This document provides details for a federal solicitation seeking construction services. The solicitation will be posted on July 23, 2021 for Correct Retro-Commissioning Deficiencies at the VAACC Columbus facility, Project #757-20-101. Interested parties should register at SAM.gov to receive updates. A one-time site visit will be scheduled for interested parties. Bids are due approximately 30 days after solicitation posting. The work includes general construction and mechanical systems balancing and testing to correct deficiencies identified. The incumbent contractor will complete work within 210 calendar days of notice to proceed.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2018 INTERNATIONAL BUILDING CODE

CHAPTER 3 - USE GROUP:

USE GROUP: B-BUSINESS

CHAPTER 4 - SPECIAL DETAILED REQUIREMENTS:

DETAILED REQUIREMENTS IF NEEDED

FIRE-RESISTANCE RATINGS REQUIREMENTS - TABLE 601:

CONSTRUCTION TYPE: 1A

STRUCTURAL FRAME: 3 HRS

BEARING WALLS:

EXTERIOR: 3 HRS

INTERIOR: 3 HRS

NON BEARING WALLS & PARTITIONS:

EXTERIOR: 0 HRS

INTERIOR: 0 HRS

FLOOR CONSTRUCTION: 2 HRS

ROOF CONSTRUCTION: 1 1/2 HRS

CHAPTER 7 - FIRE-RESISTANCE-RATED CONSTRUCTION:

SHAFT ENCLOSURES: 2 HRS

EXIT ENCLOSURES: 2 HRS

EXIT PASSAGEWAYS: 0 HRS

CHAPTER 8 - INTERIOR FINISHES:

EXIT ENCLOSURES & PASSAGEWAYS: CLASS B

CORRIDORS: CLASS C

ROOMS & ENCLOSED SPACES: CLASS C

INTERIOR FLOOR FINISH: MINIMUM CLASS II

CHAPTER 9 - FIRE PROTECTION SYSTEMS:

SPRINKLER SYSTEM: FULLY SUPPRESSED

FIRE ALARM SYSTEM: YES

CHAPTER 10 - MEANS OF EGRESS:

DOOR WIDTH: 32" MINIMUM CLEAR WIDTH

CORRIDOR WIDTH: .2" PER OCCUPANT, BUT NOT LESS THAN 44"

LENGTH OF EXIT TRAVEL: 200'

2018 NFPA 101 LIFE SAFETY CODE

OCCUPANCY (6.1.11):

BUSINESS - OUTPATIENT CLINIC (AMBULATORY)

AMBULATORY HEALTH CARE (CHAPTER 20/21)

BUILDING TYPE:

TYPE 1 (332)

FIRE-RESISTANCE RATING REQUIREMENTS - TABLE A8.2.1.2:

STRUCTURAL FRAME: 3 HRS

BEARING WALLS:

EXTERIOR: 3 HRS

INTERIOR: 3 HRS

NON BEARING WALLS AND PARTITIONS

EXTERIOR: 0 HRS

INTERIOR: 0 HRS

FLOOR CONSTRUCTION: 2 HRS

ROOF CONSTRUCTION: 1 1/2 HOURS

FIRE-RESISTANCE RATED CONSTRUCTION - TABLE A8.6.5/7.1.3.2.1

SHAFT ENCLOSURES: 2 HRS

EXIT ENCLOSURES: 2 HRS

SMOKE BARRIERS (20.3.7.5):

1 HOUR

TRAVEL DISTANCE (20.2.6.2):

REMOTE POINT TO EXIT 200 FOOT MAX

OTHER APPLICABLE CODES AND STANDARDS

1. VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL

2. OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

3. ENERGY POLICY ACT OF 2005 (EPACT)

4. FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS:

MEMORANDUM OF UNDERSTANDING (MOU)

5. EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL,

ENERGY AND TRANSPORTATION MANAGEMENT

6. ASHRAE STANDARD 15-2007

7. ASHRAE STANDARD 62.1-2004

8. NATIONAL ELECTRICAL CODE (NEC) - 2020

9. INTERNATIONAL PLUMBING CODE (IPC) - 2018

10. NFPA 99 HEALTH CARE FACILITIES CODE - 2018

11. HVAC DESIGN MANUAL - MARCH 2020

12. PG-18-3 DESIGN AND CONSTRUCTION PROCEDURES - JULY 2004

13. PG 18-13 VA BARRIER FREE DESIGN STANDARD - JANUARY 2017

14. PG-18-15 MINIMUM REQUIREMENTS FOR A/E SUBMISSIONS - MAY 2006

PROJECT NUMBER:

SUBMITTAL FOR:

DRAWING INDEX: CODE DATA:LOCATION MAP:

DESCRIPTION OF WORK:

CORRECT RETRO COMMISSIONING

DEFICIENCIES

420 N. JAMES ROAD, COLUMBUS, OH 43219

757-20-101

BID AND CONSTRUCTION

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

BID AND CONSTRUCTION

Project Number

Building Number

Drawing Number

CHALMERS P. WYLIE VAACC

Project Title

Location

Issued Date Checked Drawn

Drawing Title

Approved: Farid F. Mehr, P.E.

Chief, Engineering Serice

Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX. (440) 546-9699

/7

/2

:4

:5

P

M C

R e v it L o c a l\

R

V A

C o lu m b u s C o rr e c t

R e tr o C

X

C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m

.r v t

GI-1

757-20-101

CBLH STAFF

CORRECT RETRO COMMISSIONING

DEFICIENCIES

04/14/21

420 N. JAMES ROAD, COLUMBUS, OH 43219

COVER

DRAWING INDEX

SHEET NO. SHEET NAME

GENERAL

GI-1 COVER

MECHANICAL

MH-0A MECHANICAL LEGEND & GENERAL NOTES

MH-0B MECHANICAL SCHEDULES

MH-0C MECHANICAL SCHEDULES

MH-0D HVAC - RTU SEQUENCES OF OPERATION REVISIONS

MH-1A FIRST FLOOR HVAC AIR DISTRIBUTION PLAN - WEST

MH-1B FIRST FLOOR HVAC AIR DISTRIBUTION PLAN -EAST

MH-2A SECOND FLOOR HVAC AIR DISTRIBUTION PLAN - WEST

MH-2B SECOND FLOOR HVAC AIR DISTRIBUTION PLAN - EAST

MH-3 THIRD FLOOR HVAC AIR DISTRIBUTION PLAN

MH-4A FOURTH FLOOR HVAC AIR DISTRIBUTION PLAN - WEST

MH-4B FOURTH FLOOR HVAC AIR DISTRIBUTION PLAN - EAST

MHP-1A FIRST FLOOR HVAC PRESSURE RELATIONSHIP PLAN - WEST

MHP-1B FIRST FLOOR HVAC PRESSURE RELATIONSHIP PLAN - EAST

MHP-2A SECOND FLOOR HVAC PRESSURE RELATIONSHIP PLAN - WEST

MHP-2B SECOND FLOOR HVAC PRESSURE RELATIONSHIP PLAN - EAST

MHP-3 THIRD FLOOR HVAC PRESSURE RELATIONSHIP PLAN

MHP-4 FOURTH FLOOR HVAC PRESSURE RELATIONSHIP PLAN

BID ITEM 1 (BASE BID): Work includes general construction as indicated on Construction Drawings and Specifications. This includes surveying existing airflow conditions at all devices indicated, rebalancing airflow at all devises indicated, adjusting VAV box airflow setpoints at all VAV boxes indicated, rebalancing existing reheat coil water flow as indicated, revising RTUs sequence of operation, testing RTUs for existing air leakage, provide corrective measures at RTUs to reduce leakage, and re-testing leakage to confirm specifications met, and replacing outdoor air control damper linkages at each RTU. All work shall be completed within 210 calendar days after receipt of Notice to Proceed.

BID ITEM 2 (Alternate NO. 1): All work indicated in Base Bid except, remove all work associated with replacing the linkages at the outside air dampers on rooftop air handling units as indicated on Drawings MH-4A and MH-4B. All work shall be completed within 196 calendar days after receipt of Notice to Proceed.

BID ITEM 3 (Alternate NO. 2): All work indicated in BID ITEM 2 (Alternate 1) except, remove all work associated with VAV’s 1-143 and 1-145 near room 1A135 as indicated in plan views 2 and 3 on Drawing MH-1A. All work shall be completed within 189 calendar days after receipt of Notice to Proceed.

BID ITEM 4, (Alternate NO. 3): All work indicated in BID ITEM 3 (Alternate 2) except, remove all work associated with VAV 1-020 in room 1B098 as indicated on plan views 2 and 3 on Drawing MH-1B. All work shall be completed within 182 calendar days after receipt of Notice to Proceed.

BID ITEM 5, (Alternate NO.4): All work indicated in BID ITEM 4 (Alternate 3) except, remove all work associated with duct terminations in room 2A075 as indicated on plan view 1 on Drawing MH-2A. All work shall be completed within 168 calendar days after receipt of Notice to Proceed.

Revisions Date

BID AND CONSTRUCTION 04/14/21

HVAC GENERAL NOTES:

HVAC LEGEND AND ABBREVIATIONS

DEMOLITION SYMBOLS: HVAC PIPING:

HVAC CONTROLS:

DUCTWORK SYMBOLS:

MANUAL BALANCING DAMPER ON DUCT

ROUND DUCT SIZE

AD ACCESS DOOR

12"Ø

RECTANGULAR DUCT SIZE24x18

ELECTRICAL CONTRACTOR

GENERAL TRADES CONTRACTOR

TEMPERATURE CONTROL CONTRACTOR

HVAC CONTRACTOR

FIRE SUPPRESSION CONTRACTOR

PLUMBING CONTRACTOR

CONNECT TO EXISTING

EC

GC

FC

PC

TC

HC

TO

OPENING IN TOP OF DUCT. SHALL BE A MINIMUM 1.5

TIMES GREATER THAN THE CROSS-SECTIONAL AREA OF

DUCT.

UC

INDICATES UNDERCUT DOOR - UNDERCUT 3/4"

SEE

ARCHITECTURAL PLANS.

