These architectural and engineering design documents detail a renovation project for the VA Maryland Healthcare System located in Baltimore, Maryland. The project involves renovating the C-Segregated Compounding Area for Hazardous Compounding at the VA Medical Center, specifically focused on upgrading areas including the Pharmacy (BA121K), Anteroom (BA121L), Hood Room A (BA121O), Hood Room B (BA121P), and Hood Room C (2C-126). The comprehensive bid documents are dated May 17, 2024, and include architectural, mechanical, electrical, plumbing, and fire suppression plans across basement and second floor levels.

The renovation encompasses multiple technical disciplines, with specific focus on creating a modern, compliant pharmaceutical compounding environment. The design incorporates advanced features such as specialized hood rooms, mobile workstations, stainless steel countertops, refrigeration units, and comprehensive safety systems including fire alarm, sprinkler, and infection control provisions. The project adheres to multiple regulatory standards including NFPA, International Building Code, VA Design Manuals, and USP 797 and 800 standards for sterile and hazardous drug preparation. The work is fully sprinklered and designed to maintain continuous operational capabilities during the phased construction process.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT

G-001

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

05/17/2024Revisions: Date:

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

COVER SHEET

INDEX OF DRAWINGS

SHEET DISCIPLINE TITLE SHEET NO.

G-001 GENERAL COVER SHEET 1

G-002 ARCHITECTURAL ARCHITECTURAL NOTES, SYMBOLS AND ABBREVIATIONS 2

AD-101 ARCHITECTURAL ARCHITECTURAL FLOOR PLANS - DEMOLITION 3

AL-101 ARCHITECTURAL ARCHITECTURAL LIFE SAFETY PLAN 4

AS-101 ARCHITECTURAL ARCHITECTURAL FLOOR PLANS - NEW WORK 5

AS-102 ARCHITECTURAL ARCHITECTURAL - FINISH FLOOR PLAN 6

AS-201 ARCHITECTURAL ARCHITECTURAL - ELEVATIONS 7

AS-501 ARCHITECTURAL ARCHITECTURAL - DETAILS 8

AS-601 ARCHITECTURAL ARCHITECTURAL - SCHEDULES 9

MH-001 MECHANICAL MECHANICAL - GENERAL NOTES, SYMBOLS & ABBREVIATIONS 10

MD-101 MECHANICAL MECHANICAL - FLOOR PLANS - DEMOLITION 11

MH-101 MECHANICAL MECHANICAL - FLOOR PLANS - NEW WORK 12

MH-102 MECHANICAL MECHANICAL - AREA C SERVICE BAY PART PLANS 13

MH-501 MECHANICAL MECHANICAL DETAILS 14

MH-601 MECHANICAL MECHANICAL SCHEDULES 15

MH-701 MECHANICAL MECHANICAL CONTROLS 16

PL-001 PLUMBING PLUMBING - GENERAL NOTES, SYMBOLS & ABBREVIATIONS 17

PD-101 PLUMBING PLUMBING - FLOOR PLANS - DEMOLITION 18

PL-101 PLUMBING PLUMBING - FLOOR PLANS - NEW WORK 19

PL-501 PLUMBING PLUMBING DETAILS AND SCHEDULES 20

ES-001 ELECTRICAL ELECTRICAL - SYMBOLS & ABBREVIATIONS 21

ED-101 ELECTRICAL ELECTRICAL - FLOOR PLANS - DEMOLITION 22

ES-101 ELECTRICAL ELECTRICAL - LIGHTING PLANS - NEW WORK 23

ES-201 ELECTRICAL ELECTRICAL - POWER PLANS - NEW WORK 24

ES-202 ELECTRICAL ELECTRICAL - POWER PLANS - NEW WORK 25

ES-501 ELECTRICAL ELECTRICAL - RISER DIAGRAMS 26

ES-601 ELECTRICAL ELECTRICAL SCHEDULES 27

FA-001 FIRE PROTECTION FIRE ALARM - PROJECT NOTES, SYMBOLS AND ABBREVIATIONS 28

FAD-101 FIRE PROTECTION FIRE ALARM - FLOOR PLANS - DEMOLITION 29

FA-101 FIRE PROTECTION FIRE ALARM - FLOOR PLANS - NEW WORK 30

FA-501 FIRE PROTECTION FIRE ALARM DETAILS 31

FS-001 FIRE PROTECTION FIRE SUPPRESSION - PROJECT NOTES, SYMBOLS AND ABBREVIATIONS 32

FSD-101 FIRE PROTECTION FIRE SUPPRESSION - FLOOR PLANS - DEMOLITION 33

FS-101 FIRE PROTECTION FIRE SUPPRESSION - FLOOR PLANS - NEW WORK 34

FS-501 FIRE PROTECTION FIRE SUPPRESSION DETAILS 35

PROJECT MAP

MAP

RENOVATE C-SEGREGATED COMPOUNDING AREA FOR HAZARDOUS COMPOUNDING

VA MARYLAND HEALTHCARE SYSTEM - VISN 5

NRM PROJECT - 512-23-108

BALTIMORE, MD. 21201

BID SUBMITTAL - CONSTRUCTION DOCUMENTS MAY 17, 2024

DS

APPLICABLE CODES

TYPE DESCRIPTION

BUILDING CODE

INTERNATIONAL BUILDING CODE (IBC) 2021

DEPARTMENT OF VETERANS AFFAIRS DESIGN MANUAL AND DESIGN GUIDES

AMERICANS WITH DISABILITIES ACT (ADA)

ACCESSIBILITY CODE ICC/ANSI A117.1-09 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES 2020 BUILDING CODE

FIRE CODE

NFPA 1, 2021

VA FIRE PROTECTION DESIGN MANUAL (VAFPDM) - JUNE 2021 EDITION

NFPA 101®, LIFE SAFETY CODE® (LSC) - 2021 EDITION

NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS - 2022 EDITION

NFPA 25, STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION

SYSTEMS - 2023 EDITION

NFPA 45, STANDARD ON FIRE PROTECTION FOR LABORATORIES USING CHEMICALS, 2019 EDITION

NFPA 70, NATIONAL ELECTRICAL CODE - 2023 EDITION

NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE - 2022 EDITION

INTERNATIONAL BUILDING CODE (IBC) - 2021 EDITION (AS AMMENDED)

MECHANICAL CODE

INTERNATIONAL MECHANICAL CODE (IMC) - EDITION 2021

2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

2021 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 1: FIRE CODE

2021 NFPA 101: LIFE SAFETY CODE

2019 AMERICAN SOCIETY OF HEATING, REFRIGERATING, AND AIR CONDITIONING ENGINEERS (ASHRAE) STANDARD 62.1

2022 ASHRAE STANDARD 90.1 ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS

ANSI/ AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) B31.1, B31.3 AND B31.9

VA HVAC DESIGN MANUAL, REV 3/1/22

NFPA 45 STANDARD ON FIRE PROTECTION FOR LABORATORIES USING CHEMICALS

PLUMBING CODE

INTERNATIONAL PLUMBING CODE (IPC)

2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

2021 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 1: FIRE CODE, AND ITS MANDATORY REFERENCED CODES AND

STANDARDS

2021 NFPA 101: LIFE SAFETY CODE, AND ITS MANDATORY REFERENCED CODES AND STANDARDS

VA PLUMBING DESIGN MANUAL, REV 5/1/2021

NFPA 45 STANDARD ON FIRE PROTECTION FOR LABORATORIES USING CHEMICALS

ELECTRICAL CODE

NFPA 70 - NATIONAL ELECTRICAL CODE, 2023

NFPA 72 - NATIONAL FIRE ALARM CODE, 2022

NFPA 110 - EMERGENCY AND STANDBY POWER SYSTEMS, 2022

NFPA 99 HEALTHCARE FACILITIES

NFPA 101 LIFE SAFETY CODE

VA ELECTRICAL DESIGN MANUAL (EDM)

VA LIGHTING DESIGN MANUAL (LDM)

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

NFPA 45 STANDARD ON FIRE PROTECTION FOR LABORATORIES USING CHEMICALS

ILLUMINATING ENGINEERING SOCIETY (IES) DESIGN GUIDELINES

USP 797 STANDARD GOVERNING THE STERILE PREPARATION OF COMPOUNDED PHARMACEUTICALS

USP 800 STANDARDS FOR SAFE HANDLING OF HAZARDOUS DRUGS

MC

A

ACT ACOUSTICAL CEILING TILE

ADJ ADJACENT

AFF ABOVE FINISH FLOOR

ALUM ALUMINUM

ANOD ANODIZED

@ AT

B

BLKG BLOCKING

C

CAB CABINET

CCT CUBICLE CURTAIN TRACK

CG CORNER WALL GUARD

CLG CEILING

CLO CLOSET

CMU CONCRETE MASONRY UNIT

CONC CONCRETE

CONT CONTINUOUS

CORR CORRIDOR

CSS CLINICAL SERVICE SINK

CPT CARPET

CT CERAMIC TILE

D

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DR DOOR

DWG DRAWING

DWR DRAWER

E

EA EACH

EG END WALL GUARD

ELEC ELECTRIC(AL)

ELEV ELEVATOR/ ELEVATION

EMER EMERGENCY

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXT EXTERIOR

F

FA FIRE ALARM

FT FEET/ FOOT

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FHS FIRE HOSE STATION (CABINET)

FHV FIRE HOSE VALVE CABINET

FLR FLOOR(ING)

FLUOR FLUORESCENT

FR FRAME

FVC FIRE VALVE CABINET

G

GALV GALVANIZE(D)

GB GRAB BAR

GC GENERAL CONTRACTOR

GOVT GOVERNMENT

GWB GYPSUM WALL BOARD

H

HC HOLLOWCORE

HDW HARDWARE

HGT HEIGHT

HM HOLLOW METAL

HORIZ HORIZONTAL

I

IB INTEGRAL BASE

ID INSIDE DIAMETER

IN INCH(ES)

