0306-03 - Liebert CW System - Materials List.xlsx
XLSX spreadsheet 19 KB Posted
- Attached to
- Liebert Chilled Water Systems Federal contract opportunity
- Solicitation number
- N0017826Q6715
About this file
This is a materials requirements list for a federal procurement of precision cooling systems by the Naval Surface Warfare Center Dahlgren Division. The requirement specifies four Liebert CoolPhase Precision Cooling Systems (Part Number DS042AZA1E0) and four Vertiv CoolPhase Outdoor Air-Cooled Microchannel Condensers (Part Number MCS056E5AD). The cooling systems are nominal 42 kW, 12-ton floor-mounted units with 460-volt, 3-phase, 60-hertz input power and 65,000 amp RMS short circuit current rating. Each system features a welded steel frame separable into three sections for transport, dual refrigeration circuits with digital scroll compressors, A-frame evaporator coil with stainless steel condensate pan, three-stage 25 kW electric reheat, Liebert iCOM microprocessor control with high-definition display, and BACnet/Modbus communication capabilities. The condensers include microchannel aluminum coils, variable speed EC fans, premium electronic control boards with CANbus communication, and 18-inch aluminum legs. Ancillary requirements include 4-inch MERV 8 filter packages, 24-inch adjustable height floorstands, and Liebert Point Leak Detection Sensor Kits for each unit.
The solicitation (N0017826Q6715) is issued by the Department of the Navy as a Request for Quotation under FAR Part 12 for commercial items with an anticipated publication date of March 24, 2026, and closing date of April 1, 2026. Award will be made on a brand name or equal basis to procure products manufactured by Vertiv Corporation, which must be compatible with existing infrastructure. The requirement is not eligible for small business set-aside and must comply with Trade Agreements Act provisions. Quotations must be submitted to contracting officer Lee Ann Mizelle at lee.a.mizelle.civ@us.navy.mil or (540) 742-8050. Prospective vendors must be authorized resellers to quote on these systems.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SOW_redacted.pdf | ||
| N0017826Q6715 (SF1449).pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| REQUIREMENTS LIST | |||
| Part Number | Description | Quantity | Unit of Issue |
| DS042AZA1E0 | Liebert CoolPhase Precision Cooling System (Specifications follow) | 4 | Each |
| Nominal 42 kW, 12 ton, floor mounted, downflow | |||
| Input Supply Voltage: 460 Volt, 3 Phase, 60 Hertz | |||
| 65,000 amp RMS Short Circuit Current Rating | |||
| 14 Gauge Welded Steel Frame with Autophoretic Coating | |||
| Frame can be field separated into three sections for transport through small areas. | |||
| Front Service Access Only | |||
| Supply Air Exits the Bottom of the Unit, Return Air enters through the Top of the Unit | |||
| Backwards Inclined Fan with Variable Speed Direct Drive EC Motors, 4.2 HP | 1 | ||
| Dual Refrigeration Circuits with Liquid Line Filter Driers, Refrigerant Sight Glasses, Expansion Valves and Liquid Line Solenoid Valves | |||
| Independent Digital Scroll Compressors with Unloading Solenoid Valve | 2 | ||
| Dual Refrigeration Circuits with Liquid Line Filter Driers, Refrigerant Sight Glasses, Expansion Valves and Liquid Line Solenoid Valves | |||
| A-Frame Evaporator Coil with Stainless Steel Condensate Pan | |||
| R-454B Refrigerant System, Field Supplied and Field Charged | |||
| Three-Stage, Finned Tubular, Stainless Steel Electric Reheat, Capacity: 25 kW | |||
| 4" MERV 8 Filter Package | |||
| Liebert iCOM Microprocessor Control with High-Definition Display | |||
| Liebert iCOM Based BMS Communication | |||
| Base Comms & Connectivity includes one Ethernet port and one RS-485 port on iCOM controller, dedicated to supporting BACnet IP, Modbus TCP/IP, BACnet 485, Modbus 485 and SNMP v1/v2c/v3 | |||
| Locking Disconnect Switch, Factory Installed | |||
| Exterior Panels Insulated and Powder Coated, Color: IBM Charcoal Gray | |||
| 24” Adjustable Height Floorstand, per Unit | 1 | ||
| Liebert Point Leak Detection Sensor Kit, Model: LT410 | 1 | ||
| MCS056E5AD | Vertiv CoolPhase Outdoor Air-Cooled Microchannel Condenser (Specifications follow) | 4 | Each |
| Input Supply Voltage: 460 Volt, 3 Phase, 60 Hertz | |||
| 65,000 amps RMS Short Circuit Current Rating | |||
| Microchannel Aluminum Coil | |||
| Variable Speed EC Fans | |||
| Premium Electronic Control Board Providing Communication with iCOM using CANbus | |||
| Aluminum Exterior Panels | |||
| 18” Aluminum Legs | |||
| **Must be an authorized reseller to quote** |