SUPPLY AIR DUCT

TO BE MOUNTED OVER ACCESSIBLE CEILING

SUPPLY AIR DIFFUSER

SHADING INDICATES TO PROVIDE QUADRANT BLANK-OFF

IN NECK OF DIFFUSER. TO BE FURNISHED WITH DIFFUSER.

INDICATES TRANSITION (SINGLE LINE)

x'-x" INDICATES BOTTOM OF DUCT DIMENSION ABOVE FINISHED FLOOR

ABOVE FINISHED FLOOR

EXHAUST AIR

RETURN AIR

SUPPLY AIR

AFF

EA

RA

SA

INDICATES QUANTITY OF WIRES (4)

TEMPERATURE CONTROL PANELTCP

VARIABLE FREQUENCY DRIVE FOR MOTOR

CURRENT TRANSFORMER ON MOTOR WIRING WITH TRANSDUCER

AIR CONDITIONING CONDENSATE

LOW PRESSURE STEAM CONDENSATE

HHWS

LPC

LPR

HHWR

ACC

VAV REHEAT WATER SUPPLY

VAV REHEAT WATER RETURN

LOW PRESSURE RETURN

PRESSURE GAUGE

MOTOR STARTER

ELECTRIC MOTOR

LOW LIMIT THERMOSTAT

VFD

EM

L

FLEXIBLE METAL EXPANSION LOOP ASSEMBLY

HUMIDITY SENSOR WITH SETPOINT ADJUSTMENT

COMBINATION FIRE/SMOKE DAMPER IN DUCT

HUMIDITY SENSOR

MOTOR OPERATED DAMPER STATIC PRESSURE SENSOR

H

H

SMOD

FSD

STRAINER

PIPE EXPANSION ANCHOR

PIPE GUIDE

FLEXIBLE PIPE CONNECTOR

THERMOMETER IN PIPE WELL

BALANCING VALVE

X

E.L.

ISOLATION VALVE

REDUCER

UNION

CHECK VALVE

MOTORIZED 3-WAY CONTROL VALVE

GAUGE PORT (PETE'S PLUG)

DRAIN VALVE WITH HOSE FITTING

MOTORIZED 2-WAY CONTROL VALVE

LOCAL DRAIN, VALVED WITH 3/4" THREADED CONNECTOR

MANUAL AIR VENTMAV

PRESSURE RELIEF VALVE

KITCHEN HOOD EXHAUSTKHE

RETURN AIR DUCT

EXHAUST AIR DUCT

CD CONDENSATE PIPINGEXISTING TO REMAIN

EXISTING TO BE REMOVED

X

XR

EXISTING TO BE RELOCATEDXRL

BRANCH PIPE CONNECTION

FIRE DAMPER IN DUCTFDD

TWO POSITION VALVE

PRESSURE REDUCING VALVE

INDICATES DIRECTION OF AIRFLOW

LIMIT OF DEMOLITION

EXISTING NEW LOCATIONXNL

THERMOSTATT

NOTE: THIS LEGEND IS INTENDED TO AID IN THE UNDERSTANDING OF SHORTHAND, SYMBOLS AND ABBREVIATIONS SHOWN IN THESE CONSTRUCTION DOCUMENTS.

IT IS NOT THE INTENTION TO DESCRIBE THE PROJECT SCOPE OF WORK, FOR DETAILED SCOPE OF WORK PLEASE REFER TO THE SUBSEQUENT DRAWINGS.

BUILDING MANAGEMENT SYSTEMBMS

DIRECT DIGITAL CONTROLDDC

LPS LOW PRESSURE STEAM

BOTTOM OF DUCTBOD

COLUMN LINECL

RADIANT CEILING PANELRCP

OUTSIDE AIROA

NORMALLY OPEN

OUTSIDE AIR FAN

RETURN FAN

N.O.

OAF

RF

SUPPLY FANSF

NORMALLY CLOSEDN.C.

CHILLED WATERCHW

CHILLED WATER RETURNCHR

CHILLED WATER SUPPLYCHS

CURRENT SENSORCS

MOTORIZED ACTUATORM

ELECTRIC ACTUATORE

HVAC DESIGN DATA

Db SUMMER

Wb SUMMER

Db WINTER

DESIGN ALTITUDE: 900 FT.

INDOOR AREA

SUMMER

Db Db

°F

89.4°F

73.9°F

-4.0°F

WINTER

°F

DESIGN CONDITIONS

BRONCHOSCOPY

TEMPERATURE SENSORT

OUTDOOR DESIGN

TEMPERATURES

A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM

EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE

PERFORMED AS INDICATED ON THESE DRAWINGS.

B. COORDINATE ALL SHUT-DOWNS OF EXISTING MECHANICAL SYSTEMS WITH OWNER A MINIMUM OF SEVEN

WORKING DAYS IN ADVANCE.

C. REFER TO TERMINAL CONNECTIONS SCHEDULE FOR SIZE OF DUCT CONNECTIONS TO TERMINAL UNITS.

D. UNLESS NOTED OTHERWISE, BRANCH DUCTS TO DIFFUSERS SHALL BE THE SAME SIZE AS THE NECK OF

THE DIFFUSER.

E. SEAL ALL OPENINGS AROUND NEW DUCT AND PIPE PENETRATIONS OF WALLS, WITH CAULK, WITHIN 24 HOURS OF INSTALLATION. THERE SHALL BE NO VISIBLE OPENINGS IN WALLS AROUND PENETRATIONS.

BONE DENSITOMETRY

BIOCHEMISTRY

AUDIOLOGY OFFICE/ THERAPY ROOM

"HOT LAB"

CONFERENCE ROOM

CLEAN SCOPE STORAGE

CLEAN CORE

CLASSROOM/ GROUP ROOM

EKG TESTING ROOM

DENTAL TREATMENT ROOM

DECONTAMINATION

CORRIDOR

CONSULT ROOM

HISTOLOGY

HAZARD WASTE DISPOSAL

GIFT SHOP (RETAIL)

EXAM/ TREATMENT

ENDOSCOPY

LASER

KITCHENETTE

HOUSE KEEPING AIDE CLOSET

LOUNGE 75 60 70 20

75 60 70 20

75 NA 75 NA

NA NA NA NA

66 60 72 20

70 50 70 20

68 60 73 20

68 60 68 30

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

MRI CONTROL ROOM

MICROBIOLOGY

MEDICATION ROOM

MANUAL CART WASH

LOCKER/ CHANGING

OCCUPATIONAL THERAPY

NURSE STATION

NUCLEAR MED SCANNING ROOM

MULTIPURPOSE STORAGE

PATIENT PREP/ RECOVERY

PACU PATIENT BAY

ORTHOPEDIC CLINIC (CAST ROOM)

OPTOMETRY

OFFICE

PULMONARY FUNCTION LAB

PROCEDURE

PHYSICAL THERAPY

PHARMACY CACHE AREA

PATIENT ROOM, ISOLATION

RECOVERY PACU

RECEIVING & LOADING

RADIOGRAPHIC/ FLUOROSCOPIC

RESIDENT DINING

75 NA 70 NA

75 70

75 60 70 20

NA NA

75 60 70 20

75 60 70 20

75 50 70 30

75 50 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 30

75 60 70 20

68 60 70 20

75 60 70 20

75 60 70 30

75 60 70 20

75 60 70 20

75 60 70 20

75 60 70 20

SUB-STERILE ROOM

SOILED UTILITY AND STORAGE

SLEEP STUDY ROOM

SCRUB AND GOWN

SCOPE STAGING AREA

ULTRASOUND

TRIAGE

TOILET

TELECOMMUNICATIONS

WALK IN REFRIGERATOR/ FREEZER

WAITING

VESTIBULE

USP 797 BUFFER

USP 797 ANTE

66 60 72 20

72 72

81 60 64 30

60 45

75 60 70 20

NA NA NA NA

75 50 70 30

NA NA NA NA

75 50 70 20

75 60 70 30

68 60 68 30

NA NA 50 NA

75 60 70 20

68 68 30

NA NA NA NA

CLEAN UTILITY AND STORAGE 70 55 70 30

REFERENCE TO CODED NOTE

EQUIPMENT OR FIXTURE MARK

AIR DISTRIBUTION DEVICE

UNIT NUMBER

EQUIPMENT

TYPE

CONNECTION SIZE AT

DEVICE

TYPE

EQ-#

CALL OUTS:

CFMA

NECK

ABBREVIATIONS:

XXX

EXISTING DIFFUSER/GRILLE TO

BE BALANCED TO LISTED CFM

MAXIMUM

RELATIVE

HUMIDITY (%)

MINIMUM

RELATIVE

HUMIDITY (%)

DUCT IN DUCT OUT

SEE SCHEDULE AND

PLANS FOR INLET

AND OUTLET DUCT

SIZES TO VAV

TERMINALS

VAV TERMINAL HOT WATER REHEAT COIL

DUCT ACCESS DOOR INSTALL MANUAL BALANCING DAMPER

FOR EACH DIFFUSER WITHIN DUCT AS

FAR FROM OUTLET AS POSSIBLE.

NOTE: WHERE VAV TERMINAL SERVES

ONLY ONE GRILLE, MANUAL

BALANCING DAMPER IS NOT

REQUIRED. DAMPER SHALL BE

LOCKING QUADRANT TYPE WITH

2-INCH INSULATION STAND-OFF.

MINIMUM OF (1) 90° CHANGE

OF DIRECTION BETWEEN EACH

DIFFUSER AND VAV TERMINAL

DIFFUSER PER PLAN

(TYPICAL)

UNLESS OTHERWISE

NOTED, BRANCH DUCTS

TO DIFFUSERS SHALL BE

SAME SIZE AS DIFFUSER

NECK.

MAINTAIN ADEQUATE SERVICE ACCESS

TO CONTROLS. T.C. SHALL DETERMINE

CONTROL PANEL LOCATION (RIGHT OR

LEFT SIDE) BASED ON SPACE AVAILABLE.

18" MINIMUM

CLEAR

RHWS

RHWR

COIL VENT

HEATING HOT

WATER COIL

2-WAY CONTROL VALVE

TEST PORT (TYPICAL)

ISOLATION VALVE (TYP.)

