02. FTQW231401, Rpr Lift Stn B2212, Drawing Set.pdf
PDF 8 MB Posted
- Attached to
- FTQW 23-1401 - Repair Lift Station B2212
- Solicitation number
- FA500425B0003
About this file
The file is a comprehensive architectural and engineering drawing set for the repair of Lift Station B2212 at Eielson Air Force Base in Alaska. The project involves replacing an existing lift station with a new bypass lift station, including mechanical, electrical, structural, and civil infrastructure modifications. Key components include a new wet well, pumps, control systems, electrical panels, heat trace systems, and associated site improvements. The drawings detail the station's layout, excavation requirements, piping configurations, hazardous area classifications, and utility connections.
The project is designed for the 354th Civil Engineer Squadron, with Design Alaska as the engineering firm. The drawing set covers multiple disciplines including site plans, demolition, force main routing, area classifications, and detailed mechanical and electrical specifications. Notable technical considerations include provisions for handling contaminated soils, classified electrical areas, heat tracing for sewer lines, and integration with existing infrastructure. The drawings are dated May 20, 2025, and include detailed technical specifications for construction, materials, and system operations, with a focus on creating a robust and functional backup lift station system.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 View Name 1/8" = 1'-0"A101
Room name
GENERAL SYMBOLS
NAME
NUMBER
SHEET LOCATION
SCALE
TRUE NORTH
GRID LINE
ROOM NAME
ROOM NUMBER
PLAN NORTH
REVISION
SEE DISCIPLINES FOR SPECIFIC SYMBOLS
PROJECT TEAM
OWNERS REPRESENTATIVE
354TH CIVIL ENGINEER SQUADRON
2310 CENTRAL AVE,
EIELSON AFB, AK 99702
907 377-0108
DESIGNERS REPRESENTATIVE
DESIGN ALASKA
601 COLLEGE ROAD
FAIRBANKS, AK 99701
907 452-1241
VICINITY MAP
PROJECT
LOCATION
F L
IG
H T
L
IN
E A
V E
NORTH ST
KODIAK ST
W A
B A
S H
A V
E
ALASKA MAP
PACIFIC OCEAN
ARCTIC OCEAN
BERING
SEA
KODIAK
ARCTIC CIRCLE
SEWARD
SITKA
JUNEAU
HAINES
WHITEHORSE YT
DAWSON YT
HAINES
JCT
HOMER
ANCHORAGE
EAGLE
CORDOVA
VALDEZ
GLENNALLEN
TOK
NORTH
POLE
NENANA
TANANA
CIRCLE
NOME
KOTZEBUE
UTQIAGVIK
(BARROW)
PRUDHOE BAY
U N
IT
E
D S
T A
T E
S
R U
S S
IA
U N
IT
E
D S
T A
T E
S C
A N
A D
A
PROJECT
LOCATION
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
20 MAY 2025
REPAIR LIFT
STATION B2212
022301
AECC511
5/19/2025 7:39:46 PM
GENERAL
INFORMATION
G010
EIELSON AIR FORCE BASE, ALASKA
354TH CIVIL ENGINEER SQUADRON
GENERAL
G010 GENERAL INFORMATION
MECHANICAL
M001 MECHANICAL ABBREVIATIONS, LEGENDS, AND
SCHEDULES
M100 MECHANICAL DEMOLITION PLAN
M200 MECHANICAL SITE PLAN
M300 MECHANICAL DETAILS
REPAIR LIFT STATION B2212
PROJECT NO. FTQW 231401
STRUCTURAL
S001 GENERAL STRUCTURAL NOTES
S100 OVERALL PLAN
S101 OVERALL SECTIONS
S200 STRUCTURAL DETAILS
S201 STRUCTURAL DETAILS
ELECTRICAL
E001 LEGEND AND SCHEDULES
E002 AREA CLASSIFICATION PLANS
E003 MISCELLANEOUS DETAILS
E050 ELECTRICAL SITE PLAN
E100 BUILDING PLANS
E600 PANEL SCHEDULES AND RISER DIAGRAM
CIVIL
C100
C200
C500
C600
C601
C700
HAZARDOUS MATERIALS
H100
H101
LOCATION MAPS, NOTES, LEGEND, ACRONYM KEY
ASBESTOS, LEAD, & PCB SAMPLE LOCATIONS &
RESULTS
EXISTING CONDITIONS AND DEMOLITION PLAN
SITE IMPROVEMENTS PLAN
FORCE MAIN PLAN AND PROFILE
EXCAVATION SECTION
EXCAVATION SECTIONS
DETAILS
022301
20 MAY 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR LIFT
STATION B2212
REG IS T ER ED P R O F E S S I O NA L ENGINEER
Peter Beardsley
CE 10934
05/20/2025
H100
LOCATION MAPS,
NOTES, LEGEND,
ACRONYM KEY
PLB
SPH
LEAD SAMPLE LOCATIONS
(<1mg/cm2)(HUD)
LEAD SAMPLE LOCATIONS
(>1mg/cm2)(HUD)
SEE LEAD SAMPLE TABULATION
RESULTS FOR CONCENTRATION FOR
LEAD SAMPLE NUMBER
ASBESTOS SAMPLE LOCATIONS
NEGATIVE (<1% ASBESTOS)
ASBESTOS SAMPLE LOCATIONS
POSITIVE (>1% ASBESTOS)
SEE ASBESTOS TABULATED RESULTS
FOR ACM SAMPLE NUMBER
LEGEND
ACRONYM KEY
ACM - ASBESTOS CONTAINING MATERIAL
CMU - CONCRETE MASONRY UNIT
HUD - U.S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT
LBP - LEAD BASED PAINT
ND - NOT DETECTED
PCB - POLYCHLORINATED BIPHENYL
XRF - X-RAY FLUORESCENCE
mg - MILLIGRAM kg - KILOGRAM cm2 - SQUARE CENTIMETER
01234
01234
PCB BULK SAMPLE LOCATIONS
- NEGATIVE (NO PCBs DETECTED)
PCB BULK SAMPLE LOCATIONS
- POSITIVE (PCBs DETECTED)
SEE TABULATED RESULTS FOR
SAMPLE NUMBER & RESULTS
PROJECT
LOCATION
HAZARDOUS MATERIAL NOTES
NORTH NORTH
10 1/2
MILE
1/40 1/8
MILE
5/15/2025 10:49 AM H100 100%.DWG
SUSTAINABLE ENVIRONMENT
Juneau: 5438 Shaune Drive Anchorage: 3105 Lakeshore Drive
ENERGY, HEALTH & SAFETY
Fairbanks: 2400 College Road 907.452.5688
Corporate No.: AECC682
1. THESE HAZARDOUS MATERIAL NOTES APPLY TO ALL HAZARDOUS MATERIAL SHEETS.
2. A HAZARDOUS MATERIALS ASSESSMENT FOR PROPOSED CONSTRUCTION HAS BEEN COMPLETED AS PART OF THIS DESIGN. ALL SAMPLE LOCATIONS AND RESULTS COLLECTED AND UTILIZED AS PART OF THIS ASSESSMENT ARE IDENTIFIED ON THE PROJECT DRAWINGS. A COPY OF THE HAZARDOUS MATERIALS REPORT IS ATTACHED TO THE 02 26 00 SPECIFICATION. THESE DRAWINGS AND THE SPECIFICATION REPRESENT THE ENTIRETY OF THE HAZARDOUS
MATERIALS ASSESSMENT FOR THIS PROJECT.
3. THE DEMOLITION SCOPE OF WORK FOR EACH DISCIPLINE IS SHOWN IN THE DEMOLITION DRAWINGS FOR EACH DISCIPLINE. ABATEMENT OF HAZARDOUS MATERIALS IS ONLY NECESSARY TO THE EXTENT REQUIRED TO COMPLETE THE SCOPE OF WORK SPECIFIED BY OTHER DISCIPLINES.
