05A 757-20-101 Correct RCx Def_DWGs.pdf
PDF 9 MB Posted
- Attached to
- Z1DA--Construction | Correct Retro Commissioning Deficiencies Project Number: 757-20-101 - VAACC Columbus
- Solicitation number
- 36C25021B0058
About this file
This document provides details for a federal solicitation seeking construction services. The solicitation will be posted on July 23, 2021 for Correct Retro-Commissioning Deficiencies at the VAACC Columbus facility, Project #757-20-101. Interested parties should register at SAM.gov to receive updates. A one-time site visit will be scheduled for interested parties. Bids are due approximately 30 days after solicitation posting. The work includes general construction and mechanical systems balancing and testing to correct deficiencies identified. The incumbent contractor will complete work within 210 calendar days of notice to proceed.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25021B0058 0004.docx | DOCX document | |
| 36C25021B0058 0003.docx | DOCX document | |
| 36C25021B0058 0002.docx | DOCX document | |
| 36C25021B0058 0001.docx | DOCX document | |
| VHA Directive 1013 Prevention and Control of Seasonal Influenza with Vaccines.pdf | ||
| 36C25021B0058_1.docx | DOCX document | |
| 04B 757-20-101 Correct RCx Def_Specifications Updated 07-19-2021.pdf | ||
| WD 07.30.2021 Franklin.pdf | ||
| 757-20-101 Correct RCx_VAACC Health Requirements.pdf | ||
| JCI DDC JA_Redacted - Complete.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2018 INTERNATIONAL BUILDING CODE
CHAPTER 3 - USE GROUP:
USE GROUP: B-BUSINESS
CHAPTER 4 - SPECIAL DETAILED REQUIREMENTS:
DETAILED REQUIREMENTS IF NEEDED
FIRE-RESISTANCE RATINGS REQUIREMENTS - TABLE 601:
CONSTRUCTION TYPE: 1A
STRUCTURAL FRAME: 3 HRS
BEARING WALLS:
EXTERIOR: 3 HRS
INTERIOR: 3 HRS
NON BEARING WALLS & PARTITIONS:
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
FLOOR CONSTRUCTION: 2 HRS
ROOF CONSTRUCTION: 1 1/2 HRS
CHAPTER 7 - FIRE-RESISTANCE-RATED CONSTRUCTION:
SHAFT ENCLOSURES: 2 HRS
EXIT ENCLOSURES: 2 HRS
EXIT PASSAGEWAYS: 0 HRS
CHAPTER 8 - INTERIOR FINISHES:
EXIT ENCLOSURES & PASSAGEWAYS: CLASS B
CORRIDORS: CLASS C
ROOMS & ENCLOSED SPACES: CLASS C
INTERIOR FLOOR FINISH: MINIMUM CLASS II
CHAPTER 9 - FIRE PROTECTION SYSTEMS:
SPRINKLER SYSTEM: FULLY SUPPRESSED
FIRE ALARM SYSTEM: YES
CHAPTER 10 - MEANS OF EGRESS:
DOOR WIDTH: 32" MINIMUM CLEAR WIDTH
CORRIDOR WIDTH: .2" PER OCCUPANT, BUT NOT LESS THAN 44"
LENGTH OF EXIT TRAVEL: 200'
2018 NFPA 101 LIFE SAFETY CODE
OCCUPANCY (6.1.11):
BUSINESS - OUTPATIENT CLINIC (AMBULATORY)
AMBULATORY HEALTH CARE (CHAPTER 20/21)
BUILDING TYPE:
TYPE 1 (332)
FIRE-RESISTANCE RATING REQUIREMENTS - TABLE A8.2.1.2:
STRUCTURAL FRAME: 3 HRS
BEARING WALLS:
EXTERIOR: 3 HRS
INTERIOR: 3 HRS
NON BEARING WALLS AND PARTITIONS
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
FLOOR CONSTRUCTION: 2 HRS
ROOF CONSTRUCTION: 1 1/2 HOURS
FIRE-RESISTANCE RATED CONSTRUCTION - TABLE A8.6.5/7.1.3.2.1
SHAFT ENCLOSURES: 2 HRS
EXIT ENCLOSURES: 2 HRS
SMOKE BARRIERS (20.3.7.5):
1 HOUR
TRAVEL DISTANCE (20.2.6.2):
REMOTE POINT TO EXIT 200 FOOT MAX
OTHER APPLICABLE CODES AND STANDARDS
1. VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL
2. OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS
3. ENERGY POLICY ACT OF 2005 (EPACT)
4. FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS:
MEMORANDUM OF UNDERSTANDING (MOU)
5. EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL,
ENERGY AND TRANSPORTATION MANAGEMENT
6. ASHRAE STANDARD 15-2007
7. ASHRAE STANDARD 62.1-2004
8. NATIONAL ELECTRICAL CODE (NEC) - 2020
9. INTERNATIONAL PLUMBING CODE (IPC) - 2018
10. NFPA 99 HEALTH CARE FACILITIES CODE - 2018
11. HVAC DESIGN MANUAL - MARCH 2020
12. PG-18-3 DESIGN AND CONSTRUCTION PROCEDURES - JULY 2004
13. PG 18-13 VA BARRIER FREE DESIGN STANDARD - JANUARY 2017
14. PG-18-15 MINIMUM REQUIREMENTS FOR A/E SUBMISSIONS - MAY 2006
PROJECT NUMBER:
SUBMITTAL FOR:
DRAWING INDEX: CODE DATA:LOCATION MAP:
DESCRIPTION OF WORK:
CORRECT RETRO COMMISSIONING
DEFICIENCIES
420 N. JAMES ROAD, COLUMBUS, OH 43219
757-20-101
BID AND CONSTRUCTION
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
CHALMERS P. WYLIE VAACC
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Farid F. Mehr, P.E.
Chief, Engineering Serice
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX. (440) 546-9699
/7
/2
:4
:5
P
M C
R e v it L o c a l\
R
V A
C o lu m b u s C o rr e c t
R e tr o C
X
C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m
.r v t
GI-1
757-20-101
CBLH STAFF
CORRECT RETRO COMMISSIONING
DEFICIENCIES
04/14/21
420 N. JAMES ROAD, COLUMBUS, OH 43219
COVER
DRAWING INDEX
SHEET NO. SHEET NAME
GENERAL
GI-1 COVER
MECHANICAL
MH-0A MECHANICAL LEGEND & GENERAL NOTES
MH-0B MECHANICAL SCHEDULES
MH-0C MECHANICAL SCHEDULES
MH-0D HVAC - RTU SEQUENCES OF OPERATION REVISIONS
MH-1A FIRST FLOOR HVAC AIR DISTRIBUTION PLAN - WEST
MH-1B FIRST FLOOR HVAC AIR DISTRIBUTION PLAN -EAST
MH-2A SECOND FLOOR HVAC AIR DISTRIBUTION PLAN - WEST
MH-2B SECOND FLOOR HVAC AIR DISTRIBUTION PLAN - EAST
MH-3 THIRD FLOOR HVAC AIR DISTRIBUTION PLAN
MH-4A FOURTH FLOOR HVAC AIR DISTRIBUTION PLAN - WEST
MH-4B FOURTH FLOOR HVAC AIR DISTRIBUTION PLAN - EAST
MHP-1A FIRST FLOOR HVAC PRESSURE RELATIONSHIP PLAN - WEST
MHP-1B FIRST FLOOR HVAC PRESSURE RELATIONSHIP PLAN - EAST
MHP-2A SECOND FLOOR HVAC PRESSURE RELATIONSHIP PLAN - WEST
MHP-2B SECOND FLOOR HVAC PRESSURE RELATIONSHIP PLAN - EAST
MHP-3 THIRD FLOOR HVAC PRESSURE RELATIONSHIP PLAN
MHP-4 FOURTH FLOOR HVAC PRESSURE RELATIONSHIP PLAN
BID ITEM 1 (BASE BID): Work includes general construction as indicated on Construction Drawings and Specifications. This includes surveying existing airflow conditions at all devices indicated, rebalancing airflow at all devises indicated, adjusting VAV box airflow setpoints at all VAV boxes indicated, rebalancing existing reheat coil water flow as indicated, revising RTUs sequence of operation, testing RTUs for existing air leakage, provide corrective measures at RTUs to reduce leakage, and re-testing leakage to confirm specifications met, and replacing outdoor air control damper linkages at each RTU. All work shall be completed within 210 calendar days after receipt of Notice to Proceed.
BID ITEM 2 (Alternate NO. 1): All work indicated in Base Bid except, remove all work associated with replacing the linkages at the outside air dampers on rooftop air handling units as indicated on Drawings MH-4A and MH-4B. All work shall be completed within 196 calendar days after receipt of Notice to Proceed.
BID ITEM 3 (Alternate NO. 2): All work indicated in BID ITEM 2 (Alternate 1) except, remove all work associated with VAV’s 1-143 and 1-145 near room 1A135 as indicated in plan views 2 and 3 on Drawing MH-1A. All work shall be completed within 189 calendar days after receipt of Notice to Proceed.
BID ITEM 4, (Alternate NO. 3): All work indicated in BID ITEM 3 (Alternate 2) except, remove all work associated with VAV 1-020 in room 1B098 as indicated on plan views 2 and 3 on Drawing MH-1B. All work shall be completed within 182 calendar days after receipt of Notice to Proceed.
BID ITEM 5, (Alternate NO.4): All work indicated in BID ITEM 4 (Alternate 3) except, remove all work associated with duct terminations in room 2A075 as indicated on plan view 1 on Drawing MH-2A. All work shall be completed within 168 calendar days after receipt of Notice to Proceed.