VENTURI STYLE BALANCE VALVE

UNION (TYPICAL)

STRAINER WITH

BLOWDOWN VALVE

DRAIN AT LOW POINT

(TYP.)

REDUCE TO CONTROL

VALVE PIPE SIZE (TYP.)

TOP TAKE-OFF

OF ALL MAINS

REHEAT

PIPING MAINS

REHEAT COIL PIPING DIAGRAM 2

NOT TO SCALE

SUPPLY VARIABLE AIR VOLUME TERMINAL DETAIL 1

NOT TO SCALE

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

BID AND CONSTRUCTION

Project Number

Building Number

Drawing Number

CHALMERS P. WYLIE VAACC

CORRECT RETRO COMMISSIONING

DEFICIENCIES

Project Title

Location

Issued Date Checked Drawn

Drawing Title

Approved: Farid F. Mehr, P.E.

Chief, Engineering Service

Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

/1

/2

:3

:4 A

M C

R e v it L o c a l\

R

V A

C o lu m b u s C o rr e c t

R e tr o

C X

C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m

.r v t

757-20-101 dad sic04/14/21

420 N. JAMES ROAD, COLUMBUS, OH 43219

Revisions Date

BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696

BROADVIEW HTS., OHIO 44147

672 EAST ROYALTON ROAD

FAX. (440) 546-9699

Mechanical Legend & General Notes

MH-0A1-65042

ER

H

F OO

IO

AVID A.

MAGALL

-65042

ER

H

F OO

IO

AVID A.

MAGALL

-65042

ER

H

F OO

IO

AVID A.

MAGALL

NEW MIN.