INT INTERIOR

INTEG INTEGRAL

INTLK INTERLOCK

L

LAM LAMINATE(D)

LAV LAVATORY

LB POUND

LT LENGTH

LH LEFT HAND

LHRB LEFT HAND REVERSE BEVEL

LOCK LOCKERS

LVR LOUVER

M

MA MEDICAL AIR

MAX MAXIMUM

MED MEDICAL/MEDICATIONS

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MTL METAL

N

N NORTH/ NITROGEN

NC NURSE CALL

NEG NEGATIVE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OH OPPOSITE HAND

O/OX OXYGEN

OPG OPENING

P

PL PLATE

PLAM PLASTIC LAMINATE

PLYWD PLYWOOD

PNL PANEL

PNT PAINT

PR PAIR

PNT PAINT(ED)

PRT PARTITION

R

RB RESILIENT BASE

REQ REQUIRED

RESIL RESILIENT

REV REVISED

RH RIGHT HAND

RHRB RIGHT HAND REVERSE BEVEL

RO ROUGH OPENING

RCP REFLECTED CEILING PLAN

S

S SOUTH

SAB SOUND ATT. BATTS

SAFB SOUND ATT. FIRE BLANKET

SCW SOLID CORE WOOD

SEAL SEALANT

SECT SECTION

SHT SHEET

SIM SIMILAR

SPEC SPECIFICATION(S)

SQ SQUARE

SSM SOLID SURFACE MATERIAL

SS STAINLESS STEEL

SSV SEAMLESS SHEET VINYL

STC SOUND TRANSMISSION CLASS

STL STEEL

STN STAIN

STOR STORAGE

STRUCT STRUCTURAL

SV SHEET VINYL

T

TC TERRA COTTA

TEL TELEPHONE

TEMP TEMPORARY

THK THICK(NESS)

TOC TOP OF CURB

TOIL TOILET

TOS TOP OF SLAB/ TOP OF STEEL

TPTN TOILET PARTITION

TV TELEVISION

TW TOP OF WALL

TYP TYPICAL

TZ TERRAZZO

U

UNO UNLESS NOTED OTHERWISE

UON UNLESS OTHERWISE NOTED

UL UNDERWRITERS LAB.

V

VAC VACUUM

VB VAPOR BARRIER

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VIF VERIFY IN FIELD

VWC VINYL WALL COVERING

W

W WEST

W/ WITH

WC WATER CLOSET/

WATER COOLER/

WALL COVERING

WD WOOD

WG WIRE GLASS

WH WALL HUNG

W/O WITHOUT

WP WATERPROOF(ING)

WR WATER RESISTANT

WS WEATHERSTRIPPING

WSCT WAINSCOT

WT WEIGHT

ABBREVIATIONS

DOOR TAG

REMOVAL KEY NOTE

ANNOTATION SYMBOLS LEGEND:

WALL / PARTITION TYPE TAG

DETAIL ELEVATION

EXTERIOR ELEVATION

CALLOUT LASSO

XXX

DIMENSION STRING

X'-X"

X-XXXX

X-XXX

X

X

X-XXX

X

X-XXX

X

DETAIL SECTIONBUILDING

SECTION

WALL SECTION

NORTH

NORTH ARROW

1ST FLOOR

100' - 0"

ELEVATION MARKER

DETAIL

NUMBER

SHEET

DETAIL NUMBER

(TYP.)

SHEET (TYP.)

ROOM TAG

ROOM

REVISION IDENTIFICATION

REVISION

REVISION NUMBER

A WINDOW TAG

DOOR (EXISTING)

DOOR

(NEW CONSTRUCTION)

R#

RENOVATION KEY NOTE

EXISTING CONSTRUCTION

(TO BE REMOVED)

XXX

A

WINDOW TAG

WINDOW UNIT

DOOR

DOOR TAG

EXAMPLE:

A101

SIM

A101

SIM

HATCH LEGEND

CONCRETE

(CAST IN PLACE OR PRECAST)

GYPSUM WALL BOARD

CONCRETE MASONRY

EARTH

RIGID INSULATION

BATT INSULATION

WOOD / LUMBER

PLYWOOD

STEEL

UNDERBED MATERIAL

BRICK

ø 5

0"

30" MIN.

M

IN

TURNING RADIUS WHEELCHAIR APPROACH

ADA CLEARANCES:

M

IN

MAX.

6"

M

IN

MIN.

11"

MIN.

8"

MAX.

17" - 25"

KNEE & TOE CLEARANCES

WALL MOUNTED SCONCE

ACCESS HATCH/PANEL

CEILING HEIGHT A.F.F.X' - X"

REFLECTED CEILING PLAN LEGEND

CHANDELIER LIGHT FIXTURE

H HEAT DETECTOR

C CO DETECTOR

1X4 LIGHT FIXTURE

(SHADING DENOTES EMERGENCY LIGHT)

RECESSED CAN LIGHT FIXTURE

OCCUPANCY SENSOR

2x2 ACOUSTICAL CEILING TILE

1X4 T&G BOARD

GYPSUM WALL BOARD

2X4 LIGHT FIXTURE

(SHADING DENOTES EMERGENCY LIGHT)

2X2 LIGHT FIXTURE

(SHADING DENOTES EMERGENCY LIGHT)

EXIT LIGHT

OS

VENEER BEAD BOARD

EXTERIOR WALL PACK LIGHT

RETURN DIFFUSER - SIZES VARIES

NOTE: REFER TO 'FP', 'M', AND 'E' DRAWINGS FOR EXACT FIXTURE /

EQUIPMENT TYPE(S), SIZES AND ADDITIONAL INFORMATION.

2x4 ACOUSTICAL CEILING TILE

PENDANT LIGHT

EXHAUST DIFFUSER - SIZES VARIES

SUPPLY DIFFUSER - SIZES VARIES

S SMOKE DETECTOR

EMERGENCY LIGHT UNIT

COMBO EXIT/EMERGENCY LIGHT UNIT

SPRINKLER HEAD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377

KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

F R e v it L o c a ls

\2

.8

.0

V

A M

C B a lt im o re

R e n o v a te C o m p o u n d in g v jd e a n h u n te r@ d e lt a -e a s .c o m

.r v t

/1

/2

:2

:0

P

M

G-002

GENERAL - NOTES, SYMBOLS,

AND ABBREVIATIONS

05/17/2024 EJL JDHRevisions: Date:

jdeanhunter

EJL MD STAMP 11.2.2023

HOOD ROOM C

2C-126

R8

R8

EXISTING TO REMAIN

ENTRY

EXISTING PARTITION & DOOR SHALL

FUNCTION AS CONSTRUCTION BARRIERS

PROVIDE DOORS WITH CLOSER

R11

HOOD

2C-126

R6

EXISTING TO REMAIN

ENTRY

CLEAN ROOM SUITE

BA121L

CHEMO HOOD

BA121K

HOOD ROOM

R1

R3

R3

R3

R2

R4

R3

R5

R7

R7

R1

R1

EXISTING TO REMAIN

ENTRY

R7

R9

TEMPORARY CONSTRUCTION BARRIERS

PROVIDE CONSTRUCTION DOORS WITH CLOSERS

R10

R10

R6

R6

R6

EXISTING TO REMAIN

ENTRY

PROJECT ACTIVITY:

PATIENT RISK GROUP:

PATIENT RISK GROUP:

TYPE C

HIGHEST RISK (Any area caring for immunocompromised patients, Oncology)

CLASS III / IV

ICRA NOTES

DESCRIPTION OF REQUIRED INFECTION PREVENTION PRECAUTIONS BY CLASS

DURING CONSTRUCTION UPON COMPLETION OF CONSTRUCTION

1. OBTAIN INFECTION CONTROL PERMIT BEFORE

CONSTRUCTION BEGINS.

2. ISOLATE HVAC SYSTEM IN AREA WHERE WORK

IS BEING DONE TO PREVENT CONTAMINATION OF

THE DUCT SYSTEM.

3. COMPLETE ALL CRITICAL BARRIERS OR

IMPLEMENT CONTROL CUBE METHOD BEFORE

CONSTRUCTION BEGINS.

4. MAINTAIN NEGATIVE AIR PRESSURE WITHIN

WORK SITE UTILIZING HEPA EQUIPPED AIR

FILTRATION UNITS.

5. REMOVE OR ISOLATE HVAC SYSTEMS IN AREA

WHERE WORK IS BEING PERFORMED.

6. DO NOT REMOVE BARRIERS FROM WORK SITE

UNTIL COMPLETE AND PROJECT IS THOROUGHLY

CLEANED BY EMS.

7. VACUUM WORK WITH HEPA FILTERED VACUUM.

8. WET MOP WITH DISINFECTANT.

9. REMOVE BARRIER MATERIAL CAREFULLY TO

MINIMIZE SPREADING OF DUST AND DEBRIS

ASSOCIATED WITH CONSTRUCTION.

10. CONTAIN CONSTRUCTION WASTE BEFORE

TRANSPORT IN TIGHTLY COVERED CONTAINERS.

11. COVER TRANSPORT RECEPTACLES OR CART

AND TAPE COVERING IN PLACE.

12. SEAL HOLES, PIPES, CONDUITS AND

PENETRATIONS APPROPRIATELY.

13. CONSTRUCT ANTEROOM & REQUIRE ALL

PERSONNEL TO PASS THROUGH THIS ROOM SO

THEY CAN BE VACUUMED USING A HEPA VACUUM

CLEANER BEFORE LEAVING WORKSITE OR THEY

CAN WEAR CLOTH OR PAPER COVERALLS THAT

ARE REMOVED EACH TIME THEY LEAVE THE

WORK SITE.

14. WEAR SHOE COVERS WHEN WITHIN ENTERING

WORK SITE.