4. PROTECT EXISTING BUILDING COMPONENTS TO REMAIN, INCLUDING STRUCTURAL ELEMENTS AND FINISHES, DURING THE COURSE OF ALL HAZARDOUS MATERIALS WORK. ALL WORK DAMAGED OR OTHERWISE MADE DEFECTIVE IN APPEARANCE SHALL BE RESTORED TO ORIGINAL CONDITION AND FUNCTION.
5. ASSUME ASBESTOS CONTAINING CONCRETE SEALANT IS PRESENT ON THE EXTERIOR OF THE UTILIDOR.
6. LEAD-BASED PAINT (PAINT CONTAINING EQUAL TO OR GREATER THAN 1.0 mg/cm²) WAS IDENTIFIED. PAINT CONTAINING LESS THAN 1 mg/cm² WAS ALSO OBSERVED. CONTROL WORKER EXPOSURES USING LEAD-SAFE WORK PRACTICES AND CHOICE OF MEANS AND METHODS TO ENSURE COMPLIANCE WITH APPLICABLE REGULATIONS AND TO AVOID CONTAMINATION OF THE WORK AREA AND SITE. ALL DEMOLITION, ABATEMENT, AND DISPOSAL OF LEAD CONTAINING MATERIAL SHALL BE COMPLETED IN ACCORDANCE WITH APPLICABLE REGULATIONS AND THE TECHNICAL SPECIFICATIONS.
7. PCBS WERE IDENTIFIED IN PAINT. ENSURE COMPLIANCE WITH APPLICABLE REGULATIONS AND CONTROL WORKER EXPOSURES. ALL DEMOLITION, ABATEMENT, AND DISPOSAL OF PCB CONTAINING PAINT SHALL BE COMPLETED IN ACCORDANCE WITH APPLICABLE REGULATIONS AND THE PROJECT
DOCUMENTS. ASSUME ALL PAINTED SURFACES ARE PAINTED WITH PCB CONTAINING PAINT.
8. ASSUME ALL CONCRETE REMOVED AS PART OF THIS PROJECT CONTAINS PCBS. CONTRACTOR MAY PROVIDE TESTING RESULTS TO CONFIRM MATERIAL DOES NOT CONTAIN PCBS. TESTING METHODOLOGY MUST BE INCLUDED IN THE CONTRACTOR’S APPROVED WORK PLAN UNDER 02 26 00.
9. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PERFORM HIS OWN ASSESSMENT PRIOR TO DEMOLITION TO VERIFY AND QUANTIFY THE PRESENCE OF HAZARDOUS MATERIALS AND POTENTIAL WORKER EXPOSURE HAZARDS WITHIN THE ANTICIPATED WORK AREAS. ADDITIONAL HAZARDOUS MATERIALS NOT IDENTIFIED IN THESE DRAWINGS MAY BE ENCOUNTERED IN HIDDEN SPACES. THE CONTRACTOR MUST IMMEDIATELY NOTIFY THE OWNER'S
REPRESENTATIVE OF CONFIRMATION OF PREVIOUSLY UNIDENTIFIED HIDDEN HAZARDS.
10. TEST RESULTS OF ANY MATERIALS AND WASTE STREAMS WILL BE TRANSMITTED BY THE CONTRACTOR TO THE OWNER'S REPRESENTATIVE WITHIN 24 HOURS OF RECEIPT. ALL MATERIALS REQUIRING A CHAIN OF CUSTODY SHALL REMAIN IN THE CONTROL OF THE CONTRACTOR UNTIL FINAL DISPOSITION.
11. REMOVE AND PROPERLY DISPOSE OF HAZARDOUS MATERIALS RESULTING FROM DEMOLITION OPERATIONS WITHIN EACH PROJECT AREA. ALL HAZARDOUS MATERIALS SHALL BE MANIFESTED AND DISPOSED OF IN A LEGAL MANNER, COMPLYING WITH ALL APPLICABLE LOCAL, STATE, AND FEDERAL LAWS AND REGULATIONS. CONTRACTOR SHALL PROVIDE DISPOSAL RECEIPTS TO THE OWNER'S REPRESENTATIVE INDICATING THE FINAL DISPOSITION OF ALL HAZARDOUS MATERIALS TRANSPORTED OFF-SITE TO A PERMITTED FACILITY FOR DISPOSAL OR REMEDIATION. THE OWNER OR OWNER'S REPRESENTATIVE WILL NOT BE SIGNATORY TO A MANIFEST, CERTIFICATE OF FINAL DISPOSAL, TRANSFER, OR CHAIN OF CUSTODY FOR ANY HAZARDOUS MATERIALS
SCHEDULED FOR DEMOLITION OR REMOVAL.
PROJECT
LOCATION
PROJECT
LOCATION
WET WELL
BAR-SCREEN
ROOM
B02
PUMP ROOM
P01
LANDING
B01
O
TP
C
XF
ER
S
W N
Q P
AN
EL
PUMP PANEL 1
GENSET
A8
L18
L19
L16
L15
L17
L14
L13
A6
L12
A7 L9
L8
L10
L11
L6
L2
L1
L3
A1
L5
L7
A2
A3
A5
A4
L4
P02
PUMP ROOM
P01
GROUND LEVEL
GENERATOR
ROOM
UTILIDOR
UTILIDOR
ACCESS
LEGEND
ASBESTOS BULK SAMPLE LOCATIONS
NEGATIVE (<1% ASBESTOS)
ASBESTOS BULK SAMPLE LOCATIONS
POSITIVE (>1% ASBESTOS)
ABC
ABC
SEE ASBESTOS
TABULATION RESULT
LEAD BASED PAINT SAMPLE
(<1mg/cm2)(HUD)
LEAD BASED PAINT SAMPLE
(>1mg/cm2)(HUD)
SEE LEAD BASED PAINT
TABULATION RESULTS FOR
CONCENTRATION
PCB BULK PAINT SAMPLE
- NEGATIVE (NO PCBs DETECTED)
PCB BULK PAINT SAMPLE
- POSITIVE (PCBs DETECTED)
SEE PCB BASED PAINT
TABULATION RESULTS FOR
CONCENTRATION
Lead Paint Sample Results (XRF) Number Color Surface Substrate Result (mg/cm²)
L1 white/green/tan wall concrete 1.8 L2 white wall concrete 0.00 L3 brown door metal 0.00 L4 white/green/tan wall concrete 0.18 L5 green generator metal 0.01 L6 gray floor concrete 0.6 L7 white/green/tan wall concrete 1.4 L8 gray floor concrete 0.06 L9 white wall concrete 0.00
L10 brown door trim metal 0.00 L11 white/green/tan wall concrete 0.7 L12 white/green/tan wall concrete 1.3 L13 white stair railing metal 0.11 L14 white wall CMU 0.00 L15 red crane rail metal 0.00 L16 white wall concrete 0.00 L17 red pipe elbow metal 0.00 L18 black pipe rack metal 0.01 L19 red pipe metal 0.00
Asbestos Bulk Sample Results (Method EPA 600/R-93/116) Sample ID Description Result
A1 tan/yellow pipe wrap ND A2 gray duct sealant ND A4 white exhaust insulation ND A5 white exhaust tank insulation ND A6 white/silver/yellow duct insulation cover ND A7 gray/white pipe sealant ND A8 tan/white pipe insulation ND
5/15/2025 10:48 AM H101 100%.DWG
022301
20 MAY 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR LIFT
STATION B2212
REG IS T ER ED P R O F E S S IO NA L ENG INEER
Peter Beardsley
CE 10934
05/20/2025
NOTE: NO SAMPLES COLLECTED FROM THIS AREA
H101
ASBESTOS, LEAD,
& PCB SAMPLE
LOCATIONS &
RESULTS
PLB
SPH
GROUND FLOOR
SCALE: 1" = 5'H101
0 5' 10'1
BASEMENT 2
SCALE: 1" = 5'H101
BASEMENT 1
SCALE: 1" = 5'H101
2 0 5' 10'
0 5' 10'
SUSTAINABLE ENVIRONMENT
Juneau: 5438 Shaune Drive Anchorage: 3105 Lakeshore Drive
ENERGY, HEALTH & SAFETY
Fairbanks: 2400 College Road 907.452.5688
Corporate No.: AECC682
PCB Bulk Paint by 3540/8082A (mg/kg) Sample ID 1 2
Color white/green/gray/yellow concrete wall white/green/tan concrete wall Aroclor-1016 ND ND Aroclor-1221 ND ND Aroclor-1232 ND ND Aroclor-1242 ND ND Aroclor-1248 ND ND Aroclor-1254 18 6.8 Aroclor-1260 2.3 0.96 Aroclor-1262 ND ND Aroclor-1268 ND ND
Total 20.3 7.76
BUILDING 2212
RCC-1
ELEV:
542.27'
18" CMP
E. INV.:536.35'
W. INV.: 536.19'
7" ASPEN
8" PINE
F.F. ELEV:
542.40'
6" CMP
INV: 536.21'
18" CMP
INV: 535.67'
STORM DRAIN
MAN HOLE
RIM: 537.39'
INV: 534.28'
GRAVEL DRIVEWAY
GRASS
GRASS
CONCRETE
WALKWAY
NORTH STREET
W
AB
AS
H
A
VE
N U
E
CONCRETE
SIDEWALK
COMMUNICATIONS
VAULT
UTILIDOR
MANHOLES
UTILIDOR
MANHOLES
ASP
HAL
T
GRASS
PFAS CONTAMINATED
SATURATED SOIL
DRAINING AND
INFILTRATION AREA
SEE SOIL CONTAMINANT
NOTES 2,3 AND 4 AND
DEWATERING NOTES 3,4
AND 5
UTILIDOR
APPROX PROJECT
LIMITS
UTILIDOR VAULT
RIM:540.47'
FLOOR527.67
SEWER VAULT
GRO AND DRO
CONTAMINATED SOIL
STOCKPILE AREA SEE SOIL
CONTAMINANT NOTE 1
CLEAN FILL
STOCKPILE AREA
A/G OIL TANK ON
CONCRETE PAD
PROTECT UTILIDOR LIDS BY BRIDGING OR
OTHER SUPPORT DURING CONSTRUCTION.
