PARTITION TYPE LEGEND
METAL STUDS @ 16" O.C., x REFER TO SPEC'S FOR GA./MIL THICKNESSS
METAL STUDS @ 12" O.C./ FURRING CHANNELS / HAT CHANNELS/ Z-
FURRING CHANNELS x REFER TO SPECS FOR GA./MIL THICKNESS
F
MATERIAL DESIGNATION
SIZE SUFFIX
1 5/8" METAL STUDS, OR 7/8" / 1 1/2" HAT CHANNELS (SEE
REMARKS)
2 1/2" METAL STUDS OR 2" / 2 1/2" Z FURRING CHANNELS (SEE
REMARKS)
3 5/8" METAL STUDS3
4" CONCRETE MASONRY UNIT (CMU) OR 4" METAL STUDS4
6" CONCRETE MASONRY UNIT (CMU) OR 6" METAL STUDS6
RATING SUFFIX
1 HR RATED CMU OR METAL STUD PARTITION (PER UL DESIGN NO.)1
2 HR RATED CMU OR METAL STUD PARTITION (PER UL DESIGN NO.)2
3 HR RATED CMU OR METAL STUD PARTITION (PER UL DESIGN NO.)3
ACCESSORIES SUFFIX
ABUSE RESISTANT GYPSUM WALL BOARD- REFER TO SPECIFICATIONSa
GENERAL PARTITION NOTES
ALL PARTITIONS EXTEND TO BOTTOM OF CONCRETE FLOOR TO METAL DECK ABOVE
UNLESS OTHERWISE INDICATED.
FILL FLUTES IN METAL DECK ABOVE PARTITION WITH FIRE SAFING INSULATION AND FIRE
STOP ENTIRE PERIMETER AT RATED PARTITIONS, AND EXTERIOR WALLS
WITH A UL LISTED JOINT SYSTEM FIRESTOP ASSEMBLY.
PROVIDE DEFLECTION TRACKS AT METAL STUD PARTITIONS THAT TERMINATE AT THE
UNDERSIDE OF STRUCTURE/ METAL DECK ABOVE.
ALL NON-BEARING PARTITIONS SHALL BE CONSTRUCTED TO LIMIT DEFLECTION TO
L/362 OF THE SPAN WITH UNIFORM 5 PSF HORIZONTAL LOADING.
ALL PENETRATIONS IN FIRE RATED PARTITIONS TO BE FIRE STOPPED AND SEALED.
ALL PARTITIONS SHALL BE SEALED TO PREVENT PASSAGE OF SMOKE.
CONTRACTOR TO REFER TO CODE/LIFE SAFETY DRAWINGS FOR RATED PARTITIONS.
PROVIDE MOISTURE RESISTANT GYPSUM BOARD AT ALL WET LOCATIONS AND AREAS
TO RECEIVE WALL TILE, REFER TO SPECIFICATIONS.
PROVIDE DOUBLE FRAMING AT ALL DOOR, WINDOW AND CASED OPENINGS JAMBS AND
HEAD CONDITIONS.
FOR ALL PARTITIONS, COORDINATE AND PROVIDE BLOCKING FOR ALL BUT NOT LIMITED
TO WALL MOUNTED ARCHITECTURAL WOODWORK, FINISH CARPENTRY, TOILET
PARTITIONS AND ACCESSORIES, EQUIPMENT, HANDRAILS, HARDWARE AND SIMILAR
MOUNTED ITEMS.
INSTALL ACOUSTICAL SEALANT AT ALL NON-RATED "i" SUFFIX PARTITIONS.
EXAMPLE: M 3 . 1 b
MATERIAL DESIGNATION
SIZE SUFFIX
RATING SUFFIX
ACCESSORY SUFFIX
(2) LAYERS OF GYPSUM WALL BOARD ON BOTH SIDESd
GYPSUM WALL BOARD/ACOUSTICAL INSULATION TO 8" ABOVE CEILING ON BOTH SIDESb
GYPSUM WALL BOARD TO 8" ABOVE CEILING ON BOTH SIDESc
NON-RATED CMU OR METAL STUD PARTITION0
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
CS12.0b
HALF WALL WITH CAP. COORDINATE WITH INTERIOR DRAWINGS.h
NON-RATED SMOKE PARTITION, DESIGNED & CONSTRUCTED TO
LIMIT THE PASSAGE OF SMOKE
s
GYPSUM WALL BOARD / THERMAL INSULATION TO DECKe
GYPSUM WALL BOARD TO DECK / ACOUSTICAL INSULATION TO 8" ABOVE CEILINGi
METAL STUDS @ 12" O.C./ FURRING CHANNELS / HAT CHANNELS/ Z-
FURRING CHANNELS x REFER TO SPECS FOR GA./MIL THICKNESS
SH
BOTTOM OF STRUCTURE
SOUND ATTENUATION BATT INSULATION
(TO UNDERSIDE OF DECK) AT 'i' SUFFIX
CONT LATERAL BRACE
SLOTTED DEFLECTION TRACK
SECT. @ FLOOR
SECT. @ CLG.
PLAN VIEW
20 GAUGE - STEEL STUDS @ 16" O.C. (SEE WALL
TYPE MARK FOR STUD WIDTH)
5/8" TYPE "X" GWB EA. SIDE FULL HEIGHT ON
STEEL STUDS TO STRUCT. ABOVE
(FOR 2 HR FIRE RATING PROVIDE 2 LAYERS
5/8" TYPE "X" GWB EA. SIDE FULL HEIGHT)
(FOR 3 HR FIRE RATING PROVIDE 3 LAYERS
1/2" TYPE "X" GWB EA. SIDE FULL HEIGHT)
SCHEDULED CEILING. SEE REFLECTED
CEILING PLAN FOR HEIGHT.
ACOUSTICAL OR FIRE RESISTIVE JOINT SEALANT
(BOTH SIDES)
SCHEDULED BASE MOLDING
ACOUSTICAL OR FIRE RESISTIVE JOINT SEALANT (BOTH
SIDES)
STC
STUD SIZE
3 5/8"
FIRE TEST
DESIGN NO. FIRE RATING
-- NON-RATEDS3.0
GAUGE
PARTITION
WIDTH
20 GA 4 7/8"
--3 5/8" UL U419 1 HRS3.1 20 GA 4 7/8"
--6" UL U419 1 HRS6.1 20 GA 7 1/4"
--6" UL U419 2 HRS6.2 20 GA 8 1/2"
N O
N R
A
TE
D W
A
LL
S G
W B
M
IN
A B
O V
E C
LG
--3 5/8" UL U419 2 HRS3.2 20 GA 6 1/8"
--6" -- NON-RATEDS6.0 20 GA 7 1/4"
--6" -- NON-RATEDS6.0d 20 GA 8 1/2"
GYPSUM LAYERS
EACH SIDE
1x 5/8" + 1x 5/8"
1x 5/8" + 1x 5/8"
2x 5/8"+ 2x 5/8"
1x 5/8" + 1x 5/8"
2x 5/8" + 2x 5/8"
1x 5/8"+ 1x 5/8"
2x 5/8"+ 2x 5/8"
--8" -- NON-RATEDS8.0 20 GA 9 1/4"
--8" -- NON-RATEDS8.0d 20 GA 10 1/2"
1x 5/8" + 1x 5/8"
2x 5/8" + 2x 5/8"
--3 5/8" -- NON-RATEDS3.0d 20 GA 6 1/8" 2x 5/8" + 2x 5/8"
--8" UL U419S8.1 20 GA 9 1/4"
NON-RATED
1x 5/8"+ 1x 5/8"1 HR
WALL TYPE S (METAL STUD)
SECT. @ FLOOR
5/8" TYPE "X" GYPSUM WALL BOARD (ONE SIDE)
BOTTOM OF DECK
EXTERIOR WALL, MASONRY WALL OR
INTERIOR PARTITION - SEE FLOOR
PLAN
SCHEDULED CEILING. SEE REFLECTED
CEILING PLAN FOR HEIGHT.
F0.0
FURRING
CHANNEL SIZE
PARTITION
WIDTH
7/8" 1-1/2"
MARK
FURRING CHANNEL
F1.0 1 5/8" 2-1/4"
SCHEDULED FLOOR FINISH AND BASE
SECT. @ FLOOR
SECT. @ CLG.
PLAN VIEW
GYPSUM WALL BOARD (ONE SIDE)
BOTTOM OF DECK
EXTERIOR WALL, MASONRY WALL OR
INTERIOR PARTITION - SEE FLOOR
PLAN
SCHEDULED CEILING. SEE REFLECTED
CEILING PLAN FOR HEIGHT.
STEEL STUDS @ 16" O.C.
STUD SIZE
2 1/2"F2.0
GAUGE
PARTITION
WIDTH
18 GA 3 1/8"
SECT. @ CLG.
PLAN VIEW
MARKSTC
FIRE TEST
DESIGN NO. FIRE RATING
-- NON-RATED
---- NON-RATED
STC
FIRE TEST
DESIGN NO. FIRE RATING
-- NON-RATED
---- NON-RATED
3/
4" M
IN
6" M
IN
SCHEDULED FLOOR FINISH AND BASE
ACOUSTICAL SEALANT
3 5/8"F3.0 18 GA 4 1/4"
ACOUSTICAL SEALANT
SOUND ATTENUATION BATT INSULATION (TO
UNDERSIDE OF DECK) AT 'i' SUFFIX
ACOUSTICAL SEALANT AT 'i' SUFFIX
CONTINUE GYPSUM BOARD TO DECK
AT 'i' SUFFIX & 'e' SUFFIX
NON-RATED18 GA ----
43-45-- NON-RATED3 5/8"F3.0i 18 GA 4 1/4"
WALL TYPE F WALL TYPE F
THERMAL INSULATION (TO UNDERSIDE OF
DECK) AT 'e' SUFFIX
6"F6.0 18 GA 6 5/8" ----
3 5/8"F3.0e 4 1/4"
BOTTOM OF DECK
"J" SHAPED RUNNER
SECT. @ FLOOR
SECT. @ CLG.