AIRFLOW

(CFM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

RTU-1 VAV TERMINAL SCHEDULE

SERVES 1ST FLOOR - WEST

RTU-2 VAV TERMINAL SCHEDULE

SERVES 1ST FLOOR - WEST

RTU-3 VAV TERMINAL SCHEDULE

SERVES 2ND FLOOR - WEST

RTU-4 VAV TERMINAL SCHEDULE

SERVES 3RD FLOOR

RTU-4 VAV TERMINAL SCHEDULE CONT'D

SERVES 3RD FLOOR

V3-200 3A033 8 700 700 500 500 1.0

3-111 3A188 8 500 500 200 200 0.3

3-110 3A184 8 500 500 330 330 0.5

3-109 3A185 8 450 450 330 330 0.5

3-108 3A183 8 500 500 200 200 0.3

3-107 3A015 8 590 590 0 - -

3-106 3A004 8 500 500 0 - -

3-105 3A215 6 210 210 210 210 0.5

3-104 3A268 8 480 510 390 390 0.6

3-103 3A081 6 220 220 220 220 0.5

3-102 3A075 10 800 800 420 420 0.5

3-101 3A149 8 730 730 510 510 0.7

3-100 3A061 6 300 300 150 150 0.5

3-099 3A057 8 660 660 500 500 0.7

3-098 3A126 8 640 640 430 430 0.6

3-097 3A151 8 730 750 600 600 0.9

3-096 3A133 8 640 640 430 430 0.6

3-095 3A120 8 730 725 510 510 0.7

3-094 3A123 8 640 640 430 430 0.6

3-093 3A110 8 740 740 430 430 0.6

3-092 3A114 8 640 640 430 430 0.6

3-090 3A107 320 320 320 210 210 0.5

3-089 3A170 6 250 250 250 250 0.5

3-088 3A168 6 250 250 250 250 0.5

3-087 3A103 8 680 680 410 410 0.6

3-086 3A006 8 700 700 210 210 0.5

3-085 3A010 4 200 200 110 110 0.5

3-084 3A017 8 550 550 550 550 0.8

3-083 3A400 8 480 480 350 350 0.5

3-082 3A008 8 550 550 550 550 0.8

3-081 3A050 8 800 800 510 510 0.7

3-080 3A086 6 220 220 220 220 0.5

3-079 3A074 8 700 700 700 700 1.0

3-078 3A076 10 950 1290 660 660 1.0

3-076 3A075 8 700 700 500 500 0.7

3-075 3A033 6 425 425 425 425 0.6

3-074 3A001 14 1900 1800 570 570 0.8

3-073 3A211 6 250 250 250 250 0.5

3-072 3A212 10 860 860 730 730 1.1

3-071 3A201 8 720 720 590 590 0.8

3-070 3A161 10 1085 1085 670 670 1.0

3-069 3A071 6 300 300 180 180 0.5

3-068 3A072 6 300 300 180 180 0.5

3-067 3A203 10 990 1110 510 510 0.7

3-066 3A216 8 650 650 430 430 0.6

3-064 3A421 8 620 620 320 320 0.9

3-062 3A426 8 650 625 450 450 0.6

3-061 3A303 8 870 870 450 450 0.6

3-060 3A440 8 465 500 320 320 0.5

3-059 3A300 10 1220 1220 850 850 1.2

3-058 3A306 6 220 220 220 220 0.5

3-057 3A227 8 560 560 400 400 0.6

3-056 3A220 8 730 730 550 550 0.8

3-065 3A414 8 620 825 620 620 0.9

3-063 3A422 8 460 650 320 320 0.5

3-091 3A100 8 730 850 510 510 0.7

3-055 3A234 8 640 640 460 460 0.7

3-054 3A239 8 680 680 570 570 0.8

3-053 3A224 8 640 640 460 460 0.7

3-052 3A228 8 740 740 460 460 0.7

3-051 3A255 10 820 820 690 690 1.0

3-050 3A240 8 540 540 540 540 0.8

3-049 3A246 8 640 640 640 640 1.0

3-048 3A264 8 770 770 350 350 0.5

3-047 3A263 6 350 350 120 120 0.5

*3-046 3A262 8 0 230 0 0 -

3-045 3A261 8 740 740 350 350 0.5

3-044 3A190 8 700 700 390 390 0.6

3-043 3A073 10 900 900 240 240 0.5

3-042 3A160 8 800 800 570 570 1.5

3-041 3A163 6 400 400 260 260 0.5

3-040 3A165 6 310 310 110 110 0.5

3-039 3A167 8 510 510 350 350 0.5

3-038 3A171 6 400 400 260 260 0.5

3-037 3A173 6 400 400 150 150 0.5

3-036 3A172 6 350 370 150 150 0.5

3-035 3A142 6 350 350 150 150 0.5

3-034 3A143 6 220 220 100 100 0.5

3-033 3A144 6 300 300 170 170 0.5

3-032 3A145 6 400 400 170 170 0.5

3-031 3A146 6 350 350 170 170 0.5

3-030 3A147 6 430 430 210 210 0.5

3-029 3A148 4 200 200 130 130 0.5

3-028 3A063 8 670 670 0 - -

3-027 3A067 6 350 350 110 110 0.5

3-025 3A060 6 170 180 80 80 0.5

3-022 3A054 6 280 325 220 220 0.5

3-021 3A052 6 450 450 200 200 0.5

3-020 3A012 10 980 980 230 230 0.5

3-019 3A411 4 200 200 180 180 0.5

3-018 3A410 6 370 370 220 220 0.5

3-017 3A413 8 460 460 200 200 0.5

3-016 3A415 6 220 220 140 140 0.5

3-015 3A456 6 240 240 180 180 0.5

3-013 3A452 6 310 310 190 190 0.5

3-012 3A451 4 120 130 120 120 0.5

3-009 3A279 4 175 175 110 110 0.5

3-007 3A276 6 250 250 170 170 0.5

3-006 3A273 6 250 250 170 170 0.5

3-004 3A271 6 250 310 150 150 0.5

3-002 3A267 6 250 250 150 150 0.5

3-026 3A062 6 280 350 180 180 0.5

3-023 3A056 6 130 225 80 80 0.5

3-014 3A454 6 300 360 250 250 0.5

3-024 3A058 6 130 180 80 80 0.5

3-010 3A310 6 250 325 160 160 0.5

3-008 3A278 6 250 325 170 170 0.5

3-011 3A312 6 250 350 160 160 0.5

3-003 3A269 6 250 280 150 150 0.5

3-001 3A265 6 200 380 100 100 0.5

3-005 3A272 6 250 325 170 170 0.5

2-079 2A459 4 150 225 80 80 0.5

2-075 2A338 10 860 860 760 760 1.1

2-074 2A338A 6 210 210 210 210 0.5

2-073 2A310 10 1220 1220 260 260 0.5

2-072 2A321 6 400 400 170 170 0.5

2-076 2A450A 6 250 325 160 160 0.5

2-137 2A512 6 300 300 300 300 0.5

2-168 2A019 10 1250 1250 340 340 0.5

2-166 2A018 8 590 590 0 - -

2-153 2A121 6 300 310 300 300 0.6

2-151 2A069 6 440 440 440 440 0.6

2-147 2A115 6 250 250 250 250 0.5

2-146 2A063 8 570 570 440 440 0.6

2-141 2A008 6 400 400 400 400 0.6

2-139 2A501 8 570 570 450 450 0.6

2-138 2A553 6 360 360 250 250 0.5

2-136 2A562 8 500 500 420 420 0.6

2-134 2A444 8 520 520 350 350 0.5

2-132 2A445 6 360 360 260 260 0.5

2-123 2A342 6 340 340 100 100 0.5

2-121 2A301 4 200 200 140 140 0.5

2-119 2A308 10 1155 1155 560 560 0.8

2-118 2A314 8 675 675 675 675 1.0

2-116 2A319 6 330 330 130 130 0.5

2-115 2A317 6 330 330 130 130 0.5

2-114 2A315 6 250 250 130 130 0.5

2-113 2A313 6 330 330 140 140 0.5

2-112 2A311 6 330 330 140 140 0.5

2-111 2A310A 8 750 750 210 210 0.5

2-105 2A074 12 1800 1800 1100 1100 2.1

2-104 2A074A 12 1700 1700 1100 1100 2.1

2-097 2A184 8 600 600 100 100 0.5

2-094 2A197 8 475 475 475 475 1.1

2-086 2A011 6 385 385 385 385 0.6

2-085 2A509 10 1100 1100 700 700 1.5

2-084 2A556 10 1250 1250 700 700 1.5

2-083 2A521 6 260 260 160 160 0.5

2-082 2A446 6 250 250 150 150 0.5

2-154 2A111 6 250 300 250 250 0.5

2-152 2A073 8 515 750 515 515 0.7

2-162 2A179 6 450 575 350 350 0.5

2-135 2A517 6 340 500 340 340 0.5

2-120 2A303 6 310 350 350 350 0.5

2-145 2A036 6 275 450 275 275 0.5

2-101 2A146 8 550 675 120 120 0.5

2-099 2A188 6 350 375 90 90 0.5

2-117 2A318 6 280 450 280 280 0.5

2-095 2A201 4 100 225 100 100 0.5

2-081 2A463 6 300 425 120 120 0.5

*2-096 2A199 16 3220 3220 500 500 0.7

1-156 1A016 6 300 300 200 200 0.5

1-160 1A007 8 600 600 200 200 0.5

1-188 1A004 8 800 800 600 600 0.9

1-183 1A063 6 380 380 220 220 0.5

1-179 1A006 14 2040 2040 2040 2040 2.9

1-178 1A070 16 3000 3000 1000 1000 2.0

1-175 1A001 10 900 900 400 400 0.8

1-173 1A005 14 2400 2400 600 600 1.2

1-170 1A078 6 280 280 280 280 0.5

1-159 1A008 6 800 800 800 800 0.6

1-157 1A010 4 280 280 100 100 0.5

1-169 1A077 14 2300 2300 800 800 1.2

1-168 1A076 10 1100 1100 400 400 0.6

1-167 1A075 10 900 900 400 400 0.6

1-184 2A189 6 300 400 200 200 0.5

1-172 1A040 6 310 500 310 310 0.5

1-171 1A080 6 320 400 200 200 0.5

1-131 1A150 10 1300 1300 1300 1300 1.9

1-121 1A154 10 900 750 350 350 0.5

1-145 1A135 6 400 450 300 300 1.2

1-125 1A175 6 400 475 300 300 0.5

1-120 1A155 6 450 510 300 300 0.5

1-140 1A030 6 440 550 230 230 0.5

1-108 1A028 10 920 1125 600 600 0.9

1-099 1A322 4 160 200 100 100 0.5

1-115 1A180 8 500 610 300 300 0.5

1-078 1A306 8 610 700 610 610 1.2

1-072 1A253 6 360 550 230 230 0.5

1-092 1A201 6 300 400 200 200 0.5

1-071 1A276 6 400 550 300 300 0.5

EXISTING

MARK

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

SPACE

SERVED

EXISTING

MARK

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

SPACE

SERVED

EXISTING

MARK

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

SPACE

SERVED

EXISTING

MARK

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

SPACE

SERVED

EXISTING

MARK

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

SPACE

SERVED

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

VAV TERMINAL SCHEDULE GENERAL NOTES:

1. ALL VAVs ARE EXISTING TO REMAIN. THE SCHEDULES ON THIS SHEET ARE FOR BALANCING SCOPE

ONLY.

2. ALL TEXT SHOWN AS LIGHT GRAY IS REFERENCE INFORMATION ONLY.

3. VAV REHEAT IS BASED ON 200 DEG F SUPPLY WATER.

4. VAV REHEAT LEAVING AIR TEMPERATURES ARE BASED ON ORIGINAL VAV DESIGN SCHEDULES.

NEW COIL

FLOW

(GPM)

LEAVING

AIR TEMP.

(DEG F)

LEAVING

AIR TEMP.

(DEG F)

LEAVING

AIR TEMP.

(DEG F)

LEAVING

AIR TEMP.

(DEG F)

LEAVING

AIR TEMP.

(DEG F)

1-143 1A135 6 440 440 300 300 1.2 75

1-144 1A134 6 420 500 300 300 0.5 75

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

BID AND CONSTRUCTION

Project Number

Building Number

Drawing Number

CHALMERS P. WYLIE VAACC

CORRECT RETRO COMMISSIONING

DEFICIENCIES

Project Title

Location

Issued Date Checked Drawn

Drawing Title

Approved: Farid F. Mehr, P.E.

Chief, Engineering Service

Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

/1

/2

:3

:4 A

M C

R e v it L o c a l\

R

V A

C o lu m b u s C o rr e c t

R e tr o

C X

C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m

.r v t

757-20-101 dad sic04/14/21

420 N. JAMES ROAD, COLUMBUS, OH 43219

Revisions Date

BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696

BROADVIEW HTS., OHIO 44147

672 EAST ROYALTON ROAD

FAX. (440) 546-9699

Mechanical Schedules

MH-0B1-65042

ER

H

F OO

IO

AVID A.

MAGALL

-65042

ER

H

F OO

IO

AVID A.

MAGALL

-65042

ER

H

F OO

IO

EXISTING

MARK

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

SPACE

SERVED

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

RTU-5 VAV TERMINAL SCHEDULE

SERVES 4TH FLOOR

RTU-5 VAV TERMINAL SCHEDULE CONT'D

SERVES 4TH FLOOR

RTU-7 VAV TERMINAL SCHEDULE

SERVES 1ST FLOOR - EAST

RTU-8 VAV TERMINAL SCHEDULE

SERVES 1ST FLOOR - EAST

RTU-10 VAV TERMINAL SCHEDULE

SERVES 2ND FLOOR - EAST

RTU-11 VAV TERMINAL SCHEDULE

SERVES 2ND FLOOR EAST

4-001 4A013 12 1550 1550 1550 1550 3.0

4-023 4A04 6 275 275 110 110 0.5

4-022 4A076 6 275 275 110 110 0.5

4-021 4A038 6 235 235 110 110 0.5

4-020 4A071A 8 575 500 350 350 0.5

4-019 4A063 8 490 490 490 490 0.71

4-018 4A348 6 180 300 110 110 0.5

4-017 4A327 4 180 180 180 180 0.5

4-016 4A329 10 665 665 270 270 0.9

4-015 4A347 6 210 250 110 110 0.5

4-014 4A344 6 300 300 110 110 0.5

4-013 4A320 12 1400 1400 1000 1000 1.44

4-012 4A063 8 520 400 400 400 0.75

4-011 4A060 12 1800 1800 1575 1575 2.3

4-010 4A343 4 160 180 80 80 0.5

4-009 4A309 10 400 400 400 400 0.75

4-008 4A342 6 220 220 110 110 0.5

4-007 4A305 6 230 230 230 230 0.5

4-006 4A020 10 645 950 260 260 2.6

4-004 4A250 12 1010 1050 1010 1010 2.2

4-002 4A008 8 550 500 200 200 0.5

4-025 4A039 4 170 325 80 80 0.5

4-024 4A072 4 190 325 90 90 0.5

4-003 4A007 14 2400 2400 600 1000 2.5

4-005 4A021 10 800 1180 800 800 1.6

TB2-4 4A258 8 405 405 170 170 1.0

TB2-3 4A261 8 475 425 200 200 1.0

TB2-2 4A307 8 350 360 140 140 1.0

TB2-1 4A340 8 470 450 200 200 1.0

TB1-7 4A255 6 250 200 120 120 0.5

TB1-6 4A253 6 270 270 110 110 0.5

TB1-5 4A251 6 165 250 80 80 0.5

TB1-4 4A301 6 230 300 110 110 0.5

TB1-3 4A324 6 290 290 120 120 0.5

TB1-2 4A326 6 305 300 130 130 0.5

TB1-1 4A306 6 230 230 230 230 0.5

4-063 4A041 8 500 500 0 - -

4-062 4A012 4 200 200 0 - -

4-061 4A201 14 2375 5040 800 800 1.15

4-060 4A006 8 660 675 410 410 0.57

4-059 4A215 4 260 260 110 110 0.5

4-058 4A213 6 260 260 110 110 0.5

4-054 4A207 6 220 230 110 110 0.5

4-053 4A209 6 300 300 110 110 0.5

4-052 4A078 4 140 140 70 70 0.5

4-051 4A080 6 230 230 110 110 0.5

4-050 4A082 6 230 230 110 110 0.5

4-048 4A132 4 190 225 70 70 0.5

4-047 4A131 6 210 210 110 110 0.5

4-046 4A130 4 140 160 70 70 0.5

4-045 4A129 6 320 320 180 180 0.5

4-044 4A128 6 420 420 130 130 0.5

4-042 4A084 6 250 250 110 110 0.5

4-040 4A140 8 600 600 440 440 0.6

4-039 4A127 4 200 210 110 110 0.5

4-038 4A061 8 490 550 550 550 1.0

4-036 4A126 6 260 260 110 110 0.5

4-035 4A101 8 700 700 700 700 1.0

4-034 4A125 8 420 420 200 200 0.5

4-026 4A090A 14 1000 1000 500 500 1.1

4-057 4A210 10 1200 1100 550 550 0.8

4-056 4A206 8 700 800 700 700 1.0

4-049 4A133 4 140 225 70 70 0.5

4-043 4A081 8 620 700 620 620 1.0

4-055 4A205 4 170 325 90 90 0.5

4-037 4A139 8 680 825 500 500 0.7

4-041 4A136 6 220 325 150 150 0.5

4-032 4A118 6 410 520 410 410 0.6

4-031 4A117 8 470 575 200 300 0.75

4-033 4A113 8 630 820 570 570 0.8

4-029 4A110 8 650 1010 650 650 1.0

4-028 4A115 4 175 250 70 70 0.5

4-030 4A201A 6 300 500 150 150 0.5

4-027 4A116 6 330 410 110 110 0.5

EXISTING

MARK

EXISTING

SPACE

SERVED

1-030 1B086 6 270 270 270 270 0.5

1-024 1B112 10 850 850 850 850 1.2

1-006 1B116 8 540 700 400 400 0.6

2-031 2B229 8 500 500 500 500 0.7

2-028 2B240 8 570 570 570 570 0.8

2-026 2B240D 10 820 820 270 270 0.5

2-025 2B240A 10 870 870 400 400 0.6

2-043 2B132 8 500 500 500 500 0.7

2-042 2B136 8 500 500 500 500 0.7

2-040 2B138 8 500 500 500 500 0.7

2-037 2B144 8 530 530 530 530 0.8

2-034 2B230 6 370 390 370 370 0.5

V11-18 2B137 5 100 100 100 100 0.6

V11-5 2B143 7 430 430 430 430 0.6

V11-6 2B141A 6 370 490 370 370 0.6

EXISTING

MARK

EXISTING

SPACE

SERVED

EXISTING

MARK

EXISTING

SPACE

SERVED

EXISTING

MARK

EXISTING

SPACE

SERVED

EXISTING

MARK

EXISTING

SPACE

SERVED

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

VAV TERMINAL SCHEDULE GENERAL NOTES:

1. ALL VAVs ARE EXISTING TO REMAIN. THE SCHEDULES ON THIS SHEET ARE FOR BALANCING SCOPE

ONLY.