Revisions Date
BID AND CONSTRUCTION 04/14/21
HVAC GENERAL NOTES:
HVAC LEGEND AND ABBREVIATIONS
DEMOLITION SYMBOLS: HVAC PIPING:
HVAC CONTROLS:
DUCTWORK SYMBOLS:
MANUAL BALANCING DAMPER ON DUCT
ROUND DUCT SIZE
AD ACCESS DOOR
12"Ø
RECTANGULAR DUCT SIZE24x18
ELECTRICAL CONTRACTOR
GENERAL TRADES CONTRACTOR
TEMPERATURE CONTROL CONTRACTOR
HVAC CONTRACTOR
FIRE SUPPRESSION CONTRACTOR
PLUMBING CONTRACTOR
CONNECT TO EXISTING
EC
GC
FC
PC
TC
HC
TO
OPENING IN TOP OF DUCT. SHALL BE A MINIMUM 1.5
TIMES GREATER THAN THE CROSS-SECTIONAL AREA OF
DUCT.
UC
INDICATES UNDERCUT DOOR - UNDERCUT 3/4"
SEE
ARCHITECTURAL PLANS.
SUPPLY AIR DUCT
TO BE MOUNTED OVER ACCESSIBLE CEILING
SUPPLY AIR DIFFUSER
SHADING INDICATES TO PROVIDE QUADRANT BLANK-OFF
IN NECK OF DIFFUSER. TO BE FURNISHED WITH DIFFUSER.
INDICATES TRANSITION (SINGLE LINE)
x'-x" INDICATES BOTTOM OF DUCT DIMENSION ABOVE FINISHED FLOOR
ABOVE FINISHED FLOOR
EXHAUST AIR
RETURN AIR
SUPPLY AIR
AFF
EA
RA
SA
INDICATES QUANTITY OF WIRES (4)
TEMPERATURE CONTROL PANELTCP
VARIABLE FREQUENCY DRIVE FOR MOTOR
CURRENT TRANSFORMER ON MOTOR WIRING WITH TRANSDUCER
AIR CONDITIONING CONDENSATE
LOW PRESSURE STEAM CONDENSATE
HHWS
LPC
LPR
HHWR
ACC
VAV REHEAT WATER SUPPLY
VAV REHEAT WATER RETURN
LOW PRESSURE RETURN
PRESSURE GAUGE
MOTOR STARTER
ELECTRIC MOTOR
LOW LIMIT THERMOSTAT
VFD
EM
L
FLEXIBLE METAL EXPANSION LOOP ASSEMBLY
HUMIDITY SENSOR WITH SETPOINT ADJUSTMENT
COMBINATION FIRE/SMOKE DAMPER IN DUCT
HUMIDITY SENSOR
MOTOR OPERATED DAMPER STATIC PRESSURE SENSOR
H
H
SMOD
FSD
STRAINER
PIPE EXPANSION ANCHOR
PIPE GUIDE
FLEXIBLE PIPE CONNECTOR
THERMOMETER IN PIPE WELL
BALANCING VALVE
X
E.L.
ISOLATION VALVE
REDUCER
UNION
CHECK VALVE
MOTORIZED 3-WAY CONTROL VALVE
GAUGE PORT (PETE'S PLUG)
DRAIN VALVE WITH HOSE FITTING
MOTORIZED 2-WAY CONTROL VALVE
LOCAL DRAIN, VALVED WITH 3/4" THREADED CONNECTOR
MANUAL AIR VENTMAV
PRESSURE RELIEF VALVE
KITCHEN HOOD EXHAUSTKHE
RETURN AIR DUCT
EXHAUST AIR DUCT
CD CONDENSATE PIPINGEXISTING TO REMAIN
EXISTING TO BE REMOVED
X
XR
EXISTING TO BE RELOCATEDXRL
BRANCH PIPE CONNECTION
FIRE DAMPER IN DUCTFDD
TWO POSITION VALVE
PRESSURE REDUCING VALVE
INDICATES DIRECTION OF AIRFLOW
LIMIT OF DEMOLITION
EXISTING NEW LOCATIONXNL
THERMOSTATT
NOTE: THIS LEGEND IS INTENDED TO AID IN THE UNDERSTANDING OF SHORTHAND, SYMBOLS AND ABBREVIATIONS SHOWN IN THESE CONSTRUCTION DOCUMENTS.
IT IS NOT THE INTENTION TO DESCRIBE THE PROJECT SCOPE OF WORK, FOR DETAILED SCOPE OF WORK PLEASE REFER TO THE SUBSEQUENT DRAWINGS.
BUILDING MANAGEMENT SYSTEMBMS
DIRECT DIGITAL CONTROLDDC
LPS LOW PRESSURE STEAM
BOTTOM OF DUCTBOD
COLUMN LINECL
RADIANT CEILING PANELRCP
OUTSIDE AIROA
NORMALLY OPEN
OUTSIDE AIR FAN
RETURN FAN
N.O.
OAF
RF
SUPPLY FANSF
NORMALLY CLOSEDN.C.
CHILLED WATERCHW
CHILLED WATER RETURNCHR
CHILLED WATER SUPPLYCHS
CURRENT SENSORCS
MOTORIZED ACTUATORM
ELECTRIC ACTUATORE
HVAC DESIGN DATA
Db SUMMER
Wb SUMMER
Db WINTER
DESIGN ALTITUDE: 900 FT.
INDOOR AREA
SUMMER
Db Db
°F
89.4°F
73.9°F
-4.0°F
WINTER
°F
DESIGN CONDITIONS
BRONCHOSCOPY
TEMPERATURE SENSORT
OUTDOOR DESIGN
TEMPERATURES
A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM
EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE
PERFORMED AS INDICATED ON THESE DRAWINGS.
B. COORDINATE ALL SHUT-DOWNS OF EXISTING MECHANICAL SYSTEMS WITH OWNER A MINIMUM OF SEVEN
WORKING DAYS IN ADVANCE.
C. REFER TO TERMINAL CONNECTIONS SCHEDULE FOR SIZE OF DUCT CONNECTIONS TO TERMINAL UNITS.
D. UNLESS NOTED OTHERWISE, BRANCH DUCTS TO DIFFUSERS SHALL BE THE SAME SIZE AS THE NECK OF
THE DIFFUSER.
E. SEAL ALL OPENINGS AROUND NEW DUCT AND PIPE PENETRATIONS OF WALLS, WITH CAULK, WITHIN 24 HOURS OF INSTALLATION. THERE SHALL BE NO VISIBLE OPENINGS IN WALLS AROUND PENETRATIONS.
BONE DENSITOMETRY
BIOCHEMISTRY
AUDIOLOGY OFFICE/ THERAPY ROOM
"HOT LAB"
CONFERENCE ROOM
CLEAN SCOPE STORAGE
CLEAN CORE
CLASSROOM/ GROUP ROOM
EKG TESTING ROOM
DENTAL TREATMENT ROOM
DECONTAMINATION
CORRIDOR
CONSULT ROOM
HISTOLOGY
HAZARD WASTE DISPOSAL
GIFT SHOP (RETAIL)
EXAM/ TREATMENT
ENDOSCOPY
LASER
KITCHENETTE
HOUSE KEEPING AIDE CLOSET
LOUNGE 75 60 70 20
75 60 70 20
75 NA 75 NA
NA NA NA NA
66 60 72 20
70 50 70 20
68 60 73 20
68 60 68 30
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
MRI CONTROL ROOM
MICROBIOLOGY
MEDICATION ROOM
MANUAL CART WASH
LOCKER/ CHANGING
OCCUPATIONAL THERAPY
NURSE STATION
NUCLEAR MED SCANNING ROOM
MULTIPURPOSE STORAGE
PATIENT PREP/ RECOVERY
PACU PATIENT BAY
ORTHOPEDIC CLINIC (CAST ROOM)
OPTOMETRY
OFFICE
PULMONARY FUNCTION LAB
PROCEDURE
PHYSICAL THERAPY
PHARMACY CACHE AREA
PATIENT ROOM, ISOLATION
RECOVERY PACU
RECEIVING & LOADING
RADIOGRAPHIC/ FLUOROSCOPIC
RESIDENT DINING
75 NA 70 NA
75 70
75 60 70 20
NA NA
75 60 70 20
75 60 70 20
75 50 70 30
75 50 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 30
75 60 70 20
68 60 70 20
75 60 70 20
75 60 70 30
75 60 70 20
75 60 70 20
75 60 70 20
75 60 70 20
SUB-STERILE ROOM
SOILED UTILITY AND STORAGE
SLEEP STUDY ROOM
SCRUB AND GOWN
SCOPE STAGING AREA
ULTRASOUND
TRIAGE
TOILET
TELECOMMUNICATIONS
WALK IN REFRIGERATOR/ FREEZER
WAITING
VESTIBULE
USP 797 BUFFER
USP 797 ANTE
66 60 72 20
72 72
81 60 64 30
60 45
75 60 70 20
NA NA NA NA
75 50 70 30
NA NA NA NA
75 50 70 20
75 60 70 30
68 60 68 30
NA NA 50 NA
75 60 70 20
68 68 30
NA NA NA NA
CLEAN UTILITY AND STORAGE 70 55 70 30
REFERENCE TO CODED NOTE
EQUIPMENT OR FIXTURE MARK
AIR DISTRIBUTION DEVICE
UNIT NUMBER
EQUIPMENT
TYPE
CONNECTION SIZE AT
DEVICE
TYPE
EQ-#
CALL OUTS:
CFMA
NECK
ABBREVIATIONS:
XXX
EXISTING DIFFUSER/GRILLE TO
BE BALANCED TO LISTED CFM
MAXIMUM
RELATIVE
HUMIDITY (%)
MINIMUM
RELATIVE
HUMIDITY (%)
DUCT IN DUCT OUT
SEE SCHEDULE AND
PLANS FOR INLET
AND OUTLET DUCT
SIZES TO VAV
TERMINALS
VAV TERMINAL HOT WATER REHEAT COIL
DUCT ACCESS DOOR INSTALL MANUAL BALANCING DAMPER
FOR EACH DIFFUSER WITHIN DUCT AS
FAR FROM OUTLET AS POSSIBLE.
NOTE: WHERE VAV TERMINAL SERVES
ONLY ONE GRILLE, MANUAL
BALANCING DAMPER IS NOT
REQUIRED. DAMPER SHALL BE
LOCKING QUADRANT TYPE WITH
2-INCH INSULATION STAND-OFF.