DO NOT DRIVE EQUIPMENT ON UTILIDOR
LIDS WITHOUT APPROPRIATE BRIDGING IN
PLACE
REMOVE 2650 SF
OF TOPSOIL
BRASS CAP MONUMENT
FIRE HYDRANT
COMMUNICATIONS MANHOLE
UNDERGROUND COMMUNICATIONS LINE
ELECTRIC JUNCTION BOX
UTILITY POLE
GUY ANCHOR
OVERHEAD ELECTRIC
SEWER MAN HOLE
SEWER LINE
STORM DRAIN MANHOLE
STORM DRAIN LINE
CULVERT
8" UTILIDOR VENT
ASPHALT ROAD
GRAVEL ROAD
LEGEND
SURVEY CONTROL POINT TABLE
POINT #
NORTHING
3904446.91
3904239.12
EASTING
1469610.68
1468993.97
ELEVATION
542.88
542.27
DESCRIPTION
BRASS CAP MONUMENT RCC-2
BRASS CAP MONUMENT RCC-1
6/9/2025 5:01 PM 022301 C100 - EXISTING CONDITIONS.DWG
022301
20 MAY 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR LIFT
STATION B2212
REGISTERED PROFESSIONA L ENGINEER
Charles Cutter Degerlund
No. CE124811 10-Jun-2025
C100
IAL
CCD
EXISTING
CONDITIONS AND
DEMOLITION PLAN
EXISTING CONDITIONS AND DEMOLITION PLAN1
C100 1" = 20'
SURVEY NOTES
1. A SURVEY WAS PERFORMED ON OCTOBER 18TH, 2023 TO SUPPORT THE DESIGN OF A
BYPASS LIFT STATION TO SUPPLEMENT CAPACITY OF THE EXISTING LIFT STATION.
2. UNDERGROUND UTILITY LOCATES WERE NOT PERFORMED FOR THIS SURVEY.
UNDERGROUND UTILITIES SHOWN WERE DETERMINED BY EXISTING SPRAY PAINT
LOCATES FOUND AT TIME OF SURVEY. BELOW GROUND UTILIDOR EXTENT IS
APPROXIMATED BASED OFF SURFACE FEATURES AND AREA MAPS.
3. IT IS UNKNOWN IF EXISTING LEASE LOT BOUNDARIES OR EASEMENTS EXIST IN AND
AROUND THIS SITE.
4. COORDINATES ARE ALASKA STATE PLANE ZONE 3, NAD83, US FEET ELEVATIONS ARE
NAVD88 VERTICAL DATUM, FEET.
SOIL CONTAMINANT NOTES
1.
2. REMOVE SURFICIAL SOILS FROM SATURATED SOIL DRAINING AREA TO A DEPTH OF
NO GREATER THAN 1 FOOT ABOVE THE SEASON HIGH GROUNDWATER LEVEL. PLACE
UNCONTAMINATED, DRY EXCAVATED MATERIAL IN THE "CLEAN" STOCKPILE AREA.
3. SLOPE BOTTOM OF "DRAINING AND INFILTRATION AREA" TO DRAIN AND
COLLECT/INFILTRATE ON THE WEST END OF THE PIT. SOIL EXCAVATED FROM BELOW
THE WATER TABLE SHALL BE PLACED WITHIN THE "DRAINING AND INFILTRATION
AREA" AND ALLOWED TO DRY.
4. FOLLOWING THE COMPLETION OF THE LIFT STATION AND UTILIDOR BUMP OUT,
SPREAD DRY SOIL TO A SMOOTH SURFACE GENERALLY MATCHING PRE
CONSTRUCTION SLOPE AND INFILTRATION. CAP WITH 8" OF COMPACTED CLEAN FILL
AND 4" OF TOPSOIL AND SEED FOR A MINIMUM 12" COVER DEPTH.
DEWATERING NOTES
1. CONTRACTOR SHALL MAINTAIN A DRY, STABLE BASE WITHIN THE SECANT PILE CELLS.
2. WATER, REGARDLESS OF SOURCE, SHALL BE COLLECTED AND PUMPED TO AN
INFILTRATION AREA.
3. AT NO TIME SHALL THE DISCHARGE HOSE, PUMPED WATER, OR ANY PART OF THE
DEWATERING SYSTEM BE AT THE ELEVATION HIGHER THAN THE ORIGINAL GROUND
SURFACE.
4. IF THE DEWATERING FLOWS EXCEED THE ABILITY OF THE DRAINING AREA TO ACCEPT
DISCHARGES, THE CONTRACTOR SHALL IDENTIFY AREAS IN THE SECANT PILE WHERE
WATER IS INFILTRATING THE CELL AND STOP WATER FLOW.
5. ANY DISCHARGES OF WATER ABOVE THE ORIGINAL GROUND SURFACE ARE NOT
ADVISED AND WILL BE THE RESPONSIBILITY OF THE CONTRACTOR.
NOTE: POINT #100 IS LOCATED 500' NORTHWEST OF THE INTERSECTION OF
NORTH ST AND WABASH AVE. ON THE SOUTHSIDE OF NORTH ST.