PLAN VIEW
STEEL C-H STUDS @ 24" O.C.
SCHEDULED CEILING. SEE REFLECTED
CEILING PLAN FOR HEIGHT.
STCSTUD SIZE
FIRE TEST
DESIGN NO. FIRE RATINGGAUGE
PARTITION
WIDTH
1" SHAFT LINER PANEL
FIRE RESISTIVE JOINT SEALANT
FIRESTOP SEALANT
SH2.2 2 HRUL-U4382-1/2" C-H 25 GA 4-3/4"
SCHEDULED BASE MOLDING
5/8" TYPE "X" GYPSUM WALL BOARD (FOR 2 HR
FIRE RATING PROVIDE 2 LAYERS TYPE "X"
GWB FULL HEIGHT)
J-SHAPED RUNNER
WALL TYPE SH (SHAFT ASSEMBLY, METAL C STUDS)
SPRAY FOAM INSULATION;
CLOSED CELL (R-6.5 MIN)
ANCHOR STUDS TO
STRUCTURE/DECK; PROVIDE
SLOTTED DEFLECTION TRACK
(2) 3-5/8" 20 GAUGE - STEEL
STUDS @ 16" O.C.
SCHEDULED CEILING. SEE REFLECTED
CEILING PLAN FOR HEIGHT.
ACOUSTICAL OR FIRE RESISTIVE JOINT
SEALANT (BOTH SIDES)
SCHEDULED BASE MOLDING
FOR DEPTH
VARIES; SEE PLAN
5/8" TYPE 'X' GYP BOARD
2'
WALL TYPE F3.0e FROM
THIS POINT
EXISTING WALL CONSTRUCTION
TO REMAIN
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0134
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
A S e rv ic e
D i s a b le d
Ve t e r an Owne d
Sm a l l
B u s ine ss
SDVOSB
CVE
BID DOCUMENTS
FULLY SPRINKLERED
Location
Issue Date
LABELLA ASSOCIATES, DPC
REGISTERED ARCHITECT
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSOLIDATE DIAGNOSTIC
CANCER CENTER
VA EAST ORANGE CAMPUS
561-18-155
BUILDING 1
Project Director
C U s e rs \z ri z v i\ D o c u m e n ts \R e v it L o c a l F ile s \2
V A
E a s t O ra n g e C a n c e r
C e n te r
A
R C
H z ri z v iF
C
G .r v t
04/22/2022 JR STAFF
A001
PARTITION TYPES & DETAILS
SCALE: 3/4" = 1'-0"A001
1 WALL DETAIL @ INFUSION BAYS
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E
)2 H
R (E
)2 H
R
(E)2HR (E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E )2
H R
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)2HR (E)2HR
(E)2HR
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR
(E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
H
R
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E )1
H R
(E )1
H R (E
)1 H
R (E
)1 H
R (E
)1 H
R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E)1HR (E)1HR
(E)1HR(E)1HR
(E )1
H R
(E )1
H R
(E)1HR(E)1HR
(E)1HR (E)1HR(E)1HR (E)1HR (E)1HR
(E )1
HR
(E )1
HR
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E)1HR(E)1HR
(E)1HR(E)1HR
(E)1HR(E)1HR
(E)1HR(E)1HR
(E)1HR(E)1HR
(E)1HR(E)1HR
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
HR
(E )1
HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)2HR(E)2HR
EXIST
SECURITY
OFFICE
EXIST
ADMIN OFFICE
EXIST
FEMALE
TLT ROOM
EXIST
NAVIGATORS
OFFICE
EXIST
ADMIN OFFICE
EXIST
STARBUCKS
EXIST
RECEPTION
DESK
EXIST
INFO DESK
EXIST
SECURITY
OFFICE
EXIST
LOBBY
EXIST
CORRIDOR
EXIST
MALE TLT RM
EXIST
PATIENT
REGISTRATION
EXIST
OPEN OFFICE
EXIST
OFFICE
EXIST
SHAFTWAY
EXIST
WALK-IN
EXIST
TRIAGE
NURSE
EXIST
TRIAGE
NURSE
EXIST
FILE ROOM
EXIST
MECH ROOM
EXIST
WHEELCHAIR
ALCOVE
EXIST
CLEAN
EXIST
PATIENT TV
AREA
EXIST
OFFICE
EXIST
OFFICE
EXIST
OFFICE
EXIST
CONF. ROOM
EXIST
CONF. ROOM
EXIST
STAIR
EXIST
ELEV #8
EXIST
ELEV #7
EXIST
ELEC
EXIST
HOT LAB
EXIST
UPTAKE
ROOM
EXIST
UPTAKE
ROOM
EXIST
UPTAKE
EXIST
TLT RM
EXIST
PET CONTROL
ROOM
EXIST
CT CONTROL
ROOM
EXIST
PET/CT
SIMULATOR
EXIST
CT
SIMULATOR
EXIST
MECH
EXIST
SOILED
EXIST
OFFICE
WORKSTATION
EXIST
WOMENS
TLT ROOM
EXIST
D.R.
EXIST
D.R.
EXIST
MECH ROOM
EXIST
CORRIDOR
EXIST
ELEC
EXIST
TLT ROOM
EXIST
PATIENT
WAITING
EXIST
CONTROL
ROOM
EXIST
EXAM ROOM
EXIST
H.C. TLT RM
EXIST
EXAM ROOM
EXIST
EXAM ROOM
EXIST
CONTROL
ROOM
EXIST
TREATMENT
ROOM
EXIST
TREATMENT
ROOM
EXIST
STORAGE
EXIST
ISOLATION
ROOM
EXIST
ISOLATION
ROOM
EXIST
OFFICE
EXIST
STAIR
EXIST
ACS URGENT
EXIST
CORRIDOR
EXIST
NURSE
STATION
EXIST
CORRIDOR
EXIST
CORRIDOR
EXIST
ELECTRICAL
ROOM
EXIST
BREAKROOM
EXIST
OFFICE
EXIST
TLT RM
EXIST
COPY
EXIST
D.R.
EXIST
EQUIP
EXIST
SHAFTWAY
EXIST
D.R.
EXIST
CLEAN
SUPPLY
EXIST
CORRIDOR
EXIST
CORRIDOR
EXIST
RECEPTION
EXIST
BAY #3
EXIST
BAY #4
EXIST
BAY #5
EXIST
BAY #6
EXIST
BAY #7
EXIST
BAY #8
EXIST
BAY # 9
EXIST
BAY #10 EXIST
BAY # 11
EXIST
BAY #12
EXIST
CLEAN
UTILITY
EXIST
DIRTY UTILITY
EXIST
BAY #2
EXIST
BAY #1
EXIST
CORRIDOR
EXIST
ENV. SERV.
EXIST
VESTIBULE
EXIST
WAITING
AREA
EXIST
CLOSET
EXIST
ADMITTING
OFFICE
EXIST
EXAM ROOM
EXIST
EXAM ROOM
EXIST
TLT RM
EXIST
ELEC. CLT
EXIST
ELEV #3
EXIST
ELEV #4
EXIST
CLOSET
EXIST
ELEV #2
EXIST
ELEV #1
EXIST
TLT RM
EXIST
MAS EXIST
SHAFTWAY
EXIST
CORRIDOR
EXIST
STORAGE
EXIST
ELEV #6
EXIST
ELEV #5
EXIST
TELEPHONE
EQUIPMENT
EXIST
VEST.
EXIST
RECEIVING /
STORAGE
EXIST
SECURE
STORAGE
EXIST
MAIL ROOM
EXIST
PHARMACIST
EXIST
REFRIGERATION
/ FREEZEREXIST
EQ. ALCOVE
EXIST
RECEPTION
EXIST
COUNSELING
EXIST
H.A.C.
EXIST
TOILET
EXIST
DATA
EXIST
DOSIMETRY
EXIST
EQ. STOR.
EXIST
STORAGE
EXIST
STORAGE
EXIST
ELEC.
EXIST
ELEC.
EXIST
PROCUR
SUPER.
EXIST
CONTROLLED
SUBSTANCE
EXIST
SUPER.
EXIST
ASSEMBLY
EXIST
DISPENSING
EXIST
ELEV. LOBBY
EXIST
VOLUNTEER
EXIST
MECH.
EXIST
STORAGE
EXIST
W/C REPAIR
EXIST
EXAM
EXIST
EXAM
EXIST
CRAWL
SPACE
EXIST
WAITING
EXIST
WAITING
EXIST
RECEPT.
EXIST
CORRIDOR
EXIST
CORRIDOR
10 11 12 13
B
C
E E
F
G
J
15 16
H
L
N
Q
R
P
K
M
3 41 2
D
A
MECHANICAL COURTYARD
AREA 1
AREA 2
AREA 1
AREA 2
S
U
T
GENERAL REMOVAL NOTES:
DASHED LINES INDICATE ITEMS TO BE REMOVED.
ELEMENTS TO REMAIN IN PLACE SHALL BE PROTECTED FROM DAMAGE, DUST AND DEBRIS.
DUST CONTROL SHALL BE THE FULL RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR SHALL PERFORM CLEAN UP OF ALL REFUSE, RUBBISH, SCRAP MATERIALS AND DEBRIS CAUSED BY THE
WORK ON A DAILY BASIS. CLEANING OF AREA SURROUNDING THE WORK AREA WHERE
CONSTRUCTION DEBRIS OR DUST ACCUMULATES WILL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
REFER TO CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTIONS
DRAWINGS FOR DEMOLITION OF ADDITIONAL ITEMS. REFER TO ABATEMENT DRAWINGS FOR
HAZARDOUS MATERIAL DEMOLITION ITEMS.
CONTRACTOR TO MAINTAIN WATER TIGHT INTEGRITY OF BUILDING AT ALL TIMES.
EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION
DOCUMENTS WHEN AVAILABLE AND ARE NOT GUARANTEED. CONTRACTORS ARE RESPONSIBLE FOR
EXAMINING THE BUILDING AND VERIFYING EXISTING CONDITIONS AND ARE TO CONTACT THE
OWNER REPRESENTATIVE REGARDING ANY DISCREPANCIES.
DEMOLITION WORK SHALL INCLUDE REMOVAL OF ALL ITEMS INDICATED TO BE REMOVED AND/OR
SALVAGED, AND LEGAL DISPOSAL OF ITEMS NOT INTENDED FOR SALVAGE. WORK SHALL ALSO
INCLUDE REMOVAL OF ALL MINOR SUPPORTS, BRACKETS, FASTENERS, CONDUITS, PIPING, AND
SIMILAR ITEMS WHICH ARE NOT INDICATED TO REMAIN.
ALL FLOOR AND WALL CONDITIONS WHICH ARE TO RECEIVE NEW CONSTRUCTION ARE TO BE
DEMOLISHED AS INDICATED AND PROPERLY PREPPED TO RECEIVE NEW FINISHES, U.N.O.
ALL FLOOR, WALL, AND CEILING CONDITIONS THAT ARE DISTURBED BY DEMOLITION ARE TO BE PATCHED, REPAIRED AND/OR PAINTED, WITH SIMILAR MATERIALS AND COLORS. REFER TO NEW WORK FLOOR PLANS, REFLECTED CEILING PLANS, AND FINISH SCHEDULE, INCLUDING PLUMBING
WORK ON FLOORS BELOW
AT WALL REMOVAL FOR MECHANICAL PENETRATIONS, OPENING TO BE APPROXIMATELY 6" LARGER
THAN DUCT SIZE ON ALL SIDES. COORDINATE WITH MECHANICAL DRAWINGS.
ALL EMBOSSED DECORATIVE DOOR KNOBS TO BE SALVAGED AND TURNED OVER TO OWNER.
FOR ADDITIONAL REMOVAL INFORMATION REFER TO SECTIONS AND DETAILS.
REMOVE ANY WALL MOUNTED ITEMS ALONG EXTERIOR WALLS WITHIN THE SCOPE OF WORK AND
PREP FOR NEW FURRING WALLS.
REFER TO ENLARGED DEMOLITION PLANS FOR MORE INFORMATION.
EXTERIOR WINDOWS ARE TO BE REPLACED IN A SEPARATE CONTRACT, THEY ARE NOT INCLUDED IN
THE SCOPE OF WORK.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
EXISTING WALL TO BE REMOVED
EXISTING DOOR AND FRAME TO BE REMOVED
EXISTING WALL TO REMAIN
EXISTING DOOR TO REMAIN
REMOVAL LEGEND:
AREA NOT IN PROJECT SCOPE
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0134
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
A S e rv ic e
D i s a b le d
Ve t e r an Owne d
Sm a l l
B u s ine ss
SDVOSB
CVE
BID DOCUMENTS
FULLY SPRINKLERED
Location
Issue Date
LABELLA ASSOCIATES, DPC
REGISTERED ARCHITECT
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSOLIDATE DIAGNOSTIC
CANCER CENTER
VA EAST ORANGE CAMPUS
561-18-155
BUILDING 1
Project Director
PLAN
NORTH
ACTUAL
NORTH
KEYPLAN
C U s e rs \z ri z v i\ D o c u m e n ts \R e v it L o c a l F ile s \2
V A
E a s t O ra n g e C a n c e r
C e n te r
A
R C
H z ri z v iF
C
G .r v t
04/22/2022 JR STAFF
AD100
PARTIAL A-LEVEL DEMOLITION PLAN
SCALE: 3/32" = 1'-0"AD100
2 PARTIAL A-LEVEL DEMOLITION PLAN
DEMO KEYNOTES
1 REMOVE EXISTING DOOR, FRAME, & HARDWARE.
1A REMOVE EXISTING DOOR & ASSOCIATED HARDWARE; PREP DOOR FRAME TO RECEIVE NEW DOOR &
HARDWARE
1B REMOVE & SALVAGE EXISTING DOOR, FRAME & ASSOCIATED HARDWARE
2 REMOVE EXISTING FLOORING & BASE DOWN TO CONCRETE. PREP SURFACE TO RECIEVE NEW
FLOORING.
3 DEMO EXISTING INTERIOR PARTITION AND/OR FURRING WALLS TO THE EXTENT SHOWN. COORDINATE
DISPOSAL OF ANY WALL MOUNTED ITEMS WITH VA.
4 REMOVE EXISTING CEILING SYSTEM INCLUDING SUPPORT SYSTEMS, GYP. SOFFITS, LIGHT FIXTURES, AND OTHER CEILING MOUNTED ITEMS. COORDINATE WITH MEP DRAWINGS FOR ADDITIONAL
INFORMATION.
4A REMOVE PORTION OF EXISTING CEILING AND LIGHTING(IF NECESSARY) TO PERFORM MECHANICAL WORK INDICATED IN ENGINEERING DRAWINGS. PATCH AND PREP FOR RE-INSTALLATION OF CEILING
AND LIGHTING TO MATCH EXISTING.
5 REMOVE EXISTING PLUMBING FIXTURE AND ASSOCIATED ACCESSORIES. COORDINATE WITH MEP
DRAWINGS FOR ADDITIONAL INFORMATION.
6 REMOVE PORTION OF EXISTING WALL TO RECEIVE NEW DOOR. COORDINATE WITH NEW WORK FOR
OPENING SIZE AND LOCATION.
7 REMOVE EXISTING LOCKERS.
8 REMOVE EXISTING FLOORING AND BASE DOWN TO CONCRETE TO THE EXTENT SHOWN. COORDINATE
WITH NEW WORK. REPAIR AND MATCH ANY EXISTING FLOORING TO REMAIN AROUND NEW WORK.
9 REMOVE EXISTING CEILING SYSTEM TO THE EXTENT SHOWN. COORDINATE WITH NEW WORK. REPAIR
AND MATCH ANY EXISTING CEILING TO REMAIN AROUND NEW WORK.
10 REMOVE EXISTING MILLWORK/CASEWORK & CONFIRM WITH VA WHAT PIECES ARE TO BE SALVAGED.
COORDINATE WITH ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
11 REMOVE EXISTING HALF-WALL AND SILL.
12 TEMPORARILY REMOVE CEILING SYSTEM AS NEEDED FOR MECHANICAL, ELECTRICAL, PLUMBING
WORK. REPLACE AFTER COMPLETED WORK. REPAIR ANY DAMAGED CEILING.
13 REMOVE EXISTING FIRE EXTINGUISHER, CABINET, SUPPORTS, AND ASSOCIATED MOUNTING ITEMS.
PATCH AND REPAIR EXISTING WALL - MATCH EXISTING FINISHES.
14 REMOVE EXISTING PATIENT HEADWALL. COORDINATE WITH MEP DEMOLITION.
15 REMOVE EXISTING SHOWER CURB, GRAB BARS, WALL TILE, AND PLUMBING FIXTURES. COORDINATE
W/ PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
16 REMOVE EXISTING GRAB BARS, WALL TILE, PLUMBING FIXTURES, AND ANY OTHER WALL MOUNTED
ACCESSORIES. COORDINATE W/ PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
17 REMOVE ALL WALL PROTECTION AND OTHER WALL MOUNTED ITEMS ON EXISTING WALL, PREP TO
RECEIVE NEW PAINT.
18 REMOVE EXISTING HEATER UNDER WINDOW. PREP AREA FOR NEW WALL FURRING.
19 REMOVE EXISTING AUTOMATIC DOOR RAILING AND FLOOR MAT.
20 REMOVE EXISTING DOOR JAMB AND HEADER.
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E)2HR (E)2HR(E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)2HR (E)2HR(E)2HR
(E )2
H R
(E )2
H R
(E)2HR
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)1SB (E)1SB(E)1SB(E
)1
S B
(E )1
S B
(E)1SB(E)1SB
(E )1
S B
(E )1
S B
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)2HR (E)2HR
(E)2HR
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E)1HR (E)1HR
(E)1HR(E)1HR
(E )1
H R
(E )1
H R
(E)1HR(E)1HR
(E)1HR (E)1HR(E)1HR (E)1HR (E)1HR
(E )1
HR
(E )1
HR
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E)1HR(E)1HR
(E)1HR(E)1HR
(E)1HR(E)1HR
(E)1HR(E)1HR
(E)1HR(E)1HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)2HR(E)2HR
GENERAL REMOVAL NOTES:
DASHED LINES INDICATE ITEMS TO BE REMOVED.
ELEMENTS TO REMAIN IN PLACE SHALL BE PROTECTED FROM DAMAGE, DUST AND DEBRIS.
DUST CONTROL SHALL BE THE FULL RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR SHALL PERFORM CLEAN UP OF ALL REFUSE, RUBBISH, SCRAP MATERIALS AND DEBRIS CAUSED BY THE
WORK ON A DAILY BASIS. CLEANING OF AREA SURROUNDING THE WORK AREA WHERE
CONSTRUCTION DEBRIS OR DUST ACCUMULATES WILL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
REFER TO CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTIONS
DRAWINGS FOR DEMOLITION OF ADDITIONAL ITEMS. REFER TO ABATEMENT DRAWINGS FOR
HAZARDOUS MATERIAL DEMOLITION ITEMS.
CONTRACTOR TO MAINTAIN WATER TIGHT INTEGRITY OF BUILDING AT ALL TIMES.
EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION
DOCUMENTS WHEN AVAILABLE AND ARE NOT GUARANTEED. CONTRACTORS ARE RESPONSIBLE FOR
EXAMINING THE BUILDING AND VERIFYING EXISTING CONDITIONS AND ARE TO CONTACT THE
OWNER REPRESENTATIVE REGARDING ANY DISCREPANCIES.
