04 - Structures - Mast Arms.pdf
PDF 2 MB Posted
- Solicitation number
- 0171-0504
- Issued by
- Hartford County, Connecticut
About this file
This file contains structural design drawings for steel mast arm assemblies prepared by the Connecticut Department of Transportation for the Installation and Revision of Traffic Control Signals in District 1 project, covering the towns of Bristol, New Britain, and Vernon. The drawings provide detailed specifications for the design, fabrication, and installation of steel mast arm structures that support traffic control signals, luminaires, and highway signs. The document includes four sheets of technical drawings (MA-1 through MA-4) depicting the index of drawings, steel mast arm assembly elevation, assembly details, and foundation details. The mast arm assemblies must be designed and fabricated by the contractor in accordance with AASHTO LRFD specifications and conform to applicable design standards. Key design requirements include minimum vertical clearance of 16 feet and maximum of 18 feet, permanent arm camber of 6 inches minimum, proper drainage provisions, grounding conductor installation, and identification tagging. The contractor is responsible for preparing layout drawings based on field survey to verify that installed mast arm assemblies will meet geometric and clearance requirements specified in the contract documents.
Foundation design specifications require drilled shaft construction with a 2-foot minimum diameter embedded 2 feet below finished grade, designed for 4,000 PSI concrete compressive strength on undisturbed earth. Reinforcement consists of 16 number 4 bars with number 4 ties spaced at 4 to 6 inches, and all reinforcement must have 3 inches of concrete cover. The foundation must accommodate three 2-inch diameter rigid metal conduit sweeps, include weepholes for drainage, and incorporate closed cell elastomer or hand-packed grout sealing. Anchor bolts, anchorage plates, and bonding conductors must be specified, with the foundation designed to be constructed by the contractor per the special provision "Traffic Control Foundation - Mast Arm." The concrete shall not receive mast arm installation until achieving minimum 4,000 PSI compressive strength. Where existing concrete sidewalks are damaged or require replacement due to installation, such work shall be paid under the separate line item "Concrete Sidewalk."
View the file
Other files
Show 40 more
Latest 50 of 86 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BEEN PERSONALLY CHECKED BY THE UNDERSIGNED.
NOT TO BE CONSTRUED TO MEAN THAT ALL ASPECTS OF THE DESIGN HAVE
THE DESIGN APPEARS TO CONFORM TO APPLICABLE CRITERIA. APPROVAL IS
TRANSPORTATION PRINCIPAL ENGINEER
STEEL MAST ARM ASSEMBLY FOUNDATION DETAILSMA-4
STEEL MAST ARM ASSEMBLY DETAILSMA-3
STEEL MAST ARM ASSEMBLY ELEVATIONMA-2
INDEX OF DRAWINGSMA-1
DRAWING TITLEDRAWING NUMBERDRAWING TITLEDRAWING NUMBER
INDEX OF DRAWINGS
- STRUCTURES - MAST ARMS
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
9/17/2024
SIGNATURE BLOCK: DRAWING TITLE:
MA-1
TOWN(S):
PLOTTED DATE:
l FILE NAME LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
IO
N
DESIGNER/DRAFTER: CHECKED BY:
INDEX OF DRAWINGS
TRANSPORTATION
DEPARTMENT OF
CONNECTICUT
K. GUTHRIE K. BROWN
INSTALLATION AND REVISION OF TRAFFIC
CONTROL SIGNALS IN DISTRICT 1
0171-0504BRISTOL, NEW BRITAIN & VERNON
04.01 D. TOMPKINS
LEVEL
3° TO 5°
3° TO 5°
OF THE POLE SHALL BE PLUMB.THE
OF THE TRAFFIC APPURTENANCES
OF POLE. AFTER THE INSTALLATION
OF THE POLE SHALL BE PLUMB. THE
OF THE TRAFFIC APPURTENANCES
OF POLE. AFTER THE INSTALLATION
M
IN
V
E R
T
IC
A L C
L E
A R
A N
C E
M
A X
V
E R
T
IC
A L
C L
E A
R A
N C
E
BACKPLATE (TYP.)
� OF TAPERED ARM
TOP OF ROADWAY
� OF TAPERED LUMINAIRE ARM
SIGNAL (TYP.)
TRAFFIC APPURTENANCE
BOTTOM OF
ARM CAP PLATE
3 - 2" Ø CONDUIT SWEEPS.