2. ALL TEXT SHOWN AS LIGHT GRAY IS REFERENCE INFORMATION ONLY.

3. VAV REHEAT IS BASED ON 200 DEG F SUPPLY WATER.

4. VAV REHEAT LEAVING AIR TEMPERATURES ARE BASED ON ORIGINAL VAV DESIGN SCHEDULES.

LEAVING

AIR TEMP.

(DEG F)

81.5

LEAVING

AIR TEMP.

(DEG F)

TB4-1 4A090B 12 1000 1000 450 450 1.3

LEAVING

AIR TEMP.

(DEG F)

LEAVING

AIR TEMP.

(DEG F)

LEAVING

AIR TEMP.

(DEG F)

EXISTING

MAX.

AIRFLOW

(CFM)

EXISTING

TERMINAL

SIZE

RTU-9 VAV TERMINAL SCHEDULE

SERVES 2ND FLOOR - EAST

2-062 2B056 8 800 850 560 560 0.8

2-066 2B115 8 600 600 360 360 0.5

2-059 2B051 8 700 900 700 700 1.0

2-058 2B053 6 350 520 150 150 0.5

2-065 2B071 6 300 350 120 120 0.5

2-057 2B051 8 400 900 700 700 0.5

EXISTING

MARK

EXISTING

SPACE

SERVED

NEW MIN.

AIRFLOW

(CFM)

NEW COIL

FLOW

(GPM)

NEW

HEATING

AIRFLOW

(CFM)

NEW MAX.

AIRFLOW

(CFM)

LEAVING

AIR TEMP.

(DEG F)

2-061 2B061 8 520 520 360 360 0.5 75

2-067 2B073 8 750 660 380 380 0.5 75

LEAVING

AIR TEMP.

(DEG F)

92.3

91.6

NEW VAV TERMINAL SCHEDULE

MARK

MAX.

AIRFLOW

(CFM)

MIN.

AIRFLOW

(CFM)

CAPACITY

(MBH)

COIL FLOW

(GPM)

ENTERING/

LEAVING AIR

TEMP. (F°)

AIR PRESS.

DROP (IN W.G.)

(NOTE 2)

WATER PRESS.

DROP (FT)

(NOTE 3)

NUMBER OF

ROWS

HEATING COIL PERFORMANCE

TERMINAL

SIZE

HEATING

AIRFLOW

PIPE SIZE

(IN)

(NOTE 4)

NOTES:

NOTE 1: BASIS OF SPECIFICATION IS TITUS DESV. TERMINALS SHALL BE CAPABLE OF OPERATING WITH A MINIMUM INLET PRESSURE OF 0.5" W.G. FURNISH WITH AIR

FLOW SWITCH, AND ACTUATOR. PROVIDE WITH SCREW ACCESS (UN-HINGED) WHERE TERMINALS ARE INSTALLED IN THE BEAM/JOIST SPACE. BOXES SHALL

BE INSULATED WITH: FIBRE-FREE.

NOTE 2: MAXIMUM AIR PRESSURE DROP SHALL BE 0.3" W.G.

NOTE 3: MAXIMUM WATER PRESSURE DROP SHALL BE 5 FEET.

NOTE 4: MINIMUM PIPE SIZE SHALL BE 3/4". SEE REHEAT COIL PIPING DIAGRAM FOR COIL PIPING.

1-020 14"Ø 1670 300 600 14.5 0.5 55/77 0.11 0.02 1 3/4"

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

BID AND CONSTRUCTION

Project Number

Building Number

Drawing Number

CHALMERS P. WYLIE VAACC

CORRECT RETRO COMMISSIONING

DEFICIENCIES

Project Title

Location

Issued Date Checked Drawn

Drawing Title

Approved: Farid F. Mehr, P.E.

Chief, Engineering Service

Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

/1

/2

:3

:4 A

M C

R e v it L o c a l\

R

V A

C o lu m b u s C o rr e c t

R e tr o

C X

C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m

.r v t

757-20-101 dad sic04/14/21

420 N. JAMES ROAD, COLUMBUS, OH 43219

Revisions Date

BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696

BROADVIEW HTS., OHIO 44147

672 EAST ROYALTON ROAD

FAX. (440) 546-9699

Mechanical Schedules

MH-0C1-65042

ER

H

F OO

IO

AVID A.

MAGALL

-65042

ER

H

F OO

IO

AVID A.

MAGALL

-65042

ER

H

F OO

IO

FAN CONTROL:

THE SUPPLY FAN (SF-C) AND RETURN FAN (RF-C) SHALL RUN CONTINUOUSLY. THE SUPPLY FAN

OUTPUT (SF-O) WILL MODULATE TO MAINTAIN THE DISCHARGE AIR STATIC PRESSURE SETPOINT

(DAP-SP). THE RETURN FAN OUTPUT (RF-O) WILL MODULATE TO MAINTAIN THE DESIRED RETURN FAN

OFFSET (%-OFFSET).

DISCHARGE AIR PRESSURE SETPOINT DETERMINATION:

THE DISCHARGE AIR PRESSURE SETPOINT (DAP-SPT) SHALL BE CONTINUOUSLY RESET BY POLLING

THE VAV BOX DAMPERS THAT ARE ASSOCIATED WITH THE RTU. IF ANY DAMPER IS OPEN GREATER

THAN 95% FOR LONGER THAN 10 MINUTES, DAP-SP WILL INCREASE BY 0.05” UNTIL NO DAMPER IS

ABOVE 95% OPEN OR UNTIL THE HIGH LIMIT SETPOINT IS REACHED. IF ALL ASSOCIATED DAMPERS ARE

LESS THAN 80% OPEN FOR LONGER THAN 10 MINUTES, DAP-SP WILL DECREASE BY 0.05” UNTIL AT

LEAST 1 DAMPER IS OPEN MORE THAN 80% OR THE LOW LIMIT SETPOINT HAS BEEN REACHED. THE

DAP-SP SHALL BE THE DEFAULT UPON STARTUP/RESTART, UNTIL THE SYSTEM HAS ATTAINED NORMAL

CONTROL.

DISCHARGE AIR TEMP SETPOINT DETERMINATION:

THE DISCHARGE AIR TEMP SETPOINT (DAT-SP) SHALL BE DETERMINED VIA RESET LOGIC BASED ON

THE RETURN AIR TEMP (RA-T). THE RETURN AIR MAXIMUM (RAT-MAX-SP) AND THE RETURN AIR

MINIMUM (RAT-MIN-SP) SET THE RANGE OF THE RESET, WHILE THE DISCHARGE AIR TEMP MAXIMUM

(DAT-MAX-SP) AND THE DISCHARGE AIR TEMP MINIMUM (DAT-MIN-SP) SET THE LIMITS ON THE ON THE

DAT-SP.

ECONOMIZER AVAILABILITY DETERMINATION:

THE ECONOMIZER FREE COOLING SHALL BE AVAILABLE WHENEVER THE RTU IS RUNNING, THE

OUTDOOR AIR ENTHALPY (OA-E) IS LESS THAN THE RETURN AIR ENTHALPY (RA-E), THE OUTDOOR AIR

TEMP (OA-T) IS LESS THAN THE EFFDAT-SP MINUS THE ECON/DAT SEPT DIFFERENTIAL

(ECONDATSPTDIFF), THE OA-T IS GREATER THAN THE ECON LOW OAT DISABLE

(LOWOATDISABLESETPT) AND THE RETURN AIR HUMIDITY IS GREATER THAN THE RETURN AIR

HUMIDITY ECON LOCKOUT (RETURNAIRHUMIDITYECONLOCKOUT).

OUTDOOR AIR DAMPER MINIMUM POSITION DETERMINATION:

THE OUTDOOR AIR DAMPER MINIMUM POSITION (MAD-MINPOS) SHALL BE DETERMINED IN ONE OF 3

WAYS. IF THE OA-T IS LESS THAN THE MINDAMPERLOWOATSETPT, THEN THE MAD-MINPOS SHALL BE

DETERMINED BY THE FOLLOWING EQUATION: (RA-T)-(MA-T)/(RA-T)-(OA-T)X100. IF THE RETURN AIR CO2

(RA-CO2) RISES ABOVE THE MINIMUM CO2 RESET SETPT (MOA-CO2RSTA), THEN THE MAD-MINPOS

WILL RESET UP TO THE MINIMUM POSITION HIGH SETPT (MIN POS HIGH SETPOINT). IF NEITHER OF THE

ABOVE SCENARIOS ARE ACTIVE, THE MAD-MINPOS SHALL BE THE VALUE OF THE OA DAMPER MIN

POSITION SETPOINT (OAD-MINPOS).

DAMPER CONTROL:

THE OUTDOOR AIR DAMPER (OA-D), RETURN AIR DAMPER (RA-D), AND EXHAUST AIR DAMPER (EA-D)

SHALL MODULATE IN UNISON WITH THE OA & EA DAMPERS OPPOSING THE RETURN DAMPER. IF

ECONOMIZER IS AVAILABLE, THE DAMPERS WILL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMP

(DA-T) AT THE DISCHARGE AIR TEMP SETPOINT (DAT-SPT). IF THE ECONOMIZER MODE IS NOT

AVAILABLE, THE DAMPERS WILL MODULATE TO MAINTAIN THE OUTDOOR AIR DAMPER MINIMUM

POSITION (MAD-MINPOS). SHOULD THE PREHEAT TEMP (PH-T) FALL BELOW THE LOW LIMIT SETPOINT

MINUS 3 DEGREES (LT-SP – 3 DEGREES), THE DAMPERS WILL MODULATE IN AN ATTEMPT TO PREVENT

A LOW TEMP ALARM.