DEMOLITION WORK SHALL INCLUDE REMOVAL OF ALL ITEMS INDICATED TO BE REMOVED AND/OR
SALVAGED, AND LEGAL DISPOSAL OF ITEMS NOT INTENDED FOR SALVAGE. WORK SHALL ALSO
INCLUDE REMOVAL OF ALL MINOR SUPPORTS, BRACKETS, FASTENERS, CONDUITS, PIPING, AND
SIMILAR ITEMS WHICH ARE NOT INDICATED TO REMAIN.
ALL FLOOR AND WALL CONDITIONS WHICH ARE TO RECEIVE NEW CONSTRUCTION ARE TO BE
DEMOLISHED AS INDICATED AND PROPERLY PREPPED TO RECEIVE NEW FINISHES, U.N.O.
ALL FLOOR, WALL, AND CEILING CONDITIONS THAT ARE DISTURBED BY DEMOLITION ARE TO BE PATCHED, REPAIRED AND/OR PAINTED, WITH SIMILAR MATERIALS AND COLORS. REFER TO NEW WORK FLOOR PLANS, REFLECTED CEILING PLANS, AND FINISH SCHEDULE, INCLUDING PLUMBING
WORK ON FLOORS BELOW
AT WALL REMOVAL FOR MECHANICAL PENETRATIONS, OPENING TO BE APPROXIMATELY 6" LARGER
THAN DUCT SIZE ON ALL SIDES. COORDINATE WITH MECHANICAL DRAWINGS.
ALL EMBOSSED DECORATIVE DOOR KNOBS TO BE SALVAGED AND TURNED OVER TO OWNER.
FOR ADDITIONAL REMOVAL INFORMATION REFER TO SECTIONS AND DETAILS.
REMOVE ANY WALL MOUNTED ITEMS ALONG EXTERIOR WALLS WITHIN THE SCOPE OF WORK AND
PREP FOR NEW FURRING WALLS.
REFER TO ENLARGED DEMOLITION PLANS FOR MORE INFORMATION.
EXTERIOR WINDOWS ARE TO BE REPLACED IN A SEPARATE CONTRACT, THEY ARE NOT INCLUDED IN
THE SCOPE OF WORK.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
EXISTING WALL TO BE REMOVED
EXISTING DOOR AND FRAME TO BE REMOVED
EXISTING WALL TO REMAIN
EXISTING DOOR TO REMAIN
REMOVAL LEGEND:
AREA NOT IN PROJECT SCOPE
EXIST
PATIENT
REGISTRATION
EXIST
OPEN OFFICE
EXIST
OFFICE
EXIST
SHAFTWAY
EXIST
FILE ROOM
EXIST
MECH ROOM
EXIST
OFFICE
EXIST
OFFICE
EXIST
OFFICE
EXIST
CONF. ROOM
EXIST
CONF. ROOM
EXIST
STAIR
EXIST
ELEV #8
EXIST
ELEV #7
EXIST
ELEC
EXIST
HOT LAB
EXIST
UPTAKE
ROOM
EXIST
UPTAKE
ROOM
EXIST
UPTAKE
EXIST
TLT RM
EXIST
PET CONTROL
ROOM
EXIST
CT CONTROL
ROOM
EXIST
PET/CT
SIMULATOR
EXIST
CT
SIMULATOR
EXIST
MECH
EXIST
SOILED
EXIST
BREAKROOM
EXIST
OFFICE
EXIST
D.R.
EXIST
EQUIP
EXIST
SHAFTWAY
EXIST
D.R.
EXIST
CLEAN
SUPPLY
EXIST
CORRIDOR
EXIST
CORRIDOR
EXIST
ADMITTING
OFFICE
EXIST
EXAM ROOM
EXIST
EXAM ROOM
EXIST
TLT RM
EXIST
ELEC. CLT
EXIST
ELEV #3
EXIST
ELEV #4 EXIST
CLOSET
EXIST
TLT RM
EXIST
CORRIDOR
EXIST
STORAGE
EXIST
TELEPHONE
EQUIPMENT
EXIST
VEST.
EXIST
RECEPTION
EXIST
COUNSELING
EXIST
H.A.C. EXIST
TOILET
J
L
N
R
P
K
M M
MATCH LINE
1 / AD102
2 4
1 1
2 4
2 4
2 4
3 3
2 4
2 4
3 3
2 4
2 4
2 4
2 4
2 4
2 4
2 4
2 4
2 4
2 4
4"
S
U
T
3' - 4"1 3/8"
1'
/2
3'
4"
3'
" 4
3'
1'
3' - 4" 4' - 1 11/32"
2 4
DEDUCT ALT-1
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0134
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
A S e rv ic e
D i s a b le d
Ve t e r an Owne d
Sm a l l
B u s ine ss
SDVOSB
CVE
BID DOCUMENTS
FULLY SPRINKLERED
Location
Issue Date
LABELLA ASSOCIATES, DPC
REGISTERED ARCHITECT
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSOLIDATE DIAGNOSTIC
CANCER CENTER
VA EAST ORANGE CAMPUS
561-18-155
BUILDING 1
Project Director
PLAN
NORTH
ACTUAL
NORTH
KEYPLAN
C U s e rs \z ri z v i\ D o c u m e n ts \R e v it L o c a l F ile s \2
V A
E a s t O ra n g e C a n c e r
C e n te r
A
R C
H z ri z v iF
C
G .r v t
04/22/2022 JR AB
AD101
PARTIAL A-LEVEL DEMOLITION PLAN -
AREA 1
DEMO KEYNOTES
1 REMOVE EXISTING DOOR, FRAME, & HARDWARE.
1A REMOVE EXISTING DOOR & ASSOCIATED HARDWARE; PREP DOOR FRAME TO RECEIVE NEW DOOR &
HARDWARE
1B REMOVE & SALVAGE EXISTING DOOR, FRAME & ASSOCIATED HARDWARE
2 REMOVE EXISTING FLOORING & BASE DOWN TO CONCRETE. PREP SURFACE TO RECIEVE NEW
FLOORING.
3 DEMO EXISTING INTERIOR PARTITION AND/OR FURRING WALLS TO THE EXTENT SHOWN. COORDINATE
DISPOSAL OF ANY WALL MOUNTED ITEMS WITH VA.
4 REMOVE EXISTING CEILING SYSTEM INCLUDING SUPPORT SYSTEMS, GYP. SOFFITS, LIGHT FIXTURES, AND OTHER CEILING MOUNTED ITEMS. COORDINATE WITH MEP DRAWINGS FOR ADDITIONAL
INFORMATION.
4A REMOVE PORTION OF EXISTING CEILING AND LIGHTING(IF NECESSARY) TO PERFORM MECHANICAL WORK INDICATED IN ENGINEERING DRAWINGS. PATCH AND PREP FOR RE-INSTALLATION OF CEILING
AND LIGHTING TO MATCH EXISTING.
5 REMOVE EXISTING PLUMBING FIXTURE AND ASSOCIATED ACCESSORIES. COORDINATE WITH MEP
DRAWINGS FOR ADDITIONAL INFORMATION.
6 REMOVE PORTION OF EXISTING WALL TO RECEIVE NEW DOOR. COORDINATE WITH NEW WORK FOR
OPENING SIZE AND LOCATION.
7 REMOVE EXISTING LOCKERS.
8 REMOVE EXISTING FLOORING AND BASE DOWN TO CONCRETE TO THE EXTENT SHOWN. COORDINATE
WITH NEW WORK. REPAIR AND MATCH ANY EXISTING FLOORING TO REMAIN AROUND NEW WORK.
9 REMOVE EXISTING CEILING SYSTEM TO THE EXTENT SHOWN. COORDINATE WITH NEW WORK. REPAIR
AND MATCH ANY EXISTING CEILING TO REMAIN AROUND NEW WORK.
10 REMOVE EXISTING MILLWORK/CASEWORK & CONFIRM WITH VA WHAT PIECES ARE TO BE SALVAGED.
COORDINATE WITH ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
11 REMOVE EXISTING HALF-WALL AND SILL.
12 TEMPORARILY REMOVE CEILING SYSTEM AS NEEDED FOR MECHANICAL, ELECTRICAL, PLUMBING
WORK. REPLACE AFTER COMPLETED WORK. REPAIR ANY DAMAGED CEILING.
13 REMOVE EXISTING FIRE EXTINGUISHER, CABINET, SUPPORTS, AND ASSOCIATED MOUNTING ITEMS.
PATCH AND REPAIR EXISTING WALL - MATCH EXISTING FINISHES.
14 REMOVE EXISTING PATIENT HEADWALL. COORDINATE WITH MEP DEMOLITION.
15 REMOVE EXISTING SHOWER CURB, GRAB BARS, WALL TILE, AND PLUMBING FIXTURES. COORDINATE
W/ PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
16 REMOVE EXISTING GRAB BARS, WALL TILE, PLUMBING FIXTURES, AND ANY OTHER WALL MOUNTED
ACCESSORIES. COORDINATE W/ PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
17 REMOVE ALL WALL PROTECTION AND OTHER WALL MOUNTED ITEMS ON EXISTING WALL, PREP TO
RECEIVE NEW PAINT.
18 REMOVE EXISTING HEATER UNDER WINDOW. PREP AREA FOR NEW WALL FURRING.
19 REMOVE EXISTING AUTOMATIC DOOR RAILING AND FLOOR MAT.
20 REMOVE EXISTING DOOR JAMB AND HEADER.
SCALE: 3/16" = 1'-0"AD101
1 PARTIAL A-LEVEL DEMOLITION PLAN - AREA 1
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)2HR(E)2HR
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E)1HR(E)1HR
(E )1
H R
(E)1HR(E)1HR
(E)1HR(E)1HR
(E)1HR(E)1HR
(E)1HR(E)1HR
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
H R
(E )1
HR
(E )1
HR
(E)2HR(E)2HR
EXISTING WALL TO BE REMOVED
EXISTING DOOR AND FRAME TO BE REMOVED
EXISTING WALL TO REMAIN
EXISTING DOOR TO REMAIN
REMOVAL LEGEND:
AREA NOT IN PROJECT SCOPE
GENERAL REMOVAL NOTES:
DASHED LINES INDICATE ITEMS TO BE REMOVED.