SIGNAL CONTROL PLANS. MINIMUM OF
NUMBER AND SIZE AS SHOWN ON TRAFFIC
ACCOMMODATE RIGID METAL CONDUITS,
BASEPLATE SHALL BE FABRICATED TO
3 - 2" Ø CONDUIT SWEEPS.
SIGNAL CONTROL PLANS. MINIMUM OF
NUMBER AND SIZE AS SHOWN ON TRAFFIC
ACCOMMODATE RIGID METAL CONDUITS,
BASEPLATE SHALL BE FABRICATED TO
A R
M A
T T
A C
H M
E N
T H
E
IG
H T
P O
L E
L E
N G
T H
ARM LENGTH
A R
M A
T T
A C
H M
E N
T H
E
IG
H T
P O
L E
L E
N G
T H
L U
M
IN
A
IR
E A
R M
A T
T A
C H
M E
N T
H E
IG
H
T
LUMINAIRE ARM LENGTH
1'-0"
THREADED PLUG
2" COUPLING WITH
INSTALL IDENTIFICATION TAG
BY THE CONTRACTOR
SHALL BE DETERMINED
UNLOADED POLE RAKE
AND SUPPORT
FOR WIRE HANDLING
TO INSIDE OF POLE
J-HOOK WELDED
INSTALL IDENTIFICATION TAG
AND SUPPORT
OF POLE FOR WIRE HANDLING
J-HOOK WELDED TO INSIDE
COMPOSED OF TWO MEMBERS
ON OUTER MEMBER OF ARMS
INSTALL IDENTIFICATION TAG OR STAMP
NEOPRENE GASKET
SEALED WITH
POLE CAP PLATE
WORD "UP" LOCATED HERE
ERECT ARM WITH THE
MAST ARM IDENTIFICATION NUMBER
STENCIL LAST CHARACTER OF
STAINLESS STEEL SCREWS (TYP.)
TO POLE OR BASEPLATE WITH
ANCHOR BOLT COVER. ATTACH
STAINLESS STEEL SCREWS (TYP.)
TO POLE OR BASEPLATE WITH
ANCHOR BOLT COVER. ATTACH
MAST ARM IDENTIFICATION NUMBER
STENCIL LAST CHARACTER OF
MAST ARM ELEVATION
ADDITIONAL DETAILS SEE
OF TAPERED ARM. FOR
PREVENT THE INTRUSION OF WATER.
CONNECTION SHALL BE DESIGNED TO
TO BE DESIGNED BY THE CONTRACTOR.
LUMINAIRE ARM TO POLE CONNECTION
FOR DETAILS
SEE DRAWING NO. MA-4
FOUNDATION
FOR DETAILS
SEE DRAWING NO. MA-4
FOUNDATION
ANCHORAGE PLATE
ANCHOR BOLTS WITH ANCHORAGE PLATE
ANCHOR BOLTS WITH
FINISHED GRADE, VARIES
FINISHED GRADE, VARIES
TRAFFIC PLANS.
APPURTENANCES WITH PROPERTIES NO LESS THAN THOSE SHOWN ON THE
THE MAST ARM ASSEMBLIES SHALL BE DESIGNED TO SUPPORT TRAFFIC
MAST ARM ASSEMBLY" OR "XX STEEL COMBINATION MAST ARM ASSEMBLY".
INTERIM SPECIFICATIONS, AS AMENDED BY THE SPECIAL PROVISION "XX STEEL
HIGHWAY SIGNS, LUMINAIRES AND TRAFFIC SIGNALS, INCLUDING THE LATEST
EDITION OF THE AASHTO LRFD SPECIFICATIONS FOR STRUCTURAL SUPPORTS FOR
THE MAST ARM ASSEMBLIES SHALL BE DESIGNED IN ACCORDANCE WITH THE LATEST
CANNOT BE MET, THE CONTRACTOR SHALL NOTIFY THE ENGINEER.
CLEARANCE REQUIREMENTS IN THE CONTRACT DOCUMENTS. IF THE REQUIREMENTS
THE MAST ARM ASSEMBLY WHEN INSTALLED WILL MEET THE GEOMETRIC AND
DRAWING BASED ON A FIELD SURVEY AND THE CONTRACT DOCUMENTS TO VERIFY
DESIGN OF EACH MAST ARM ASSEMBLY, THE CONTRACTOR SHALL PREPARE A LAYOUT
STRUCTURE ARE SHOWN ON THE TRAFFIC CONTROL SIGNAL PLAN. PRIOR TO
THE LOCATIONS OF THE TRAFFIC APPURTANENCES SUPPORTED BY THE
THE MAST ARM ASSEMBLY, INCLUDING THE ARM SPAN, ARM ORIENTATION, AND
COMBINATION MAST ARM ASSEMBLY".