HEATING VALVE AND PUMP CONTROL:

THE PREHEAT PUMP (PHP-C) SHALL BE ENABLED ANYTIME THE OA-T IS BELOW THE OALT-SP. WHEN

ENABLED, THE PREHEAT VALVE OUTPUT (PH-O) SHALL MODULATE TO MAINTAIN THE DA-T AT THE

DAT-SP. IT WILL ALSO MODULATE OPEN TO MAINTAIN THE PREHEAT TEMP (PH-T) AT THE LOW LIMIT

SETPOINT (LT-SP). THE PH-O SHALL MODULATE TO 100% IN THE EVENT OF A LOW TEMPERATURE

ALARM (LT-A).

COOLING VALVE CONTROL:

WHEN ENABLED BY THE CHILLED WATER SYSTEM, THE COOLING VALVE OUTPUT (CLG-O) WILL

MODULATE TO MAINTAIN THE DA-T AT THE DAT-SP.

EXISTING SEQUENCES OF

OPERATION FOR RTUs 1 THRU 7 & 9

NOTES:

A. BOLD TEXT WITH A STRIKE-THROUGH WITHIN THE SEQUENCE OF OPERATIONS INDICATES A

REVISION. ALL ITEMS IN LIGHT INK ARE EXISTING TO REMAIN.

REVISED SEQUENCES OF OPERATION

FOR RTUs 1 THRU 7 & 9

FAN CONTROL:

THE SUPPLY FAN (SF-C) AND RETURN FAN (RF-C) SHALL RUN CONTINUOUSLY. THE SUPPLY FAN

OUTPUT (SF-O) WILL MODULATE TO MAINTAIN THE DISCHARGE AIR STATIC PRESSURE SETPOINT

(DAP-SP). THE RETURN FAN OUTPUT (RF-O) WILL MODULATE TO MAINTAIN THE DESIRED RETURN FAN

OFFSET (%-OFFSET).

DISCHARGE AIR PRESSURE SETPOINT DETERMINATION:

THE DISCHARGE AIR PRESSURE SETPOINT (DAP-SPT) SHALL BE CONTINUOUSLY RESET BY POLLING

THE VAV BOX DAMPERS THAT ARE ASSOCIATED WITH THE RTU. IF ANY DAMPER IS OPEN GREATER

THAN 95% FOR LONGER THAN 10 MINUTES, DAP-SP WILL INCREASE BY 0.05” UNTIL NO DAMPER IS

ABOVE 95% OPEN OR UNTIL THE HIGH LIMIT SETPOINT IS REACHED. IF ALL ASSOCIATED DAMPERS ARE

LESS THAN 80% OPEN FOR LONGER THAN 10 MINUTES, DAP-SP WILL DECREASE BY 0.05” UNTIL AT

LEAST 1 DAMPER IS OPEN MORE THAN 80% OR THE LOW LIMIT SETPOINT HAS BEEN REACHED. THE

DAP-SP SHALL BE THE DEFAULT UPON STARTUP/RESTART, UNTIL THE SYSTEM HAS ATTAINED NORMAL

CONTROL.

DISCHARGE AIR TEMP SETPOINT DETERMINATION:

THE DISCHARGE AIR TEMP SETPOINT (DAT-SP) SHALL BE DETERMINED VIA RESET LOGIC BASED ON

THE RETURN AIR TEMP (RA-T). THE RETURN AIR MAXIMUM (RAT-MAX-SP) AND THE RETURN AIR

MINIMUM (RAT-MIN-SP) SET THE RANGE OF THE RESET, WHILE THE DISCHARGE AIR TEMP MAXIMUM

(DAT-MAX-SP) AND THE DISCHARGE AIR TEMP MINIMUM (DAT-MIN-SP) SET THE LIMITS ON THE ON THE

DAT-SP.

ECONOMIZER AVAILABILITY DETERMINATION:

THE ECONOMIZER FREE COOLING SHALL BE AVAILABLE WHENEVER THE RTU IS RUNNING, THE

OUTDOOR AIR TEMP (OA-T) IS LESS THAN 65 DEG F, THE OA-T IS GREATER THAN THE ECON LOW OAT

DISABLE (LOWOATDISABLESETPT) AND THE RETURN AIR HUMIDITY IS GREATER THAN THE RETURN AIR

HUMIDITY ECON LOCKOUT (RETURNAIRHUMIDITYECONLOCKOUT).

OUTDOOR AIR DAMPER MINIMUM POSITION DETERMINATION:

THE OUTDOOR AIR DAMPER MINIMUM POSITION DETERMINATION SHALL BE USED WHEN AHU

ECONOMIZER FREE COOLING IS NOT AVAILABLE.

THE OUTDOOR AIR DAMPER MINIMUM POSITION (MAD-MINPOS) SHALL BE DETERMINED BY THE

FOLLOWING:

- IF THE OAT < (RAT- 5 DEG F) OR OAT > (RAT+ 5 DEG F), THE OUTDOOR AIR DAMPER SHALL

MODULATE TO MAKE THE FOLLOWING EQUATION, [(RAT-MAT)/(RAT-OAT)] x 100, EQUAL TO THE

MINIMUM OUTDOOR AIR PERCENTAGE OF THE RTU.

- IF (RAT - 5 DEG F) < OAT < (RAT + 5 DEG F), THE OUTDOOR AIR DAMPER POSITION SHALL BE AT

ITS FIXED MINIMUM POSITION DETERMINED BY THE BALANCER AT 100% AIRFLOW CONDITION.

- IF THE RETURN AIR CO2 (RA-CO2) RISES ABOVE THE MINIMUM CO2 RESET SETPT

(MOA-CO2RSTA), THEN THE MAD-MINPOS WILL RESET UP TO THE MINIMUM POSITION HIGH SETPT

(MIN POS HIGH SETPOINT). THIS HIGH SETPOINT SHALL BE 10% GREATER THAN THE MINIMUM

OUTDOOR AIR PERCENTAGE OF THE RTU.

DAMPER CONTROL:

THE OUTDOOR AIR DAMPER (OA-D), RETURN AIR DAMPER (RA-D), AND EXHAUST AIR DAMPER (EA-D)

SHALL MODULATE IN UNISON WITH THE OA & EA DAMPERS OPPOSING THE RETURN DAMPER. IF

ECONOMIZER IS AVAILABLE, THE DAMPERS WILL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMP

(DA-T) AT THE DISCHARGE AIR TEMP SETPOINT (DAT-SPT). IF THE ECONOMIZER MODE IS NOT

AVAILABLE, THE DAMPERS WILL MODULATE TO MAINTAIN THE OUTDOOR AIR DAMPER MINIMUM

POSITION (MAD-MINPOS). SHOULD THE PREHEAT TEMP (PH-T) FALL BELOW THE LOW LIMIT SETPOINT

MINUS 3 DEGREES (LT-SP – 3 DEGREES), THE DAMPERS WILL MODULATE IN AN ATTEMPT TO PREVENT

A LOW TEMP ALARM.

HEATING VALVE AND PUMP CONTROL:

THE PREHEAT PUMP (PHP-C) SHALL BE ENABLED ANYTIME THE OA-T IS BELOW THE OALT-SP. WHEN

ENABLED, THE PREHEAT VALVE OUTPUT (PH-O) SHALL MODULATE TO MAINTAIN THE DA-T AT THE

DAT-SP. IT WILL ALSO MODULATE OPEN TO MAINTAIN THE PREHEAT TEMP (PH-T) AT THE LOW LIMIT

SETPOINT (LT-SP). THE PH-O SHALL MODULATE TO 100% IN THE EVENT OF A LOW TEMPERATURE

ALARM (LT-A).

COOLING VALVE CONTROL:

WHEN ENABLED BY THE CHILLED WATER SYSTEM, THE COOLING VALVE OUTPUT (CLG-O) WILL

MODULATE TO MAINTAIN THE DA-T AT THE DAT-SP.

NOTES:

A. BOLD TEXT WITHIN THE SEQUENCE OF OPERATIONS INDICATES A REVISION. ALL ITEMS IN LIGHT INK

ARE EXISTING TO REMAIN.

DISCHARGE AIR PRESSURE SETPOINT (DEFAULT)

DISCHARGE AIR MAXIMUM SETPOINT

DISCHARGE AIR MINIMUM SETPOINT

RETURN FAN OFFSET

RETURN AIR TEMP MAXIMUM SETPOINT

RETURN AIR TEMP MINIMUM SETPOINT

DISCHARGE AIR TEMP MAXIMUM SETPOINT

DISCHARGE AIR TEMP MINIMUM SETPOINT

ECON/DAT SEPT DIFFERENTIAL

ECON LOW OAT DISABLE SETPOINT

RETURN AIR HUMIDITY ECON LOCKOUT

MINIMUM DAMPER LOW OAT SETPOINT

MINIMUM OUTSIDE AIR VENTILATION (%)

MINIMUM CO2 RESET SETPOINT

MINIMUM POSITION HIGH SETPOINT (%)

OA DAMPER MIN POSITION SETPOINT (%)

PREHEAT LOW LIMIT SETPOINT

DAP-SP

DAP-MAX-SP

DAP-MIN-SP

% OFFSET

RAT-MAX-SP

RAT-MIN-SP

DAT-MAX-SP

DAT-MIN-SP

ECON-DAT-SP-DIFF

OATLOW-DISABLE

NOT MAPPED TO METASYS

OAD-MINPOS

OABLEND%-SPT

MOA-CO2RSTA

MOA-CO2RSTB

OAD-MINPOS

LT-SP

1"

1.5"

0.5"

20%

-5

DESCRIPTION ABBREVIATION VALUE

CURRENT SET-POINTSSUPPLY VAV BOX W/ REHEAT CONTROLS 1

NOT TO SCALE

CONTROL DIAGRAM

SEQUENCE OF OPERATION FOR VARIABLE

VOLUME REHEAT COIL

RUN CONDITIONS:

A. COOLING MODE:

1. SPACE THERMOSTAT SHALL MODULATE VAV BOX DAMPER TO

MAINTAIN SETPOINT.