MINIMUM OF (1) 90° CHANGE
OF DIRECTION BETWEEN EACH
DIFFUSER AND VAV TERMINAL
DIFFUSER PER PLAN
(TYPICAL)
UNLESS OTHERWISE
NOTED, BRANCH DUCTS
TO DIFFUSERS SHALL BE
SAME SIZE AS DIFFUSER
NECK.
MAINTAIN ADEQUATE SERVICE ACCESS
TO CONTROLS. T.C. SHALL DETERMINE
CONTROL PANEL LOCATION (RIGHT OR
LEFT SIDE) BASED ON SPACE AVAILABLE.
18" MINIMUM
CLEAR
RHWS
RHWR
COIL VENT
HEATING HOT
WATER COIL
2-WAY CONTROL VALVE
TEST PORT (TYPICAL)
ISOLATION VALVE (TYP.)
VENTURI STYLE BALANCE VALVE
UNION (TYPICAL)
STRAINER WITH
BLOWDOWN VALVE
DRAIN AT LOW POINT
(TYP.)
REDUCE TO CONTROL
VALVE PIPE SIZE (TYP.)
TOP TAKE-OFF
OF ALL MAINS
REHEAT
PIPING MAINS
REHEAT COIL PIPING DIAGRAM 2
NOT TO SCALE
SUPPLY VARIABLE AIR VOLUME TERMINAL DETAIL 1
NOT TO SCALE
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
CHALMERS P. WYLIE VAACC
CORRECT RETRO COMMISSIONING
DEFICIENCIES
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Farid F. Mehr, P.E.
Chief, Engineering Service
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
/1
/2
:3
:4 A
M C
R e v it L o c a l\
R
V A
C o lu m b u s C o rr e c t
R e tr o
C X
C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m
.r v t
757-20-101 dad sic04/14/21
420 N. JAMES ROAD, COLUMBUS, OH 43219
Revisions Date
BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696
BROADVIEW HTS., OHIO 44147
672 EAST ROYALTON ROAD
FAX. (440) 546-9699
Mechanical Legend & General Notes
MH-0A1-65042
ER
H
F OO
IO
AVID A.
MAGALL
-65042
ER
H
F OO
IO
AVID A.
MAGALL
-65042
ER
H
F OO
IO
AVID A.
MAGALL
NEW MIN.
AIRFLOW
(CFM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
RTU-1 VAV TERMINAL SCHEDULE
SERVES 1ST FLOOR - WEST
RTU-2 VAV TERMINAL SCHEDULE
SERVES 1ST FLOOR - WEST
RTU-3 VAV TERMINAL SCHEDULE
SERVES 2ND FLOOR - WEST
RTU-4 VAV TERMINAL SCHEDULE
SERVES 3RD FLOOR
RTU-4 VAV TERMINAL SCHEDULE CONT'D
SERVES 3RD FLOOR
V3-200 3A033 8 700 700 500 500 1.0
3-111 3A188 8 500 500 200 200 0.3
3-110 3A184 8 500 500 330 330 0.5
3-109 3A185 8 450 450 330 330 0.5
3-108 3A183 8 500 500 200 200 0.3
3-107 3A015 8 590 590 0 - -
3-106 3A004 8 500 500 0 - -
3-105 3A215 6 210 210 210 210 0.5
3-104 3A268 8 480 510 390 390 0.6
3-103 3A081 6 220 220 220 220 0.5
3-102 3A075 10 800 800 420 420 0.5
3-101 3A149 8 730 730 510 510 0.7
3-100 3A061 6 300 300 150 150 0.5
3-099 3A057 8 660 660 500 500 0.7
3-098 3A126 8 640 640 430 430 0.6
3-097 3A151 8 730 750 600 600 0.9
3-096 3A133 8 640 640 430 430 0.6
3-095 3A120 8 730 725 510 510 0.7
3-094 3A123 8 640 640 430 430 0.6
3-093 3A110 8 740 740 430 430 0.6
3-092 3A114 8 640 640 430 430 0.6
3-090 3A107 320 320 320 210 210 0.5
3-089 3A170 6 250 250 250 250 0.5
3-088 3A168 6 250 250 250 250 0.5
3-087 3A103 8 680 680 410 410 0.6
3-086 3A006 8 700 700 210 210 0.5
3-085 3A010 4 200 200 110 110 0.5
3-084 3A017 8 550 550 550 550 0.8
3-083 3A400 8 480 480 350 350 0.5
3-082 3A008 8 550 550 550 550 0.8
3-081 3A050 8 800 800 510 510 0.7
3-080 3A086 6 220 220 220 220 0.5
3-079 3A074 8 700 700 700 700 1.0
3-078 3A076 10 950 1290 660 660 1.0
3-076 3A075 8 700 700 500 500 0.7
3-075 3A033 6 425 425 425 425 0.6
3-074 3A001 14 1900 1800 570 570 0.8
3-073 3A211 6 250 250 250 250 0.5
3-072 3A212 10 860 860 730 730 1.1
3-071 3A201 8 720 720 590 590 0.8
3-070 3A161 10 1085 1085 670 670 1.0
3-069 3A071 6 300 300 180 180 0.5
3-068 3A072 6 300 300 180 180 0.5
3-067 3A203 10 990 1110 510 510 0.7
3-066 3A216 8 650 650 430 430 0.6
3-064 3A421 8 620 620 320 320 0.9
3-062 3A426 8 650 625 450 450 0.6
3-061 3A303 8 870 870 450 450 0.6
3-060 3A440 8 465 500 320 320 0.5
3-059 3A300 10 1220 1220 850 850 1.2
3-058 3A306 6 220 220 220 220 0.5
3-057 3A227 8 560 560 400 400 0.6
3-056 3A220 8 730 730 550 550 0.8
3-065 3A414 8 620 825 620 620 0.9
3-063 3A422 8 460 650 320 320 0.5
3-091 3A100 8 730 850 510 510 0.7
3-055 3A234 8 640 640 460 460 0.7
3-054 3A239 8 680 680 570 570 0.8
3-053 3A224 8 640 640 460 460 0.7
3-052 3A228 8 740 740 460 460 0.7
3-051 3A255 10 820 820 690 690 1.0
3-050 3A240 8 540 540 540 540 0.8
3-049 3A246 8 640 640 640 640 1.0
3-048 3A264 8 770 770 350 350 0.5
3-047 3A263 6 350 350 120 120 0.5
*3-046 3A262 8 0 230 0 0 -
3-045 3A261 8 740 740 350 350 0.5
3-044 3A190 8 700 700 390 390 0.6
3-043 3A073 10 900 900 240 240 0.5
3-042 3A160 8 800 800 570 570 1.5
3-041 3A163 6 400 400 260 260 0.5
3-040 3A165 6 310 310 110 110 0.5
3-039 3A167 8 510 510 350 350 0.5
3-038 3A171 6 400 400 260 260 0.5
3-037 3A173 6 400 400 150 150 0.5
3-036 3A172 6 350 370 150 150 0.5
3-035 3A142 6 350 350 150 150 0.5
3-034 3A143 6 220 220 100 100 0.5
3-033 3A144 6 300 300 170 170 0.5
3-032 3A145 6 400 400 170 170 0.5
3-031 3A146 6 350 350 170 170 0.5
3-030 3A147 6 430 430 210 210 0.5
3-029 3A148 4 200 200 130 130 0.5
3-028 3A063 8 670 670 0 - -
3-027 3A067 6 350 350 110 110 0.5
3-025 3A060 6 170 180 80 80 0.5
3-022 3A054 6 280 325 220 220 0.5
3-021 3A052 6 450 450 200 200 0.5
3-020 3A012 10 980 980 230 230 0.5
3-019 3A411 4 200 200 180 180 0.5
3-018 3A410 6 370 370 220 220 0.5
3-017 3A413 8 460 460 200 200 0.5
3-016 3A415 6 220 220 140 140 0.5
3-015 3A456 6 240 240 180 180 0.5
3-013 3A452 6 310 310 190 190 0.5
3-012 3A451 4 120 130 120 120 0.5
3-009 3A279 4 175 175 110 110 0.5
3-007 3A276 6 250 250 170 170 0.5
3-006 3A273 6 250 250 170 170 0.5
3-004 3A271 6 250 310 150 150 0.5
3-002 3A267 6 250 250 150 150 0.5
3-026 3A062 6 280 350 180 180 0.5
3-023 3A056 6 130 225 80 80 0.5
3-014 3A454 6 300 360 250 250 0.5
3-024 3A058 6 130 180 80 80 0.5
3-010 3A310 6 250 325 160 160 0.5
3-008 3A278 6 250 325 170 170 0.5
3-011 3A312 6 250 350 160 160 0.5
3-003 3A269 6 250 280 150 150 0.5
3-001 3A265 6 200 380 100 100 0.5
3-005 3A272 6 250 325 170 170 0.5
2-079 2A459 4 150 225 80 80 0.5
2-075 2A338 10 860 860 760 760 1.1
2-074 2A338A 6 210 210 210 210 0.5
2-073 2A310 10 1220 1220 260 260 0.5
2-072 2A321 6 400 400 170 170 0.5
2-076 2A450A 6 250 325 160 160 0.5
2-137 2A512 6 300 300 300 300 0.5
2-168 2A019 10 1250 1250 340 340 0.5
2-166 2A018 8 590 590 0 - -
2-153 2A121 6 300 310 300 300 0.6
2-151 2A069 6 440 440 440 440 0.6
2-147 2A115 6 250 250 250 250 0.5
2-146 2A063 8 570 570 440 440 0.6
2-141 2A008 6 400 400 400 400 0.6
2-139 2A501 8 570 570 450 450 0.6
2-138 2A553 6 360 360 250 250 0.5
2-136 2A562 8 500 500 420 420 0.6
2-134 2A444 8 520 520 350 350 0.5
2-132 2A445 6 360 360 260 260 0.5
2-123 2A342 6 340 340 100 100 0.5
2-121 2A301 4 200 200 140 140 0.5
2-119 2A308 10 1155 1155 560 560 0.8
2-118 2A314 8 675 675 675 675 1.0
2-116 2A319 6 330 330 130 130 0.5
2-115 2A317 6 330 330 130 130 0.5
2-114 2A315 6 250 250 130 130 0.5
2-113 2A313 6 330 330 140 140 0.5
2-112 2A311 6 330 330 140 140 0.5
2-111 2A310A 8 750 750 210 210 0.5
2-105 2A074 12 1800 1800 1100 1100 2.1
2-104 2A074A 12 1700 1700 1100 1100 2.1
2-097 2A184 8 600 600 100 100 0.5
2-094 2A197 8 475 475 475 475 1.1
2-086 2A011 6 385 385 385 385 0.6
2-085 2A509 10 1100 1100 700 700 1.5
2-084 2A556 10 1250 1250 700 700 1.5
2-083 2A521 6 260 260 160 160 0.5
2-082 2A446 6 250 250 150 150 0.5
2-154 2A111 6 250 300 250 250 0.5
2-152 2A073 8 515 750 515 515 0.7
