The file contains a Requirements List for Acoustic Panels for the Naval Surface Warfare Center, Dahlgren Division (NSWCDD). The specifications call for acoustic panels with a minimum 2" thickness, weighing no more than 1.25 lbs per square foot, wrapped in gray fabric, and capable of sound absorption across multiple frequency ranges (25 Hz to 4000 Hz). The panels must be field-cuttable to accommodate wall obstructions and remain intact in temperatures ranging from 32°F to 90°F at 90% relative humidity.

The associated federal contract opportunity (Solicitation Number N0017825Q6854) is a small business set-aside Request for Quotation (RFQ) for commercial acoustic panels and installation. The solicitation requires TAA-compliant materials, with quotes due by 14 August 2025 at 12:00 p.m. EST and an anticipated award date of 15 September 2025. Award will be made on a Lowest Price Technically Acceptable basis, with a firm fixed price. Offerors must be SAM-registered and provide documentation from the original equipment manufacturer verifying their authorized reseller status. Shipping destination is FOB Dahlgren, VA 22448-5114.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Acoustical Panels (specifications follow)
Minimum 2" thickness
Weight- no more than 1.25 lbs. per square foot
Fabric wrapped after field cutting to size- color Gray
Minimum sound absorption of 25 (Hertz) Hz @ .4 / 250 Hz @ .74 / 500 Hz @ 1.24 / 1000 Hz @ 1.25 / 2000 Hz @ 1.22 /4000 Hz @ 1.14.
Enough material to cover the included space layout and call out coverage area to include necessary field cutting
Attached to the wall surface in a manner that remain intact in a temperature range from 90 degrees Fahrenheit at 90% relative humidity down to 32 degrees Fahrenheit
Field cut to suit around obstructions on the walls including doors, vents, conduit, outlets, and supports, and other obstructions