B. HEATING MODE:

1. VAV BOX DAMPER SHALL CLOSE TO HEATING AIRFLOW POSITION.

2. SPACE THERMOSTAT SHALL MODULATE HOT WATER VALVE TO

MAINTAIN SETPOINT.

T

C O

IL

R

E H

E A

T

X-SUPPLY AIR DUCT

UNITARY

CONTROLLER

XFORMER

SUPPLY AIR

NOT TO SCALE

T

E

C. BAS SHALL MONITOR AND DISPLAY THE FOLLOWING:

1. TEMPERATURE SETPOINT

2. ROOM TEMPERATURE

3. AIR FLOW (CFM)

4. DAMPER POSITION

5. VALVE POSITION

6. DISCHARGE TEMPERATURE

DISCHARGE

TEMPERATURE

SENSORAIRFLOW

SENSOR

REHEAT

CONTROL

VALVE

DDC THERMOSTAT

WITH REMOTE SENSOR 120V/24AC

TRANSFORMER

BY T.C.

LOW VOLTAGE

WIRING BY T.C.

COMMUNICATION

BUS TO OTHER

CONTROLLERS

GENERAL TEMPERATURE CONTROLS NOTES:

1. TEMPERATURE CONTROLS SHALL BE JOHNSON CONTROLS (JCI). ALL CONTROLS WORK SHALL INTERFACE

WITH EXISTING JCI BUILDING CONTROL SYSTEM.

2. ONLY TECHNICIANS SPECIFICALLY TRAINED, LICENSED, AND AUTHORIZED TO WORK ON JCI CONTROLS

SHALL BE ALLOWED TO ACCESS THE EXISTING BUILDING CONTROL SYSTEM FOR THE PURPOSE OF

COMPLETING WORK REQUIRED UNDER THIS CONTRACT.

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

BID AND CONSTRUCTION

Project Number

Building Number

Drawing Number

CHALMERS P. WYLIE VAACC

CORRECT RETRO COMMISSIONING

DEFICIENCIES

Project Title

Location

Issued Date Checked Drawn

Drawing Title

Approved: Farid F. Mehr, P.E.

Chief, Engineering Service

Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

/1

/2

:3

:4 A

M C

R e v it L o c a l\

R

V A

C o lu m b u s C o rr e c t

R e tr o

C X

C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m

.r v t

757-20-101 dad sic04/14/21

420 N. JAMES ROAD, COLUMBUS, OH 43219

Revisions Date

BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696

BROADVIEW HTS., OHIO 44147

672 EAST ROYALTON ROAD

FAX. (440) 546-9699

HVAC - RTU Sequences of

Operation Revisions

MH-0D

jwf

UP

Phys.Office

1A326

Phys.Office

1A324

MSA

Reception

1A306

Entry

1A300 Reception

1A303 CRC Office

1A211

EXAM

1A213

EXAM

1A215 Office

1A217

Mechanical Room

1A350

Fire Pump Room

1A351

Electrical Room

1A360

Office

1A332

Counsel Office

1A325

Counsel Office

1A323

Counsel Office

1A321

Counsel Office

1A319 Counsel Office

1A317 Consult

1A315

Exam

1A313 Quiet

1A311

Sub-Waiting

1A308 Waiting

1A302

Public Toilet

1A304

Public Toilet

1A305

PROCEDURE

1A212

Corridor

1A310

Corridor

1A301 Corridor

1A209

DIAB EDUC

1A214

EXAM

1A219

EXAM

1A221

Corridor

1A208

Exam

1A223

Office

1A225

Triage

1A227

Triage

1A229

Corridor

1A207

CONF

1A205

Corridor

1A200

Chief Office

1A262

Corridor

1A250

Counsel Office

1A281

Counsel Office

1A282

Counsel Office

1A283

Counsel Office

1A284

Corridor

1A280

Counsel Office

1A285

Counsel Office

1A287

Counsel Office

1A289

DTC Office

1A291

Corridor

1A330 Office

1A333

Office

1A334

Elec

1A455

Group

1A561

Stair No. 1

1S001

Vestibule

1A023

DTC Office

1A292

HAC

1A331

DTC Office

1A290

BFB Tech Office

1A288

Biofeedback Treatment

Room

1A286

ADL Toilet

1A028A

Staff Toilet

1A279

Rehab Counsel

1A277

Corridor

1A270

SW Office

1A278

Nurse/Pharm.

1A261

Connected Care

1A260

Resident

1A259

Connected Care

1A258 Reception

1A203

Work Area

1A204

Exam

1A226

Corridor

1A206

Connected Care

1A256

Connected Care

1A254

Connected Care

1A252

Patient Toilet

1A257

Patient Toilet

1A255

Connected Care

1A253

Connected Care

1A251

SWS Office

1A272

Connected Care

1A274

Connected Care

1A276 Rehab

Counsel

1A275

Rehab Counsel

1A273

Psych. Office

1A271

Shower

1A028B

Storage

1A028C ADL Kitchen

1A028D

PRRC/Basic Space

1A028

Telecommunications

1A024

Electrical Room

1A025

Corridor

1A026

Elevator Lobby

1A007

Corridor

1A022

Corridor

1A159

Attorney

1A190B

Attorney

1A190

Attorney

1A190A

Office

1A191

Intern Office

1A181

Toilet Room

1A158

Office

1A157

Break Out Space

1A155A

Staff Work Area

1A155

Office

1A155B

Office

1A155C

Storage/ Media Center

1A156 Multi. Room

1A176

Chief Office 1A177

Waiting/Admin.

1A175

Office

1A178

PBS Chief

1A172 Vet Trans Service

1A171

Storage

1A175A

Entry

1A150

Sub-Waiting

1A122

OEF/OIF

Social Work

CM

1A120 OEF/OIF RN

CM

1A118

Office

1A114

Corridor

1A107

Corridor

1A151

Employee Health

1A123

Employee Health Exam

1A121

OEF/OIF

Nurse

Check-in

1A119

OEF/OIF

Phys/RN

Office

1A143

OEF/OIF

Physician

Office

1A141

Enrollment Exam

1A139

Corridor

1A108

OEF/OIF

Exam

1A144

OEF/OIF

Exam

1A142

OEF/OIF

Exam

1A140

OEF/OIF

Exam

1A138

Enrollment Nurse

1A136

Police

1A134

HAC

1A152

Education Equipment

1A154A

Kitchen

1A154

Toilet Room

1A153

R.O.I. Work

1A180 Library/ Education

1A165B Circulation

1A165A

Learning Exchange

Center

1A165C

Staff Work Area

1A165D

Corridor

1A021

Business Center

1A164 Training

1A161

Work Room

1A163

A.C.P. Super

1A132 Police Chief

1A102A

Police Administration

1A102

OEF/OIF LPN

1A130 Corridor

1A109

Police Office 1A137

Mental Health

1A117

Screen

1A135

LGBT

1A115

Voluntary Check In

1A101

Tricare 1A111

Enrollment

ID

1A131

Toilet Room

1A108A

Stair No. 3

1S003

EKG/Lab

1A112

Office (VIC)

1A110

Telecommunications

1A106

Arms Room

1A033A Evidence

Room

1A033

Eletrical Room

1A105

Hold

1A032

Toilet Room

1A104

Enrollment

1A103

Police Office

1A031

Operation/Control Room

1A030

Public Toilet

1A008

Toilet Room

1A010

Mechanical Room

1A009 HVAC Control

Room

1A340

Emergency Electrical

Distribution

1A013

Telecommunications

1A014

Electrical Rm 1A015

Stair No. 2

1S002 Vestibule

1A016

Corridor

1A012

Service Elevator Lobby

1A011

Corridor

1A017

Perc

1A072

Retail

1A073

Canteen Storage

1A074

Dining/ Canteen

1A070

Lobby/Waiting

1A006

Waiting

1A005

Work Study

1A050A

Waiting

1A050

Office

1A052

Office 6

1A054 Office 7

1A056

Corridor

1A051

Office 5

1A053

Office

1A055

Office

1A042

Office

1A044

Conference Room

1A059

Office 4

1A058

Office 3

1A060 Workroom

1A061

Office 2

1A062

File Room

1A063

Review Room

1A064

State Employee

Office

1A066 Contract Open Office

1A065

Food Service

1A075

Kitchen

1A076

Chief Office

1A078

Kitchen Storage

1A077

Corridor

1A040

Office

1A047

Office

1A045

Storage

1A043

Office

1A041

Corridor

1A019

Travel Clerk

1A080

Teller

1A081

Agent Cashier/ Teller

1A081A

Agent Cashier/ Teller

1A081B

HAC

1A020

Corridor

1A018

Enrollment

ID

1A113

Corridor

1A057

Kitchen Storage

1A077A

Starbucks

1A006A

OIF/OEF

Reception

1A006C

Room

1A130A

Reception

1A004

Lobby

1A003

Room

2A189

Office

1A164A

Corridor

1A202

Waiting

1A201

Exam

1A228

1A224

Office

1A222

Exam

1A220

DIAB EDUC

1A218

EXAM

1A216

SOILED

1A210 sult

Consult

1A548

Office

1A549

Office

1A550

Group

1A567

Group

1A568

Toilet

A451

Toilet

1A452

Toilet

1A454

Toilet

A453

Waiting

1A560

Phys.Office

1A322

200R

Phys.Office

1A320

Phys.Office

1A318

Phys.Office

1A316

Phys.Office

1A314

Phys.Office

1A312 1-078

175E

500E

250R

300S

700R

400R

450S

450S

400S

800R

400S

700R

1-175

1-173

600S

600S

600S

700R

500S

200R

200S

1-172

100R

100S

100R

100S

200S100R

100S

600E

100S

500S

125S600E

500S

575S

575S

900E

575S

575S

1-169

600S 500S

400E 450S 450S

400E 1-167

1-168

100R

100S

1-188

1-171

200R

1-170

80S

80R

75E

600E

230S230S

400S 400S

500E500E

630R

530S

100S

100S

1-120

250S

100S 150S

850R

325R

325S

1-125

125S

125E

200S 430S

140S

130S

600R

300S

300S

1-115

325S

325S

1-108

525R

175S

175R

300R

400S

1-131

OIF/OEF

Program Manager

1A116 60S

70R

1-140

400S

1-184

100R 150R

125R

150S100S

125S

125R

125S

600E

500S

1-179

1-144

1-178

3000S

3000S

3000S

2000R

1500R

1500R

3000S

2000R 2000R

550R 400S 75R

75S

100R

100S

125R

125S

200S

200R

75E

75E

60S

175R

175S

100R

160R

160S

1-0721-071

100S

75E

1-099

Med

400S

175R

175R

1-092

280S

200E

200E

100S

800R

650S

1-121

2000R

1-160

1-159

1-157

1-183

1-156

3000S

2000R

1-182

1-180

1-161

1-162

1-164

D1

DEMOLITION CODED NOTES:

D1 REFER TO ENLARGED PLANS ON THIS SHEET.