(E) BUILDING 2212
F.F. ELEV:
542.40'
(E) GRASS
GRASS
NORTH STREET
(E) GRASS
(E) 8" PINE (E) GRAVEL DRIVEWAY
(E) 7" ASPEN
(E) UTILIDOR
C700
(E) UTILIDOR MANHOLE
RIM: 540.47
FLOOR:527.67
(E) SEWER VAULT
UTILIDOR BUMPOUT,
PER STRUCTURAL
SECANT WALL,
PER STRUCTURAL
UNDERGROUND
ELECTRIC LINE, TYP
H-FRAME, PER ELECTRICAL
C600
-4.0:1
-4 .0
:1
-4.0:1 -4 .0
:1
-4 .0
:1
-4.0:1
-4.0:1
-4 .0
:1
CONNECTION WITH
EXISTING GRADE
FORCE MAIN
C500
C700
FINISH GRADE
ADJACENT TO HATCH: 540
GRAVITY MAIN
C700
LIFT STATION,
PER MECHANICAL
RIM:541.3
BOLLARDS,
TYP 4
C700
BOLLARDS,
TYP 4
C700
BRASS CAP MONUMENT
FIRE HYDRANT
COMMUNICATIONS MANHOLE
UNDERGROUND COMMUNICATIONS LINE
ELECTRIC JUNCTION BOX
UTILITY POLE
GUY ANCHOR
OVERHEAD ELECTRIC
SEWER MAN HOLE
SEWER LINE
STORM DRAIN MANHOLE
STORM DRAIN LINE
CULVERT
8" UTILIDOR VENT
ASPHALT
LEGEND
5/22/2025 5:57 PM 022301 C200 - SITE IMPROVEMENTS.DWG
022301
20 MAY 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR LIFT
STATION B2212
REGISTERED PROFESSIONA L ENGINEER
Charles Cutter Degerlund
No. CE124811 23-May-2025
C200
IAL
CCD
SITE
IMPROVEMENTS
PLAN
SITE IMPROVEMENTS PLAN1
C200 1" = 10'
GENERAL NOTES
1. ALL DISTURBED AREAS TO RECEIVE 4" TOPSOIL AND SEED UNLESS OTHERWISE
INDICATED.
(E) BUILDING 2212
F.F. ELEV:
542.40'
BP: 1+00.00 P
I:
1+
.8
PI: 2+05.57
EP: 2+17.88
1+00 1+50
2+
2+18
'-0
" M
IN
10'-0"MIN
LIFT STATION
H-FRAME PER ELECTRICAL
PROTECT CONCRETE FUEL TANK PAD
DOUBLE CLEANOUT,
PER MECHANICAL
DOUBLE CLEANOUT,
PER MECHANICAL
UTILIDOR BUMPOUT
M300
M300
BOLLARDS, TYP 4
C700
BOLLARDS, TYP 4
C700
5'-0"
MAX
5'-0"
MAX
FORCE MAIN PROFILE
0+90 1+00 1+50 2+00 2+20
LIFT STATION
FORCE MAIN PER
MECHANICAL
CONNECTION WITH EXISTING GRAVITY SEWER LINE
4'-0" MINIMUM
SEE NOTE 1
EXISTING GRADEFINISH GRADE
DOUBLE CLEAN OUT
PER MECHANICAL
DOUBLE CLEAN OUT
PER MECHANICAL
5/23/2025 11:23 AM 022301 C500 - FORCE MAIN PLAN AND PROFILE.DWG
022301
20 MAY 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR LIFT
STATION B2212
REGISTERED PROFESSIONA L ENGINEER
Charles Cutter Degerlund
No. CE124811 23-May-2025
C500
IAL
CCD
FORCE MAIN PLAN
AND PROFILE
FORCE MAIN PLAN AND PROFILE1
C500 1" = 10'
GENERAL NOTES
1. GEOTECHNICAL FIELD INVESTIGATIONS COLLECTED FEB 2024 OBSERVED THE
GROUND WATER TABLE AT 436', APPROXIMATELY 5' BELOW GROUND SURFACE
WITHIN THE PROPOSED SITE IMPROVEMENTS.
0+00 0+50 1+00
(E) UTILIDOR
UTILIDOR
ADDITION,
PER
STRUCTURAL
LIFT STATION
TREMIE
SLAB, PER
STRUCTURAL
ELEV: 527. 67
8" MIN ABOVE SECANT WALL
FINISH GRADE
EXISTING GRADE
SECANT PILE WALL
PER STRUCTURAL
SEE NOTE 1
1.00 % MIN, GRAVITY MAIN PER MECHANICAL
TREMIE
SLAB, PER
STRUCTURAL
SECANT PILE WALL
PER STRUCTURAL
CONNECT TO EXISTING
SEWER MAIN INVERT
ELEVATION WITHIN
UTILIDOR
5/22/2025 5:57 PM 022301 C600 - EXCAVATION SECTION - LIFT STATION.DWG
022301
20 MAY 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR LIFT
STATION B2212
REGISTERED PROFESSIONA L ENGINEER
Charles Cutter Degerlund
No. CE124811 23-May-2025
C600
IAL
CCD
EXCAVATION
SECTION
NORTH SOUTH SECTION THROUGH LIFT STATION AND UTILIDOR BUMP OUT1
C600 1" = 5'
GENERAL NOTES
1. GEOTECHNICAL FIELD INVESTIGATIONS COLLECTED FEB 2024 OBSERVED THE
GROUND WATER TABLE AT 436', APPROXIMATELY 5' BELOW GROUND SURFACE
WITHIN THE PROPOSED SITE IMPROVEMENTS.
1 4
18"
12"
OSHA SAFE
LAYBACK, TYP.
SHOWN 1.5H:1V
FOR PLANNING
GRASSED AREA, TYPDRIVING SURFACE , TYP
APPROXIMATELY
4-6"
REPLACE SURFACE
TO MATCH GRAVEL
DRIVE
4" TOPSOIL AND SEED TO MATCH EXISTING
2" INSULATION AND WATERPROOFING, SEE
NOTES 1 & 2
COMMON FILL
COMPACT TOP 12"
TO 90%
STRUCTURAL FILL.
95% COMPACTION,
MAX 8" LIFTS
(E) INSULATION
C700
4"
2% FOR 5'-0" 2% FOR 5'-0"
CUT TOP OF
INSULATION AT
ACCESS HATCH
TO 45 DEG
ANGLE, TYP
2" INSULATION AND
WATERPROOFING,
SEE NOTES 1 & 2
COMMON FILL.
COMPACT TOP 12"
TO 90%
CONCRETE
UTILIDOR AND
ACCESS HATCH
PER STRUCTURAL
4/29/2025 3:05 PM 022301 C601 - EXCAVATION SECTION - MATERIAL STORAGE.DWG
022301
20 MAY 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR LIFT
STATION B2212
REGISTERED PROFESSIONA L ENGINEER
Charles Cutter Degerlund
No. CE124811 23-May-2025
C601
IAL
CCD
EXCAVATION
SECTIONS
UTILIDOR SECTIONS1
C601 NO SCALE
INSULATION/WATERPROOFING NOTES
1. APPLY 2" THICK POLYSTYRENE INSULATION TO UTILIDORS, ACCESS VAULTS AND MANHOLES, PREEXISTING INSULATION MAY
BE PRESENT. DO NOT INSULATE INTERIOR CONCRETE SURFACES.
2. UTILIDORS, ACCESS VAULTS AND MANHOLES SHALL BE WATERTIGHT CONSTRUCTION. EXTERIOR SURFACES SHALL BE
COATED WITH WATERPROOFING BITUMINOUS SHEET MEMBRANE. BASIS OF DESIGN IS GRACE BITUTHENE 3000.