2-162 2A179 6 450 575 350 350 0.5
2-135 2A517 6 340 500 340 340 0.5
2-120 2A303 6 310 350 350 350 0.5
2-145 2A036 6 275 450 275 275 0.5
2-101 2A146 8 550 675 120 120 0.5
2-099 2A188 6 350 375 90 90 0.5
2-117 2A318 6 280 450 280 280 0.5
2-095 2A201 4 100 225 100 100 0.5
2-081 2A463 6 300 425 120 120 0.5
*2-096 2A199 16 3220 3220 500 500 0.7
1-156 1A016 6 300 300 200 200 0.5
1-160 1A007 8 600 600 200 200 0.5
1-188 1A004 8 800 800 600 600 0.9
1-183 1A063 6 380 380 220 220 0.5
1-179 1A006 14 2040 2040 2040 2040 2.9
1-178 1A070 16 3000 3000 1000 1000 2.0
1-175 1A001 10 900 900 400 400 0.8
1-173 1A005 14 2400 2400 600 600 1.2
1-170 1A078 6 280 280 280 280 0.5
1-159 1A008 6 800 800 800 800 0.6
1-157 1A010 4 280 280 100 100 0.5
1-169 1A077 14 2300 2300 800 800 1.2
1-168 1A076 10 1100 1100 400 400 0.6
1-167 1A075 10 900 900 400 400 0.6
1-184 2A189 6 300 400 200 200 0.5
1-172 1A040 6 310 500 310 310 0.5
1-171 1A080 6 320 400 200 200 0.5
1-131 1A150 10 1300 1300 1300 1300 1.9
1-121 1A154 10 900 750 350 350 0.5
1-145 1A135 6 400 450 300 300 1.2
1-125 1A175 6 400 475 300 300 0.5
1-120 1A155 6 450 510 300 300 0.5
1-140 1A030 6 440 550 230 230 0.5
1-108 1A028 10 920 1125 600 600 0.9
1-099 1A322 4 160 200 100 100 0.5
1-115 1A180 8 500 610 300 300 0.5
1-078 1A306 8 610 700 610 610 1.2
1-072 1A253 6 360 550 230 230 0.5
1-092 1A201 6 300 400 200 200 0.5
1-071 1A276 6 400 550 300 300 0.5
EXISTING
MARK
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
SPACE
SERVED
EXISTING
MARK
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
SPACE
SERVED
EXISTING
MARK
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
SPACE
SERVED
EXISTING
MARK
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
SPACE
SERVED
EXISTING
MARK
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
SPACE
SERVED
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
VAV TERMINAL SCHEDULE GENERAL NOTES:
1. ALL VAVs ARE EXISTING TO REMAIN. THE SCHEDULES ON THIS SHEET ARE FOR BALANCING SCOPE
ONLY.
2. ALL TEXT SHOWN AS LIGHT GRAY IS REFERENCE INFORMATION ONLY.
3. VAV REHEAT IS BASED ON 200 DEG F SUPPLY WATER.
4. VAV REHEAT LEAVING AIR TEMPERATURES ARE BASED ON ORIGINAL VAV DESIGN SCHEDULES.
NEW COIL
FLOW
(GPM)
LEAVING
AIR TEMP.
(DEG F)
LEAVING
AIR TEMP.
(DEG F)
LEAVING
AIR TEMP.
(DEG F)
LEAVING
AIR TEMP.
(DEG F)
LEAVING
AIR TEMP.
(DEG F)
1-143 1A135 6 440 440 300 300 1.2 75
1-144 1A134 6 420 500 300 300 0.5 75
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
CHALMERS P. WYLIE VAACC
CORRECT RETRO COMMISSIONING
DEFICIENCIES
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Farid F. Mehr, P.E.
Chief, Engineering Service
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
/1
/2
:3
:4 A
M C
R e v it L o c a l\
R
V A
C o lu m b u s C o rr e c t
R e tr o
C X
C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m
.r v t
757-20-101 dad sic04/14/21
420 N. JAMES ROAD, COLUMBUS, OH 43219
Revisions Date
BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696
BROADVIEW HTS., OHIO 44147
672 EAST ROYALTON ROAD
FAX. (440) 546-9699
Mechanical Schedules
MH-0B1-65042
ER
H
F OO
IO
AVID A.
MAGALL
-65042
ER
H
F OO
IO
AVID A.
MAGALL
-65042
ER
H
F OO
IO
EXISTING
MARK
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
SPACE
SERVED
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
RTU-5 VAV TERMINAL SCHEDULE
SERVES 4TH FLOOR
RTU-5 VAV TERMINAL SCHEDULE CONT'D
SERVES 4TH FLOOR
RTU-7 VAV TERMINAL SCHEDULE
SERVES 1ST FLOOR - EAST
RTU-8 VAV TERMINAL SCHEDULE
SERVES 1ST FLOOR - EAST
RTU-10 VAV TERMINAL SCHEDULE
SERVES 2ND FLOOR - EAST
RTU-11 VAV TERMINAL SCHEDULE
SERVES 2ND FLOOR EAST
4-001 4A013 12 1550 1550 1550 1550 3.0
4-023 4A04 6 275 275 110 110 0.5
4-022 4A076 6 275 275 110 110 0.5
4-021 4A038 6 235 235 110 110 0.5
4-020 4A071A 8 575 500 350 350 0.5
4-019 4A063 8 490 490 490 490 0.71
4-018 4A348 6 180 300 110 110 0.5
4-017 4A327 4 180 180 180 180 0.5
4-016 4A329 10 665 665 270 270 0.9
4-015 4A347 6 210 250 110 110 0.5
4-014 4A344 6 300 300 110 110 0.5
4-013 4A320 12 1400 1400 1000 1000 1.44
4-012 4A063 8 520 400 400 400 0.75
4-011 4A060 12 1800 1800 1575 1575 2.3
4-010 4A343 4 160 180 80 80 0.5
4-009 4A309 10 400 400 400 400 0.75
4-008 4A342 6 220 220 110 110 0.5
4-007 4A305 6 230 230 230 230 0.5
4-006 4A020 10 645 950 260 260 2.6
4-004 4A250 12 1010 1050 1010 1010 2.2
4-002 4A008 8 550 500 200 200 0.5
4-025 4A039 4 170 325 80 80 0.5
4-024 4A072 4 190 325 90 90 0.5
4-003 4A007 14 2400 2400 600 1000 2.5
4-005 4A021 10 800 1180 800 800 1.6
TB2-4 4A258 8 405 405 170 170 1.0
TB2-3 4A261 8 475 425 200 200 1.0
TB2-2 4A307 8 350 360 140 140 1.0
TB2-1 4A340 8 470 450 200 200 1.0
TB1-7 4A255 6 250 200 120 120 0.5
TB1-6 4A253 6 270 270 110 110 0.5
TB1-5 4A251 6 165 250 80 80 0.5
TB1-4 4A301 6 230 300 110 110 0.5
TB1-3 4A324 6 290 290 120 120 0.5
TB1-2 4A326 6 305 300 130 130 0.5
TB1-1 4A306 6 230 230 230 230 0.5
4-063 4A041 8 500 500 0 - -
4-062 4A012 4 200 200 0 - -
4-061 4A201 14 2375 5040 800 800 1.15
4-060 4A006 8 660 675 410 410 0.57
4-059 4A215 4 260 260 110 110 0.5
4-058 4A213 6 260 260 110 110 0.5
4-054 4A207 6 220 230 110 110 0.5
4-053 4A209 6 300 300 110 110 0.5
4-052 4A078 4 140 140 70 70 0.5
4-051 4A080 6 230 230 110 110 0.5
4-050 4A082 6 230 230 110 110 0.5
4-048 4A132 4 190 225 70 70 0.5
4-047 4A131 6 210 210 110 110 0.5
4-046 4A130 4 140 160 70 70 0.5
4-045 4A129 6 320 320 180 180 0.5
4-044 4A128 6 420 420 130 130 0.5
4-042 4A084 6 250 250 110 110 0.5
4-040 4A140 8 600 600 440 440 0.6
4-039 4A127 4 200 210 110 110 0.5
4-038 4A061 8 490 550 550 550 1.0
4-036 4A126 6 260 260 110 110 0.5
4-035 4A101 8 700 700 700 700 1.0
4-034 4A125 8 420 420 200 200 0.5
4-026 4A090A 14 1000 1000 500 500 1.1
4-057 4A210 10 1200 1100 550 550 0.8
4-056 4A206 8 700 800 700 700 1.0
4-049 4A133 4 140 225 70 70 0.5
4-043 4A081 8 620 700 620 620 1.0
4-055 4A205 4 170 325 90 90 0.5
4-037 4A139 8 680 825 500 500 0.7
4-041 4A136 6 220 325 150 150 0.5
4-032 4A118 6 410 520 410 410 0.6
4-031 4A117 8 470 575 200 300 0.75
4-033 4A113 8 630 820 570 570 0.8
4-029 4A110 8 650 1010 650 650 1.0
4-028 4A115 4 175 250 70 70 0.5
4-030 4A201A 6 300 500 150 150 0.5
4-027 4A116 6 330 410 110 110 0.5
EXISTING
MARK
EXISTING
SPACE
SERVED
1-030 1B086 6 270 270 270 270 0.5
1-024 1B112 10 850 850 850 850 1.2
1-006 1B116 8 540 700 400 400 0.6
2-031 2B229 8 500 500 500 500 0.7
2-028 2B240 8 570 570 570 570 0.8
2-026 2B240D 10 820 820 270 270 0.5
2-025 2B240A 10 870 870 400 400 0.6
2-043 2B132 8 500 500 500 500 0.7
2-042 2B136 8 500 500 500 500 0.7
2-040 2B138 8 500 500 500 500 0.7
2-037 2B144 8 530 530 530 530 0.8
2-034 2B230 6 370 390 370 370 0.5
V11-18 2B137 5 100 100 100 100 0.6
V11-5 2B143 7 430 430 430 430 0.6
V11-6 2B141A 6 370 490 370 370 0.6
EXISTING
MARK
EXISTING
SPACE
SERVED
EXISTING
MARK
EXISTING
SPACE
SERVED
EXISTING
MARK
EXISTING
SPACE
SERVED
EXISTING
MARK
EXISTING
SPACE
SERVED
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
VAV TERMINAL SCHEDULE GENERAL NOTES:
1. ALL VAVs ARE EXISTING TO REMAIN. THE SCHEDULES ON THIS SHEET ARE FOR BALANCING SCOPE
ONLY.