1. DO NOT REMOVE BARRIERS FROM WORK AREA

UNTIL COMPLETED PROJECT IS INSPECTED BY

THE OWNER’S SAFETY DEPARTMENT AND

INFECTION PREVENTION COORDINATOR AND

THOROUGHLY CLEANED BY (EMS)

ENVIRONMENTAL MANAGEMENT SERVICES.

2. REMOVE BARRIER MATERIALS CAREFULLY TO

MINIMIZE SPREADING OF DIRT AND DEBRIS

ASSOCIATED WITH CONSTRUCTION.

3. VACUUM WORK AREA WITH HEPA FILTERED

VACUUMS.

4. WET MOP AREA WITH DISINFECTANT.

5. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS

WHERE WORK IS BEING PERFORMED

6. CONTAIN CONSTRUCTION WASTE BEFORE

TRANSPORT IN TIGHTLY COVERED CONTAINERS.

7. COVER TRANSPORT RECEPTACLES OR CARTS.

TAPE COVERING UNLESS SOLID LID

8. VACUUM WORK AREA WITH HEPA FILTERED

VACUUMS.

9. WET MOP AREA WITH DISINFECTANT.

10. INSTALLATION OF STICKY DUST COLLECTION

MAT AT ENTRANCE OF CONTAINED WORK (INSIDE

BARRIER, NOT OUTSIDE)

CLASS: CLASS IV

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377

KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

AB

DC

NORTH

KEYPLAN

F R e v it L o c a ls

\2

.8

.0

V

A M

C B a lt im o re

R e n o v a te C o m p o u n d in g v jd e a n h u n te r@ d e lt a -e a s .c o m

.r v t

/1

/2

:2

:0

P

M

AD-101

ARCHITECTURAL - FLOOR PLANS -

DEMOLITION

05/17/2024 EJL JDH

GENERAL REMOVAL NOTES

A. ITEMS DESIGNATED ON PLAN BY DASHED LINE ARE EXISTING ELEMENTS TO BE

REMOVED. REFER TO OTHER TRADE DRAWINGS FOR OTHER REMOVALS, INCLUDING

MODIFICATIONS THAT MAY EXTEND BEYOND AREAS SHOWN.

B. FOR DURATION OF PROJECT, EXISTING CONSTRUCTION AND/OR EQUIPMENT TO

REMAIN FROM DAMAGE OR CONSTRUCTION ACTIVITIES. WHERE CONSTRUCTION

ACTIVITIES RESULT IN DAMAGE TO EXISTING CONSTRUCTION TO BE RETAINED,

REPLACE/REPAIR EXISTING CONSTRUCTION TO RETURN IT TO ITS ORIGINAL

CONDITION. WHERE REMOVAL OF EXISTING CONSTRUCTION, PIPING, DUCTWORK,

AND OTHER ITEMS CREATES OPENINGS IN WALLS, FLOORS OR CEILINGS, PATCH

OPENINGS IMMEDIATELY WITH SAME MATERIALS AS ADJACENT CONSTRUCTION

AND/OR TO MAINTAIN REQUIRED FIRE RATING. ANY WORK AFFECTING THE WALL

MUST BE PAINTED TO MATCH EXISTING COLOR AND LAYERS. PROVIDE TWO COASTS

OF PAINT AND TWO COATS OF PRIMER MIN.

C. PROVIDE FULL HEIGHT TEMPORARY CONSTRUCTION BARRIERS WHERE REQUIRED TO

PREVENT DUST POLLUTION OF SURROUNDING OCCUPIED AREAS. CONSTRUCTION

BARRIERS ARE REQUIRED PER THE ICRA PERMIT. SEAL AIR-TIGHT. PARTITIONS MUST

BE INSTALLED IN ACCORDANCE WITH FIRE PROTECTION AND EGRESS

REQUIREMENTS. MAINTAIN MEANS OF EGRESS ACCESS TO EXITS DURING

CONSTRUCTION.

D. TAKE PROPER MEASURES TO PREVENT DUST MIGRATION TO AREAS OUTSIDE THE

CONSTRUCTION AREA BY CLOSING ALL OPENINGS IN DUCTS, WALLS, FLOORS AND

CEILINGS. PROVIDE CONTINUOUS EXHAUST TO EXTERIOR TO MAINTAIN NEGATIVE

PRESSURE IN CONSTRUCTION AREA.

E. COORDINATE WITH OWNER FOR EQUIPMENT TO BE SALVAGED AND RETURNED TO

OWNER. THE OWNER WILL RETAIN ALL SALVAGE THAT IS OF VALUE AS DESIGNATED

BY THE USER OR BUILDING ENGINEER. REMOVE FROM THE BUILDING AND DISPOSE

OF IN A LAWFUL MANNER ALL DEBRIS AND/OR ITEMS NOT RETAINED BY OWNER.

F. ADHESIVE MATS SHALL BE PLACED INSIDE CONSTRUCTION AREA ONLY TO REDUCE

TRIP HAZARD PER INFECTION CONTROL PROCEDURE. MATS ARE TO BE REPLACED

WITH NEW SHEET ON AN AS-NEEDED BASIS, BUT AT A MINIMUM OF DAILY BASIS.

G. COORDINATE WITH OTHER TRADE DRAWINGS FOR REMOVAL WORK, AS REQUIRED.

REMOVAL KEY NOTES

R1 REMOVE EXISTING PARTITION. PATCH AND REPAIR AS NEEDED.

R2 REMOVE EXISTING CASEWORK/CABINETS. PATCH AND REPAIR AS NEEDED.

R3 REMOVE EXISTING EQUIPMENT. COORDINATE WITH GC AND OWNER

R4 REMOVE EXISTING SINK AND CABINET.

R5 REMOVE EXISTING COUNTERTOP, PREP AREA TO RECEIVE NEW COUNTERTOP.

R6 REMOVE EXISTING CEILING. PREP AREA TO RECEIVE NEW LIGHTING AND CEILING.

R7 REMOVE EXISTING DOOR AND FRAME

R8 REMOVE EXISTING FURNITURE. COORDINATE WITH OWNER.

R9 REMOVE EXISTING EYEWASH

R10 REMOVE EXISTING ADA ACCESS PUSH BUTTON. V.I.F. LOCATION

R11 REMOVE EXISTING WINDOW PANEL & SUBFRAME, PREPARE AREA FOR PANEL

INFILL & LOUVER PENETRATION

SCALE: 1/4" = 1'-0"AD-101

3 SECOND FLOOR- REMOVAL PLAN

SCALE: 1/4" = 1'-0"AD-101

4 SECOND FLOOR - REMOVAL RCP

SCALE: 1/4" = 1'-0"AD-101

1 BASEMENT-REMOVAL PLAN

SCALE: 1/4" = 1'-0"AD-101

2 BASEMENT-REMOVAL RCP

0'

SCALE: 1/4" = 1'-0"

1' 2' 8'4'

Revisions: Date:

SS

MALE

TOIL.

SUPERV.

OFFICE

S-9

STAIR #5

DIETETIC CLEAN

CART SENDING

TERMINAL

ELEC.

CLO

H.A.C.

AIRLOCK

STORAGE

CORRIDOR

CORRIDOR

FEC

FEC

STERILIZE

GOWN

AIRLOCK

CORRIDOR

PROCEDURAL

LAB

ANIMAL

LAB

ANIMAL

WARD

CAGE

WASHING

CONTAINMENT

ANIMAL WARD

CONTAINMENT

ANIMAL WARD

CONTAINMENT

ANIMAL WARD

HAZARD

ANIMAL WARDHAZARD

ANIMAL WARD

HAZARD

ANIMAL

WARD

HAZARD

ANIMAL

WARD

HAZARD

ANIMAL

WARD

BARRIER

ANIMAL WARD

BARRIER

ANIMAL WARD

BARRIER

ANIMAL WARD

BARRIER

ANIMAL WARD

SHOWER

CORRIDOR

AIRLOCK AIRLOCK

MAIL

REPRO.

FEMALE

TOIL.

P.T.S.

UP

8K

SOILED

LINEN

GREASE

INTERCEPTOR

HAC

SUBSISTENCE

STORAGE

SILVER

COLLECTION

STOR.

KEEPER

VEST.

LOUNGE

OFFICE

BB103

BB146

BB147

BB118

BB120

BB123

BB124

BB122

BB102

BB100d

BB100c

BB100e

BB100b

CB-26

CB-25

CB-22

CB-23

BB121

CB-15

BB106a

BB106

BB106b BB109a

BB109

BB111BB108

BB112

BB117

BB119

BB107

BB116

CB-12

CB-13

H12B2-72

BLDG. MGMT.

SEC'Y/WAITING

BLDG. MGMT.

SUPERV. OFFICE

BLDG. MGMT.

SUPERV. OFFICE

BLDG. MGMT.

CHIEF OFFICE

BLDG. MGMT.

FEMALE LKR'S

BLDG. MGMT.

MALE LKR'S

BLDG. MGMT.

STAFF LOUNGE

BLDG. MGMT.

STORAGE

DIET. STAFF

DINING/TRAINING

HAC

CLEAN LINEN

SORTING/STORAGE

MALE

TOIL.

DIETETIC FOOD

PROCESSING

OFFICE

SUPERV.

OFFICE

TELETYPE

TRAY

MAKE UP

S-12

S-9

STAIR #5

DIETETIC CLEAN

CART SENDING

TERMINAL

P-4

H.A.C.

ELEC.

CLO

H.A.C.

STORAGE

FEC

FEC

ADMIN. AREA

BULK STORAGESOLUTION

STORAGE

SEC'Y

WAITING

ASS'T

CHIEF

CART

STOR.

AIRLOCK

PROCEDURAL

LAB

CONTAINMENT

ANIMAL WARD

HAZARD

ANIMAL WARD

HAZARD

ANIMAL

WARD

BARRIER

ANIMAL WARD

AIRLOCK

MAIL

TELE.