ELEMENTS TO REMAIN IN PLACE SHALL BE PROTECTED FROM DAMAGE, DUST AND DEBRIS.
DUST CONTROL SHALL BE THE FULL RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR SHALL PERFORM CLEAN UP OF ALL REFUSE, RUBBISH, SCRAP MATERIALS AND DEBRIS CAUSED BY THE
WORK ON A DAILY BASIS. CLEANING OF AREA SURROUNDING THE WORK AREA WHERE
CONSTRUCTION DEBRIS OR DUST ACCUMULATES WILL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
REFER TO CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTIONS
DRAWINGS FOR DEMOLITION OF ADDITIONAL ITEMS. REFER TO ABATEMENT DRAWINGS FOR
HAZARDOUS MATERIAL DEMOLITION ITEMS.
CONTRACTOR TO MAINTAIN WATER TIGHT INTEGRITY OF BUILDING AT ALL TIMES.
EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION
DOCUMENTS WHEN AVAILABLE AND ARE NOT GUARANTEED. CONTRACTORS ARE RESPONSIBLE FOR
EXAMINING THE BUILDING AND VERIFYING EXISTING CONDITIONS AND ARE TO CONTACT THE
OWNER REPRESENTATIVE REGARDING ANY DISCREPANCIES.
DEMOLITION WORK SHALL INCLUDE REMOVAL OF ALL ITEMS INDICATED TO BE REMOVED AND/OR
SALVAGED, AND LEGAL DISPOSAL OF ITEMS NOT INTENDED FOR SALVAGE. WORK SHALL ALSO
INCLUDE REMOVAL OF ALL MINOR SUPPORTS, BRACKETS, FASTENERS, CONDUITS, PIPING, AND
SIMILAR ITEMS WHICH ARE NOT INDICATED TO REMAIN.
ALL FLOOR AND WALL CONDITIONS WHICH ARE TO RECEIVE NEW CONSTRUCTION ARE TO BE
DEMOLISHED AS INDICATED AND PROPERLY PREPPED TO RECEIVE NEW FINISHES, U.N.O.
ALL FLOOR, WALL, AND CEILING CONDITIONS THAT ARE DISTURBED BY DEMOLITION ARE TO BE PATCHED, REPAIRED AND/OR PAINTED, WITH SIMILAR MATERIALS AND COLORS. REFER TO NEW WORK FLOOR PLANS, REFLECTED CEILING PLANS, AND FINISH SCHEDULE, INCLUDING PLUMBING
WORK ON FLOORS BELOW
AT WALL REMOVAL FOR MECHANICAL PENETRATIONS, OPENING TO BE APPROXIMATELY 6" LARGER
THAN DUCT SIZE ON ALL SIDES. COORDINATE WITH MECHANICAL DRAWINGS.
ALL EMBOSSED DECORATIVE DOOR KNOBS TO BE SALVAGED AND TURNED OVER TO OWNER.
FOR ADDITIONAL REMOVAL INFORMATION REFER TO SECTIONS AND DETAILS.
REMOVE ANY WALL MOUNTED ITEMS ALONG EXTERIOR WALLS WITHIN THE SCOPE OF WORK AND
PREP FOR NEW FURRING WALLS.
REFER TO ENLARGED DEMOLITION PLANS FOR MORE INFORMATION.
EXTERIOR WINDOWS ARE TO BE REPLACED IN A SEPARATE CONTRACT, THEY ARE NOT INCLUDED IN
THE SCOPE OF WORK.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
EXIST
SECURITY
OFFICE
EXIST
ADMIN OFFICE
EXIST
FEMALE
TLT ROOM
EXIST
NAVIGATORS
OFFICE
EXIST
ADMIN OFFICE
EXIST
INFO DESK
EXIST
CORRIDOR
EXIST
MALE TLT RM
EXIST
WHEELCHAIR
ALCOVE
EXIST
CLEAN
EXIST
PATIENT TV
AREA
EXIST
OFFICE
EXIST
MECH
EXIST
SOILED
EXIST
OFFICE
WORKSTATION
EXIST
WOMENS
TLT ROOM
EXIST
D.R.
EXIST
D.R.
EXIST
MECH ROOM
EXIST
CORRIDOR
EXIST
ELEC
EXIST
TLT ROOM
EXIST
PATIENT
WAITING
EXIST
CONTROL
ROOM
EXIST
EXAM ROOM
EXIST
H.C. TLT RM
EXIST
EXAM ROOM
EXIST
EXAM ROOM
EXIST
CONTROL
ROOM
EXIST
TREATMENT
ROOM
EXIST
TREATMENT
ROOM
EXIST
STORAGE
EXIST
ISOLATION
ROOM
EXIST
ISOLATION
ROOM
EXIST
OFFICE
EXIST
ACS URGENT
EXIST
CORRIDOR
EXIST
NURSE
STATION
EXIST
CORRIDOR
EXIST
CORRIDOR
EXIST
ELECTRICAL
ROOM
EXIST
BREAKROOM
EXIST
OFFICE
EXIST
TLT RM
EXIST
COPY
EXIST
D.R.
EXIST
CORRIDOR
EXIST
RECEPTION
EXIST
BAY #3
EXIST
BAY #4
EXIST
BAY #5
EXIST
BAY #6
EXIST
BAY #7
EXIST
BAY #8
EXIST
BAY # 9
EXIST
BAY #10
EXIST
BAY # 11 EXIST
BAY #12
EXIST
CLEAN
UTILITY
EXIST
DIRTY UTILITY
EXIST
BAY #2
EXIST
BAY #1
EXIST
CORRIDOR
EXIST
ENV. SERV.
EXIST
VESTIBULE
EXIST
WAITING
AREA
EXIST
CLOSET
EXIST
TLT RM
EXIST
TLT RM
EXIST
DOSIMETRY
EXIST
EQ. STOR.
EXIST
STORAGE
EXIST
STORAGE
EXIST
ELEC.
B
C
E
E
F
G
J
H
K
D
10' - 7"
2 4
1 1
2 4
2 4
2 4
MATCH LINE
1 / AD101
2 4 2 4
2 42 4
2 4
2 4
2 4
2 4
2 4
2 4
2 4
2 4
1A
2 4
2 4
4 2
A
3' - 4" 4' - 1 11/32"
4"
3'
3' - 6"3' - 8" 6
7' - 0 7/16"
1B
5'
EXIST
STAIR 1
4A
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0134
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
A S e rv ic e
D i s a b le d
Ve t e r an Owne d
Sm a l l
B u s ine ss
SDVOSB
CVE
BID DOCUMENTS
FULLY SPRINKLERED
Location
Issue Date
LABELLA ASSOCIATES, DPC
REGISTERED ARCHITECT
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSOLIDATE DIAGNOSTIC
CANCER CENTER
VA EAST ORANGE CAMPUS
561-18-155
BUILDING 1
Project Director
PLAN
NORTH
ACTUAL
NORTH
KEYPLAN
C U s e rs \z ri z v i\ D o c u m e n ts \R e v it L o c a l F ile s \2
V A
E a s t O ra n g e C a n c e r
C e n te r
A
R C
H z ri z v iF
C
G .r v t
04/22/2022 JR AB
AD102
PARTIAL A-LEVEL DEMOLITION PLAN -
AREA 2
DEMO KEYNOTES
1 REMOVE EXISTING DOOR, FRAME, & HARDWARE.
1A REMOVE EXISTING DOOR & ASSOCIATED HARDWARE; PREP DOOR FRAME TO RECEIVE NEW DOOR &
HARDWARE
1B REMOVE & SALVAGE EXISTING DOOR, FRAME & ASSOCIATED HARDWARE
2 REMOVE EXISTING FLOORING & BASE DOWN TO CONCRETE. PREP SURFACE TO RECIEVE NEW
FLOORING.
3 DEMO EXISTING INTERIOR PARTITION AND/OR FURRING WALLS TO THE EXTENT SHOWN. COORDINATE
DISPOSAL OF ANY WALL MOUNTED ITEMS WITH VA.
4 REMOVE EXISTING CEILING SYSTEM INCLUDING SUPPORT SYSTEMS, GYP. SOFFITS, LIGHT FIXTURES, AND OTHER CEILING MOUNTED ITEMS. COORDINATE WITH MEP DRAWINGS FOR ADDITIONAL
INFORMATION.
4A REMOVE PORTION OF EXISTING CEILING AND LIGHTING(IF NECESSARY) TO PERFORM MECHANICAL WORK INDICATED IN ENGINEERING DRAWINGS. PATCH AND PREP FOR RE-INSTALLATION OF CEILING
AND LIGHTING TO MATCH EXISTING.
5 REMOVE EXISTING PLUMBING FIXTURE AND ASSOCIATED ACCESSORIES. COORDINATE WITH MEP
DRAWINGS FOR ADDITIONAL INFORMATION.
6 REMOVE PORTION OF EXISTING WALL TO RECEIVE NEW DOOR. COORDINATE WITH NEW WORK FOR
OPENING SIZE AND LOCATION.
7 REMOVE EXISTING LOCKERS.
8 REMOVE EXISTING FLOORING AND BASE DOWN TO CONCRETE TO THE EXTENT SHOWN. COORDINATE
WITH NEW WORK. REPAIR AND MATCH ANY EXISTING FLOORING TO REMAIN AROUND NEW WORK.
9 REMOVE EXISTING CEILING SYSTEM TO THE EXTENT SHOWN. COORDINATE WITH NEW WORK. REPAIR
AND MATCH ANY EXISTING CEILING TO REMAIN AROUND NEW WORK.