WITH THE SPECIAL PROVISION "XX STEEL MAST ARM ASSEMBLY" OR "XX STEEL
BE DESIGNED, FABRICATED AND INSTALLED BY THE CONTRACTOR IN ACCORDANCE
THE MAST ARM ASSEMBLY, INCLUDING THE ANCHORAGE TO THE FOUNDATION, SHALL
INSTALL IDENTIFICATION TAG
PERMANENT
ARM CAMBER
6" MIN.
6" MIN.
PERMANENT LUMINAIRE
ARM CAMBER
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
11/18/2025
SIGNATURE BLOCK: DRAWING TITLE:
MA-2
FILE NAME: LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
ASSEMBLY ELEVATION
STEEL MAST ARM
TRANSPORTATION
ON ARMPLATE WHEN STAMPED OPTION IS USED
FOR INNER MAST ARM IDENTIFICATION
ALTERNATE LOCATION
SPLICE OPTIONAL
SLIP TYPE FIELD
ON BASEPLATE WHEN STAMPED OPTION IS USED
FOR MAST ARM IDENTIFICATION
ALTERNATE LOCATION
1'-0"
ON BASEPLATE WHEN STAMPED OPTION IS USED
FOR MAST ARM IDENTIFICATION
ALTERNATE LOCATION
PREVENT THE INTRUSION OF WATER
CONNECTION SHALL BE DESIGNED TO
DESIGNED BY THE CONTRACTOR.
ARM TO POLE CONNECTION TO BE
RING STIFFENED BUILT-UP BOX
NEOPRENE GASKET
SEALED WITH
POLE CAP PLATE
ELEVATION - MAST ARM
/4"=1'-0"1SCALE:
ELEVATION - COMBINATION MAST ARM
/4"=1'-0"1SCALE:
MAST ARM ASSEMBLY NOTES
B
MA-3
B
MA-3
MA-3
C
MA-3
C
60°
HAND HOLE
OF REINFORCED�
HAND HOLE
OF REINFORCED�
A
MA-3
BY THE CONTRACTOR
SHALL BE DETERMINED
UNLOADED POLE RAKE
F
MA-3
F
MA-3
F
MA-3
F
MA-3
SCALE AS NOTED
K. GUTHRIE K. BROWN
INSTALLATION AND REVISION OF TRAFFIC
CONTROL SIGNALS IN DISTRICT 1
04.02 D. TOMPKINS
TUBE MATERIAL STRENGH: IN KSI
ARM LENGTH: IN FEET (METERS)
DATE OF MANUFACTURE: MM/YY
MANUFACTURER:
IDENTIFICATION NUMBER: XXX-XXX-Y
90°
D
IR
E C
T
IO
N O
F T
R A
F F
IC
� OF POLE
D
IR
E C
T
IO
N O
F T
R A
F
IC
90°
30°
20°
30°
20°
HAND HOLE LOCATION
ALTERNATE REINFORCED
� OF POLE
STEEL BOLTS
AND COVER WITH STAINLESS
ATTACH CHAIN TO FRAME
� OF POLE
HAND HOLE
REINFORCED
HAND HOLE
REINFORCED
SCALE: 1 1/2" = 1'-0"
SCALE: 3/4" = 1'-0"
SCALE: 3/4" = 1'-0"
VERTICAL
MARKER AT BASE OF ARM
MARK "UP" WITH PERMANENT INK
TOP OF ARM. AFTER GALVANIZING,
HAND HOLE FRAME
NEOPRENE GASKET
HAND HOLE COVER WITH
WELDING STRICTLY PROHIBITED
SCREWS (TYP.)
RESISTANT STAINLESS STEEL
WITH SELF-TAPPING TAMPER
ATTACH TAG TO POLE AND ARM
OF ARM
AND ORIENTATION
OF ARM
AND ORIENTATION
TO POLE CONNECTION (TYP.)
GUSSET PLATE FOR ARM
TO POLE CONNECTION (TYP.)
GUSSET PLATE FOR ARM
STEEL CHAIN
¼" x 1'-6" LONG STAINLESS
½" Ø STAINLESS STEEL BOLT
TO HAND HOLE FRAME WITH
ATTACH GROUNDING CONDUCTOR
INTO BACKFILL.