2. ALL TEXT SHOWN AS LIGHT GRAY IS REFERENCE INFORMATION ONLY.
3. VAV REHEAT IS BASED ON 200 DEG F SUPPLY WATER.
4. VAV REHEAT LEAVING AIR TEMPERATURES ARE BASED ON ORIGINAL VAV DESIGN SCHEDULES.
LEAVING
AIR TEMP.
(DEG F)
81.5
LEAVING
AIR TEMP.
(DEG F)
TB4-1 4A090B 12 1000 1000 450 450 1.3
LEAVING
AIR TEMP.
(DEG F)
LEAVING
AIR TEMP.
(DEG F)
LEAVING
AIR TEMP.
(DEG F)
EXISTING
MAX.
AIRFLOW
(CFM)
EXISTING
TERMINAL
SIZE
RTU-9 VAV TERMINAL SCHEDULE
SERVES 2ND FLOOR - EAST
2-062 2B056 8 800 850 560 560 0.8
2-066 2B115 8 600 600 360 360 0.5
2-059 2B051 8 700 900 700 700 1.0
2-058 2B053 6 350 520 150 150 0.5
2-065 2B071 6 300 350 120 120 0.5
2-057 2B051 8 400 900 700 700 0.5
EXISTING
MARK
EXISTING
SPACE
SERVED
NEW MIN.
AIRFLOW
(CFM)
NEW COIL
FLOW
(GPM)
NEW
HEATING
AIRFLOW
(CFM)
NEW MAX.
AIRFLOW
(CFM)
LEAVING
AIR TEMP.
(DEG F)
2-061 2B061 8 520 520 360 360 0.5 75
2-067 2B073 8 750 660 380 380 0.5 75
LEAVING
AIR TEMP.
(DEG F)
92.3
91.6
NEW VAV TERMINAL SCHEDULE
MARK
MAX.
AIRFLOW
(CFM)
MIN.
AIRFLOW
(CFM)
CAPACITY
(MBH)
COIL FLOW
(GPM)
ENTERING/
LEAVING AIR
TEMP. (F°)
AIR PRESS.
DROP (IN W.G.)
(NOTE 2)
WATER PRESS.
DROP (FT)
(NOTE 3)
NUMBER OF
ROWS
HEATING COIL PERFORMANCE
TERMINAL
SIZE
HEATING
AIRFLOW
PIPE SIZE
(IN)
(NOTE 4)
NOTES:
NOTE 1: BASIS OF SPECIFICATION IS TITUS DESV. TERMINALS SHALL BE CAPABLE OF OPERATING WITH A MINIMUM INLET PRESSURE OF 0.5" W.G. FURNISH WITH AIR
FLOW SWITCH, AND ACTUATOR. PROVIDE WITH SCREW ACCESS (UN-HINGED) WHERE TERMINALS ARE INSTALLED IN THE BEAM/JOIST SPACE. BOXES SHALL
BE INSULATED WITH: FIBRE-FREE.
NOTE 2: MAXIMUM AIR PRESSURE DROP SHALL BE 0.3" W.G.
NOTE 3: MAXIMUM WATER PRESSURE DROP SHALL BE 5 FEET.
NOTE 4: MINIMUM PIPE SIZE SHALL BE 3/4". SEE REHEAT COIL PIPING DIAGRAM FOR COIL PIPING.
1-020 14"Ø 1670 300 600 14.5 0.5 55/77 0.11 0.02 1 3/4"
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
CHALMERS P. WYLIE VAACC
CORRECT RETRO COMMISSIONING
DEFICIENCIES
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Farid F. Mehr, P.E.
Chief, Engineering Service
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
/1
/2
:3
:4 A
M C
R e v it L o c a l\
R
V A
C o lu m b u s C o rr e c t
R e tr o
C X
C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m
.r v t
757-20-101 dad sic04/14/21
420 N. JAMES ROAD, COLUMBUS, OH 43219
Revisions Date
BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696
BROADVIEW HTS., OHIO 44147
672 EAST ROYALTON ROAD
FAX. (440) 546-9699
Mechanical Schedules
MH-0C1-65042
ER
H
F OO
IO
AVID A.
MAGALL
-65042
ER
H
F OO
IO
AVID A.
MAGALL
-65042
ER
H
F OO
IO
FAN CONTROL:
THE SUPPLY FAN (SF-C) AND RETURN FAN (RF-C) SHALL RUN CONTINUOUSLY. THE SUPPLY FAN
OUTPUT (SF-O) WILL MODULATE TO MAINTAIN THE DISCHARGE AIR STATIC PRESSURE SETPOINT
(DAP-SP). THE RETURN FAN OUTPUT (RF-O) WILL MODULATE TO MAINTAIN THE DESIRED RETURN FAN
OFFSET (%-OFFSET).
DISCHARGE AIR PRESSURE SETPOINT DETERMINATION:
THE DISCHARGE AIR PRESSURE SETPOINT (DAP-SPT) SHALL BE CONTINUOUSLY RESET BY POLLING
THE VAV BOX DAMPERS THAT ARE ASSOCIATED WITH THE RTU. IF ANY DAMPER IS OPEN GREATER
THAN 95% FOR LONGER THAN 10 MINUTES, DAP-SP WILL INCREASE BY 0.05” UNTIL NO DAMPER IS
ABOVE 95% OPEN OR UNTIL THE HIGH LIMIT SETPOINT IS REACHED. IF ALL ASSOCIATED DAMPERS ARE
LESS THAN 80% OPEN FOR LONGER THAN 10 MINUTES, DAP-SP WILL DECREASE BY 0.05” UNTIL AT
LEAST 1 DAMPER IS OPEN MORE THAN 80% OR THE LOW LIMIT SETPOINT HAS BEEN REACHED. THE
DAP-SP SHALL BE THE DEFAULT UPON STARTUP/RESTART, UNTIL THE SYSTEM HAS ATTAINED NORMAL
CONTROL.
DISCHARGE AIR TEMP SETPOINT DETERMINATION:
THE DISCHARGE AIR TEMP SETPOINT (DAT-SP) SHALL BE DETERMINED VIA RESET LOGIC BASED ON
THE RETURN AIR TEMP (RA-T). THE RETURN AIR MAXIMUM (RAT-MAX-SP) AND THE RETURN AIR
MINIMUM (RAT-MIN-SP) SET THE RANGE OF THE RESET, WHILE THE DISCHARGE AIR TEMP MAXIMUM
(DAT-MAX-SP) AND THE DISCHARGE AIR TEMP MINIMUM (DAT-MIN-SP) SET THE LIMITS ON THE ON THE
DAT-SP.
ECONOMIZER AVAILABILITY DETERMINATION:
THE ECONOMIZER FREE COOLING SHALL BE AVAILABLE WHENEVER THE RTU IS RUNNING, THE
OUTDOOR AIR ENTHALPY (OA-E) IS LESS THAN THE RETURN AIR ENTHALPY (RA-E), THE OUTDOOR AIR
TEMP (OA-T) IS LESS THAN THE EFFDAT-SP MINUS THE ECON/DAT SEPT DIFFERENTIAL
(ECONDATSPTDIFF), THE OA-T IS GREATER THAN THE ECON LOW OAT DISABLE
(LOWOATDISABLESETPT) AND THE RETURN AIR HUMIDITY IS GREATER THAN THE RETURN AIR
HUMIDITY ECON LOCKOUT (RETURNAIRHUMIDITYECONLOCKOUT).
OUTDOOR AIR DAMPER MINIMUM POSITION DETERMINATION:
THE OUTDOOR AIR DAMPER MINIMUM POSITION (MAD-MINPOS) SHALL BE DETERMINED IN ONE OF 3
WAYS. IF THE OA-T IS LESS THAN THE MINDAMPERLOWOATSETPT, THEN THE MAD-MINPOS SHALL BE
DETERMINED BY THE FOLLOWING EQUATION: (RA-T)-(MA-T)/(RA-T)-(OA-T)X100. IF THE RETURN AIR CO2
(RA-CO2) RISES ABOVE THE MINIMUM CO2 RESET SETPT (MOA-CO2RSTA), THEN THE MAD-MINPOS
WILL RESET UP TO THE MINIMUM POSITION HIGH SETPT (MIN POS HIGH SETPOINT). IF NEITHER OF THE
ABOVE SCENARIOS ARE ACTIVE, THE MAD-MINPOS SHALL BE THE VALUE OF THE OA DAMPER MIN
POSITION SETPOINT (OAD-MINPOS).