10 REMOVE EXISTING MILLWORK/CASEWORK & CONFIRM WITH VA WHAT PIECES ARE TO BE SALVAGED.
COORDINATE WITH ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
11 REMOVE EXISTING HALF-WALL AND SILL.
12 TEMPORARILY REMOVE CEILING SYSTEM AS NEEDED FOR MECHANICAL, ELECTRICAL, PLUMBING
WORK. REPLACE AFTER COMPLETED WORK. REPAIR ANY DAMAGED CEILING.
13 REMOVE EXISTING FIRE EXTINGUISHER, CABINET, SUPPORTS, AND ASSOCIATED MOUNTING ITEMS.
PATCH AND REPAIR EXISTING WALL - MATCH EXISTING FINISHES.
14 REMOVE EXISTING PATIENT HEADWALL. COORDINATE WITH MEP DEMOLITION.
15 REMOVE EXISTING SHOWER CURB, GRAB BARS, WALL TILE, AND PLUMBING FIXTURES. COORDINATE
W/ PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
16 REMOVE EXISTING GRAB BARS, WALL TILE, PLUMBING FIXTURES, AND ANY OTHER WALL MOUNTED
ACCESSORIES. COORDINATE W/ PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
17 REMOVE ALL WALL PROTECTION AND OTHER WALL MOUNTED ITEMS ON EXISTING WALL, PREP TO
RECEIVE NEW PAINT.
18 REMOVE EXISTING HEATER UNDER WINDOW. PREP AREA FOR NEW WALL FURRING.
19 REMOVE EXISTING AUTOMATIC DOOR RAILING AND FLOOR MAT.
20 REMOVE EXISTING DOOR JAMB AND HEADER.
SCALE: 3/16" = 1'-0"AD102
1 PARTIAL A-LEVEL DEMOLITION PLAN - AREA 2
REF.
1S B
1S B
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E)2HR (E)2HR(E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E )2
H R
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)2HR (E)2HR(E)2HR
1S B
1S B
1S B
1S B
1HR1HR
H
R
H R
1HR1HR
H
R
H R
1S B
1S B
1S B
1S B
1SB 1SB
1S B
1S B
1SB 1SB
(E)1SB (E)1SB(E)1SB
1S B
1S B
1S B
1S B
(E )2
H R
(E )2
H R
1SB 1SB1SB 1SB 1SB
S M
S M
SMSM
S M
S M
H
R
H R
H
R
H R
1HR 1HR1HR 1HR 1HR 1HR
SMSM
(E)2HR
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR
(E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
H
R
H R
(E)2HR(E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)1SB (E)1SB(E)1SB
(E )1
S B
(E )1
S
B(E)1SB(E)1SB
(E )1
S B
(E )1
S B
10 11 12 13
B
C
E
F
G
J
15 16
H
L
N
Q
R
P
K
M
3 41 2
D
PHARM.
SPEC.
A-472
PRIVATE
INFUSION
BAY 6
A-476
INFUSION
BAY 7
A-470.7
INFUSION
BAY 8
A-470.8
PRIVATE
INFUSION
BAY 9
A-477
INFUSION
BAY 1
A-470.1
INFUSION
BAY 4
A-470.4
INFUSION
BAY 5
A-470.5
INFUSION
BAY 2
A-470.2
INFUSION
BAY 3
A-470.3
INFUSION
BAY 10
A-470.10
INFUSION
BAY 11
A-470.11
INFUSION
BAY 12
A-470.12
INFUSION
BAY 13
A-470.13
MED. RM.
A-471
NURSE
STATION
A-475
WOMENS
TOILET
A-498
MENS
TOILET
A-499
RECEPTION
A-497
NP/EXAM 1
A-495
NP/EXAM 2
A-494
NP/EXAM 3
A-493
NP/EXAM 4
A-492
NP/EXAM 5
A-491
EXAM 1
A-428
432 SF
WAITING
ROOM
A-496
STAFF
TOILET /
SHOWER
A-479
O2 TANK
STOR.
A-478
ELEC. ROOM
AE-430
SOILED
UTILITY
A-431
EXAM 6
A-423
CONSULT
A-422
ELEC. CL.
AE-421
CT SIM
DRESS. RM
A-435A
TOILET
A-434
EX. CLEAN
SUPPLY
A-403
CT CONTROL
ROOM
A-439
CT
SIMULATOR
A-438
PET
CONTROL
ROOM
A-404
D.R.
A-402
TOILET
A-401
PET / CT
SIMULATOR
A-405
HOT
ROOM
A-409
HOT LAB
A-408
HOT ROOM
A-407
HOT ROOM
A-406
CHIEF OF
PHYSICS
A-447
WOMENS
TOILET
A-445
MECHANICAL
ROOM
AM-443
DR
A-444A
DR
A-444B
CONTROL
RM
A-463A
LINAC VAULT
A-463
EXAM
A-452
TOILET
A-451
TOILET
A-506
53 SF
ELEC.
248 SF
SECURITY
OFFICE
SECURITY
HOLDING
A-509
PSYCH. 1
A-502
PSYCH. 2
A-503
RAD. ONC.
SERVICE
CHIEF
OFFICE
A-504
STOR.
A-505
AO
A-507
M.A.S.
OFFICE
A-508
EXAM
A-453
EXAM
A-454
112 SF
OFFICE
129 SF
OFFICE
151 SF
OFFICE
ELEC.
AE-501
75 SF
ELEV. 8
88 SF
ELEV. 7
76 SF
ELEV. 2
75 SF
ELEV. 1
77 SF
ELEV. 4
78 SF
ELEV. 3
275 SF
COFFEE
1330 SF
LOBBY
121 SF
RECEPTION
STOR.
A-460E
EQUIP.
A-460B
LINAC VAULT
A-460
STOR.
A458
DOSIMETRY
A-456
CONTROL
A-459
LINK
A-360
EXAM 2
A-427
CLEAN
UTILITY
A-432
PATIENT ACCESS CORRIDOR
STOR.
A-433
ELEC.
A-441
4'
WC
SCALE
REF.
FUTURE OC. UNIT
STOR.
A-460D
ELEC.
A-461
MECHANICAL COURTYARD
CRASH
CART
SOILED
UTILITY
A-436
MAIN CANCER
CENTER ENTRY
MECH.
AM-437
EMERGENCY
EXIT ONLY,
NO ENTRY
REF. OC.
TOILET
A-473
FR.
U.C.
REF.
N.S.
A-429
EXAM 5
A-424
EXAM 3
A-426
FEMALE
DRESS.
ROOM
A-435B
MD WORK
RM
A-448
PROCEDURE
RM
A-442
AREA 1
AREA 2
AREA 1
AREA 2
CHIEF TECH
A-446
EQ ALCOVE
A-449
EXAM 4
A-425
RAD ONC
A-510
RAD ONC
A-515
RAD ONC
A-514
RAD ONC
A-513
RAD ONC
A-512
SM CONF. /
FAMILY
CONSULT
A-511
WHEELCHAIR
STOR.
A-490B
CORRIDOR
A-500A
CORRIDOR
A-500B
CORRIDOR
A-500C
CORRIDOR
A-500
CORRIDOR
A-500
CORRIDOR
A-490A
CORRIDOR
A-490
CL.
A-460A
HALL
A-455CORRIDOR
A-450B
CORRIDOR
A-450A
DESK
A-462
HALL
A-444
CORRIDOR
A-440B
CORRIDOR
A-440A
CORRIDOR
A-430A
CORRIDOR
A-430B
CORRIDOR
A-470A
NOURISHMENT
A-474
CL.
A-405A
CL.
A-405B
CORRIDOR
A-400
A
4094 SF
CRAWL
SPACE
410 SF
TELE. EQUIP.
55 SF
VEST.
87 SF
TLT
63 SF
HAC
62 SF
MECH.
153 SF
COUNSELING
87 SF
VOLUNTEER 167 SF
WAITING
77 SF
SHOE
FITTING
92 SF
RECEPT.
142 SF
EXAM
169 SF
EXAM
117 SF
W/C REPAIR
1380 SF
STORAGE
949 SF
ELEV. LOBBY
199 SF
PHARMACY
WAITING
2946 SF
MED
STORAGE
547 SF
RECEIVING /
STOR.
93 SF
SECURE
STOR.
161 SF
PHARMACIST
176 SF
CONTROLLED
SUBSTANCE
104 SF
PROCUR
SUPER.
111 SF
SUPER.
103 SF
DISPENSING
S
U
T
A500
CORRIDOR
A-420A
SHARED
WORK RM
A-413
STORAGE
AM-411
CL.
AM-412
BREAKROOM
A-419
MULTI-PURPOSE
ROOM
A-417
STOR.
A-415
MECHANICAL
ROOM
A-418
STAFF LOCKERS
S
TA
FF
L
O C
K E
R S
SHARED
WORK RM
A-414
CORRIDOR
A-410A
CORRIDOR
A-410B
H&W A-480
EXIST
STAIR 1
A501
DEDUCT
ALT-1
CORRIDOR
A-410
GENERAL PLAN NOTES:
1. ALL DIMENSIONS TO BE TAKEN FROM CENTERLINE
OF WALL UNLESS INDICATED OTHERWISE. REFER
TO SHEET A-001 - PARTITION TYPES FOR ACTUAL
DIMENSIONS
2. JOINTS ABUTTING EXISTING WALLS ARE TO BE
TAPED AND FINISHED
3. COORDINATE NEW DATA & POWER LOCATIONS
WITH OWNER AND ELECTRICAL DRAWINGS
4. CONTRACTOR SHALL PROVIDE BLOCKING AS
REQUIRED FOR ALL MILLWORK AND EQUIPMENT
INSTALLATION
5. FURNITURE AND EQUIPMENT TO BE PROVIDED BY
OWNER. VERIFY FINAL LOCATION AND
REQUIREMENTS OF ALL EQUIPMENT WITH OWNER
6. PATCH ALL EXISTING WALLS AS REQUIRED;
PREPARE ALL WALLS FOR PAINT
7. WALLS TO BE PARTITION TYPE S3.0i UNLESS
OTHERWISE NOTED, REFER TO SHEET A-001 -
PARTITION TYPES FOR ADDITIONAL INORMATION
8. ALL EXTERIOR WALLS WITHIN THE PROJECT
SCOPE ARE TO BE FURRED OUT ON THE INTERIOR
WITH PARTITION TYPE F3.0e, REFER TO SHEET
A-001 - PARTITION TYPES FOR ADDITIONAL
INFORMATION.