WITH OPTIONAL ELBOW. OUTLET
2" Ø PVC PIPE WEEPHOLE
OR ARM
AND ORIENTATION
3 - 2" Ø CONDUIT SWEEPS.
SIGNAL CONTROL PLANS. MINIMUM OF
NUMBER AND SIZE AS SHOWN ON TRAFFIC
ACCOMMODATE RIGID METAL CONDUITS,
BASEPLATE SHALL BE FABRICATED TO
ANCHOR BOLT (TYP.)
OVER WEEPHOLE OPENING
GALVANIZED CONCRETE NAILS
MESH ATTACHED WITH 4
23 GAGE GALVANIZED
PLACE 4" X 4" PIECE OF
WITH GROUND CLAMP
BOLT AND TO GROUND ROD
HAND HOLE WITH GROUNDING
GROUNDING CONDUCTOR TO
ATTACH #8 BARE COPPER
TO GROUND ROD WITH GROUND CLAMP
CONDUCTOR TO BONDING BUSHINGS AND
ATTACH #8 BARE COPPER GROUNDING
USED IN LIEU OF THE CLOSED CELL ELASTOMER.
THE FOUNDATION. HAND PACKED GROUT MAY BE
BOTTOM OF THE BASEPLATE AND THE TOP OF
COMPLETELY FILL THE OPENING BETWEEN THE
BELOW BASEPLATE. THE ELASTOMER SHALL
SEAL WITH 1'-1" Ø CONCENTRIC HOLE PLACED
4½" THK. X 1'-6" Ø CLOSED CELL ELASTOMER
OR HAND PACKED GROUT
CLOSED CELL ELASTOMER RING
FOR SEAM WELD
ALLOWABLE LIMITS
FOR SEAM WELD
ALLOWABLE LIMITS
FOR SEAM WELD
ALLOWABLE LIMITS FOR SEAM WELD
ALLOWABLE LIMITS
1" MAX FROM BOTTOM OF NUT
TO TOP OF FOUNDATION
SCALE: 1 1/2" = 1'-0"
SCALE: 1 1/2" = 1'-0"
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
11/18/2025
SIGNATURE BLOCK: DRAWING TITLE:
MA-3
FILE NAME: LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
ASSEMBLY DETAILS
STEEL MAST ARM
TRANSPORTATION
TUBE MATERIAL STRENGH: IN KSI
ARM LENGTH: IN FEET (METERS)
DATE OF MANUFACTURE: MM/YY
MANUFACTURER
IDENTIFICATION NUMBER: XXX-XXX-Y
WALL THK. OF TUBULAR MEMBER
SEALANT AFTER GALVANIZING
CAULK WITH BEAD OF SILICONE
GROUND FLUSH WITH BASE METAL
PENETRATION GROOVE WELD
REQUIRED, SPLICE WITH COMPLETE
CONTINUOUS BACKING RING. IF
UT
CJP
BASEPLATE OR FLANGE PLATE
WITH 2 FLANGE PLATES INTERIOR
POLES AND OVERHEAD MEMBER
DRAIN HOLE, IN FLANGE PLATE OF
" MIN.4
" MIN. (TYP.)4
1" Ø MAX. DRAIN HOLE (TYP.)
BACKING RING
TUBULAR MEMBER
FILLET WELD TOE
HANGING DIRECTION
"8
7LEDGE >
TUBULAR MEMBER FOR VENTING�
HOLE CONCENTRIC ABOUT
G
TRANSVERSE PLATE
BOLT CIRCLE
BOLT HOLE (TYP.)
PLATE
OF TRANSVERSE�
POLE WITH 1 SEAM WELD
POLE WITH 2 SEAM WELD
STRUCTURE IDENTIFICATION - N.T.S
A
MA-2
SECTION
B
MA-2
SECTION
D
SECTION
E
DETAIL
C
MA-2
DETAIL
D
E
OF ARM�
TAG OPTION
STAMPED OPTION
G
SECTION
3"=1'-0"SCALE:
F
MA-2
TRANSVERSE PLATE DETAIL
1 1/2"=1'-0"SCALE:
GALVANIZING
FOR CLEAR VISIBILTY AFTER
" MIN. STAMP DEPTH AS REQUIRED32
" LETTER HEIGHT (TYP.)2
SCALE AS NOTED
K. GUTHRIE K. BROWN
INSTALLATION AND REVISION OF TRAFFIC
CONTROL SIGNALS IN DISTRICT 1
04.03 D. TOMPKINS
A
C H
O R
B O
L T
L E
N G
T H
A N
C H
O R
B O
L T
E M
B E
D M
E N
T
EDGE OF SIDEWALK
ANCHOR BOLTS (TYP.)