SWITCH BD.

REPRO.

P.T.S.

PICKING

AREA

INPATIENT

PHARMACY

DRUG INFORMATION

METHADONE PKG./

VAULT

LOUNGE/

LOCKERS

OFFICE OFFICE CLERK

CLERK

SUPERVISOR

OFFICE

SUPERVISOR

OFFICE

CART

STORAGE

FEMALE

TOIL.

P.T.S.

CORRIDOR

W/C

M.TOILET

W/C

F.TOILET

UP

CHIEF

RECEIV'G.

BB114

BA106a BA107

BA108

BA121a

BA103

BA119a

BA119b

BA119c

BA118b

BA118d

BA118e

BA120h

BA120g

BA120i

BA121h

BA121i

BA121g

BA121j

BA121f

BA120

BA121c

BA121b

BA121

CB-7

CB-5

BA104

BA105e

BA105a

BA105o

BA105n

BA105

BA109a

BA110

BA109

CB-6

BA101

BB101

BB115

BA121d

BB109b

BB111

BB113

CB-24

BA106

BA120b

BA121e

BA120j

BA120d BA120f

BA120eBA120cBA120a

BA102

BA117a

CB-8

BB110

BB109

BB116

CB-12

UP

142 SF

PHARMACY

BA121K

175 SF

ANTEROOM

BA121L

99 SF

HOOD ROOM A

BA121O

100 SF

HOOD ROOM B

BA121P

EXISTING TO REMAIN

LIFE SAFETY LEGEND

1 HOUR FIRE RESISTANCE RATING

2 HOUR FIRE RESISTANCE RATING

PRIMARY EGRESS PATH

SECONDARY EGRESS PATH

MRP MOST REMOTE POINT OF EGRESS

ACCESS

EXIT DISCHARGE

TD = XX' - XX" TRAVEL DISTANCE TO EXIT

FIRE EXTINGUISHER

FIRE EXTINGUISHER CABINET

SMOKE BARRIER (1HR RATED,

UNLESS OTHERWISE SHOWN)

HOOD ROOM C

2C-126

STAIR #1

HEMODIALYSIS

2C-127

EXAM ROOM

2C-127b

EXAM ROOM

2C-127c

NURSE STATION

C2-35

DIETETICS

2C-127E

EXAM ROOM

2C-127F

CORRIDOR

C2-28

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377

KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

AB

DC

NORTH

KEYPLAN

F R e v it L o c a ls

\2

.8

.0

V

A M

C B a lt im o re

R e n o v a te C o m p o u n d in g v jd e a n h u n te r@ d e lt a -e a s .c o m

.r v t

/1

/2

:2

:0

P

M

AL-101

LIFE SAFETY PLAN

05/17/2024 EJL JDH

SCALE: 3/32" = 1'-0"AL-101

1 ARCHITECTURAL - FLOOR PLANS - PARTIAL BASEMENT LIFE SAFETY PLAN

SCALE: 3/32" = 1'-0"AL-101

2 ARCHITECTURAL - FLOOR PLANS - PARTIAL 2ND FLOOR LIFE SAFETY PLAN

0'

SCALE: 3/32" = 1'-0"

5'-4" 21'-4"10'-8"

NOTES:

1. MODIFY EXISTING PARTITIONS TO MEET 1 HOUR FIRE RATING.

Revisions: Date:

18' - 11"

AS-201

AS-201

AS-201

AS-201

142 SF

PHARMACY

BA121K

175 SF

ANTEROOM

BA121L

99 SF

HOOD ROOM A

BA121O

100 SF

HOOD ROOM B

BA121P

EXISTING TO REMAIN

ENTRY

9' - 3" 9' - 3"

103 104

A1.1

A1.1

A1.1

1"6'

TEMPORARY

CONSTRUCTION BARRIERS

PROVIDE CONSTRUCTION

DOORS WITH CLOSERS

B

B

9 10

A1.3

1' - 11"

3'

/2

1'

/2

B1.1

2'

2' - 7 1/2"

1'

/2

1'

/2

130 SF

HOOD ROOM C

2C-126

AS-201

EXISTING TO REMAIN

ENTRY

TEMPORARY CONSTRUCTION BARRIERS

PROVIDE CONSTRUCTION DOORS WITH

CLOSERS

A1.3

A1.3

1' - 9"

ALIGN

1'

B1.1

6 1/2"

AS-501

AS-501

6 6

ENTRY

8' - 0"

8' - 0"

8' - 0" 8' - 0"

ANTEROOM

BA121L

PHARMACY

BA121K

HOOD ROOM A

BA121O

HOOD ROOM B

BA121P

EXISTING TO REMAIN

EXISTING TO REMAIN ENTRY

HOOD ROOM C

2C-126 8' - 0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377

KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

AB

DC

NORTH

KEYPLAN

F R e v it L o c a ls

\2

.8

.0

V

A M

C B a lt im o re

R e n o v a te C o m p o u n d in g v jd e a n h u n te r@ d e lt a -e a s .c o m

.r v t

/1

/2

:2

:1

P

M

AS-101

ARCHITECTURAL - FLOOR PLANS -

NEW WORK

05/17/2024 EJL JDH

SCALE: 1/4" = 1'-0"AS-101

1 BASEMENT-NEW WORK PLAN

SCALE: 1/4" = 1'-0"AS-101

3 SECOND FLOOR- NEW WORK PLAN

SCALE: 1/4" = 1'-0"AS-101

2 BASEMENT-NEW WORK RCP

SCALE: 1/4" = 1'-0"AS-101

4 SECOND FLOOR - NEW WORK RCP

GENERAL ARCHITECTURAL NOTES

A. VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS. NOTIFY THE ARCHITECT OF

DISCREPANCIES PRIOR TO COMMENCING WORK. EXISTING CONDITIONS THAT WOULD

AFFECT THE EXECUTION OF THE WORK MUST BE BROUGHT TO THE ATTENTION OF THE

ARCHITECT PRIOR TO COMMENCING THE WORK.

B. DIMENSIONS GIVEN ON PLANS ARE FROM FINISHED FACE TO FINISHED FACE UNLESS

OTHERWISE NOTED. DIMENSIONS ARE NOT ADJUSTABLE WITHOUT THE APPROVAL OF

THE ARCHITECT UNLESS OTHERWISE NOTED.

C. PROVIDE BLOCKING IN WALLS AS REQUIRED TO SUPPORT WALL MOUNTED ITEMS.

LOCATE EQUIPMENT AND COORDINATE BLOCKING LOCATIONS IN FIELD.

D. PROVIDE PROTECTION OF EXISTING FINISHES AND/OR MATERIALS. RESTORE TO

ORIGINAL CONDITIONS AREAS OR FINISHES DAMAGED BY THE WORK, AT THE EXPENSE

OF THE CONTRACTOR. REMOVE MEANS OF PROTECTION AT THE END OF THE

PROJECT.

E. ALL SCRATCHES, DENTS, CRACKS, HOLES, OPENINGS, IRREGULARITIES AND/OR

DEFECTS IN BOTH EXISTING AND NEW CONSTRUCTION SURFACES ARE TO BE

PATCHED TO PROVIDE A UNIFORM AND SMOOTH FINISHED SURFACE. CLEAN AND SAND

SMOOTH SURFACES BEFORE APPLYING FINISH MATERIALS.

F. REMOVE ALL EXCESS BUILD-UP OF EXISTING AND/OR NEW WALL AND PAINT

MATERIALS FROM ALL NEW AND EXISTING WALL SURFACES. CLEAN AND FINISH SAND

SMOOTH TO PROVIDE A UNIFORM AND SMOOTH WALL SURFACE READY FOR THE

APPLICATION OF FINISH MATERIALS.

G. DIMENSIONS LOCATING DOORS OR INTERIOR WINDOWS ARE TO OUTSIDE EDGE OF

FRAME UNLESS NOTED OTHERWISE. REFER TO DOOR & WINDOW SHEETS FOR FRAME

TYPE, SIZE AND DETAILS.

H. REFER TO CIVIL, STRUCTURAL, FIRE PROTECTION, PLUMBING, MECHANICAL, AND

ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.

I. NEW WORK SHALL BE COMPLIANT WITH NFPA 45.

RENOVATION KEY NOTES

1 INSTALL PARTITION AND DOOR

2 INSTALL PASS-THROUGH WINDOW

3 INSTALL EQUIPMENT. SEE EQUIPMENT SCHEDULE.

4 INSTALL MOBILE WORKSTATION SYSTEM.

5 INSTALL MOBILE BASE CABINET.

6 INSTALL GYP BOARD CEILING & LIGHTING FIXTURES.

7 INSTALL DOOR W/ WITH CLOSER AT EXISTING PARTITION

8 INSTALL WALL MOUNTED SINK. SEE PLUMBING SCHEDULE

9 INSTALL STICKY DUST COLLECTION MAT

10 INSTALL ADA ACCESS PUSH BUTTON

11 INSTALL FIRE SHUTTER @ PASS THROUGH WINDOW. SEE DETAILS 5/6/7-AS-501

12 INSTALL CARD READER

NOTE: REFER TO ELEC. DRAWINGS FOR LIGHTING LAYOUT.

NOTE: REFER TO ELEC. DRAWINGS FOR LIGHTING LAYOUT.