3. SEE STRUCTURAL FOR JOINT SEALANT FOR WALL-TO-LID JOINTS.
UTILIDOR EXCAVATION SECTION UTILIDOR ACCESS HATCH EXCAVATION SECTION
6'-0"
APPROXIMATE GROUNDWATER DEPTH
MIN TRENCH WIDTH:
INSULATED PIPE O.D. + 12"
MAX TRENCH WIDTH: UP TO 30"
O.D. + 6" INSULATION + 16"
GRAVITY MAIN PER MECHANICAL
6" MIN BEDDING
1'-0" MIN COVER
SURFACE FINISH COURSE
5/22/2025 5:46 PM 022301 C700 - DETAILS.DWG
022301
20 MAY 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR LIFT
STATION B2212
REGISTERED PROFESSIONA L ENGINEER
Charles Cutter Degerlund
No. CE124811 23-May-2025
C700
IAL
CCD
DETAILS
SURFACE FINISH TO
MATCH ADJACENT FINISH
STRUCTURAL
FILL
UTILITY BEDDING MATERIAL
MARKING
TAPE
M
IN
4"
6" 6"
AS
REQUIRED
18" MAX
UNDERGROUND ELECTRICAL TRENCH1
C700 NOT TO SCALE
6" MIN BEDDING
MIN TRENCH WIDTH:
INSULATED PIPE O.D. + 12"
MAX TRENCH WIDTH: UP TO
30" O.D. + 6" INSULATION +
16"
FORCE MAIN TRENCH DETAIL2
C700 NO SCALE
PIPE O.D. + INSULATION
24"
12" MIN COVER
4' - 0" MIN COVER TO
TOP OF INSULATION
SURFACE FINISH COURSE
3" DETECTABLE UTILITY
WARNING TAPE
SLOPE PER CURRENT
OSHA STANDARDS
REPLACE OVER DEPTH
OR UNSTABLE SOIL
TRACER WIRE
PIPE WITH
INSULATION,
PER
MECHANICAL
NOTES
1. INSTALLATION PROCEDURES SHALL BE AS SPECIFIED BY
THE DIRECT BURY PIPE MANUFACTURER.
2. FOR NON-PAVING AREAS, BACKFILL MATERIAL ABOVE
THE PIPE BEDDING.
3. SHEETING AND SHORING SHALL BE AS REQUIRED PER
OSHA STANDARDS.
4. USE 3" DETECTABLE MARKING TAPE, BURIED 24" ABOVE
UPPER SURFACE OF PIPE INSULATION. GREEN =
SANITARY SEWER, BLUE = WATER DISTRIBUTION.
5. KEEP TRENCH FREE OF WATER DURING BACKFILL
GRADE
GRAVEL ACCESS ROAD OPEN AREAS
STRUCTURAL
FILL TO MATCH
DEPTH OF
EXISTING
ACCESS ROAD,
N.F.S.
MATERIAL
BEYOND
AGGREGATE
SURFACE
COURSE
GRAVITY MAIN TRENCH DETAIL3
C700 NO SCALE
1. CONTRACTOR MAY UTILIZE ALTERNATIVE
METHODS FOR SHORING AND BRACING AS
NEEDED TO MINIMIZE EXCAVATION
FOOTPRINT.
NOTES
BOLLARD LAYOUT AND DETAIL 4
C700 NO SCALE
CAP TOP SECTION PLAN AT H-FRAME AND CLEANOUTS
6"
1'-2"
4" ALL AROUND
3' -0
3"
4' -0
CONCRETE BASE
FG
PIPE CAP, WELD TO
PIPE, GRIND SMOOTH,
AND PAINT YELLOW
6" OD SCHEDULE 40
STEEL PIPE. FILL
WITH CONCRETE
AND PAINT YELLOW
SLOPE TO DRAIN
DOUBLE CLEANOUT
H-FRAME
5'-0" O C
M
AX, TYP
2'-0"
MIN,
TYP
C. CONCRETE
1. GENERAL:
A. ALL CAST-IN-PLACE CONCRETE SHALL HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH (f'c) OF
4,500 PSI.
B. CONCRETE SHALL MEET ALL REQUIREMENTS OF ACI 301 SPECIFICATION FOR STRUCTURAL
CONCRETE BUILDINGS.
C. ALL PERMANENTLY EXPOSED CONCRETE EDGES TO BE CHAMFERED 3/4", UNO
D. PROVIDE SLEEVES FOR ALL UTILITY OPENINGS.
E. DIMENSIONS SHOWN ON DRAWING SHALL SUPERSEDE THOSE SHOWN ON GENERAL NOTES.
2. REINFORCING:
A. REINFORCING BARS SHALL CONFORM TO ASTM A615 GRADE 60. WELDED WIRE FABRIC SHALL
CONFORM TO ASTM A185.
B. DETAIL REINFORCING BARS IN ACCORDANCE WITH THE ACI DETAILING MANUAL AND THE ACI
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, LATEST EDITION.
C. HORIZONTAL FOUNDATION AND WALL REINFORCING SHALL BE CONTINUOUS AROUND CORNERS AND
INTERSECTIONS; PROVIDE CORNER BARS.
D. PROVIDE ALL ACCESSORIES NECESSARY TO SUPPORT REINFORCING AT POSITIONS SHOWN ON THE
DRAWINGS. PROVIDE SUFFICIENT TIE BARS TO SUPPORT ALL REINFORCING.
E. DO NOT CUT ANY REINFORCEMENT AT OPENINGS.
F. UNLESS A REINFORCING SPLICE, CLEAR DISTANCE BETWEEN REINFORCING SHALL NOT BE LESS
THAN 1.5 BAR DIAMETERS NOR LESS THAN 1 1/2''.
G. MINIMUM LAP SPLICE LENGTHS FOR CONCRETE REINFORCING BARS SHALL BE AS FOLLOWS:
a. SPLICES WITH 12” OR MORE OF FRESH CONCRETE PLACED BENEATH: 80 BAR DIAMETERS
b. ALL OTHER SPLICES: 62 BAR DIAMETERS
H. PROVIDE REINFORCEMENT COVER AS FOLLOWS (ACI 7.7), UNLESS NOTED OTHERWISE ON
DRAWINGS:
a. CONCRETE POURED AGAINST EARTH ........... 3" ±3/8"
b. CONCRETE EXPOSED TO EARTH OR WEATHER:
• NO. 6 OR LARGER .................................. 2" ±3/8"
• NO. 5 OR SMALLER ................................ 1 1/2" ±3/8"
c. CONCRETE SLABS ON GRADE ........................... PLACE REINFORCING AT SLAB MID-DEPTH
3. EMBEDDED ANCHORS:
A. WHERE ANCHOR BOLT PROJECTION IS NOT SPECIFIED, BOLTS SHALL EXTEND PAST FACE OF NUT BY
AT LEAST ONE FULL THREAD.
E. POST-INSTALLED ANCHORS
POST-INSTALLED ANCHORS SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE:
CONCRETE
ADHESIVE ANCHORS:
• EXTERIOR: HILTI HIT-RE 500 V3 OR RED HEAD C6+, 304 OR 316
STAINLESS THREADED ROD
SCREW ANCHORS
• EXTERIOR: SIMPSON TITEN HD, 316 STAINLESS
1. INSTALL POST-INSTALLED ANCHORS ONLY AS INDICATED ON THE DRAWINGS OR WITH SPECIFIC WRITTEN
APPROVAL OF THE ENGINEER PRIOR TO INSTALLATION.
2. THE CONTRACTOR MAY NOT USE SUBSTITUTES FOR THE POST-INSTALLED ANCHORS WITHOUT PRIOR
APPROVAL OF THE ENGINEER.
3. SEE DRAWINGS FOR ANCHOR TYPE, SIZE, AND EMBEDMENT DEPTHS. INSTALL ANCHORS AS OUTLINED IN MANUFACTURER'S SPECIFICATIONS AND ICC REPORTS. UTILIZE PROPER DRILL TYPE, BIT SIZE, AND HOLE
CLEANING, DRIVING OR TIGHTENING TECHNIQUES, UNLESS NOTED OTHERWISE.
4. ANCHORS INSTALLED IN UTILIDOR FLOORS AND WITHIN 18" OF UTILIDOR FLOORS SHALL BE STAINLESS
STEEL CONFORMING TO THE "EXTERIOR APPLICATIONS" PRODUCTS LISTED ABOVE.
5. ANCHORS INSTALLED IN WASTEWATER CONVEYANCE AND/OR WASTEWATER TREATMENT SYSTEMS SHALL BE STAINLESS STEEL CONFORMING TO THE "EXTERIOR APPLICATIONS" PRODUCTS LISTED ABOVE.