9. ALL CASEWORK IN ALL EXAM ROOMS IN PROJECT
SCOPE ARE TO BE PRE-MANUFACTURED AND TO
BE SUPPLIED BY CONTRACTOR.
10. ALL FIRE AND SMOKE RATED WALLS AT EXISTING
LOCATIONS ARE TO BE INSPECTED AND UPGRAED
TO MEET INDICATED RATING REQUIREMENTS.
NEW DOOR: SEE DOOR SCHEDULE
FOR ADDITIONAL INFORMATION
DETAIL TAG:
DETAIL NUMBER: TOP
SHEET NUMBER: BOTTOMA101
SIM
DOOR TAGS SEE A600
ROOM TAG
ROOM NAME
150 SF
FIRE EXTINGUISHER CABINET
(1 PER 75FT OF TRAVEL)
FX
FLOOR PLAN LEGEND:
PARTITION TYPES SEE A001XXXX
X AXXX
ELEVATION TAG:
DETAIL NUMBER: ARROW
SHEET NUMBER: CENTER
AUTO-OPERATOR PUSH ACTUATORSPP
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0134
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
A S e rv ic e
D i s a b le d
Ve t e r an Owne d
Sm a l l
B u s ine ss
SDVOSB
CVE
BID DOCUMENTS
FULLY SPRINKLERED
Location
Issue Date
LABELLA ASSOCIATES, DPC
REGISTERED ARCHITECT
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSOLIDATE DIAGNOSTIC
CANCER CENTER
VA EAST ORANGE CAMPUS
561-18-155
BUILDING 1
Project Director
PLAN
NORTH
ACTUAL
NORTH
KEYPLAN
C U s e rs \z ri z v i\ D o c u m e n ts \R e v it L o c a l F ile s \2
V A
E a s t O ra n g e C a n c e r
C e n te r
A
R C
H z ri z v iF
C
G .r v t
04/22/2022 JR AB
A100
PARTIAL A-LEVEL FLOOR PLAN
SCALE: 3/32" = 1'-0"A100
1 PARTIAL A-LEVEL FLOOR PLAN
UP
REF.
1S B
1S B
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E)2HR (E)2HR(E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)2HR (E)2HR(E)2HR
1S B
1S B
1S B
1SB 1SB
(E)1SB (E)1SB(E)1SB
1S B
1S B
1S B
1S B
(E )2
H R
(E )2
H R
1SB 1SB1SB 1SB 1SB
S M
SMSM
S M
H
R
H R
H
R
H R
1HR 1HR1HR 1HR 1HR 1HR
(E)2HR
(E )2
H R
(E )2
H R
(E)2HR (E)2HR
(E)2HR (E)2HR
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR
(E)1SB (E)1SB(E)1SB(E
)1
S B
(E )1
S B
(E)1SB(E)1SB
(E )1
S B
(E )1
S B
10 11 12 13
J
J
15 16
H H
L
N
Q
R
P
K
M
EXAM 6
A-423
CONSULT
A-422
ELEC. CL.
AE-421
CT SIM
DRESS. RM
A-435A
EX. CLEAN
SUPPLY
A-403
CT CONTROL
ROOM
A-439
CT
SIMULATOR
A-438
PET
CONTROL
ROOM
A-404
D.R.
A-402
TOILET
A-401
PET / CT
SIMULATOR
A-405
HOT
ROOM
A-409
HOT LAB
A-408
HOT ROOM
A-407
HOT ROOM
A-406
TOILET
A-506
EXIST
53 SF
ELEC.
PSYCH. 1
A-502
PSYCH. 2
A-503
RAD. ONC.
SERVICE
CHIEF
OFFICE
A-504
STOR.
A-505
AO
A-507
M.A.S.
OFFICE
A-508
ELEC.
AE-501
ELEV. 8
ELEV. 7
ELEV. 4
ELEV. 3
EXAM 2
A-427
STOR.
A-433
MECHANICAL COURTYARD
SOILED
UTILITY
A-436
MECH.
AM-437
EXAM 5
A-424
EXAM 3
A-426
9' - 11 1/2"
7'
/2
A
LI
G N
ALIGN
15' - 3 3/4"
CLR
7' - 10"
MATCH LINE
1 / A102
FEC
(E) FEC
FEC
CORRIDOR
A-430A
EXAM 1
A-428
CORRIDOR
A-410
A-420A
A-422
A-423
A-432
A-435A
A-502A
A-503A
A-507
A-504
A-505
A-506
A400
5'
/2
4'
9'
9'
9'
9'
/2
8'
/2
6'
/2
8'
/2
ALIGN
ALIGN
RAD ONC
A-515
RAD ONC
A-514
RAD ONC
A-513
RAD ONC
A-512 SM CONF. /
FAMILY
CONSULT
A-511
RAD ONC
A-510
EXAM 4
A-425
A-515 A-514 A-513
A-511A
A-512
A-511B
A-510
A-508
A-424
A-427
SOILED
UTILITY
A-431
CLEAN
UTILITY
A-432
A-425
A-426
5' - 0"
5' - 0" 8' - 1" 8' - 5" 8' - 9" 8' - 5"
C
LR
5'
CORRIDOR
A-500C
CORRIDOR
A-500A
CORRIDOR
A-500B
A-500
A-502B
A-503B
S
U
T
5' - 0"
7'
/1 6"
F2.0 F2.0F2.0 F2.0F2.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0eF3.0eF3.0eF3.0e
F3.0e
F3.0e
F3.0e
F3.0eF3.0
F3.0e
F3.0e
F3.0e
F3.0e
F3.0e
S3.0
A-430A
PP
PP
A
LI
G N
ALIGN
ALIGN
10' - 0" 1' - 8"
6'
0"
2'
14' - 2 13/32" 1' - 4"
3' - 11" 3' - 7"
ALIGN
ALIGN
BREAKROOM
A-419
CORRIDOR
A-410A
MULTI-PURPOSE
ROOM
A-417
STORAGE
AM-411
CL.
AM-412
CORRIDOR
A-410B
SHARED
WORK RM
A-414
STOR.
A-415
SHARED
WORK RM
A-413
A403
A501
A501
A501
A501
FX
FX
A-413
A-411
A-412 A-414
A-417
A-419
A-410B
A-415
S3.0
ALIGN
5' - 0"
S3.0
S3.0
5' - 0"
5' - 0"
5' - 0"
5' - 0"
A-410C
DEDUCT
ALT -1
A-430
S3.0
GENERAL PLAN NOTES:
1. ALL DIMENSIONS TO BE TAKEN FROM CENTERLINE
OF WALL UNLESS INDICATED OTHERWISE. REFER
TO SHEET A-001 - PARTITION TYPES FOR ACTUAL
DIMENSIONS
2. JOINTS ABUTTING EXISTING WALLS ARE TO BE
TAPED AND FINISHED
3. COORDINATE NEW DATA & POWER LOCATIONS
WITH OWNER AND ELECTRICAL DRAWINGS
4. CONTRACTOR SHALL PROVIDE BLOCKING AS
REQUIRED FOR ALL MILLWORK AND EQUIPMENT
INSTALLATION
5. FURNITURE AND EQUIPMENT TO BE PROVIDED BY
OWNER. VERIFY FINAL LOCATION AND
REQUIREMENTS OF ALL EQUIPMENT WITH OWNER
6. PATCH ALL EXISTING WALLS AS REQUIRED;
PREPARE ALL WALLS FOR PAINT
7. WALLS TO BE PARTITION TYPE S3.0i UNLESS
OTHERWISE NOTED, REFER TO SHEET A-001 -
PARTITION TYPES FOR ADDITIONAL INORMATION
8. ALL EXTERIOR WALLS WITHIN THE PROJECT
SCOPE ARE TO BE FURRED OUT ON THE INTERIOR
WITH PARTITION TYPE F3.0e, REFER TO SHEET
A-001 - PARTITION TYPES FOR ADDITIONAL
INFORMATION.
9. ALL CASEWORK IN ALL EXAM ROOMS IN PROJECT
SCOPE ARE TO BE PRE-MANUFACTURED AND TO
BE SUPPLIED BY CONTRACTOR.
10. ALL FIRE AND SMOKE RATED WALLS AT EXISTING
LOCATIONS ARE TO BE INSPECTED AND UPGRAED
TO MEET INDICATED RATING REQUIREMENTS.