DAMPER CONTROL:
THE OUTDOOR AIR DAMPER (OA-D), RETURN AIR DAMPER (RA-D), AND EXHAUST AIR DAMPER (EA-D)
SHALL MODULATE IN UNISON WITH THE OA & EA DAMPERS OPPOSING THE RETURN DAMPER. IF
ECONOMIZER IS AVAILABLE, THE DAMPERS WILL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMP
(DA-T) AT THE DISCHARGE AIR TEMP SETPOINT (DAT-SPT). IF THE ECONOMIZER MODE IS NOT
AVAILABLE, THE DAMPERS WILL MODULATE TO MAINTAIN THE OUTDOOR AIR DAMPER MINIMUM
POSITION (MAD-MINPOS). SHOULD THE PREHEAT TEMP (PH-T) FALL BELOW THE LOW LIMIT SETPOINT
MINUS 3 DEGREES (LT-SP – 3 DEGREES), THE DAMPERS WILL MODULATE IN AN ATTEMPT TO PREVENT
A LOW TEMP ALARM.
HEATING VALVE AND PUMP CONTROL:
THE PREHEAT PUMP (PHP-C) SHALL BE ENABLED ANYTIME THE OA-T IS BELOW THE OALT-SP. WHEN
ENABLED, THE PREHEAT VALVE OUTPUT (PH-O) SHALL MODULATE TO MAINTAIN THE DA-T AT THE
DAT-SP. IT WILL ALSO MODULATE OPEN TO MAINTAIN THE PREHEAT TEMP (PH-T) AT THE LOW LIMIT
SETPOINT (LT-SP). THE PH-O SHALL MODULATE TO 100% IN THE EVENT OF A LOW TEMPERATURE
ALARM (LT-A).
COOLING VALVE CONTROL:
WHEN ENABLED BY THE CHILLED WATER SYSTEM, THE COOLING VALVE OUTPUT (CLG-O) WILL
MODULATE TO MAINTAIN THE DA-T AT THE DAT-SP.
EXISTING SEQUENCES OF
OPERATION FOR RTUs 1 THRU 7 & 9
NOTES:
A. BOLD TEXT WITH A STRIKE-THROUGH WITHIN THE SEQUENCE OF OPERATIONS INDICATES A
REVISION. ALL ITEMS IN LIGHT INK ARE EXISTING TO REMAIN.
REVISED SEQUENCES OF OPERATION
FOR RTUs 1 THRU 7 & 9
FAN CONTROL:
THE SUPPLY FAN (SF-C) AND RETURN FAN (RF-C) SHALL RUN CONTINUOUSLY. THE SUPPLY FAN
OUTPUT (SF-O) WILL MODULATE TO MAINTAIN THE DISCHARGE AIR STATIC PRESSURE SETPOINT
(DAP-SP). THE RETURN FAN OUTPUT (RF-O) WILL MODULATE TO MAINTAIN THE DESIRED RETURN FAN
OFFSET (%-OFFSET).
DISCHARGE AIR PRESSURE SETPOINT DETERMINATION:
THE DISCHARGE AIR PRESSURE SETPOINT (DAP-SPT) SHALL BE CONTINUOUSLY RESET BY POLLING
THE VAV BOX DAMPERS THAT ARE ASSOCIATED WITH THE RTU. IF ANY DAMPER IS OPEN GREATER
THAN 95% FOR LONGER THAN 10 MINUTES, DAP-SP WILL INCREASE BY 0.05” UNTIL NO DAMPER IS
ABOVE 95% OPEN OR UNTIL THE HIGH LIMIT SETPOINT IS REACHED. IF ALL ASSOCIATED DAMPERS ARE
LESS THAN 80% OPEN FOR LONGER THAN 10 MINUTES, DAP-SP WILL DECREASE BY 0.05” UNTIL AT
LEAST 1 DAMPER IS OPEN MORE THAN 80% OR THE LOW LIMIT SETPOINT HAS BEEN REACHED. THE
DAP-SP SHALL BE THE DEFAULT UPON STARTUP/RESTART, UNTIL THE SYSTEM HAS ATTAINED NORMAL
CONTROL.
DISCHARGE AIR TEMP SETPOINT DETERMINATION:
THE DISCHARGE AIR TEMP SETPOINT (DAT-SP) SHALL BE DETERMINED VIA RESET LOGIC BASED ON
THE RETURN AIR TEMP (RA-T). THE RETURN AIR MAXIMUM (RAT-MAX-SP) AND THE RETURN AIR
MINIMUM (RAT-MIN-SP) SET THE RANGE OF THE RESET, WHILE THE DISCHARGE AIR TEMP MAXIMUM
(DAT-MAX-SP) AND THE DISCHARGE AIR TEMP MINIMUM (DAT-MIN-SP) SET THE LIMITS ON THE ON THE
DAT-SP.
ECONOMIZER AVAILABILITY DETERMINATION:
THE ECONOMIZER FREE COOLING SHALL BE AVAILABLE WHENEVER THE RTU IS RUNNING, THE
OUTDOOR AIR TEMP (OA-T) IS LESS THAN 65 DEG F, THE OA-T IS GREATER THAN THE ECON LOW OAT
DISABLE (LOWOATDISABLESETPT) AND THE RETURN AIR HUMIDITY IS GREATER THAN THE RETURN AIR
HUMIDITY ECON LOCKOUT (RETURNAIRHUMIDITYECONLOCKOUT).
OUTDOOR AIR DAMPER MINIMUM POSITION DETERMINATION:
THE OUTDOOR AIR DAMPER MINIMUM POSITION DETERMINATION SHALL BE USED WHEN AHU
ECONOMIZER FREE COOLING IS NOT AVAILABLE.
THE OUTDOOR AIR DAMPER MINIMUM POSITION (MAD-MINPOS) SHALL BE DETERMINED BY THE
FOLLOWING:
- IF THE OAT < (RAT- 5 DEG F) OR OAT > (RAT+ 5 DEG F), THE OUTDOOR AIR DAMPER SHALL
MODULATE TO MAKE THE FOLLOWING EQUATION, [(RAT-MAT)/(RAT-OAT)] x 100, EQUAL TO THE
MINIMUM OUTDOOR AIR PERCENTAGE OF THE RTU.
- IF (RAT - 5 DEG F) < OAT < (RAT + 5 DEG F), THE OUTDOOR AIR DAMPER POSITION SHALL BE AT
ITS FIXED MINIMUM POSITION DETERMINED BY THE BALANCER AT 100% AIRFLOW CONDITION.
- IF THE RETURN AIR CO2 (RA-CO2) RISES ABOVE THE MINIMUM CO2 RESET SETPT
(MOA-CO2RSTA), THEN THE MAD-MINPOS WILL RESET UP TO THE MINIMUM POSITION HIGH SETPT
(MIN POS HIGH SETPOINT). THIS HIGH SETPOINT SHALL BE 10% GREATER THAN THE MINIMUM
OUTDOOR AIR PERCENTAGE OF THE RTU.
DAMPER CONTROL:
THE OUTDOOR AIR DAMPER (OA-D), RETURN AIR DAMPER (RA-D), AND EXHAUST AIR DAMPER (EA-D)
SHALL MODULATE IN UNISON WITH THE OA & EA DAMPERS OPPOSING THE RETURN DAMPER. IF
ECONOMIZER IS AVAILABLE, THE DAMPERS WILL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMP
(DA-T) AT THE DISCHARGE AIR TEMP SETPOINT (DAT-SPT). IF THE ECONOMIZER MODE IS NOT
AVAILABLE, THE DAMPERS WILL MODULATE TO MAINTAIN THE OUTDOOR AIR DAMPER MINIMUM
POSITION (MAD-MINPOS). SHOULD THE PREHEAT TEMP (PH-T) FALL BELOW THE LOW LIMIT SETPOINT
MINUS 3 DEGREES (LT-SP – 3 DEGREES), THE DAMPERS WILL MODULATE IN AN ATTEMPT TO PREVENT
A LOW TEMP ALARM.
HEATING VALVE AND PUMP CONTROL:
THE PREHEAT PUMP (PHP-C) SHALL BE ENABLED ANYTIME THE OA-T IS BELOW THE OALT-SP. WHEN
ENABLED, THE PREHEAT VALVE OUTPUT (PH-O) SHALL MODULATE TO MAINTAIN THE DA-T AT THE
DAT-SP. IT WILL ALSO MODULATE OPEN TO MAINTAIN THE PREHEAT TEMP (PH-T) AT THE LOW LIMIT
SETPOINT (LT-SP). THE PH-O SHALL MODULATE TO 100% IN THE EVENT OF A LOW TEMPERATURE
ALARM (LT-A).
COOLING VALVE CONTROL:
WHEN ENABLED BY THE CHILLED WATER SYSTEM, THE COOLING VALVE OUTPUT (CLG-O) WILL
MODULATE TO MAINTAIN THE DA-T AT THE DAT-SP.
NOTES:
A. BOLD TEXT WITHIN THE SEQUENCE OF OPERATIONS INDICATES A REVISION. ALL ITEMS IN LIGHT INK
ARE EXISTING TO REMAIN.
DISCHARGE AIR PRESSURE SETPOINT (DEFAULT)
DISCHARGE AIR MAXIMUM SETPOINT
DISCHARGE AIR MINIMUM SETPOINT
RETURN FAN OFFSET
RETURN AIR TEMP MAXIMUM SETPOINT
RETURN AIR TEMP MINIMUM SETPOINT
DISCHARGE AIR TEMP MAXIMUM SETPOINT
DISCHARGE AIR TEMP MINIMUM SETPOINT
ECON/DAT SEPT DIFFERENTIAL
ECON LOW OAT DISABLE SETPOINT
RETURN AIR HUMIDITY ECON LOCKOUT
MINIMUM DAMPER LOW OAT SETPOINT
MINIMUM OUTSIDE AIR VENTILATION (%)
MINIMUM CO2 RESET SETPOINT
MINIMUM POSITION HIGH SETPOINT (%)
OA DAMPER MIN POSITION SETPOINT (%)
PREHEAT LOW LIMIT SETPOINT
DAP-SP
DAP-MAX-SP
DAP-MIN-SP
% OFFSET
RAT-MAX-SP
RAT-MIN-SP
DAT-MAX-SP
DAT-MIN-SP
ECON-DAT-SP-DIFF
OATLOW-DISABLE
NOT MAPPED TO METASYS
OAD-MINPOS
OABLEND%-SPT
MOA-CO2RSTA
MOA-CO2RSTB
OAD-MINPOS
LT-SP
1"
1.5"
0.5"
20%
-5
DESCRIPTION ABBREVIATION VALUE
CURRENT SET-POINTSSUPPLY VAV BOX W/ REHEAT CONTROLS 1
NOT TO SCALE
CONTROL DIAGRAM
SEQUENCE OF OPERATION FOR VARIABLE
VOLUME REHEAT COIL
RUN CONDITIONS:
A. COOLING MODE:
1. SPACE THERMOSTAT SHALL MODULATE VAV BOX DAMPER TO
MAINTAIN SETPOINT.