0'

SCALE: 1/4" = 1'-0"

1' 2' 8'4'

Revisions: Date:

142 SF

PHARMACY

BA121K

175 SF

ANTEROOM

BA121L

99 SF

HOOD ROOM A

BA121O

100 SF

HOOD ROOM B

BA121P

EXISTING TO REMAIN

ENTRY

PNT-3

PNT-3

PNT-3

PNT-3

PNT-3

130 SF

HOOD ROOM C

2C-126

EXISTING TO REMAIN

ENTRY

PNT-3

FLOOR FINISH LEGEND

RF-1

142 SF

PHARMACY

BA121K

175 SF

ANTEROOM

BA121L

99 SF

HOOD ROOM A

BA121O

100 SF

HOOD ROOM B

BA121P

EXISTING TO REMAIN

ENTRY

1 2

130 SF

HOOD ROOM C

2C-126

EXISTING TO REMAIN

ENTRY

2 4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377

KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

AB

DC

NORTH

KEYPLAN

F R e v it L o c a ls

\2

.8

.0

V

A M

C B a lt im o re

R e n o v a te C o m p o u n d in g v jd e a n h u n te r@ d e lt a -e a s .c o m

.r v t

/1

/2

:2

:1

P

M

AS-102

ARCHITECTURAL - FINISH &

EQUIPMENT PLAN

05/17/2024 EJL JDH

SCALE: 1/4" = 1'-0"AS-102

1 BASEMENT-FINISH PLAN

SCALE: 1/4" = 1'-0"AS-102

2 SECOND FLOOR- FINISH PLAN

ROOM FINISH SCHEDULE LEGEND

MATERIAL /

FINISH NAME DESCRIPTION

ACT ACOUSTICAL CEILING TILE

CFT CERAMIC FLOOR TILE

CMU CONCRETE MASONRY UNITS

CONC. CONCRETE

CWT CERAMIC WALL TILE

EPY EPOXY

EX. EXISTING

GWB GYPSUM WALL BOARD

LVT LUXURY VINYL TILE

PNT PAINT

RF RUBBER FLOORING

ROOM FINISH SCHEDULE

ROOM

NUMBER

ROOM NAME

FLOOR

BASE

WALLS CEILING

COMMENTS

FINISH FINISH FINISH

2C-126 HOOD ROOM C RF-1 RF INTEGRAL PNT-1/PNT-2 GYP

BA121K PHARMACY RF-1 RF INTEGRAL PNT-1/PNT-2 GYP

BA121L ANTEROOM RF-1 RF INTEGRAL PNT-1/PNT-2 GYP

BA121O HOOD ROOM A RF-1 RF INTEGRAL PNT-1/PNT-2 GYP

BA121P HOOD ROOM B RF-1 RF INTEGRAL PNT-1/PNT-2 GYP

NOTES:

1. WALLS MUST BE COVERED WITH EPOXY PAINT OR HEAVY GAUGE POLYMER.

2. WALLS ARE PNT-2 UNLESS NOTED OTHERWISE.

3. SEE SPEC SECTION 090600 FOR PNT SELECTION.

SCALE: 1/4" = 1'-0"AS-102

3 BASEMENT-EQUIPMENT PLAN

SCALE: 1/4" = 1'-0"AS-102

4 SECOND FLOOR- EQUIPMENT PLAN

EQUIPMENT SCHEDULE

EQUIPMENT NUMBER EQUIPMENT NAME Manufacturer Model FURNISH/INSTALL COMMENTS

1 EDGEGARD HOOD BAKER EG-5252 GF/GF

2 CHEMO SHIELD BAKER CS600 GF/GF

3 PHARMACY REFRIGERATOR DOUBLE DOOR SO-LOW DH4-49SD

4 PHARMACY REFRIGERATOR SINGLE DOOR SO-LOW DH4-27SD GF/GF

5 MOBILE WORKSTATION KEWAUNEE FE30M8402

GF/GF

GC/GC

0'

SCALE: 1/4" = 1'-0"

1' 2' 8'4'

Revisions: Date:

PASSTHROUGH

WINDOW

MOBILE CABINET, TYP.

MOBILE

WORKSTATION

SLIDING

DOOR

FINISH

PANEL

AS-501

2' - 0"

2'

0"

3'

STAINLESS STEEL

COUNTERTOP

BASE AS

SCHED.6' - 0"

MOBILE BASE CABINET, TYP.

STAINLESS STEEL COUNTERTOP

MOBILE WORKSTATION

2'

0"

BASE AS SCHED. 2'

2' - 0"

6' - 0"

REFRIGERATOR UNIT

SLIDING DOOR

BASE AS SCHED.

3'

2'

PUSH BUTTON

7'

SHUTTER DOOR

1'

3'

PASSTHROUGH WINDOW

BASE AS SCHED.

1' - 1"

4'

B B

AS-501

MOBILE BASE CABINET, TYP.

STAINLESS STEEL COUNTERTOP

MOBILE WORKSTATION

6' - 0"

2' - 0"

2'

BASE AS SCHED.

SOAP DISPENSER

3'

WALL

MOUNTED

SCRUB SINK

3' - 0" 7 1/2"

2'

0"

MOBILE CABINET, TYP.

MOBILE

WORKSTATION

PASS THROUGH

WINDOW

AS-501

3'

BASE AS SCHED.

2' - 0"

2'

6' - 0"

CABINET HOOD

BASE AS SCHED.

BASE CABINET, TYP.

S.S. COUNTERTOP W/ BACKSPLASH

2'

0"

PASSTHROUGH

WINDOW

BASE AS SCHED.

1'

1' - 0" 1' - 3 1/2"

3'

/2

B

AS-501

NEW MECHANICAL

HOOD

BASE AS

SCHED.

REFRIGERATOR PASSTHROUGH WINDOW

BASE AS SCHED.3'

/2

1'

2' - 4"

B

AS-501

CABINET HOOD

REFRIGERATOR

BASE AS SCHED.

WALL MOUNTED SINK

BASE AS SCHED.

AUTOMATIC DOOR PUSH BUTTON

2'

0"

3' - 0"

MOBILE BASE CABINET, TYP.

STAINLESS STEEL COUNTERTOP

MOBILE SHELVING UNIT

BASE AS SCHED.

8' - 0"

2' - 0"

2'

2'

0"

CARD READER

BASE AS SCHED.

MOBILE BASE CABINET, TYP.

STAINLESS STEEL COUNTERTOP

MOBILE WORKSTATION

2'

0"

2'

2' - 0"

CABINET HOOD

BASE AS SCHED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377

KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

F R e v it L o c a ls

\2

.8

.0

V

A M

C B a lt im o re

R e n o v a te C o m p o u n d in g v jd e a n h u n te r@ d e lt a -e a s .c o m

.r v t

/1

/2

:2

:1

P

M

AS-201

ARCHITECTURAL - ELEVATIONS

05/17/2024 EJL JDH

SCALE: 3/8" = 1'-0"AS-201

1 PHARMACY- ELEVATION 1

SCALE: 3/8" = 1'-0"AS-201

2 PHARMACY - ELEVATION 2

SCALE: 3/8" = 1'-0"AS-201

3 PHARMACY -ELEVATION 3

SCALE: 3/8" = 1'-0"AS-201

4 ANTEROOM- ELEVATION 1

SCALE: 3/8" = 1'-0"AS-201

5 ANTEROOM - ELEVATION 2

SCALE: 3/8" = 1'-0"AS-201

6 ANTEROOM - ELEVATION 3

SCALE: 3/8" = 1'-0"AS-201

8 HOOD ROOM A - ELEVATION 2

SCALE: 3/8" = 1'-0"AS-201

9 HOOD ROOM A - ELEVATION 3

SCALE: 3/8" = 1'-0"AS-201

11 HOOD ROOM B - ELEVATION 2

SCALE: 3/8" = 1'-0"AS-201

12 HOOD ROOM B - ELEVATION 3

SCALE: 3/8" = 1'-0"AS-201

13 HOOD ROOM C - ELEVATION 1

SCALE: 3/8" = 1'-0"AS-201

14 HOOD ROOM C - ELEVATION 2

SCALE: 3/8" = 1'-0"AS-201

15 HOOD ROOM C - ELEVATION 3

SCALE: 3/8" = 1'-0"AS-201

10 HOOD ROOM B - ELEVATION 1

0'

SCALE: 3/8" = 1'-0"

1'-4" 5'-4"2'-8"

SCALE: 3/8" = 1'-0"AS-201

7 HOOD ROOM A - ELEVATION 1

Revisions: Date:

LOUVER WIDTH

LO

U

V E

R H

E

IG

H T

LOUVER

FRAME

LOUVER

BLADES

SEE MECHANICAL FOR LOUVER TYPES

LOUVER FRAME

EXISTING WALL

INSECT SCREEN

WALL ANGLE FRAME

SEALANT @

PERIMETER, TYP

NOTES:

1. LOUVER/DAMPER ASSEMBLIES TO BE ASSEMBLED

AT LOUVER MANUFACTURER FACTORY.

2. CLIP ANGLES AND EXTENDED SILL TO BE PROVIDED

BY LOUVER MANUFACTURER.

3. INSTALLATION OF LOUVER TO BE IN ACCORDANCE

WITH LOUVER MANUFACTURER'S RECOMMENDATIONS.

EXISTING

EXTERIOR WALL

BIRD SCREEN

CLIP ANGLES

STORM BLADE

LOUVER

LOUVER ASSEMBLY

FINISH TO MATCH WALL

EXTERIOR

BACKER ROD & SEALANT

HEAD FLASHING, CARRY OVER

LOUVER ASSEMBLY AND TURN UP

AT ANGLE CLIPS

INTERIOREXTERIOR

SILL FLASHING, CARRY UNDER &

BEHIND LOUVER ASSEMBLY

3-SIDED SQUARE

HOOD

PAD LOCKABLE SLIDE BOLT

STOPPERS

ASTRAGAL

5 1/2"

CULUS CLASSIFIED TO: ANSI/UL 10B AND

CAN/ULC-S104 ROLLING COUNTER FIRE DOOR

#22 GA. INTERLOCKING SLATS

1 HOUR RATED

ALARMGARD CRANK OPERATION

MINIMUM #16 GA STEEL STUDS

REQUIRED AT JAMB AND SILL

#14 PHILIPS PAN HEAD TAPPING SCREWS

3" LONG W/ STEEL & FIBER WASHERS. 18"

ON CENTER MAXIMUM

1/2"

2"

STEEL BRACKET PLATE

ABOVE

2"

2"

OPENING WIDTH

5"

#12 GA GUIDE

DISTANCE BETWEEN GUIDES

TOP HOOD BEAD

TURNED UP11"11 3/4" ±

8 3/4" ±

4" B

O T

T O

M O

F D

O O

R O

P E

N

IN

G T

O F

.F

REMOVABLE HAND

CRANK

CLEAR SEALANT

PARTITION AS SCHED.