F O
U N
D A
T
IO
N L
E N
G T
H
(M
IN
IM
U
M S
IZ
E
A N
D S
P A
C
IN
G O
F R
E
IN
F O
R C
E M
E N
T
M E
A S
U R
E D
F R
O M
S L
O P
E D
F
IN
IS
H
E D
G R
A D
E
E M
B E
D M
E N
T D
E P
T H
M E
A S
U R
E D
F R
O M
L E
V E
L F
IN
IS
H E
D G
R A
D E
E M
B E
D M
E N
T D
E P
T H
RIGID METAL CONDUIT (TYP.)
C
O V
E R
T
IE
S
/S P
IR
A
L S
S
P A
C
IN
G /P
IT
C
H
C
O V
E R
FOUNDATION DIA.
2'-0"
CLAD STEEL GROUND ROD
COPPER ⅝" x 10'
EARTH FINISHED GRADES
1" X 1" BEVEL WITH
3" COVER
REINFORCEMENT)
(MINIMUM NUMBER AND SIZE OF
16 - #8 EQUALLY SPACED
SPACING/PITCH, MAX.
WHICH SHALL HAVE #4 TIES/SPIRALS @ 4"
EXCLUSIVE TO THE TOP 2' OF FOUNDATION,
OF REINFORCEMENT, SIZE AND SPACING
ALTERNATE TIE SPLICES 180°. TYPICAL MINIMUM
#4 TIES/SPIRALS @ 6" SPACING/PITCH,
ANCHOR BOLT (TYP.)
ANCHOR BOLT (TYP.)
CAP END (TYP.)
THREAD AND
REINFORCEMENT (TYP.).
PLACE TO CLEAR ANCHOR BOLTS AND
MINIMUM OF 3 - 2" Ø CONDUIT SWEEPS.
SHOWN ON TRAFFIC SIGNAL CONTROL PLANS.
RIGID METAL CONDUIT, NUMBER AND SIZE AS
ANCHORAGE PLATE
SIDEWALK
CONCRETE
TOP OF
PROJECTION
ANCHOR BOLT
BUSHING (TYP.)
INSULATING BONDING
SCALE: 3/4" = 1'-0"
FINISHED GRADE VARIES
TOP OF EARTH
AND ORIENTATION OF ARM�
WITH OPTIONAL ELBOW
2" Ø PVC PIPE WEEPHOLE
OF ARM
AND ORIENTATION�
ANCHORAGE PLATE
FOR PAYMENT UNDER THE ITEM "CONCRETE SIDEWALK".
PREFORMED EXPANSION JOINT FILLER AND JOINT SEALANT SHALL BE INCLUDED THE COST OF
TO FOUNDATION INSTALLATION SHALL BE PAID FOR UNDER THE ITEM "CONCRETE SIDEWALK".
OR CUT DURING INSTALLATION, REPLACE THE ENTIRE SECTION. ALL SIDEWALK REPLACED DUE
WHERE AN EXISTING CONCRETE SIDEWALK ABUTTING A FOUNDATION IS DAMAGED
PAYMENT UNDER THE ITEM "TRAFFIC CONTROL FOUNDATION - MAST ARM".
CASING AND WEEPHOLES, INCLUDING THE DESIGN AND FABRICATION, TO BE INCLUDED FOR
REINFORCEMENT, THE COST OF THE FOUNDATION, INCLUDING THE EXCAVATION, CONCRETE,
SHAFT HAS ATTAINED A COMPRESSIVE STRENGTH, f'c, GREATER THAN OR EQUAL TO 4000 PSI.
THE MAST ARM SHALL NOT BE ERECTED ON THE FOUNDATION UNTIL THE CONCRETE IN THE
THE CONCRETE SHALL BE PLACED IN THE EXCAVATION AGAINST UNDISTURBED EARTH.
UNLESS OTHERWISE NOTED.
REINFORCEMENT IS NOT PERMITTED. ALL REINFORCEMENT SHALL HAVE 3" COVER,
THE REINFORCEMENT SHALL BE ASSEMBLED WITH WIRE TIES. WELDING TO ASSEMBLE
THE REINFORCEMENT SHALL BE UNCOATED AND CONFORM TO ASTM A615, GRADE 60.