B. HEATING MODE:
1. VAV BOX DAMPER SHALL CLOSE TO HEATING AIRFLOW POSITION.
2. SPACE THERMOSTAT SHALL MODULATE HOT WATER VALVE TO
MAINTAIN SETPOINT.
T
C O
IL
R
E H
E A
T
X-SUPPLY AIR DUCT
UNITARY
CONTROLLER
XFORMER
SUPPLY AIR
NOT TO SCALE
T
E
C. BAS SHALL MONITOR AND DISPLAY THE FOLLOWING:
1. TEMPERATURE SETPOINT
2. ROOM TEMPERATURE
3. AIR FLOW (CFM)
4. DAMPER POSITION
5. VALVE POSITION
6. DISCHARGE TEMPERATURE
DISCHARGE
TEMPERATURE
SENSORAIRFLOW
SENSOR
REHEAT
CONTROL
VALVE
DDC THERMOSTAT
WITH REMOTE SENSOR 120V/24AC
TRANSFORMER
BY T.C.
LOW VOLTAGE
WIRING BY T.C.
COMMUNICATION
BUS TO OTHER
CONTROLLERS
GENERAL TEMPERATURE CONTROLS NOTES:
1. TEMPERATURE CONTROLS SHALL BE JOHNSON CONTROLS (JCI). ALL CONTROLS WORK SHALL INTERFACE
WITH EXISTING JCI BUILDING CONTROL SYSTEM.
2. ONLY TECHNICIANS SPECIFICALLY TRAINED, LICENSED, AND AUTHORIZED TO WORK ON JCI CONTROLS
SHALL BE ALLOWED TO ACCESS THE EXISTING BUILDING CONTROL SYSTEM FOR THE PURPOSE OF
COMPLETING WORK REQUIRED UNDER THIS CONTRACT.
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
CHALMERS P. WYLIE VAACC
CORRECT RETRO COMMISSIONING
DEFICIENCIES
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Farid F. Mehr, P.E.
Chief, Engineering Service
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
/1
/2
:3
:4 A
M C
R e v it L o c a l\
R
V A
C o lu m b u s C o rr e c t
R e tr o
C X
C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m
.r v t
757-20-101 dad sic04/14/21
420 N. JAMES ROAD, COLUMBUS, OH 43219
Revisions Date
BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696
BROADVIEW HTS., OHIO 44147
672 EAST ROYALTON ROAD
FAX. (440) 546-9699
HVAC - RTU Sequences of
Operation Revisions
MH-0D
jwf
UP
Phys.Office
1A326
Phys.Office
1A324
MSA
Reception
1A306
Entry
1A300 Reception
1A303 CRC Office
1A211
EXAM
1A213
EXAM
1A215 Office
1A217
Mechanical Room
1A350
Fire Pump Room
1A351
Electrical Room
1A360
Office
1A332
Counsel Office
1A325
Counsel Office
1A323
Counsel Office
1A321
Counsel Office
1A319 Counsel Office
1A317 Consult
1A315
Exam
1A313 Quiet
1A311
Sub-Waiting
1A308 Waiting
1A302
Public Toilet
1A304
Public Toilet
1A305
PROCEDURE
1A212
Corridor
1A310
Corridor
1A301 Corridor
1A209
DIAB EDUC
1A214
EXAM
1A219
EXAM
1A221
Corridor
1A208
Exam
1A223
Office
1A225
Triage
1A227
Triage
1A229
Corridor
1A207
CONF
1A205
Corridor
1A200
Chief Office
1A262
Corridor
1A250
Counsel Office
1A281
Counsel Office
1A282
Counsel Office
1A283
Counsel Office
1A284
Corridor
1A280
Counsel Office
1A285
Counsel Office
1A287
Counsel Office
1A289
DTC Office
1A291
Corridor
1A330 Office
1A333
Office
1A334
Elec
1A455
Group
1A561
Stair No. 1
1S001
Vestibule
1A023
DTC Office
1A292
HAC
1A331
DTC Office
1A290
BFB Tech Office
1A288
Biofeedback Treatment
Room
1A286
ADL Toilet
1A028A
Staff Toilet
1A279
Rehab Counsel
1A277
Corridor
1A270
SW Office
1A278
Nurse/Pharm.
1A261
Connected Care
1A260
Resident
1A259
Connected Care
1A258 Reception
1A203
Work Area
1A204
Exam
1A226
Corridor
1A206
Connected Care
1A256
Connected Care
1A254
Connected Care
1A252
Patient Toilet
1A257
Patient Toilet
1A255
Connected Care
1A253
Connected Care
1A251
SWS Office
1A272
Connected Care
1A274
Connected Care
1A276 Rehab
Counsel
1A275
Rehab Counsel
1A273
Psych. Office
1A271
Shower
1A028B
Storage
1A028C ADL Kitchen
1A028D
PRRC/Basic Space
1A028
Telecommunications
1A024
Electrical Room
1A025
Corridor
1A026
Elevator Lobby
1A007
Corridor
1A022
Corridor
1A159
Attorney
1A190B
Attorney
1A190
Attorney
1A190A
Office
1A191
Intern Office
1A181
Toilet Room
1A158
Office
1A157
Break Out Space
1A155A
Staff Work Area
1A155
Office
1A155B
Office
1A155C
Storage/ Media Center
1A156 Multi. Room
1A176
Chief Office 1A177
Waiting/Admin.
1A175
Office
1A178
PBS Chief
1A172 Vet Trans Service
1A171
Storage
1A175A
Entry
1A150
Sub-Waiting
1A122
OEF/OIF
Social Work
CM
1A120 OEF/OIF RN
CM
1A118
Office
1A114
Corridor
1A107
Corridor
1A151
Employee Health
1A123
Employee Health Exam
1A121
OEF/OIF
Nurse
Check-in
1A119
OEF/OIF
Phys/RN
Office
1A143
OEF/OIF
Physician
Office
1A141
Enrollment Exam
1A139
Corridor
1A108
OEF/OIF
Exam
1A144
OEF/OIF
Exam
1A142
OEF/OIF
Exam
1A140
OEF/OIF
Exam
1A138
Enrollment Nurse
1A136
Police
1A134
HAC
1A152
Education Equipment
1A154A
Kitchen
1A154
Toilet Room
1A153
R.O.I. Work
1A180 Library/ Education
1A165B Circulation
1A165A
Learning Exchange
Center
1A165C
Staff Work Area
1A165D
Corridor
1A021
Business Center
1A164 Training
1A161
Work Room
1A163
A.C.P. Super
1A132 Police Chief
1A102A
Police Administration
1A102
OEF/OIF LPN
1A130 Corridor
1A109
Police Office 1A137
Mental Health
1A117
Screen
1A135
LGBT
1A115
Voluntary Check In
1A101
Tricare 1A111
Enrollment
ID
1A131
Toilet Room
1A108A
Stair No. 3
1S003
EKG/Lab
1A112
Office (VIC)
1A110
Telecommunications
1A106
Arms Room
1A033A Evidence
Room
1A033
Eletrical Room
1A105
Hold
1A032
Toilet Room
1A104
Enrollment
1A103
Police Office
1A031
Operation/Control Room
1A030
Public Toilet
1A008
Toilet Room
1A010
Mechanical Room
1A009 HVAC Control
Room
1A340
Emergency Electrical
Distribution
1A013
Telecommunications
1A014
Electrical Rm 1A015
Stair No. 2
1S002 Vestibule
1A016
Corridor
1A012
Service Elevator Lobby
1A011
Corridor
1A017
Perc
1A072
Retail
1A073
Canteen Storage
1A074
Dining/ Canteen
1A070
Lobby/Waiting
1A006
Waiting
1A005
Work Study
1A050A
Waiting
1A050
Office
1A052
Office 6
1A054 Office 7
1A056
Corridor
1A051
Office 5
1A053
Office
1A055
Office
1A042
Office
1A044
Conference Room
1A059
Office 4
1A058
Office 3
1A060 Workroom
1A061
Office 2
1A062
File Room
1A063
Review Room
1A064
State Employee
Office
1A066 Contract Open Office
1A065
Food Service
1A075
Kitchen
1A076
Chief Office
1A078
Kitchen Storage
1A077
Corridor
1A040
Office
1A047
Office
1A045
Storage
1A043
Office
1A041
Corridor
1A019
Travel Clerk
1A080
Teller
1A081
Agent Cashier/ Teller
1A081A
Agent Cashier/ Teller
1A081B
HAC
1A020
Corridor
1A018
Enrollment
ID
1A113
Corridor
1A057
Kitchen Storage
1A077A
Starbucks
1A006A
OIF/OEF
Reception
1A006C
Room
1A130A
Reception
1A004
Lobby
1A003
Room
2A189
Office
1A164A
Corridor
1A202
Waiting
1A201
Exam
1A228
1A224
Office
1A222
Exam
1A220
DIAB EDUC
1A218
EXAM
1A216
SOILED
1A210 sult
Consult
1A548
Office
1A549
Office
1A550
Group
1A567
Group
1A568
Toilet
A451
Toilet
1A452
Toilet
1A454
Toilet
A453
Waiting
1A560
Phys.Office
1A322
200R
Phys.Office
1A320
Phys.Office
1A318
Phys.Office
1A316
Phys.Office
1A314
Phys.Office
1A312 1-078
175E
500E
250R
300S
700R
400R
450S
450S
400S
800R
400S
700R
1-175
1-173
600S
600S
600S
700R
500S
200R
200S
1-172
100R
100S
100R
100S
200S100R
100S
600E
100S
500S
125S600E
500S
575S
575S
900E
575S
575S
1-169
600S 500S
400E 450S 450S
400E 1-167
1-168
100R
100S
1-188
1-171
200R
1-170
80S
80R
75E
600E
230S230S
400S 400S
500E500E
630R
530S
100S
100S
1-120
250S
100S 150S
850R
325R
325S
1-125
125S
125E
200S 430S
140S
130S
600R
300S
300S
1-115
325S
325S
1-108
525R
175S
175R
300R
400S
1-131
OIF/OEF
Program Manager
1A116 60S
70R
1-140
400S
1-184
100R 150R
125R
150S100S
125S
125R
125S
600E
500S
1-179
1-144
1-178
3000S
3000S
3000S
2000R
1500R
1500R
3000S
2000R 2000R
550R 400S 75R
75S
100R
100S
125R
125S
200S
200R
75E
75E
60S
175R
175S
100R
160R
160S
1-0721-071
100S
75E
1-099
Med
400S
175R
175R
1-092
280S
200E
200E
100S
800R
650S
1-121
2000R
1-160
1-159
1-157
1-183
1-156
3000S
2000R
1-182
1-180
1-161
1-162
1-164
D1
DEMOLITION CODED NOTES:
D1 REFER TO ENLARGED PLANS ON THIS SHEET.