REMOVE AND REPLACE CEILINGS AS NECESSARY TO ACCOMPLISH WORK.

RELOCATE EXISTING THERMOSTAT TO LOCATION INDICATED ON THE NEW WORK PLAN. CONTRACTOR

SHALL PATCH AND FINISH WALL TO MATCH SURROUNDING SURFACES.

D2

D3

BALANCER NOTES:

A. PRIOR TO ANY ADJUSTMENTS, TAKE BASELINE AIRFLOW MEASUREMENTS AT ALL DIFFUSERS AND

GRILLES THAT ARE INDICATED TO BE BALANCED.

B. ADJUST VAV BOX MAXIMUM AIRFLOW VIA THE BAS PER THE VAV TERMINAL SCHEDULES ON SHEET MH-0B

AND MH-0C.

C. BALANCE THE SUPPLY DIFFUSERS AND GRILLES CONNECTED TO THE VAV AND ASSOCIATED RETURN AND

EXHAUST GRILLES AS INDICATED ON PLAN. THIS SHALL BE ACCOMPLISHED VIA EXISTING DUCT VOLUME

DAMPERS.

D. ADJUST HEATING AIRFLOW VIA THE BAS AND REHEAT WATER FLOW SHALL BE BALANCED PER VAV

TERMINAL SCHEDULES ON SHEET MH-0B AND MH-0C.

E. BALANCING SHALL BE COMPLETED AFTER 6:00 P.M. ON WEEKDAYS.

F. DAMAGED CEILING TILES SHALL BE REPLACED.

MECHANICAL LEGEND:

AREA NOT IN SCOPE OF THIS PROJECT

AREA INCLUDED IN SCOPE OF THIS PROJECT. CONTRACTOR SHALL FOLLOW BALANCER

NOTES ON THIS SHEET FOR THESE AREAS.

OEF/OIF LPN

1A130

Voluntary Check In

1A101

Toilet Room

1A108A

EKG/Lab

1A112

Office (VIC)

1A110

Room

1A130A

X-22x18

X -1 x 4 X

-1 x

X-16x14 X-14x14

X -1 x

X-18x12

T

T

CAP

CAP

D2

D3

D2

XRL

D2

D2Police Office 1A137

Mental Health

1A117

Screen 1A135

LGBT

1A115

Tricare

1A111

Enrollment

ID

1A131

Enrollment

ID

1A113

PATCH WALL

PATCH WALL

OEF/OIF LPN

1A130

Voluntary Check In

1A101

Toilet Room

1A108A

EKG/Lab

1A112

Office (VIC)

1A110

Room

1A130A

X-22x18

X -1 x 4 X

-1 x

X-16x14 X-14x14

X -1 x

X-18x12

100S

125S

125R

100R 125R

125S

100R

100S

100S

100R

100S

100R

100R

100S140S

140R

1-143 1-145

T

T

D2

XNL

D2

Police Office 1A137

Mental Health

1A117

Screen 1A135

LGBT

1A115

Tricare

1A111

Enrollment

ID

1A131

Enrollment

ID

1A113

6" Ø

6" Ø

N

0' 8' 16' 32' 64'

SCALE: 3/32" = 1'0"

FIRST FLOOR HVAC AIR DISTRIBUTION PLAN - WEST

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

BID AND CONSTRUCTION

Project Number

Building Number

Drawing Number

CHALMERS P. WYLIE VAACC

CORRECT RETRO COMMISSIONING

DEFICIENCIES

Project Title

Location

Issued Date Checked Drawn

Drawing Title

Approved: Farid F. Mehr, P.E.

Chief, Engineering Service

Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

/1

/2

:3

:4 A

M C

R e v it L o c a l\

R

V A

C o lu m b u s C o rr e c t

R e tr o

C X

C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m

.r v t

757-20-101 dad sic04/14/21

420 N. JAMES ROAD, COLUMBUS, OH 43219

Revisions Date

BID AND CONSTRUCTION 04/14/21 TEL. (440) 546-9696

BROADVIEW HTS., OHIO 44147

672 EAST ROYALTON ROAD

FAX. (440) 546-9699

First Floor HVAC

Air Distribution Plan - West

MH-1A

UP

N

NOT TO SCALE

FIRST FLOOR KEY PLAN

N

0'

SCALE: 1/8" = 1'0"

4' 8' 16' 32'

ENLARGED PARTIAL FIRST

FLOOR HVAC DEMOLITION PLAN

N

0'

SCALE: 1/8" = 1'0"

4' 8' 16' 32'

ENLARGED PARTIAL

FIRST FLOOR HVAC PLAN

WEST

EAST

-65042

ER

H

F OO

IO

AVID A.

MAGALL

-65042

ER

H

F OO

IO

AVID A.

MAGALL

-65042

ER

H

F OO

IO

Pharmacy Waiting

1B003

Controlled Substance

Vault

1B222 Refrigerator/Freezer

1B224

Packaging

1B220

Consultant 1

1B240A

Consultant 2

1B240B

Consultant 3

1B240C

Consultant 4

1B240D

Consultant 5

1B240E

Consultant 6

1B240F

Staff Toilet

1B241

Staff Toilet

1B242

Assistant Chief Office

1B202

Pharmacy Administation

Office

1B200

Chief Office

1B203

HAC

1B207

Super.

Pharmacy

1B209

Work Room

1B204

Corridor

1B212

Conference/Education/Workroom

1B211

Patient Advocate

1B022

Patient Advocate

1B021

Patient Advocate

1B020

Elevator Lobby

1B001

Telecommunications

1B002

Stair No. 4

1S004

Electrical Room

1B031

Waiting

1B030

Logistics

1B210

Clinical Pharmacy

1B208

Change

1B042

Change

1B044 Toilet Room

1B046A

Ultrasound

1B046

Ultrasound

1B048

Fee Basis

1B206

Bone Density

1B050

Staff Lockers/Lounge

1B229

Break Room

1B052

Corridor

1B004 Corridor

1B005

Methadone Staff Work

1B223

Lock Shop

1B225

Inventory/Stock MNG/ Prog.

Asst.

1B226 Receiving/ Counter

1B227

Compound

1B237

Drug Cache

1B236

Dispensing

1B230

Window Filling

1B231

Storage/ Shelving

1B232

Mail Filling

1B233

Prosthetics Storage

1B238

Sub-Waiting

1B033

Corridor

1B034

Supervisor

1B061

Radiology

1B041

Toilet Room

1B043

Toilet Room

1B045 Rad. Control Room

1B049

Radiology

1B047

Toilet Room

1B054

Sub-Waiting

1B035

Corridor

1B037

Soiled Utility Room

1B051 Change

1B053

Exam 7

1B250G

Exam 8

1B250H

Corridor

1B036

Exam 9

1B257 Exam

1B258

UCC

1B254

Patient Toilet/Shower

1B256

Exam 6

1B250F

Exam 1

1B250A

Exam 2

1B250BUCC

Reception

1B250C

Exam 4

1B250D

Exam 5

1B250E

Patient Toilet

1B255

Care Giver

1B251C

PACS

1B251B

Care Giver

1B251A

Corridor

1B252

Telecommunications

1B006

Electrical Room

1B007

Storage

1B265

Nurse Office

1B263

Storage

1B261

Corridor

1B253

Corridor

1B009

Logistics File Storage

1B008

Physician Office

1B264

Nurse Office 1B262

Soiled Utility Room

1B272

Patient Toilet

1B260

Patient Toilet

1B274

Stretcher Storage

1B276

Corridor

1B280

Nurse Office

1B275

Exam

1B278

Staff Toilet

1B281

Washroom

1B106

Corridor

1B270

Shared Office

1B273

Logistics file storage

1B108

Waiting

1B271 Bio-Hazard

1B110

Soiled Linen Cart

1B112

Stair No. 5

1S005

Corridor

1B010

Recieving Shipping Docks

1B113

Receiving & Issue Area

1B111

Unpost. Hold.

1B109

Staff Toilet

1B114

Storekeeper Office

1B115

Form Storage

1B107

CHIEF

1B117

Secretary/Waiting

1B118

Open Office

1B116

Chief Office

1B119

Central Linen Stor. (Envir.

Serv.)

1B105

Staff Toilet

1B120

4 Isolation

1B259

Clean

1B277

Exam

1B279

Medical Gas Storage

1B104

Toilet Room

1B259A

Change

1B083 Sub-Waiting

1B084

Cry. Storage

1B085 Clean

1B086

EMS

Supervisor

1B087

HAC

1B102

Corridor

1B012

Envirn.

Services Office

1B101B

Media Vault

1B121 Reverse Osmosis

1B103A Logistics

1B103

Supply Storage (Env.

Serv.)

1B101

Scan Room

1B100B

Equipment

1B098

Toilet Room

1B093

Sub

1B091

Interview

1B095

M.R.I.

1B097

Control

1B100A

Office

1B094

Office

1B092

Biomed

1B090

Waiting

1B096

Ra…