030-EP-011 - Addendum No 01 - Stamped.pdf

PDF 1 MB Posted

Attached to
Z2DZ--Modernize Generator Project Federal contract opportunity
Solicitation number
36C26126R00310005
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21

About this file

This document is an electrical plan drawing for a construction project at the Honolulu Veterans Affairs Medical Center. The project involves modernizing generators at the VA Pacific Island Health Care System, with design services provided by GDM-AE, Inc. located in Vancouver, Washington.

The drawing shows Building 30's partial first floor and site electrical plan with detailed specifications for temporary and permanent generator installation. Key requirements include: providing a 300-kilowatt portable generator with 90 minutes of fuel capacity; installing a temporary power distribution system that feeds emergency-side automatic transfer switches (ATS-1, ATS-2, ATS-5, and ATS-FP); establishing 480-volt, three-phase, 30-ampere circuits with number eight phase conductors; and retrofitting the generator switchboard enclosure and main fuel tank enclosure. The basis of design specifies Caterpillar generators and UL891/508 shop-certified switchboard manufacturers (TR Electrical Services). Critical constraints include: the contractor must propose temporary generator placement within seven days of Notice to Proceed; all generator work must be performed after normal business hours; temporary power must remain operational until new generators are fully installed; and work on existing generators must be completed by the local Caterpillar dealer, Hawthorn Cat, to maintain UL listing. The final bid documents are dated December 22, 2025, with an addendum issued as a Solicitation RFI on May 15, 2026.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DZ--Modernize Generator Project, newest first.
File Type Posted
36C26126R0031 0005.pdf PDF
000-EJ-002 - Addendum No 01 - Stamped.pdf PDF
36C26125N0436 459-24-001 Modernize Generator System VAMC Honolulu - 030-EP-012 Addendum 1. pdf.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

030-EP-012

030-EP-012

(E) PNL 'E'

(3) 2"C.

030-EP-012

030-EP-012

(3) 2"C.

(2) 2"C.

(E) ATS-1

(E) ATS-2

300KW TEMP

GENERATOR

SWITCH GEAR RM

1-B05

(N) ELECTRICAL VAULT

SEE CIVIL SHEETS

FOR DETAILS

SEE CONTINUATION ON

SHEET 030-EP-012

SEE CONTINUATION ON

SHEET 030-EP-012

TEMP DISTRIBUTION PANEL

(E) ATS-1

PROJECT KEY PLAN

HONOLULU VETERANS AFFAIRS

1 JARRETT WHITE RD | HONOLULU, HI 96819

E

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

''1

CONSULTANT

CONSULTANT: A/E:

GDM-AE, INC.

1308 NE 134TH ST SUITE A

VANCOUVER, WA 98685

P: 541.436.4723

MICHAEL REBSTOCK, PE

WWW.GDM-AE.COM

FULLY

SPRINKLERED

CONSTRUCTION

FACILITIES

MANAGEMENT

(CFM) 459 PATTERSON RD.

HONOLULU, HI 96819-1522

35% SCHEMATIC DESIGN

65% DESIGN DEVELOPMENT

07-10-2025 08-28-2025

95% CONSTRUCTION DOCUMENTS 10-16-2025

100% CONSTRUCTION DOCUMENTS 11-26-2025

FINAL BID DOCUMENTS 12-22-2025

ADDENDUM 1 - SOLICITATION RFI 05-15-2026

A u to d e s k D o c s /2

-0

V

A H o n o lu lu G e n e ra to rs

/2 -0

H o n o lu lu

H

I M

G S

V A

M C

E le c tr ic a l_ r2

.r v t

030-EP-011

BUILDING 30 PARTIAL FIRST FLOOR AND

SITE ELECTRICAL PLAN

MER AJW

MODERNIZE GENERATORS

VA PACIFIC ISLAND HEALTH CARE SYSTEM

FINAL BID DOCUMENTS 459-24-001

05-15-2026

3/32" = 1'-0"1

BLDG 30 PARTIAL FIRST FLOOR AND SITE ELECTRICAL PLAN

GENERAL NOTES

1. TEMPORARY GENERATOR LOCATIONS SHOWN IN DRAWINGS ARE

PROPOSED LOCATIONS ONLY. CONTRACTOR TO PERFORM

ASSESSMENT AND PROPOSE A PLACEMENT LOCATION. CONTRACTOR

SHALL SUBMIT A REQUEST FOR TEMPORARY GENERATOR LOCATION TO

COR WITHIN 7 DAYS OF NTP FOR VA CONSIDERATION WITH USAG.