PASS-THROUGH WINDOW

ASSEMBLY

8 PC. UNIVERSAL

STAINLESS STEEL

MOUNTING FRAME

SET

1" 2' - 0" 1"

MECHANICAL

INTERLOCK, NON-

LOCKING, STAINLESS

STEEL T-HANDLES

OVER CENTER

COMPRESSION LATCH,

STAINLESS STEEL

PASS THROUGH

WINDOW ASSEMBLY

1 1/2"

8 PC. UNIVERSAL

STAINLESS STEEL

MOUNTING FRAME

SET

BASE CABINET W/SSM

COUNTERTOP. SEE

DWG 4/A-601

4"

1 1/2" 2 1/2"

MECHANICAL

INTERLOCK, NON-

LOCKING, STAINLESS

STEEL T-HANDLES

OVER CENTER

COMPRESSION LATCH,

STAINLESS STEEL

1" 1' - 0" 1"

1/

2"

PASS THROUGH

WINDOW ASSEMBLY

EXISTING OUTER WINDOW

FRAME

EXHAUST

LOUVER. SEE

MECH DWG.

EXISTING

STRUCTURE.

LOUVER ASSEMBLY

EXISTING STRUCTURE

5/8" GYP BD.

3" BATT INSULATION

SEALANT

LOUVER FRAME

INSULATED BLANK

OFF PANEL

EXISTING WINDOW

OUTER FRAME

3 5/8" METAL STUD

ALIGN TO EDGE OF SILL

EXISTING OUTER WINDOW

FRAME

EXHAUST

LOUVER. SEE

MECH DWG.

EXISTING WINDOW

ASSEMBLY

LOUVER ASSEMBLY

EXISTING STRUCTURE

5/8" GYP BD.

3" BATT INSULATION

LOUVER FRAME

INSULATED BLANK

OFF PANEL

EXISTING WINDOW

OUTER FRAME

3 5/8" METAL STUD

EXISTING

STRUCTURE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377

KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

F R e v it L o c a ls

\2

.8

.0

V

A M

C B a lt im o re

R e n o v a te C o m p o u n d in g v jd e a n h u n te r@ d e lt a -e a s .c o m

.r v t

/1

/2

:2

:2

P

M

AS-501

DETAILS

05/17/2024 EJL JDH

SCALE: 1 1/2" = 1'-0"AS-501

2 LOUVER ELEVATION

SCALE: 1 1/2" = 1'-0"AS-501

3 LOUVER JAMB DETAIL TYP.

SCALE: 1 1/2" = 1'-0"AS-501

1 LOUVER, TYP

SCALE: 1 1/2" = 1'-0"AS-501

7 FIRE SHUTTER - ELEVATION DETAIL

SCALE: 3" = 1'-0"AS-501

9 FIRE SHUTTER - PLAN DETAIL

SCALE: 1 1/2" = 1'-0"AS-501

8 FIRE SHUTTER - SECTION DETAIL

SCALE: 1 1/2" = 1'-0"AS-501

6 PASS THROUGH WINDOW @ PHARMACY

SCALE: 1 1/2" = 1'-0"AS-501

10 PASSTHROUGH WINDOW

1. SEE MECH DWG FOR LOUVER LOCATIONS.

NOTES:

0'

SCALE: 1-1/2" = 1'-0"

2" 4" 1'-4"8"

SCALE: 1 1/2" = 1'-0"AS-501

4 LOUVER @ WINDOW SECTION DETAIL

SCALE: 1 1/2" = 1'-0"AS-501

5 LOUVER @ WINDOW JAMB DETAIL

Revisions: Date:

2" 2"

F-1

S E

E S

C H

E D

U

LE

2"

SCHEDULE

SEE

FRAME TYPE LEGEND

DOUBLE DOOR

2" 2"SEE SCHEDULE

G-1 S

E E

S C

H E

D U

LE

2"

A

S E

E S

C H

E D

U

LE

SCHEDULE

SEE

FLUSH MOUNTED

DOOR

DOOR TYPE LEGEND

FLUSH MOUNTED SLIDING

DOUBLE DOORS

S E

E S

C H

E D

U

LE

SCHEDULE

SEE

INACTIVE

LEAF

B

2"

INTERIOR PARTITION

METAL STUD LINTEL AS

REQ. FOR SPAN

METAL RUNNER CHANNEL

SEALANT, TYP.

HOLLOW METAL FRAME AS

SCHEDULED

DOOR AS SCHEDULED

M

IN

4" 2"

INTERIOR PARTITION

(2) METAL STUDS FLOOR TO TOP

OF WALL, BRACE TO STRUCTURE

SEALANT, TYP.

HOLLOW METAL FRAME (AS

SCHEDULED)

DOOR AS SCHEDULED

ADJACENT

WALL

(3) ANCHORS PER JAMB

PARTITION TYPE A1.1

SEALANT, BOTH SIDES

BOTTOM OF STRUCTURE

SEALANT, BOTH SIDES

TOP OF STRUCTURE

3 5/8" METAL STUD, 16"

O.C.

5/8" GYPSUM BOARD TYPE

CEILING AS SCHEDULED

3" SAFB

5"

S E

C T

IO

N

P

LA

N V

IE

W

S E

C T

IO

N

CEILING RUNNER, FASTEN TO STRUCTURE

AT 16": O.C., MINIMUM

FLOOR RUNNER, FASTEN TO STRUCTURE

AT 24": O.C., MINIMUM

FIRE RESISTANCE RATING = N/A

STC RATING = 49

NON-RATED PARTITION

A1.3

FIRE UL STC SAB

1HR 47 1 1/2"U419

NOTES

A1.2 N/A N/A N/AN/A

A1.5 N/A N/A N/AN/A

A1.4 1HR 49 3"U419

USE 1/2" GYP. BD.

N/A

N/A

STANDARD PARTITION PARTITION TYPE B1.1

SEALANT

BOTTOM OF STRUCTURE

SEALANT

TOP OF STRUCTURE

1 1/2" METAL STUD, 16"

O.C.

5/8" GYPSUM BOARD TYPE

CEILING AS SCHEDULED

1" SAFB

S E

C T

IO

N

P

LA

N V

IE

W

S E

C T

IO

N

CEILING RUNNER, FASTEN TO STRUCTURE

AT 16": O.C., MINIMUM

FLOOR RUNNER, FASTEN TO STRUCTURE

AT 24": O.C., MINIMUM

FIRE RESISTANCE RATING = N/A

STC RATING = 49

NON-RATED PARTITION

FURRING PARTITION

B.3

FIRE UL STC SAB NOTES

B.2 N/A N/A N/AN/A

B.5 N/A N/A N/AN/A

B.4

N/A

N/A

N/A N/A N/AN/A N/A

N/A N/A N/AN/A N/A

CL

MUNTIN W/ RECESSED

EGRESS DEVICES

BOTTOM RAILS

TOP RAILS

THERMALLY BROKEN

SADDLE ADA

THRESHOLD

EXTERIORINTERIOR

TOP HOUSING

ASSEMBLY

7" 5"

5"

1/ 2"

1/

2"SEALANT

SIDELITE ASSEMBLY W/ PIVOT

2"

SLIDING DOOR

ASSEMBLY W/ PIVOTS

BI PARTING DOOR FRAME

EXTERIOR

INTERIOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377

KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

F R e v it L o c a ls

\2

.8

.0

V

A M

C B a lt im o re

R e n o v a te C o m p o u n d in g v jd e a n h u n te r@ d e lt a -e a s .c o m

.r v t

/1

/2

:2

:2

P

M

AS-601

ARCHITECTURAL - SCHEDULES

05/17/2024 EJL JDH

SCALE: 1 1/2" = 1'-0"AS-601

1 DOOR HEAD DETAIL

SCALE: 1 1/2" = 1'-0"AS-601

2 DOOR JAMB DETAIL

DOOR SCHEDULE

DOOR

NUMBER

TO ROOM: NAME FLOOR LEVEL

DOOR FRAME

FIRE

RATING

GLASS

DETAILS

HARDWARE

GROUP

COMMENTSDOOR

TYPE

OPENING SIZE

THICKNESS DOOR MATERIAL DOOR FINISH

FRAME

TYPE

FRAME MATERIAL FRAME FINISH HEAD JAMB

HEIGHT WIDTH

101 PHARMACY BASEMENT A 7' - 0" 3' - 6" 1 3/4" SCW PNT F-1 HM PNT - 1/AS-601 2/AS-601 HW-1

102 ANTEROOM BASEMENT B 7' - 0" 5' - 11 7/8" ALUM ANOD G-1 ALUM ANOD - 4/AS-601 3/AS-601 HW-4

103 HOOD ROOM A BASEMENT A 7' - 0" 3' - 6" 1 3/4" SCW PNT F-1 HM PNT - 1/AS-601 2/AS-601 HW-2

104 HOOD ROOM B BASEMENT A 7' - 0" 3' - 6" 1 3/4" SCW PNT F-1 HM PNT - 1/AS-601 2/AS-601 HW-2

201 HOOD ROOM C SECOND FLOOR PLAN B 7' - 0" 3' - 6" 1 3/4" SCW PNT ETR ETR PNT 1/AS-601 2/AS-601 HW-3 REPLACEMENT DOOR IN EXISTING FRAME