GENERAL STRUCTURAL NOTES
A. DESIGN CRITERIA
1. BUILDING CODE........................................................................................ 2021 IBC (INTERNATIONAL BUILDING CODE)
UFC 3-301-01
2. SNOW LOADS
GROUND SNOW LOAD Pg ........................................................ 70 PSF
3. SEISMIC LOADS
SS ............................................................................................... 0.966 S1 ............................................................................................... 0.377 SITE CLASS................................................................................. D
SEISMIC DESIGN CATEGORY.................................................. D
RISK CATEGORY ....................................................................... III IMPORTANCE FACTOR............................................................. 1.25 ANALYSIS PROCEDURE........................................................... EQUIVALENT LATERAL FORCE METHOD
B. FOUNDATION
1. FOUNDATION DESIGN IS BASED ON A GEOTECHNICAL INVESTIGATION PREPARED BY SHANNON AND WILSON
DATED 02/24.
2. ALL ORGANIC AND/ OR OTHER UNSUITABLE MATERIAL SHALL BE REMOVED FROM SUB-GRADE AND
BACKFILLED WITH STRUCTURAL FILL.
3. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MEASURES TO PREVENT ANY FROST OR ICE FROM
PENETRATING ANY FOOTING OR SLAB SUB-GRADE BEFORE AND AFTER PLACING CONCRETE UNTIL SUCH
SUB-GRADES ARE PERMANENTLY PROTECTED BY THE BUILDING STRUCTURE.
4. AT PERIMETER FOUNDATION WALLS, BRING GRADE UP EVENLY (WITH MAXIMUM 6" LIFTS) ON EACH SIDE OF
WALL TO FINAL ELEVATIONS.
5. STRUCTURAL FILL IS TO BE SELECT MATERIAL, TYPE A: NON-FROST SUSCEPTIBLE, CLEAN, FREE DRAINING, WELL GRADED BROKEN STONE, SAND GRAVEL OR OTHER INORGANIC SOIL MATERIALS MEETING THE
FOLLOWING GRADATION AFTER COMPACTION:
SIZE %PASSING
4 INCH 100
NO. 4 30-60
NO. 200 0-5
D. STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL WIDE FLANGE MEMBERS SHALL BE ASTM A572 - GRADE 50 (Fy = 50 KSI) OR A992 (Fy
= 50 KSI).
2. ANGLES, PLATES, AND CHANNELS SHALL BE ASTM A36 (Fy = 36 KSI).
3. PIPE SHALL CONFORM TO ASTM A53 GRADE B (Fy = 35 KSI).
4. ALL STRUCTURAL STEEL SHALL BE DETAILED AND FABRICATED IN ACCORDANCE WITH THE LATEST EDITION
OF THE AISC STEEL CONSTRUCTION MANUAL.
5. WELDING SHALL BE PERFORMED WITH E70XX ELECTRODES. WELDING SHALL BE DONE BY QUALIFIED
WELDERS AND SHALL CONFORM TO THE AWS D1.1 STRUCTURAL WELDING CODE-STEEL, LATEST EDITION.
ALL WELDS ARE INTENDED TO BE CONTINUOUS UNLESS NOTED OTHERWISE.
6. FIELD WELDS NOTED THROUGHOUT THE CONTRACT DOCUMENTS ARE ACCEPTABLE LOCATIONS FOR FIELD
WELDING AT THE CONTRACTOR'S OPTION. FIELD WELDS MAY BE PERFORMED IN THE SHOP.
F. GENERAL
1. CONTRACTOR IS TO FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS TO MATCH NEW CONSTRUCTION TO
EXISTING CONSTRUCTION.
2. THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OR SEQUENCE OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION.
SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO: BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S MEANS, METHODS, TECHNIQUES, SEQUENCES FOR PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE PROGRAMS INCIDENT THERETO (NOR SHALL OBSERVATION VISITS TO
THE SITE INCLUDE INSPECTION OF THESE ITEMS).
3. STRUCTURAL DRAWINGS ARE A PORTION OF THE CONTRACT DOCUMENTS AND ARE INTENDED TO BE USED WITH CIVIL, MECHANICAL, AND ELECTRICAL DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE REQUIREMENTS FROM THESE DISCIPLINES INTO THEIR SHOP DRAWINGS AND WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND IMPLEMENTATION OF ALL SCAFFOLDING, BRACING AND SHORING.
5. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION. LOADS SHALL
NOT EXCEED THE DESIGN LIVE LOAD.
6. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, PLUMBING AND ELECTRICAL WITH
THE APPROPRIATE TRADES, DRAWINGS AND SUBCONTRACTORS PRIOR TO CONSTRUCTION.
7. DO NOT USE SCALED DIMENSIONS TAKEN FROM STRUCTURAL DRAWINGS. CONTACT STRUCTURAL
ENGINEER TO REQUEST SUPPLEMENTAL DIMENSION INFORMATION IF REQUIRED.
8. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE SEAL OF
A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF ALASKA.
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
20 MAY 2025
REPAIR LIFT
STATION B2212
022301
AECC511
5/16/2025 3:10:00 PM
PSB
MTE
GENERAL
STRUCTURAL
NOTES
S001
CONTINUOUS PERIODIC
IBC CODE
REFERENCE
CODE or STANDARD
REFERENCE
FREQUENCYSYSTEM or MATERIAL
INSPECTION
REMARKS
PERIODIC: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT WHERE THE WORK TO BE INSPECTED HAS BEEN OR IS BEING
PERFORMED.
CONTINUOUS: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED.
THE FOLLOWING STRUCTURAL ITEMS REQUIRE SPECIAL INSPECTION PER IBC SECTIONS 1704-1707.
SEE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR INSPECTION AND TESTING THAT ARE NOT PART OF SPECIAL INSPECTIONS.
SPECIAL INSPECTIONS
INSPECT CONCRETE PLACEMENT
FOR PROPER APPLICATION
TECHNIQUES. VERIFY USE OF
APPROVED MIX DESIGN
TABLE 1705.3, 1904.1,
1904.2
ACI 318-19: 26.5, 26.13.3 X
FIRST 20% OF EACH PLACEMENT TO VERIFY
PROPER PLACEMENT TECHNIQUES
INSPECT ADHESIVE ANCHORS
INSTALLED IN HORIZONTALLY OR
UPWARDLY INCLINED ORIENTATIONS
TO RESIST SUSTAINED TENSION
LOADS
TABLE 1705.3
ACI 318-19: 26.7,
26.13.3.2(e) X
INSPECT ANCHORS
POST-INSTALLED IN HARDENED
CONCRETE, MECHANICAL ANCHORS
AND ADHESIVE ANCHORS NOT
DEFINED BELOW
TABLE 1705.3
ACI 318-19: 26.7,
6.13.3.2(h), 26.13.3.2(i) X
SPECIAL INSPECTIONS APPLY TO ANCHOR
PRODUCT NAME, TYPE, AND DIMENSIONS,
HOLE DIMENSIONS, COMPLIANCE WITH DRILL
BIT REQUIREMENTS, CLEANLINESS OF THE
HOLE AND ANCHOR, ADHESIVE EXPIRATION
DATE, ANCHOR/ADHESIVE INSTALLATION,
ANCHOR EMBEDMENT, AND TIGHTENING
TORQUE. INSPECTION FREQUENCY PER
MANUFACTURER'S REQUIREMENTS BUT NOT
LESS THAN 10% OF EACH ANCHOR, DOWEL,
OR ADHESIVE TYPE
INSPECT ANCHORS CAST IN
CONCRETE
TABLE 1705.3
ACI 318-19: 26.7,
26.13.3.3(g)
X ALL BOLTS VISUALLY INSPECTED
INSPECT REINFORCEMENT TABLE 1705.3
ACI 318-19: CH. 20, 25.2,
25.3, 26.6.1 - 26.6.3
X ALL REINFORCEMENT VISUALLY INSPECTED
CONCRETE
DIVISION #03 - CONCRETE
FOR CONCRETE ELEMENTS,
PERFORM ADDITIONAL INSPECTIONS
IN ACCORDANCE WITH SECTION
DIVISION #03 SPECIAL INSPECTION
TABLE
TABLE
1705.8
VERIFY PLACEMENT LOCATIONS AND
PLUMBNESS, CONFIRM ELEMENT
DIAMETERS, BELL DIAMETERS (IF
APPLICABLE), LENGTHS,
EMBEDMENT INTO BEDROCK (IF
APPLICABLE) AND ADEQUATE
END-BEARING STRATA CAPACITY.