REMOVE AND REPLACE CEILINGS AS NECESSARY TO ACCOMPLISH WORK.
RELOCATE EXISTING THERMOSTAT TO LOCATION INDICATED ON THE NEW WORK PLAN. CONTRACTOR
SHALL PATCH AND FINISH WALL TO MATCH SURROUNDING SURFACES.
D2
D3
BALANCER NOTES:
A. PRIOR TO ANY ADJUSTMENTS, TAKE BASELINE AIRFLOW MEASUREMENTS AT ALL DIFFUSERS AND
GRILLES THAT ARE INDICATED TO BE BALANCED.
B. ADJUST VAV BOX MAXIMUM AIRFLOW VIA THE BAS PER THE VAV TERMINAL SCHEDULES ON SHEET MH-0B
AND MH-0C.
C. BALANCE THE SUPPLY DIFFUSERS AND GRILLES CONNECTED TO THE VAV AND ASSOCIATED RETURN AND
EXHAUST GRILLES AS INDICATED ON PLAN. THIS SHALL BE ACCOMPLISHED VIA EXISTING DUCT VOLUME
DAMPERS.
D. ADJUST HEATING AIRFLOW VIA THE BAS AND REHEAT WATER FLOW SHALL BE BALANCED PER VAV
TERMINAL SCHEDULES ON SHEET MH-0B AND MH-0C.
E. BALANCING SHALL BE COMPLETED AFTER 6:00 P.M. ON WEEKDAYS.
F. DAMAGED CEILING TILES SHALL BE REPLACED.
MECHANICAL LEGEND:
AREA NOT IN SCOPE OF THIS PROJECT
AREA INCLUDED IN SCOPE OF THIS PROJECT. CONTRACTOR SHALL FOLLOW BALANCER
NOTES ON THIS SHEET FOR THESE AREAS.
OEF/OIF LPN
1A130
Voluntary Check In
1A101
Toilet Room
1A108A
EKG/Lab
1A112
Office (VIC)
1A110
Room
1A130A
X-22x18
X -1 x 4 X
-1 x
X-16x14 X-14x14
X -1 x
X-18x12
T
T
CAP
CAP
D2
D3
D2
XRL
D2
D2Police Office 1A137
Mental Health
1A117
Screen 1A135
LGBT
1A115
Tricare
1A111
Enrollment
ID
1A131
Enrollment
ID
1A113
PATCH WALL
PATCH WALL
OEF/OIF LPN
1A130
Voluntary Check In
1A101
Toilet Room
1A108A
EKG/Lab
1A112
Office (VIC)
1A110
Room
1A130A
X-22x18
X -1 x 4 X
-1 x
X-16x14 X-14x14
X -1 x
X-18x12
100S
125S
125R
100R 125R
125S
100R
100S
100S
100R
100S
100R
100R
100S140S
140R
1-143 1-145
T
T
D2
XNL
D2
Police Office 1A137
Mental Health
1A117
Screen 1A135
LGBT
1A115
Tricare
1A111
Enrollment
ID
1A131
Enrollment
ID
1A113
6" Ø
6" Ø
N
0' 8' 16' 32' 64'
SCALE: 3/32" = 1'0"
FIRST FLOOR HVAC AIR DISTRIBUTION PLAN - WEST
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
CHALMERS P. WYLIE VAACC
CORRECT RETRO COMMISSIONING
DEFICIENCIES
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Farid F. Mehr, P.E.
Chief, Engineering Service
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
/1
/2
:3
:4 A
M C
R e v it L o c a l\
R
V A
C o lu m b u s C o rr e c t
R e tr o
C X
C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m
.r v t
757-20-101 dad sic04/14/21
420 N. JAMES ROAD, COLUMBUS, OH 43219
Revisions Date
BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696
BROADVIEW HTS., OHIO 44147
672 EAST ROYALTON ROAD
FAX. (440) 546-9699
First Floor HVAC
Air Distribution Plan - West
MH-1A
UP
N
NOT TO SCALE
FIRST FLOOR KEY PLAN
N
0'
SCALE: 1/8" = 1'0"
4' 8' 16' 32'
ENLARGED PARTIAL FIRST
FLOOR HVAC DEMOLITION PLAN
N
0'
SCALE: 1/8" = 1'0"
4' 8' 16' 32'
ENLARGED PARTIAL
FIRST FLOOR HVAC PLAN
WEST
EAST
-65042
ER
H
F OO
IO
AVID A.
MAGALL
-65042
ER
H
F OO
IO
AVID A.
MAGALL
-65042
ER
H
F OO
IO
Pharmacy Waiting
1B003
Controlled Substance
Vault
1B222 Refrigerator/Freezer
1B224
Packaging
1B220
Consultant 1
1B240A
Consultant 2
1B240B
Consultant 3
1B240C
Consultant 4
1B240D
Consultant 5
1B240E
Consultant 6
1B240F
Staff Toilet
1B241
Staff Toilet
1B242
Assistant Chief Office
1B202
Pharmacy Administation
Office
1B200
Chief Office
1B203
HAC
1B207
Super.
Pharmacy
1B209
Work Room
1B204
Corridor
1B212
Conference/Education/Workroom
1B211
Patient Advocate
1B022
Patient Advocate
1B021
Patient Advocate
1B020
Elevator Lobby
1B001
Telecommunications
1B002
Stair No. 4
1S004
Electrical Room
1B031
Waiting
1B030
Logistics
1B210
Clinical Pharmacy
1B208
Change
1B042
Change
1B044 Toilet Room
1B046A
Ultrasound
1B046
Ultrasound
1B048
Fee Basis
1B206
Bone Density
1B050
Staff Lockers/Lounge
1B229
Break Room
1B052
Corridor
1B004 Corridor
1B005
Methadone Staff Work
1B223
Lock Shop
1B225
Inventory/Stock MNG/ Prog.
Asst.
1B226 Receiving/ Counter
1B227
Compound
1B237
Drug Cache
1B236
Dispensing
1B230
Window Filling
1B231
Storage/ Shelving
1B232
Mail Filling
1B233
Prosthetics Storage
1B238
Sub-Waiting
1B033
Corridor
1B034
Supervisor
1B061
Radiology
1B041
Toilet Room
1B043
Toilet Room
1B045 Rad. Control Room
1B049
Radiology
1B047
Toilet Room
1B054
Sub-Waiting
1B035
Corridor
1B037
Soiled Utility Room
1B051 Change
1B053
Exam 7
1B250G
Exam 8
1B250H
Corridor
1B036
Exam 9
1B257 Exam
1B258
UCC
1B254
Patient Toilet/Shower
1B256
Exam 6
1B250F
Exam 1
1B250A
Exam 2
1B250BUCC
Reception
1B250C
Exam 4
1B250D
Exam 5
1B250E
Patient Toilet
1B255
Care Giver
1B251C
PACS
1B251B
Care Giver
1B251A
Corridor
1B252
Telecommunications
1B006
Electrical Room
1B007
Storage
1B265
Nurse Office
1B263
Storage
1B261
Corridor
1B253
Corridor
1B009
Logistics File Storage
1B008
Physician Office
1B264
Nurse Office 1B262
Soiled Utility Room
1B272
Patient Toilet
1B260
Patient Toilet
1B274
Stretcher Storage
1B276
Corridor
1B280
Nurse Office
1B275
Exam
1B278
Staff Toilet
1B281
Washroom
1B106
Corridor
1B270
Shared Office
1B273
Logistics file storage
1B108
Waiting
1B271 Bio-Hazard
1B110
Soiled Linen Cart
1B112
Stair No. 5
1S005
Corridor
1B010
Recieving Shipping Docks
1B113
Receiving & Issue Area
1B111
Unpost. Hold.
1B109
Staff Toilet
1B114
Storekeeper Office
1B115
Form Storage
1B107
CHIEF
1B117
Secretary/Waiting
1B118
Open Office
1B116
Chief Office
1B119
Central Linen Stor. (Envir.
Serv.)
1B105
Staff Toilet
1B120
4 Isolation
1B259
Clean
1B277
Exam
1B279
Medical Gas Storage
1B104
Toilet Room
1B259A
Change
1B083 Sub-Waiting
1B084
Cry. Storage
1B085 Clean
1B086
EMS
Supervisor
1B087
HAC
1B102
Corridor
1B012
Envirn.
Services Office
1B101B
Media Vault
1B121 Reverse Osmosis
1B103A Logistics
1B103
Supply Storage (Env.
Serv.)
1B101
Scan Room
1B100B
Equipment
1B098
Toilet Room
1B093
Sub
1B091
Interview
1B095
M.R.I.
1B097
Control
1B100A
Office
1B094
Office
1B092
Biomed
1B090
Waiting
1B096
Ra…
This is the start of the file's text. The full file is on GovTribe.