SCALE: 1" = 1'-0"AS-601

5 PARTITION TYPES

WINDOW TYPE SCHEDULE

WINDOW

TAG TYPE

ROUGH OPENING FRAME DETAIL GLAZING

MANUFACTURER MODEL NO. COMMENTSWIDTH HEIGHT FRAME MATERIAL FRAME FINISH HEAD JAMB SILL THICKNESS TYPE

B PASS THROUGH WINDOW 1' - 0" 1' - 0" STAINLESS STEEL STAINLESS STEEL - - - - - CLEAN AIR

PRODUCTS

CAP18W-ST

D PASS THROUGH WINDOW 1' - 0" 1' - 0" STAINLESS STEEL STAINLESS STEEL - - - - - CLEAN AIR

PRODUCTS

CAP18W-SST

0'

SCALE: 1-1/2" = 1'-0"

2" 4" 1'-4"8"0'

SCALE: 1" = 1'-0"

3" 6" 2'1'

SCALE: 1 1/2" = 1'-0"AS-601

4 SLIDING HEAD DETAIL

SCALE: 1 1/2" = 1'-0"AS-601

3 SLIDING JAMB DETAIL

Revisions: Date:

P

M

MH-001

MECHANICAL - GENERAL NOTES,

SYMBOLS & ABBREVIATIONS

Revisions: Date:

T

SUPPLY AIR DEVICE. ARROWS

INDICATE DIRECTION OF BLOW

RETURN AIR DEVICE. ARROWS

INDICATE DIRECTION OF BLOW

MOTOR OPERATED DAMPER

BRANCH DUCT

TURNING VANES

DUCT TRANSITION

RECTANGULAR TO ROUND DUCT TRANSITION

THERMOSTAT

CONTROL VALVE (CV) - MODULATING

CONTROL VALVE (CV) - TWO-POSITION

CONTROL VALVE (CV) - 3-WAY MODULATING

CONTROL VALVE (CV) - 3-WAY TWO-POSITION

SHUT-OFF VALVE

OUTSIDE AIR DUCT

EXHAUST AIR DEVICE

AREA STATES CFM

AIR DEVICE DESIGNATION

AREA STATES NECK SIZES

STATES TYPE OF SYSTEM.

MECHANICAL EQUIPMENT DESIGNATION

STATES NUMBER OR LETTER CORRESPONDING

TO RELATED SCHEDULE.

LETTER REPRESENTS

MANUFACTURER &

MODEL NO.

RTU-XXX

CONNECT TO EXISTING

REMOVE FROM EXISTING

PLAN NOTE REFERENCE SYMBOL

MECHANICAL SYMBOLS AND ABBREVIATIONS

A/E ARCHITECT / ENGINEER

AP ACCESS PANEL

BDD BACKDRAFT DAMPER

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

CD/COND CONDENSATE

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CO CLEANOUT

CV CONTROL VALVE

DB DRY-BULB TEMPERATURE

DEG DEGREE

DIA, Ø DIAMETER

DN DOWN

DP DIFFERENTIAL PRESSURE

DWG DRAWING

EF EXHAUST FAN

ENT ENTERING

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

F FAHRENHEIT

FD FLOOR DRAIN

GA GAUGE

GAL GALLONS

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HP HORSEPOWER

HPC HIGH PRESSURE RETURN (STEAM CONDENSATE)

HPS HIGH PRESSURE STEAM

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HOT WATER PUMP

HWS HEATING HOT WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

ID INSIDE DIAMETER

KW KILOWATT

KWH KILOWATT-HOUR

LPC LOW PRESSURE RETURN (STEAM CONDENSATE)

LPR LOW PRESSURE STEAM RETURN

LPS LOW PRESSURE STEAM SUPPLY

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH 1000 BTU'S PER HOUR

MCA MINIMUM CIRCUIT AMPACITY

MPS MEDIUM PRESSURE STEAM

MPC MEDIUM PRESSURE CONDENSATE

NA NOT APPLICABLE

NC NORMALLY CLOSED

NO NORMALLY OPEN

NO. NUMBER

NTS NOT TO SCALE

OA OUTSIDE AIR

P PUMP

PD PRESSURE DROP OR DIFFERENCE

PG PRESSURE GAGE

PH PHASE

PSI POUNDS PER SQUARE INCH

RA RETURN AIR

RPM REVOLUTIONS PER MINUTE

RX REMOVE EXISTING

SA SUPPLY AIR

SQFT/SF SQUARE FEET

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TOT TOTAL

TYP TYPICAL

UH UNIT HEATER

V. VOLTS

VAV VARIABLE AIR VOLUME

VI VIBRATION ISOLATOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

05/17/2024Revisions: Date:

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

MECHANICAL GENERAL NOTES

1. ALL WORK SHALL CONFORM TO LATEST INTERNATIONAL MECHANICAL AND PLUMBING CODES; VA

HVAC AND PLUMBING DESIGN MANUAL.

2. ALL WORK SHALL BE COORDINATED WITH ARCHITECTURAL, STRUCTURAL, FIRE PROTECTION, MECHANICAL AND ELECTRICAL DRAWINGS. CONTRACTOR SHALL BE REQUIRED TO FURNISH, INSTALL AND CONNECT WITH APPROPRIATE SERVICES ALL ITEMS SHOWN ON THE DRAWING AT NO

ADDITIONAL COST TO OWNER.

3. THE CONTRACTOR SHALL REVIEW THE WORK AND SHALL COORDINATE WITH THE WORK OF OTHER

TRADES.

4. SLEEVE AND SEAL ALL PIPING PASSING THROUGH WALLS, FLOORS AND ROOF UNLESS NOTED

OTHERWISE.

5. ALL HANGERS AND SUPPORTS SHALL BE SECURED TO STRUCTURE ABOVE.

6. ALL CUTTING, PATCHING AND REPAIR WORK SHALL BE THE RESPONSIBILITY OF THE TRADE

INVOLVED.

7. ALL INSULATION, FITTINGS, COVERS AND FINISHES SHALL HAVE A MAXIMUM FLAME SPREAD RATING OF 25 AND A MAXIMUM SMOKE DEVELOPED RATING OF 50 AND ALL BE IN COMPLIANCE WITH NFPA

90A. REFER TO SPECIFICATIONS.

8. ALL CORE DRILLING, CUTTING AND PATCHING SHALL BE DONE BY THE TRADE. PROVIDE FOR X-RAY

OR GPR OF ALL PENETRATIONS THRU STRUCTURAL SLAB OR WALLS.

9. ALL SLAB PENETRATIONS AND PENETRATIONS THRU RATED WALLS SHALL BE PROVIDED WITH

APPROVED FIRE STOP MATERIAL.

10. ALL EQUIPMENT SHALL BE INSTALLED IN SUCH A WAY TO FACILITATE MAINTENANCE & REPAIR AND

TO ENSURE FACTORY REQUIRED CLEARANCES ARE MET.

11. PROVIDE DETAILED COORDINATED SHOP DRAWINGS (SHEET METAL, PIPING ETC.) TO ENSURE ALL

SYSTEMS ARE COORDINATED AND ALL REQUIRED CEILING HEIGHTS CAN BE ACCOMMODATED.

12. ALL SPECIFICATIONS AND DRAWINGS, I.E. ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL, ARE COMPLIMENTARY AND MUST BE USED IN COMBINATION

TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.

13. ANY INFORMATION CONFLICTS WITHIN THE SPECIFICATIONS AND/OR DRAWINGS SHALL BE

BROUGHT TO THE ARCHITECT'S ATTENTION. THE CONTRACTOR SHALL NOT PROCEED WITH ANY

WORK UNTIL ALL CONFLICTS ARE RESOLVED AND THE CLARIFYING INFORMATION IS ISSUED.

14. THESE DRAWINGS ARE SCHEMATIC AND ARE INTENDED TO CONVEY A FUNCTIONAL SYSTEMS AND

TO DEPICT THE GENERAL LOCATION OF THE SYSTEMS' COMPONENTS.

15. THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF WORK WITH THE WORK OF OTHER TRADES. MINOR DEVIATIONS FROM THE PLANS MAY BE MADE TO AVOID MINOR CONFLICTS. WHEN MAJOR CONFLICTS ARE APPARENT, THE CONTRACT OFFICER SHALL BE ADVISED IMMEDIATELY AND

AFFECTED WORK SHALL NOT BE CONSIDERED UNTIL THE CONFLICT HAS BEEN RESOLVED.

16. THE CONTRACTOR SHALL VERIFY ALL VOLTAGE AND POWER REQUIREMENTS FOR ALL EQUIPMENT

AND COORDINATE WITH THE CONTRACT DRAWINGS PRIOR TO ISSUANCE OF SHOP DRAWINGS AND

PURCHASE OF EQUIPMENT.

17. ALL SYSTEMS SHALL BE CLEAN OF FOREIGN MATERIAL AND ROUGH SPOTS PRIOR TO BEING

PLACED IN SERVICE AND BEFORE OPERATIONAL TESTS ARE PERFORMED.

18. INSTALLATION OF ALL EQUIPMENT AND THEIR ACCESSORIES SHALL BE PER MANUFACTURER'S

PUBLISHED RECOMMENDATIONS.

FIRE DAMPER

DS

BALANCING VALVE

PHASING NOTES

1. CONSTRUCTION WORK SHALL START ON THE 2ND FLOOR. AFTER WORK ON THE

2ND FLOOR IS COMPLETE AND OPERATIONAL, BASEMENT WORK SHALL

COMMENCE TO ENSURE CONTINUOUS COMPOUNDING OPERATION.

