0306-03 - Liebert CW System - Materials List.xlsx

XLSX spreadsheet 19 KB Posted

Attached to
Liebert Chilled Water Systems Federal contract opportunity
Solicitation number
N0017826Q6715
Issued by
Department of the Navy Naval Sea Systems Command

About this file

This is a materials requirements list for a federal procurement of precision cooling systems by the Naval Surface Warfare Center Dahlgren Division. The requirement specifies four Liebert CoolPhase Precision Cooling Systems (Part Number DS042AZA1E0) and four Vertiv CoolPhase Outdoor Air-Cooled Microchannel Condensers (Part Number MCS056E5AD). The cooling systems are nominal 42 kW, 12-ton floor-mounted units with 460-volt, 3-phase, 60-hertz input power and 65,000 amp RMS short circuit current rating. Each system features a welded steel frame separable into three sections for transport, dual refrigeration circuits with digital scroll compressors, A-frame evaporator coil with stainless steel condensate pan, three-stage 25 kW electric reheat, Liebert iCOM microprocessor control with high-definition display, and BACnet/Modbus communication capabilities. The condensers include microchannel aluminum coils, variable speed EC fans, premium electronic control boards with CANbus communication, and 18-inch aluminum legs. Ancillary requirements include 4-inch MERV 8 filter packages, 24-inch adjustable height floorstands, and Liebert Point Leak Detection Sensor Kits for each unit.

The solicitation (N0017826Q6715) is issued by the Department of the Navy as a Request for Quotation under FAR Part 12 for commercial items with an anticipated publication date of March 24, 2026, and closing date of April 1, 2026. Award will be made on a brand name or equal basis to procure products manufactured by Vertiv Corporation, which must be compatible with existing infrastructure. The requirement is not eligible for small business set-aside and must comply with Trade Agreements Act provisions. Quotations must be submitted to contracting officer Lee Ann Mizelle at lee.a.mizelle.civ@us.navy.mil or (540) 742-8050. Prospective vendors must be authorized resellers to quote on these systems.

View the file

Other files for this federal contract opportunity

Other files attached to Liebert Chilled Water Systems, newest first.
File Type Posted
SOW_redacted.pdf PDF
N0017826Q6715 (SF1449).pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

REQUIREMENTS LIST
Part NumberDescriptionQuantityUnit of Issue
DS042AZA1E0Liebert CoolPhase Precision Cooling System (Specifications follow)4Each
Nominal 42 kW, 12 ton, floor mounted, downflow
Input Supply Voltage: 460 Volt, 3 Phase, 60 Hertz
65,000 amp RMS Short Circuit Current Rating
14 Gauge Welded Steel Frame with Autophoretic Coating
Frame can be field separated into three sections for transport through small areas.
Front Service Access Only
Supply Air Exits the Bottom of the Unit, Return Air enters through the Top of the Unit
Backwards Inclined Fan with Variable Speed Direct Drive EC Motors, 4.2 HP1
Dual Refrigeration Circuits with Liquid Line Filter Driers, Refrigerant Sight Glasses, Expansion Valves and Liquid Line Solenoid Valves
Independent Digital Scroll Compressors with Unloading Solenoid Valve2
Dual Refrigeration Circuits with Liquid Line Filter Driers, Refrigerant Sight Glasses, Expansion Valves and Liquid Line Solenoid Valves
A-Frame Evaporator Coil with Stainless Steel Condensate Pan
R-454B Refrigerant System, Field Supplied and Field Charged
Three-Stage, Finned Tubular, Stainless Steel Electric Reheat, Capacity: 25 kW
4" MERV 8 Filter Package
Liebert iCOM Microprocessor Control with High-Definition Display
Liebert iCOM Based BMS Communication
Base Comms & Connectivity includes one Ethernet port and one RS-485 port on iCOM controller, dedicated to supporting BACnet IP, Modbus TCP/IP, BACnet 485, Modbus 485 and SNMP v1/v2c/v3
Locking Disconnect Switch, Factory Installed
Exterior Panels Insulated and Powder Coated, Color: IBM Charcoal Gray
24” Adjustable Height Floorstand, per Unit1
Liebert Point Leak Detection Sensor Kit, Model: LT4101
MCS056E5ADVertiv CoolPhase Outdoor Air-Cooled Microchannel Condenser (Specifications follow)4Each
Input Supply Voltage: 460 Volt, 3 Phase, 60 Hertz
65,000 amps RMS Short Circuit Current Rating
Microchannel Aluminum Coil
Variable Speed EC Fans
Premium Electronic Control Board Providing Communication with iCOM using CANbus
Aluminum Exterior Panels
18” Aluminum Legs
**Must be an authorized reseller to quote**

File details come from the government source that posted it. Updated .