOUNT FIXTURES, RAILS, MILLWORK, AND

ACCESSORIES PER MANUFACTURER'S RECOMMENDATIONS TO MEET

APPLICABLE BUILDING CODES. WHERE MASONRY CONSTRUCTION IS

INDICATED, CONTRACTOR TO PROVIDE ANCHORS INTO MASONRY AND

GROUT CELLS FULL AS REQUIRED TO MOUNT FIXTURES AND ACCESSORIES

PER MANUFACTURER'S RECOMMENDATIONS.

11. FIRE STOPPING IS REQUIRED AT: A. ALL PENETRATIONS THROUGH FIRE AND

SMOKE RESISTIVE FLOOR AND ROOF CONSTRUCTION. B. ALL VOIDS AND

JOINTS AT TOP AND BOTTOM OF ALL FIRE AND SMOKE RESISTIVE WALLS AND

PARTITIONS. C. CONTROL AND EXPANSION JOINTS IN ALL FIRE / SMOKE

RESISTIVE WALLS AND PARTITIONS AND FIRE RESISTIVE FLOOR AND ROOF

CONSTRUCTION.

12. WHERE INTERIOR MASONRY IS TO BE EXPOSED, BULLNOSE CORNER UNITS

TO BE USED. STARTER COURSE TO BE SQUARE UNIT WITH BULLNOSE

ABOVE.

13. WHERE MASONRY CONSTRUCTION IS INDICATED, CONTRACTOR SHALL

COORDINATE LOCATION, SIZE, TYPE, AND SPACING OF ALL MASONRY

ANCHORS AND REINFORCEMENT WITH STRUCTURAL DRAWINGS.

14. WHERE GYPSUM BOARD IS INDICATED TO BE INSTALLED AT WET LOCATIONS,

INCLUDING BUT NOT LIMITED TO TOILETS AND JANITOR'S CLOSETS,

MOISTURE AND MOLD-RESISTANT GYPSUM BOARD SHALL BE PROVIDED.

GENERAL NOTES - PARTITIONS

(G1)(G1)

ONE LAYER OF 5/8" GWB ON

BOTH SIDES OF

3 5/8" 25 GAUGE MTL STUD AT

24" O.C. WITH GYP AND

INSULATION UP TO

STRUCTURE (STC 48)

(G1)

STRUCTURE ABOVE.

(G2)

ONE LAYER OF 5/8" GWB ON

BOTH SIDES OF 3 5/8" MTL STUD

WITH GYP 6" ABOVE CEILING

STEEL STUDS, 3 5/8" AT 16" O.C.

(092216)

M

IN

ACOUSTIC SEALANT ALL SIDES

TOP AND BOTTOM (079219)

BASE, RE: FINISH PLAN

FINISH CEILING. RE: RCP.

STRUCTURE ABOVE.

BASE, RE: FINISH PLAN

(G3)

ONE LAYER OF 5/8" GWB ON

BOTH SIDES OF 2 1/2" MTL STUD

WITH GYP 6" ABOVE CEILING

STEEL STUDS, 2 1/2" AT 16" O.C.

(092216)

M

IN

FINISH CEILING. RE: RCP.

STRUCTURE ABOVE.

BASE, RE: FINISH PLAN

GYPSUM BOARD, 5/8" (092900)

GYPSUM BOARD, 5/8" (092900)

GYPSUM BOARD, 5/8" (092900)

ACOUSTIC SEALANT ALL SIDES

TOP AND BOTTOM (079219)

STEEL STUDS, 3 5/8" 25 GAUGE

AT 24" O.C. (092216)

GYPSUM BOARD, 5/8" (092900)

GLASS FIBER ACOUSTICAL

BLANKET INSULATION, MATCH

CAVITY DEPTH (092900)

GLASS FIBER ACOUSTICAL

BLANKET INSULATION, MATCH

CAVITY DEPTH (092900)

GLASS FIBER ACOUSTICAL

BLANKET INSULATION, MATCH

CAVITY DEPTH (092900)

SLIP TYPE HEAD JOINT, 2 1/2"

(092216)SLIP TYPE HEAD JOINT, 3 5/8"

(092216)

SLIP TYPE HEAD JOINT, 3 5/8"

(092216)

GENERAL SERVICES ADMINISTRATION

PUBLIC BUILDING SERVICE

HEARTLAND REGION 6

2300 MAIN STREET, 7TH FLOOR

KANSAS CITY, M0 64108-2416

N

2ND FLOOR

SENSITIVE BUT UNCLASSIFIED (SBU)

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

DO NOT REMOVE THIS NOTICE

PROPERLY DESTROY OR RETURN DOCUMENTS WHEN NO LONGER

NEEDED

2ND FLOOR

100% CONSTRUCTION DOCUMENTS

08/11/2017

FEDERAL PUBLIC DEFENDER EXPANSION

N1558030

ROBERT RUSBARSKY

ROBERT J. DOLE U.S. COURTHOUSE

500 STATE AVENUE

KANSAS CITY KS 66101

KS0094

SFS ARCHITECTURE

SMITH & BOUCHER

GS-06-P-15-GY-D-7000

WO-23

C E R T

IF

IC

A T

IO

N S

K E Y

P L A N

R E V

IS

IO

N

N O T E S

PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE:

SHEET OF

DISCIPLINE SHEET TYPE SEQUENCE

DRAWING NO.

DRAWING TITLE

FILE NAME

CHECKED BY

DRAWN BY DATE DRAFTED:

PROJECT NO.

GSA PM

SUB. DATE

SUBMISSION

DESCRIPTION

PROJECT

TITLE

BUILDING NOs.

OTHER

BUILDING NO.

CITY/ST./ZIP

STREET

NAME

D R A W

IN

G

P R O J E C T

B U

IL

D

IN

G

SUB A/E

PRIME A/E

A/E CONTR. NO.

C O N T R A C T O R S

G R

AP

H

IC

SC

AL

E

MARK DATE DESCRIPTION

FLOOR NO.

FACILITY CODE

PROJECT

A/E W.O. NO.

24 X 36

WF, MK

KS

KS0094ZZ

/1

/2

:0 :0

P

M

A111

FLOOR PLAN AND PARTITION TYPES

N1558030-A111.DWG

1/8" = 1'-0"A111

2 FLOOR PLAN

1" = 1'-0"

TYPES - WALLS

08' 16'8'

1/8" = 1'-0"

01' 2'1'

1" = 1'-0"

LEGEND - KEYNOTES FLOOR PLAN

Key Value Keynote Text

A2 WORKSTATIONS, PROVIDED BY THE GOVERNMENT.

A3 COPIER, PROVIDED BY THE GOVERNMENT.

A4 SMOKE CURTAIN (105200)

A9 SALVAGED DOOR. RE: DEMO PLAN

A10 SALVAGED DOOR.

A13 ADJUST DOOR CLOSER. OPENING FORCE OF THE DOOR SHOULD

NOT EXCEED FIVE POUNDS MAXIMUM.

A111

OFFICE 1OFFICE 2OFFICE 3OFFICE 4OFFICE 5

RECEPTIONIST AREA

WALKWAY 6

sreynolds Highlight sreynolds Highlight sreynolds Highlight sreynolds Highlight

Sheets
A111 - FLOOR PLAN AND PARTITION TYPES
A131 - CEILING PLAN
A601 - DOOR TYPES AND SCHEDULES
AD111 - DEMOLITION PLAN
AD121 - CEILING DEMOLITION PLAN
G001 - COVER
ID111 - FINISH PLAN, LEGEND, AND SCHEDULE
ID211 - ENLARGED PLAN, INT. ELE.& DETAILS