M.03 - PORTLAND AND HYDRAULIC CEMENT CONCRETE.
SHALL CONFORM TO THE REQUIREMENTS OF 6.01 - CONCRETE FOR STRUCTURES AND
THE COMPRESSIVE STRENGTH OF THE CONCRETE IN THE CONSTRUCTED FOUNDATION
COMPRESSIVE STRENGTH, f'c, USED IN DESIGN OF THE FOUNDATION SHALL BE 4,000 PSI.
THE CONCRETE FOR THE FOUNDATION SHALL CONFORM TO CLASS PCC04460. THE
EMBEDDED MAST ARM ANCHORAGE AND THE FOUNDATION REINFORCEMENT.
ADEQUATE FOR THE MAST ARM REACTIONS AND TO AVOID CONFLICTS BETWEEN THE
ASSEMBLY AND THE MAST ARM ANCHORAGE TO ENSURE THAT THE FOUNDATION IS
THE DESIGN OF THE FOUNDATION SHALL BE COORDINATED WITH THE MAST ARM
EXPLORATIONS AND INVESTIGATIONS SHALL BE DETERMINED BY THE CONTRACTOR.
SHAFT FOUNDATION EXCAVATION. THE NEED AND EXTENT OF ALL SUBSURFACE
GROUND WATER, ETC.) IN THE LOCATION OF, ADJACENT TO AND BELOW THE DRILLED
ON THE SUBSURFACE CONDITIONS (CHARACTER OF THE SOIL AND ROCK, PRESENCE OF
THE FOUNDATION SHALL BE DESIGNED FOR THE SOILS AND ROCK PROPERTIES BASED
SPECIAL PROVISION "TRAFFIC CONTROL FOUNDATION - MAST ARM".
FABRICATED, AND CONSTRUCTED BY THE CONTRACTOR IN ACCORDANCE WITH THE
THE DRILLED SHAFT FOUNDATION FOR THE MAST ARM ASSEMBLY SHALL BE DESIGNED,
2'-0" MINIMUM
BELOW FINISHED GRADE
SIDEWALKS, FOR ACCESS
FACE OR REAR FACE AT
3'-0" MIN., FRONT
8" CONDUIT PROJECTION
TOOLED EDGE ADJACENT TO CONCRETE SIDEWALK
TOPPED WITH JOINT SEALANT
¼" PREFORMED EXPANSION JOINT FILLER
3" PROJECTION ABOVE
SLOPED FINISHED EARTH GRADE
OF ADJACENT SIDEWALK
WITH EARTH BACKFILL, SLOPE TO MATCH CROSS-SLOPE
TOP OF FOUNDATION, LEVEL WHEN SURROUNDED
2'-6" SPLICE ALTERNATE SPLICES
45°
22.5°
SCALE: 3/4" = 1'-0"
3" ABOVE LEVEL FINISHED EARTH GRADE
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
3/28/2025
SIGNATURE BLOCK: DRAWING TITLE:
MA-4
FILE NAME LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
DESIGNER/DRAFTER: CHECKED BY: DETAILS
ASSEMBLY FOUNDATION
STEEL MAST ARM
TRANSPORTATION
FOUNDATION NOTES
G
F
SECTION
G
SECTION
FOUNDATION DIA.
FOUNDATION DIA.
/4"=1'-0"3SCALE:
FOUNDATION DETAIL
TOP OF ANCHORAGE PLATE
ROUGHEN SURFACE
OPTIONAL CONSTRUCTION JOINT,
SCALE AS NOTED
BOLT CIRCLE DIA.
BOLT CIRCLE DIA.
DIAMETER OF THE POLE AT THE BASE PLUS 6" ± 1"
BOLT CIRCLE DIAMETERS:
4'-0" OTHERWISE
3'-0" FOR MAST ARMS WITH POLE DIAMETERS AT THE BASE LESS THAN OR EQUAL TO 1'-6"
FOUNDATION DIAMETERS:
K. GUTHRIE K. BROWN
INSTALLATION AND REVISION OF TRAFFIC
CONTROL SIGNALS IN DISTRICT 1
04.04 D. TOMPKINS
| 413-315-1828 | |
| 2026-05-01T19:00:52-0400 | |
| SLR | |
| David Tompkins | |
| I am the author of this document |
File details come from the government source that posted it. Updated .