2. TEMPORARY POWER SYSTEM MUST BE ONLINE PRIOR TO

CONSTRUCTION. COORDINATION WITH VA ON ANY REQUIRED OUTAGES

OF EMERGENCY POWER WITH VA PRIOR TO INSTALLATION.

3. TEMPORARY POWER CONNECTIONS SHALL REMAIN OPERATIONAL

UNTIL NEW GENERATORS HAVE BEEN COMPLETELY INSTALLED AND

READY FOR CUTOVER FROM TEMPORARY EQUIPMENT.

4. ALL WORK RELATED TO CONNECTING TEMPORARY GENERATOR

SYSTEM SHALL BE PERFORMED AFTER NORMAL BUSINESS HOURS. ALL

WORK TESTING AND COMMISIONING GENERATOR AND OPERATION OF

TRANSFER SWITCHES SHALL BE PERFORMED AFTER NORMAL BUSINESS

HOURS.

5. ALL GENERATOR WORK ON EXISTING GENERATOR SHALL BE

PERFORMED BY THE LOCAL CATERPILLAR DEALER HAWTHORN CAT TO

MAINTAIN UL LISTING.

6. THE GENERATOR MANUFACTURE FOR THE BASIS OF DESIGN IS

CATERPILLAR. THE CONTRACTOR IS RESPONSIBLE FOR ALL COST

ASSOCIATED DUE TO ALTERNATE SELECTION AND REJECTED

SUBMITTALS.

NORTH

7. THE BASES OF DESIGN FOR THE GENERATOR SWITCHBOARD

ENCLOSURE RETRO FIT AND MAIN FUEL TANK ENCLOSURE WAS BY TR

ELECTRICAL SERVICES LOCATED IN BOX ELDER, SOUTH DAKOTA.

MANUFACTURE SHALL BE A UL891 AND 508 SHOP. ALL COSTS

ASSOCIATED WITH ALTERNATE MANUFACTURERS ARE THE

RESPONSIBILITY OF THE CONTRACTOR. VA IS NOT LIABLE FOR ANY

ALTERNATIVES. CONTRACTOR TO SUBMIT FULL DESIGN FOR

APPROVAL PRIOR TO CONSTRUCTION.

KEY NOTES

1 PROVIDE 480V. 3PH, 30A CIRCUIT WITH #8 PHASE CONDUCTORS FOR

PANEL IN FUEL TANK AREA. PROVIDE 30A/3P CIRCUIT BREAKER IN

AVAILABLE SPACE. SEE ONE-LINE DIAGRAM ON SHEET 2/000-EJ-002.

2 PROVIDE 300KW PORTABLE GENERATOR WITH 90 MINUTES OF FUEL

CAPACITY. PROVIDE TEMPORARY DISTRIBUTION TO TEMPORARY

FEEDS TO EMERGENCY SIDE OF ATS-1, ATS-2, ATS-5, AND ATS-FP. SEE

TEMPORARY POWER ONE-LINE ON SHEET 000-EJ-002.

Revisions: Date:

1.

NOTES

Total KVA: KVA

EW-TM-1 120 1 - - - - - -

32A-TM-1 120 1

30-FWS-1 120 1

30-FP-2 120 1

30-FP-1B 120 1 - - - - - -

30-FP-1A 120 1 - - - - - -

30-DT-1 120 1 - - - - - - - - - - - - - -

30-TM-1 120 1 - - - - - - - - - - - - - -

TAG VOLTAGE PHASE CONDUCTORS RACEWAY PHASE N G SIZE FUSE

EQUIPMENT RATED VOLTAGE HP KVA KW FLA MCA MOCP # PARALLEL BRANCH CIRCUIT DISCONNECT NOTES

BLDG 30 - ELECTRICAL MECHANICAL EQUIPMENT SCHEDULE

File details come from the government source that posted it. Updated .