RECORD CONCRETE OR GROUT
VOLUMES
TABLE
1705.8
X
INSPECT DRILLING OPERATIONS AND
MAINTAIN COMPLETE AND
ACCURATE RECORDS FOR EACH
ELEMENT
TABLE
1705.8
X
CAST-IN-PLACE DEEP FOUNDATION ELEMENTS
PRIOR TO PLACEMENT OF
COMPACTED FILL, OBSERVE
SUBGRADE AND VERIFY THAT SITE
HAS BEEN PREPARED PROPERLY
TABLE
1705.6
X
BY THE GEOTECHNICAL ENGINEER OR
OTHER APPROVED INSPECTOR
VERIFY EXCAVATIONS ARE
EXTENDED TO PROPER DEPTH AND
HAVE REACHED PROPER MATERIAL
TABLE
1705.6
X
BY THE GEOTECHNICAL ENGINEER OR
OTHER APPROVED INSPECTOR
VERIFY MATERIALS BELOW
SHALLOW FOUNDATIONS ARE
ADEQUATE TO ACHIEVE THE DESIGN
BEARING CAPACITY
TABLE
1705.6
X
BY THE GEOTECHNICAL ENGINEER OR
OTHER APPROVED INSPECTOR
SOILS
DIVISION #31 - EARTHWORK
A K
AF AL
T S
TA
E
O
49 TH
S
Patrick S. Brandon
SE 141370
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
R
16-MAY-2025
S101
S101
(E) HATCH
S101
S200 3__________
S200
2 PROVIDE WATER-TIGHT
SEAL BETWEEN EXISTING
UTILIDOR AND PILE.
CONCEPT: GROUT FILL
CONCEPTUAL PILE WALL &
REINFORCING.
SEE NOTES, THIS SHEET
S100
S100
S100
S100
OPP
OPP
S100
44' - 10"
42' - 6"
APPROX
9' - 0
APPROX
17' - 0"
A P
P R
O X
S100
W14X68
W X
W X
W14X48
CONCEPTUAL SECANT PILE RING.
SEE NOTES, THIS SHEET
CONCRETE SECANT PILE,
PER SPECIFICATION
REINFORCE PILES WITH
CONTINUOUS WIDE FLANGE
COLUMNS, ORIENTED AS
SHOWN ON PLAN.
CONCEPTUAL REINFORCING
SIZE: W12X40
CONCEPTUAL WHALER
SHEAR CONNECTION
PER
WHALER PER PLAN
GROUT FILL ANNULAR
SPACE BTW BEAM &
SECANT PILE. TYP, FULL
LENGTH OF BEAMS
S100
1" MAX
5/16
5/16
3/4"X6"X9" SHEAR TAB
5/16
3-SIDES
1/2" STIFFENER
PLATE, BOTH SIDES
5/16
3-SIDES
1" MAX
5/16
5/16
3/4"X6"X18" SHEAR TAB
5/16
3-SIDES
1/2" STIFFENER
PLATE, BOTH SIDES
5/16
3-SIDES
5/16
5/16
5/16
5/16
1/2" PLATE
0' - 8"
CJP
CLIP FLANGE
8"
/4
REMOVE CONCRETE AS
NECESSARY TO INSTALL LATERAL
WHALER CONNECTION
FACE OF PILE
REINFORCING
WHALER PER PLAN
5/16 8
1" MIN
5/16 8
5/16 8
1/2"X8"XREQ
PLATE TOP
AND BOT
5/16 8
GROUT FILL ANNULAR SPACE
BTW BEAM & SECANT PILE
FOLLOWING ATTACHMENT.
TYP, FULL LENGTH OF BEAMS
1/4" = 1'-0"S100
1 OVERALL PLAN
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
20 MAY 2025
REPAIR LIFT
STATION B2212
022301
AECC511
5/16/2025 3:10:01 PM
PSB
MTE
OVERALL PLAN
S100
1/2" = 1'-0"S100
2 CONCEPTUAL - TYPICAL SECANT PILE & WHALER
GENERAL NOTES
1. EXCAVATION SHORING AND GROUNDWATER DAMMING SYSTEM SHOWN IS
CONCEPTUAL. CONTRACTOR'S GEOTECHNICAL ENGINEER SHALL BE RESPONSIBLE
FOR THE DESIGN OF EXCAVATION SHORING AND DEWATERING DESIGN. SEE
SPECIFICATION 31 63 16.
2. EXTENTS OF EXCAVATION AND RETAINING WALLS IS CONCEPTUAL. CONTRACTOR TO
DETERMINE OVERALL PLAN DIMENSIONS OF EXCAVATION NECESSARY TO PERFORM
WORK.
3. GROUNDWATER SEEPAGE RATES INTO EXCAVATION SHALL MEET THE REQUIREMENTS
OF THAT LISTED IN SECTIONS 02 61 13 AND 31 63 16.
1" = 1'-0"S100
4 CONCEPTUAL - WHALER-TO-STRUT CONNECTION
1" = 1'-0"S100
3 CONCEPTUAL - WHALER-TO-WHALER CONNECTION
1" = 1'-0"S100
5 CONCEPTUAL - WHALER SHEAR CONNECTION
A K
AF AL
T S
TA
E
O
49 TH
S
Patrick S. Brandon
SE 141370
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
EXISTING LIFT
STATION FINISHED
FLOOR
0' - 0"
UTILIDOR FLOOR
-14' - 9"
FINISHED GRADE
-0' - 6"
TREMIE SLAB CAST UNDER
(E) UTILIDOR 2' - 0" MIN
4" LEVELING SLAB
ATOP TREMIE SLAB
PER CIVIL
M
IN
G E
O T
E C
H T
O C
O N
F
IR
M
A P
P R
O X
" TREMIE SLAB
TREMIE SLAB
TOP OF LIFT STATION
PER CIVIL
FILL ANNULAR SPACE
BETWEEN LIFT STATION
AND RING WALL WITH
SELF CONSOLIDATING
MATERIAL. SEE NOTES,
THIS SHEET
PREP PILE SURFACE
PRIOR TO TREMIE SLAB
PLACEMENT. SEE
NOTES, THIS SHEET
SURFACE WATER
RELIEF PORTS. SEE
NOTES, THIS SHEET
(8) 1"Ø STAINLESS STEEL ADHESIVE
ANCHORS, 36" EMBED INTO TREMIE SLAB.
ENSURE HOLES ARE NOT WATER FILLED
WHEN INSTALLING EPOXY ANCHORS.
TREMIE CONCRETE MINIMUM AGE PRIOR TO
INSTALLING ADHESIVE ANCHORS: 7 DAYS
TREMIE CONCRETE MINIMUM AGE PRIOR TO
LOADING ANCHORS: 21 DAYS
APPROXIMATE
WATER TABLE
APPROX EXCAVATION
SLOPE
CONCEPTUAL PILE WALL & REINFORCING.
SEE NOTES, THIS SHEET
-7' - 0"
A P
P R
O X
V
E R
IF
Y
W M
F R
M
IN
A P
P R
O X
EXISTING LIFT
STATION FINISHED
FLOOR
0' - 0"
UTILIDOR FLOOR
-14' - 9"
FINISHED GRADE
-0' - 6"PER CIVIL
~ TREMIE SLAB ~
M
IN
G E
O T
E C
H T
O C
O N
F
IR
M
A P
P R
O X
PREP PILE SURFACE PRIOR TO
TREMIE SLAB PLACEMENT.
SEE NOTES, THIS SHEET
SURFACE WATER
RELIEF PORTS. SEE
NOTES, THIS SHEET
CONCEPTUAL PILE WALL
& REINFORCING.
