000-EJ-002 - Addendum No 01 - Stamped.pdf

PDF 645 KB Posted

Attached to
Z2DZ--Modernize Generator Project Federal contract opportunity
Solicitation number
36C26126R00310005
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21

About this file

This document is an electrical one-line diagram for Building 30 at the VA Pacific Island Health Care System, prepared by GDM-AE, Inc. as part of final bid documents for a generator modernization project located at 459 Patterson Road, Honolulu, Hawaii. The project involves two construction phases, with Phase 1 focusing on temporary power provisions and Phase 2 addressing permanent electrical upgrades to the generator and switchboard systems.

Phase 1 requires the contractor to disconnect the existing generator feeder from the 1200A main breaker in the generator switchboard and remove existing generator controls and control wiring. The contractor must submit a temporary power plan for review prior to installation and ensure temporary power is online before performing any work impacting normal generator operation. Phase 2 involves installing a new retrofit interior compatible with Schneider Electric I-LINE, rated for 480Y/277V, three-phase, four-wire service at 1200A capacity. Key requirements include installing a new 1200A main circuit breaker for emergency distribution and a 50A main circuit breaker for the fire pump circuit, reconnecting existing feeders, providing new 50A conductors for the emergency fire pump circuit, and installing a new 1200A quick-connect cabinet with provisions for future load bank. The U.S. Department of Veterans Affairs is the federal agency managing this project through Construction Facilities Management (CFM), with an issue date of May 15, 2026. Temporary power requirements include a 300KW/375KVA portable generator, a 480Y/277V, three-phase, four-wire temporary distribution panel rated for 600A, and temporary power cabling connections to the emergency side of each automatic transfer switch.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DZ--Modernize Generator Project, newest first.
File Type Posted
36C26126R0031 0005.pdf PDF
030-EP-011 - Addendum No 01 - Stamped.pdf PDF
36C26125N0436 459-24-001 Modernize Generator System VAMC Honolulu - 030-EP-012 Addendum 1. pdf.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FROM

30-MV-SWITCH

GEN 30

480V, 3Ø, 4W, 0.8PF

750KW, 937KVA

XFMR

1500KVA

480/277V 11500V:

(E)BLDG 30

225AT

225AF

(E)ATS-FP

480/277V 240A

FIRE PUMP

25HP, 20.1KW

(E)SWITCHBOARD "GEN"

480V, 3Ø, 4W

1000A

1200AT

1200AF

400A 250A 50A

TO

ATS-2 (E)SWITCHBOARD "MSB"

480V, 3Ø, 4W 2000A

2000AT

2000AF

250A 600A

TO

ATS-2

400A800A

TO

PNL 'N'

400A

TO

ROOF NAC

400A 250A

TO

POWER METER

NE

600A

TO

ATS-5

(E)ATS-1

480/277V 400A

NE

(E)PNL E

480/ 277V

400A

150A

TO

UNKNOWN

100A

FROM

30-MV-SWITCH

GEN 30

480V, 3Ø, 4W, 0.8PF

750KW, 937KVA

XFMR

1500KVA

480/277V 11500V:

(E)BLDG 30

225AT

225AF

(E)ATS-FP

480/277V 240A

FIRE PUMP

25HP, 20.1KW

400A 250A 100A

TO

ATS-2 (E)SWITCHBOARD "MSB"

480V, 3Ø, 4W 2000A

2000AT

2000AF

250A

TO

ATS-2

800A

TO

PNL 'N'

400A

TO

ROOF NAC

400A 250A

TO

POWER METER

NE

600A

TO

ATS-5

(E)ATS-1

480/277V 400A

NE

(E)PNL E

480/ 277V

400A

150A

TO

UNKNOWN

MAIN FP

50AT

100AF

SPARE

100A

SPARE

TO

ATS-5

400A

MAIN GEN

1200AT

1200AF

GENERATOR

CONTROLS

LOAD BANK

1200AT

1200AF

A

CO

NN

EC

TI

ON

CA

BI

NE

T

K

[34-1200]

N.O.

[34-1200]

600A

TO

ATS-5

TEMP GEN

480V, 3Ø, 4W, 0.8PF

300KW, 375KVA

TEMP POWER DP

225A

600A

225A 300A 50A

TO

ATS-1

TO

ATS-2

TO

ATS-5

TO

ATS-FP

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 101/ 2'

3' 0'

1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

Fi le

P at h

VA FORM 08 - 6231 1

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

U.S. Department of Veterans Affairs

PHASEARCHITECT/ENGINEER OF RECORD STAMP

LOCATION

CONSULTANT

MER AJW

MODERNIZE GENERATORS

VA PACIFIC ISLAND HEALTH CARE SYSTEM

FINAL BID DOCUMENTS

CONSULTANT: A/E:

GDM-AE, INC.