DRUG INFO

BA120J

SUPV OFFICE

BA120D

CLERK

BA120F

ADMIN AREA

BA120

WAITING

BA120E

OFFICE

BA120C

CORRIDOR

CB-8

RX. EA GRILLE

RX. EA GRILLE

RX. VAV

RX. 14"Ø SA UP

RX. 10"ø SA

RX. 10"ø SA

RX. 10"ø SA

RX. 10"ø SA

RX. 10"ø SA

RX.10"ø EA

RX. FUME HOOD

RX. FUME HOOD

RX. 10"ø EA

RX. LAMINAR

FLOW DIFFUSER

w/HEPA FILTER

(TYP. OF 5)

EX. EA UP

INTO PLENUM

EX. EA GRILLE

RX. HEPA FAN FILTER

UNIT (TYP. OF 2)

RX. FUME

HOOD

EX. EA

GRILLE

EX. RA UP INTO PLENUM

RX. 22"x14 EA

EX. 10"Ø EA

EX. 10"Ø EA

DUCT RISE

E X x

S

A

EX. 12"x10" SA

E X x

R

A

E X x

E

A

E X x

R

A

EX. RA DIFFUSER

EX. 22"x14" EA

EX. 10"Ø SA

EX. 28"x16" SA

EX. VAV

EX. 28"x16" RA

EX. VAV

EX. 10"Ø SA

EX. 16"x12" SA

EX. 1

" HWS

AND HWR

EX. HWS

AND HWR

EX. 1

" HWS

AND HWR

INPT PHARMACY

BA121

INVESTIGATIVE DRUG SVC

BA121L

R X

S

A

CLEAN ROOM SUITE

BA121L

CHEMO HOOD

BA121K

HOOD ROOM

CLEAN ROOM SUITE

BA121L

CHEMO HOOD

BA121K

HOOD ROOM

EXISTING TO REMAIN

ENTRY

RX. 16"x6"

TRANSFER

AIR GRILLE

(TYP. OF 2)

RX. 12"x4" TRANSFER

GRILLE (TYP. OF 2)

UP

DN

C.7

C.8

D

D.3

E

ELEVATOR

LOBBY

8A100

ELEVATOR

S-8

ELEVATOR

S-9

MECH

EQUIP RM

8D100

STAIR

RX. 1-CF-66

RX. AIRFLOW

CONTROL VALVE

RX. 9"x12" EA

EX. 10"Ø EA

RX. EA

DUCT UP

EX. 1-CF-64

EX. 1-CF-75

EX. 1-CF-131

EX. 1-CF-130

RX. HEPA

FILTER

EX. 10"Ø

DOWN

EX. 12"Ø

DOWN

EX. 12"Ø EA

EX. 1-CF-63

EX. 1-CF-129

EX. MCC-8

EX. PANEL 8D-L1

EX. UH

EX. FD

EX. FD

EX. 50"x24"

EA

EX. 28"x30"

EX. 20"x28"

EX.

18"x22"

EX.

10"x12"

EX. FD

EX. UH

EX. MOD

EX. PANEL 8D-L

EX. T2-8DL

EX.

DISCONNECT

RX. 8"Ø

EA

EX. 8"x8"

EX. HEPA

FILTER

EX. JC1

CONTROL

PANEL

EX. MOD

EX. 12"x12" RA

EX. 10"Ø RA

RX. VAV

RX. 14"x12" SA

RX. 8"Ø

RX. 10"x10" SA

EX.

" HWS AND HWR

HOOD ROOM C

RX.

" HWS

AND HWR

HOOD ROOM C

2C-126

RX. RA DIFFUSER

RX. 10"Ø RA UP TO

INTERSTITIAL SPACE

RX. 8"Ø SA UP TO

INTERSTITIAL SPACE

RX. BASEBOARD HEATERS

RX. 8"Ø SA

UP TO

INTERSTITIAL

SPACE

RX. LINEAR SLOT DIFFUSER

(TYP. OF 2)

EX. RA

DIFFUSER

HOOD ROOM C

2C-126

EX. 10"Ø RA UP TO

INTERSTITIAL SPACE

A

M

MD-101

SCALE: 1/4" = 1'-0"

BASEMENT PART PLAN - DEMOLITION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans

Affairs

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD STAMPSUBCONSULTANTS

321 4 5 6 7 8 9 10

05/17/2024Revisions: Date:

DELTA ENGINEERS, ARCHITECTS & SURVEYORS

8401 CONNECTICUT AVE SUITE 350

CHEVY CHASE, MARYLAND 20815

301.718.0080

MORABITO CONSULTANTS, INC.

STRUCTURAL ENGINEERING

952 RIDGEBROOK ROAD, SUITE 1700

SPARKS, MARYLAND 21152

410.467.2377KOFFEL ASSOCIATES, INC.

8815 CENTRE PARK DR STE 200

COLUMBIA, MD 21045

410.750.2246

VETERAN DESIGN & CONSTRUCTION INC.

5523 RESEARCH PARK DRIVE SUITE 110

BALTIMORE, MARYLAND 21228

443.543.5081

512-23-108RENOVATE C-SEGREGATED

COMPOUNDING AREA FOR

HAZARDOUS COMPOUNDING

VAMC BALTIMORE

KEYPLAN

C D

B A

NORTH

0'

SCALE: 1/4" = 1'-0"

1' 2' 8'4'0'

SCALE: 1/8" = 1'-0"

2' 4' 16'8'

MECHANICAL - FLOOR PLANS -

DEMOLITION

SCALE: 1/8" = 1'-0"

EIGHTH FLOOR PART PLAN - DEMOLITION

2ND FL

AREA OF WORK

BASEMENT

AREA OF WORK

EIGHTH FL.

AREA OF WORK

GENERAL NOTES

A. DUCTWORK SHOWN ON "SECOND FLOOR PART PLAN - DEMOLITION"

IS LOCATED IN INTERSTITIAL SPACE.

PLAN NOTES

CUT AND CAP EX. 22"x14" EA AT PHARMACY WALL AND PREPARE

FOR RECONNECTION.

REMOVE VERTICAL EA DISCHARGE DUCT AS NECESSARY TO

FACILITATE INSTALLATION OF NEW FANS. EX. EXHAUST STACK AT

ROOF TO REMAIN.

EX. 10"Ø EA TO DUCT CHASE NEAR COLUMN LINE D.3 AND BETWEEN

COLUMN LINES 8 AND 9. NOTE 4 ON "EIGHTH FLOOR PART PLAN"

INDICATES THIS LOCATION.

REFER TO PLAN NOTE 3.

CUT AND CAP 12"x12" RA.

REFER TO "SECOND FLOOR INTERSTITIAL PART PLAN" ON THIS

SHEET FOR CONTINUATION.

REFER TO "SECOND FLOOR PART PLAN" ON THIS SHEET FOR

CONTINUATION.

MB

SCALE: 1/4" = 1'-0"

SECOND FLOOR INTERSTITIAL PART PLAN - DEMOLITION

SCALE: 1/4" = 1'-0"

SECOND FLOOR PART PLAN - DEMOLITION

10"ø SA

VAVS-1

12"ø SA

EX. 10"Ø EA RISE

10"ø EA

DRUG INFO

BA120J

SUPV OFFICE

BA120D

CLERK

BA120F

ADMIN AREA

BA120

WAITING

BA120E

OFFICE

BA120C

CORRIDOR

CB-8

EX. EA

GRILLE

(UNDER)

EX. EA

GRILLE

(UNDER)

12"ø

A

8"ø

A

12"ø

A

12"ø

A

EX. 10"Ø EA

(TYP OF 2)

OFFICE

BA120A

SUPV OFFICE

BA120B

E X x

S

A

EX. 12"x10" SA

E X x

R

A

E X x

E

A

E X x

R

A

EX. RA DIFFUSER

EX. 22"x14" EA

EX. 10"Ø SA

EX. 28"x16" SA

EX. VAV

EX. 28"x16" RA

EX. VAV

EX. 10"Ø SA

E X x

S

A

12"ø SA

12"ø

A

EX. 1

" HWS

AND HWR

EX. HWS

AND HWR

EX. 1

" HWS

AND HWR

12"x14" SA

VAVS-4

12"ø EA

12"ø SA 16"x10" SA

VAVS-3

16"ø SA

8"ø SA

12"ø SA

8"ø SA

10"ø SA8"ø SA

10"x10" EA

(TYP. OF 2)

10"x10" EA

12"x12" EA

VAVS-2

22"x14" EA

T H

T H

T H T H

" HWS

AND HWR

(TYP. OF 3)

PHARMACY

BA121K

ANTEROOM

BA121L

HOOD ROOM A

BA121O

HOOD ROOM B

BA121P

14"x18"

750B

6"x8"

125B

8"x6" EA

8"ø EA

" FLEXIBLE

TUBING (TYP.)

EXISTING TO REMAIN

ENTRY

EX. 12"x12" RA

EX. 10"Ø RA

VAVS-5

14"x10" SA

12"Ø EA

REFER TO SHEET

MH102 FOR

CONTINUATION

EX.

" HWS AND HWR

10"Ø SA

10"Ø SA

HOOD ROOM C

2C126

EF-5

12"x6" EA

13 13

ENTRY

UP

DN

C.7

C.8

D

D.3

E

ELEVATOR

LOBBY

8A100

ELEVATOR

S-8

ELEVATOR

S-9

MECH

EQUIP RM

8D100

STAIR

EF-3

EF-4

FLTR-2

12"Ø EA

NEW HEAVY

DUTY DAMPER

(TYP. OF 2)

EA UP

THRU

ROOF

VAVE-2

EX. 10"Ø EA

EX.

1-CF-64

EX. 1-CF-75

EX. 1-CF-131

EX. 1-CF-130

EX. 10"Ø

DOWN

EX. 12"Ø

DOWN

EX. 12"Ø

EA

EX. 1-CF-63

EX. 1-CF-129

EX. MCC-8

EX. PANEL 8D-L1

EX. UH

EX. FD

EX. FD

EX. 50"x24"

EA

EX. 28"x30"

EX. 20"x28"

EX.

18"x22"

EX. 10"x12"

EX. FD

EX. MOD

EX. PANEL 8D-L

EX. T2-8DL

EX.

DISCONNECT

EX.