NEW DOOR: SEE DOOR SCHEDULE
FOR ADDITIONAL INFORMATION
DETAIL TAG:
DETAIL NUMBER: TOP
SHEET NUMBER: BOTTOMA101
SIM
DOOR TAGS SEE A600
ROOM TAG
ROOM NAME
150 SF
FIRE EXTINGUISHER CABINET
(1 PER 75FT OF TRAVEL)
FX
FLOOR PLAN LEGEND:
PARTITION TYPES SEE A001XXXX
X AXXX
ELEVATION TAG:
DETAIL NUMBER: ARROW
SHEET NUMBER: CENTER
AUTO-OPERATOR PUSH ACTUATORSPP
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0134
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
A S e rv ic e
D i s a b le d
Ve t e r an Owne d
Sm a l l
B u s ine ss
SDVOSB
CVE
BID DOCUMENTS
FULLY SPRINKLERED
Location
Issue Date
LABELLA ASSOCIATES, DPC
REGISTERED ARCHITECT
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSOLIDATE DIAGNOSTIC
CANCER CENTER
VA EAST ORANGE CAMPUS
561-18-155
BUILDING 1
Project Director
PLAN
NORTH
ACTUAL
NORTH
KEYPLAN
C U s e rs \z ri z v i\ D o c u m e n ts \R e v it L o c a l F ile s \2
V A
E a s t O ra n g e C a n c e r
C e n te r
A
R C
H z ri z v iF
C
G .r v t
04/22/2022 JR AB
A101
PARTIAL A-LEVEL FLOOR PLAN - AREA
SCALE: 3/16" = 1'-0"A101
1 PARTIAL A-LEVEL FLOOR PLAN - AREA 1
UP
)2
H R
(E )2
H R
(E )2
H R
(E )2
H R
(E)2HR(E)2HR1S
B
1S B
1S B
1S B
1HR1HR
H
R
H R
1HR1HR
H
R
H R
1S B
1S B
1S B
1S B
1SB 1SB
S M
S M
SMSM
S M
S M
SMSM
(E)2HR(E)2HR
H
R
H R
10 11 12 13
B
C
E
F
G
J
15 16
H
145 7
D
PHARM.
SPEC.
A-472
PRIVATE
INFUSION
BAY 6
A-476
INFUSION
BAY 7
A-470.7
INFUSION
BAY 8
A-470.8
PRIVATE
INFUSION
BAY 9
A-477
INFUSION
BAY 1
A-470.1
INFUSION
BAY 4
A-470.4
INFUSION
BAY 5
A-470.5
INFUSION
BAY 2
A-470.2
INFUSION
BAY 3
A-470.3
INFUSION
BAY 10
A-470.10
INFUSION
BAY 11
A-470.11
INFUSION
BAY 12
A-470.12
INFUSION
BAY 13
A-470.13
MED. RM.
A-471
NURSE
STATION
A-475
WOMENS
TOILET
A-498
MENS
TOILET
A-499
RECEPTION
A-497
NP/EXAM 1
A-495 NP/EXAM 2
A-494
NP/EXAM 3
A-493
NP/EXAM 4
A-492
NP/EXAM 5
A-491
EXAM 1
A-428
WAITING
ROOM
A-496
STAFF
TOILET /
SHOWER
A-479
O2 TANK
STOR.
A-478
ELEC. ROOM
AE-430
SOILED
UTILITY
A-431
TOILET
A-434
CHIEF OF
PHYSICS
A-447
WOMENS
TOILET
A-445
MECHANICAL
ROOM
AM-443
DR
A-444A
DR
A-444B
CONTROL
RM
A-463A
LINAC VAULT
A-463
EXAM
A-452
TOILET
A-451
85 SF
TOILET
SECURITY
HOLDING
A-509
EXAM
A-453
EXAM
A-454
STOR.
A-460E
EQUIP.
A-460B
LINAC VAULT
A-460
STOR.
A458
DOSIMETRY
A-456
CONTROL
A-459
LINK
A-360
CLEAN
UTILITY
A-432
STOR.
A-433
ELEC.
A-441
C
LE
A R
4'
WC
SCALE
STOR.
A-460D
ELEC.
A-461
CRASH CART
SOILED
UTILITY
A-436
EMERGENCY
EXIT ONLY,
NO ENTRY
TOILET
A-473
U.C.
REF.
N.S.
A-429
FEMALE
DRESS.
ROOM
A-435B
MD WORK
RM
A-448
PROCEDURE
RM
A-442
MATCH LINE
1 / A101
C
LE
A R
8'
CT SIM
DRESS. RM
A-435A
CLEAR
4' - 0" 2' - 10" 5' - 10" 2' - 10"
ALIGNALIGN
NOURISHMENT
A-474
4'
CORRIDOR
A-490A
CORRIDOR
A-470A
INFUSION
A-470
CORRIDOR
A-430B
A-432
A-431
A-435A
A-435B
A-478
A-479
A-473
A-472
A-471
A-476 A-477
A-428
A-491A-492A-493A-494A-495
A-490A
A-497
A-498
A500 6
A-470
A-440B
A400
A400
A400
A501
A402
9'
/2
7' - 11 1/2" 8' - 4 1/2" 8' - 4 1/2" 8' - 8" 8' - 8" 15' - 11 1/2" 8' - 3"
8' - 9 1/2" 5' - 10 1/2"
CLR
7' - 10"
10' - 11" 8' - 0 1/2" 8' - 0 1/2" 10' - 11 1/2"
9'
6'
8'
8'
/2
8'
6'
/2
2' - 5 1/2"
A401
EQ ALCOVE
A-449
9' - 0 1/2"
WHEELCHAIR
STOR.
A-490B
CHIEF TECH
A-446
ALIGN
ALIGN
A500
CORRIDOR
A-440A
A-442
A-448
A501
A501
O.C.
FUTURE
O.C.REF. REF.
FR.
A
8'
/2
8'
8'
8'
8'
/2
8'
2'
/2
CLR
4' - 0"
A-499
CLR
9' - 5"
TYP.
3' - 10"
TYP.
1' - 6"
6' - 0"
1'
3'
0"
TYP.
1' - 6"
TYP.
3' - 8"
2'
4'
1/
4'
5' - 11 1/8" 9' - 4" 4' - 5 3/4" 4' - 5"
F3.0
F3.0
F3.0eF3.0e F3.0e F3.0e F3.0e
F3.0
F3.0F3.0
F2.0F3.0eF3.0eF3.0eF3.0eF3.0e
A5005
F3.0F3.0
A500
A50012
TYP.
A-360
A
F3.0e
F3.0e
F9.0e
A500
A402
B
A501
PP
PP
PP
PP
FX
FX
FXALIGN
ALIGN
6'
3'
3'
2'
8'
0"
7'
5'
0"
8'
5'
7'
6'-5" 11'-3 1/2"
14' - 5" 5' - 0"
19' - 5" 9' - 10"
C
LR
5'
8' - 9" 4' - 3" 11' - 10" 8' - 3"
A-429
S3.0
C
LR
6'
8'
1'
9'
/4
R 51' - 8"
3'
A
LI
G N
3' - 0"
4'
3'
2'
7'
2'
0"
6'
1"
12' - 6 3/8" 11' - 6" 12' - 9 1/2"
5' - 8 1/16" 6' - 5" 6' - 10"
A
LI
G N
13' - 0" 11' - 0"
11" 16' - 7" 2' - 4"
8 3/8"
1' - 0 5/8"
1' - 0 5/8"
1' - 0 5/8"
8 3/8"
8 3/8"
1' - 0 5/8"
5" 5" 5"
4 3/8"
1' - 0 5/8"
4 1/4"
3/
8"F3.0e F3.0e F3.0e
3'
A001
A001
A601
1'
/8
3/
8"
A601
A601
3/
8"
1'
/8
1'
/8
A601
A601
A601
A601
A601
F3.0e
A-496
A-440C
F3.0
F3.0F3.0
EXIST
STAIR 1
S3.2
SH1.2
INFILL WALL TO
MATCH EXISTING
A501
A5006
A500 6
A500 A500 66
C
LR
1'
ST-1
S3.0
7'
8'
7'
8'
7'
S3.0
1'
2'
S3.0
1' - 9"
A501
A601
GENERAL PLAN NOTES:
1. ALL DIMENSIONS TO BE TAKEN FROM CENTERLINE
OF WALL UNLESS INDICATED OTHERWISE. REFER
TO SHEET A-001 - PARTITION TYPES FOR ACTUAL
DIMENSIONS
2. JOINTS ABUTTING EXISTING WALLS ARE TO BE
TAPED AND FINISHED
3. COORDINATE NEW DATA & POWER LOCATIONS
WITH OWNER AND ELECTRICAL DRAWINGS
4. CONTRACTOR SHALL PROVIDE BLOCKING AS
REQUIRED FOR ALL MILLWORK AND EQUIPMENT
INSTALLATION
5. FURNITURE AND EQUIPMENT TO BE PROVIDED BY
OWNER. VERIFY FINAL LOCATION AND
REQUIREMENTS OF ALL EQUIPMENT WITH OWNER
6. PATCH ALL EXISTING WALLS AS REQUIRED;
PREPARE ALL WALLS FOR PAINT
7. WALLS TO BE PARTITION TYPE S3.0i UNLESS
OTHERWISE NOTED, REFER TO SHEET A-001 -
PARTITION TYPES FOR ADDITIONAL INORMATION
8. ALL EXTERIOR WALLS WITHIN THE PROJECT
SCOPE ARE TO BE FURRED OUT ON THE INTERIOR
WITH PARTITION TYPE F3.0e, REFER TO SHEET
A-001 - PARTITION TYPES FOR ADDITIONAL
INFORMATION.
9. ALL CASEWORK IN ALL EXAM ROOMS IN PROJECT
SCOPE ARE TO BE PRE-MANUFACTURED AND TO
BE SUPPLIED BY CONTRACTOR.
10. ALL FIRE AND SMOKE RATED WALLS AT EXISTING
LOCATIONS ARE TO BE INSPECTED AND UPGRAED
TO MEET INDICATED RATING REQUIREMENTS.
NEW DOOR: SEE DOOR SCHEDULE
FOR ADDITIONAL INFORMATION
DETAIL TAG:
DETAIL NUMBER: TOP
SHEET NUMBER: BOTTOMA101
SIM
DOOR TAGS SEE A600
ROOM TAG
ROOM NAME
150 SF
FIRE EXTINGUISHER CABINET
(1 PER 75FT OF TRAVEL)
FX
FLOOR PLAN LEGEND:
PARTITION TYPES SEE A001XXXX
X AXXX
ELEVATION TAG:
DETAIL NUMBER: ARROW
SHEET NUMBER: CENTER
AUTO-OPERATOR PUSH ACTUATORSPP
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small…