1308 NE 134TH ST SUITE A

VANCOUVER, WA 98685

P: 541.436.4723

MICHAEL REBSTOCK, PE

WWW.GDM-AE.COM

459-24-00135% SCHEMATIC DESIGN

65% DESIGN DEVELOPMENT

07-10-2025 08-28-2025

FULLY

SPRINKLERED

459 PATTERSON RD.

HONOLULU, HI 96819-1522

CONSTRUCTION

FACILITIES

MANAGEMENT

(CFM)

05-15-2026

95% CONSTRUCTION DOCUMENTS 10-16-2025

Revisions: Date:

11-26-2025100% CONSTRUCTION DOCUMENTS

12-22-2025FINAL BID DOCUMENTS

05-15-2026ADDENDUM 1 - SOLICITATION RFI

000-EJ-002

BUILDING 30 PARTIAL ELECTRICAL

ONE-LINE DIAGRAM

SCALE: NTS

1 BUILDING 30 ELECTRICAL ONE-LINES - PHASE 1

SCALE: NTS

2 BUILDING 30 ELECTRICAL ONE-LINES - PHASE 2

A1

PHASE 1 KEYNOTES

DISCONNECT EXISTING GENERATOR FEEDER FROM 1200A MAIN BREAKER IN

THE GENERATOR SWITCHBOARD AND DEMO EXISTING GENERATOR

CONTROLS AND CONTROL WIRING BACK TO SOURCE. EXISTING GENERATOR

FEEDER CONDUCTORS AND SWITCHBOARD SHALL REMAIN EXISTING.

DISCONNECT ALL CONDUCTORS FROM EXISTING CIRCUIT BREAKERS AND

DEMO EXISTING CIRCUIT BREAKERS AND BUSSING. ALL EXISTING FEEDER

CONDUCTORS SHALL REMAIN UNLESS OTHERWISE NOTED.

DEMO FEEDER CONDUCTOR TO ATS-FP.

1. CONTRACTOR TO SUBMIT TEMPORARY POWER PLAN FOR REVIEW PRIOR TO

INSTALLATION. TEMPORARY POWER MUST BE INSTALLED AND ONLINE PRIOR

TO PERFORMING ANY WORK WHICH WILL IMPACT THE NORMAL OPERATION OF

THE EXISTING GENERATOR.

2. REFER TO ELECTRICAL FEEDER SCHEDULE ON SHEET 000-EG-001 FOR

CONDUIT AND CONDUCTOR FEEDER REQUIREMENTS.

GENERAL NOTES

B1

PHASE 2 KEYNOTES

INSTALL NEW RETROFIT INTERIOR COMPATIBLE TO SCHNEIDER ELECTRIC

I-LINE INTERIOR. INTERIOR TO BE MANUFACTURED BY AN UL 508 SHOP.

INTERIOR SHALL BE 480Y/277V,3PH,4WR AND RATED FOR 1200A. INTERIOR

SHALL ACCOMMODATE A 1200A MAIN CIRCUIT BREAKER FOR THE

EMERGENCY DISTRIBUTION EDP AND A 50A MAIN CIRCUIT BREAKER FOR FIRE

PUMP FP.

EXTEND AND RECONNECT EXISTING FEEDER.

PROVIDE NEW 50A CONDUCTORS FOR EMERGENCY FIRE PUMP CIRCUIT IN

EXISTING CONDUIT.

INSTALL EXISTING SPARE CIRCUIT BREAKERS INTO NEW INTERIOR.

INSTALL NEW 1200A MAIN CIRCUIT BREAKER GEN-MAIN IN INCOMING SECTION

OF THE EXISTING GENERATOR SWITCHBOARD AND RECONNECT EXISTING

GENERATOR FEEDER. CIRCUIT BREAKER SHALL BE INSTALL BY SWITCHGEAR

VENDOR. FEEDER TO BE RECONNECTED BY ELECTRICAL CONTRACTOR.

PROVIDE NEW 1200A QUICK CONNECT CABINET AND PROVISIONS FOR

FUTURE LOAD BANK. SEE SHEET 030-EP-012 FOR ADDITIONAL INFORMATION.

PROVIDE NEW 1200A BREAKER FOR QUICK CONNECT CABINET. PROVIDE WITH

INTEGRAL KIRK-KEY INTERLOCK IN NORMALLY OPEN CONFIGURATION. TIE

INTO NEW MAIN BREAKER SERVING EMERGENCY SWITCHBOARD.

A1

A2

A2

B2

B3

B4

B1

B2

B3

B4B2 B2 B2

A3

B5

B6

A3

B5

B6

B7

B7

T1

TEMPORARY POWER KEY NOTES

PROVIDE 300KW/375KVA PORTABLE GENERATOR FOR TEMPORARY STANDBY

EMERGENCY POWER. SEE SHEET 030-EP-011 FOR LOCATION AND MORE

INFORMATION.

PROVIDE 480Y/277V, 3PH, 4W TEMPORARY DISTRIBUTION PANEL, RATED FOR

600A, MLO.

PROVIDE TEMPORARY POWER CABLING FOR TEMPORARY POWER

CONNECTIONS TO THE EMERGENCY SIDE OF EACH ATS AS SHOWN.

T2

T3T1

T2

T3

SCALE: NTS

3 BUILDING 30 ELECTRICAL ONE-LINES - TEMPORARY POWER

File details come from the government source that posted it. Updated .