SEE NOTES, THIS SHEET
APPROXIMATE
WATER TABLE
-7' - 0"
M
IN
A P
P R
O X
UTILIDOR FLOOR
-14' - 9"
FINISHED GRADE
-0' - 6"
GROUT BETWEEN
(E) UTILIDOR AND
SECANT PILE
TREMIE SLAB BEYOND
PER CIVIL
APPROX EXCAVATION
SLOPE
CONCEPTUAL PILE WALL & REINFORCING.
SEE NOTES, THIS SHEET
APPROXIMATE
WATER TABLE
-7' - 0"
1/4" = 1'-0"S101
1 LIFT STATION OVERALL SECTION
1/4" = 1'-0"S101
2 MANHOLE OVERALL SECTION
1/4" = 1'-0"S101
3 PILE AT (E) UTILIDOR
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
20 MAY 2025
REPAIR LIFT
STATION B2212
022301
AECC511
5/16/2025 3:10:41 PM
PSB
MTE
OVERALL
SECTIONS
S101
GENERAL NOTES
1. EXCAVATION SHORING AND GROUNDWATER DAMMING SYSTEM SHOWN IS CONCEPTUAL.
CONTRACTOR'S GEOTECHNICAL ENGINEER SHALL BE RESPONSIBLE FOR THE DESIGN OF EXCAVATION
SHORING AND DEWATERING DESIGN. SEE SECTION 31 63 16.
2. EXTENTS OF EXCAVATION AND RETAINING WALLS IS CONCEPTUAL. CONTRACTOR TO DETERMINE
OVERALL PLAN DIMENSIONS OF EXCAVATION NECESSARY TO PERFORM WORK.
3. GROUNDWATER SEEPAGE RATES INTO EXCAVATION SHALL MEET THE REQUIREMENTS OF THAT
LISTED IN SECTIONS 02 61 13 AND 31 63 16.
4. CONTRACTOR TO CONFIRM WATER TABLE ELEVATION DOES NOT EXCEED TOP OF (E) UTILIDOR.
EXCAVATION SHORING CONCEPT USES WATER TABLE ELEVATION SHOWN. NOTIFY COR IF WATER
TABLE ELEVATION IS FOUND HIGHER THAN THAT SHOWN ON THESE DRAWINGS.
5. ANNULAR FILL MATERIAL AT LIFT STATION BASIN TO BE FREE DRAINING AND SELF CONSOLIDATING, 3/4" CRUSHED AGGREGATE OR SIMILAR.
6. INSIDE FACE OF SECANT PILES TO BE FREE OF IN-SITU SOIL PRIOR TO TREMIE SLAB PLACEMENT.
CONTRACTOR TO SUBMIT PLAN FOR CLEANING PILE FACE & VERIFYING PILE FACE IS FREE OF IN-SITU SOIL PRIOR TO TREMIE SLAB PLACEMENT. THE PURPOSE OF PILE SURFACE CLEANING IS TO CREATE AS TIGHT A WATER SEAL AS POSSIBLE BETWEEN THE SLAB AND PILE WALL IN ORDER TO REDUCE
DEWATERING VOLUMES, NOT FOR CONCRETE ADHESION.
7. PROVIDE 4"Ø DRILLED RELIEF PORTS AT THE PERIMETER OF THE LIFT STATION RING WALL, AT 4'-0" OC.
INSTALL 1'-0" ABOVE GROUND WATER TABLE ELEVATION AT TIME OF CONSTRUCTION.
A K
AF AL
T S
TA
E
O
49 TH
S
Patrick S. Brandon
SE 141370
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
WATERPROOF AND INSULATE
NEW AND EXPOSED EXISTING
CONCRETE SURFACES
S200
LOW VENT PER
S201
HIGH VENT PER
S201
LID SUPPORT
PER SECTION
(E) UTILIDOR LID
SECTIONS, TYP
S200
TYP
0' - 8"
4' - 10"
#5 @ 12" OCEW, CENTERED
IN WALL
UTILIDOR FLOOR
-14' - 9"
FINISHED GRADE
-0' - 6"
WALL REINFORCING
PER
HYDROPHILIC WATER
STOP AT ALL JOINTS
#5 @ 8" OC
#5 @ 16" OC
SLAB REINFORCING
PER
MANHOLE ACCESS
LADDER PER
S201
TREMIE SLAB PER
S101
UTILIDOR ACCESS
HATCH PER
S201
PER CIVIL
S200
S200
-1
/2
C O
V E
R
S200
S200
(E) UTILIDOR WALL
#5 @ 12" OCEW
CENTERED IN WALL
HYDROPHILIC WATERSTOP
AT ALL JOINTS
#5 ADHESIVE DOWELS IN WALL AND
SLAB. SPACING TO MATCH WALL AND
SLAB REINFORCEMENT. 6" EMBEDMENT,
12" PROJECTION
8" SLAB
REINFORCED W/ #5
@ 12" OCEW
CENTERED IN SLAB
#5 CORNER BARS W/ 24" LEGS @ 12"
OC. TYP ALL CORNERS
TYP
0' - 8"
0' - 6" 9' - 4" 0' - 6"
SHORE (E) LIDS UNTIL NEW
LID CONCRETE HAS
ACHIEVED DESIGN STRENGTH
SAWCUT WALL FLUSH WITH
EXISTING UTILIDOR SLAB
8' - 0"
Utilidor Floor -14' - 9"
UTILIDOR FLOOR
-14' - 9"
UTILIDOR FLOOR
-14' - 9"
3/8"X4"X6" BENT PLATE, FULL
LENGTH WITH 5/8"Ø, 4" LONG
SHEAR STUDS @ 8" OC
(4) #8 LONGITUDINAL REINFORCING
EQUALLY DISTRIBUTED WITHIN SHADED
AREA
#5 @ 8" OC
#5 @ 16" OC
HYDROPHILIC WATER
STOP AT ALL JOINTS
WALL REINFORCING
PER
SLAB REINFORCING
PER
TREMIE SLAB PER
S101
DOWEL SIZE AND SPACING
TO MATCH WALL DOWELS
STD HOOKS AT
TOP & BOT
S200
S200
(V E
R
IF
Y
2' - 9"
-1
/2
C O
V E
R
5' - 6"
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
20 MAY 2025
REPAIR LIFT
STATION B2212
022301
AECC511
5/16/2025 3:10:47 PM
PSB
MTE
STRUCTURAL
DETAILS
S200
1/2" = 1'-0"S200
3 MANHOLE LID PLAN
1/2" = 1'-0"S200
4 MANHOLE SECTION 2
1/2" = 1'-0"S200
2 MANHOLE SLAB AND WALL PLAN
1/2" = 1'-0"S200
1 UTILIDOR DEMOLITION PLAN
1. UTILIDOR WALL-TO-LID JOINTS SHALL BE SEALED GENEROUSLY WITH 3/4" HIGH BY 4"
WIDE CONTINUOUS STRIP OF FIBER PLASTIC ROOF COATING OR APPROVED EQUAL,
AND TWO RUNS OF MARINE GRADE OAKUM FILLER MATERIAL, PRESSED INTO
MASTIC.
2. LID-TO-LID JOINTS SHALL BE SEALED BY PRESSING INTO JOINT ONE (1) OR TWO (2)
RUNS OF OAKUM TYPE FILLER AS A BACKER MATERIAL, THEN TROWEL IN A
GENEROUS LAYER OF "FIBERED PLASTIC ROOF COATING" OR APPROVED EQUAL.
3. ENSURE ALL JOINTS FORM A CONTINUOUS SEAL THROUGHOUT LENGTH OF JOINT.
GENERAL NOTES
1/2" = 1'-0"S200
5 MANHOLE SECTION 3
A K
AF AL
T S
TA
E
O
49 TH
S
Patrick S. Brandon
SE 141370
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
TYP
8" MIN
INSERT 2" LONG THREADED PVC
NIPPLE INTO OUTLET COUPLING
ATTACH FLEXIBLE TUBE ON
NIPPLE WITH CLAMP.
FLEXIBLE TUBE TO BE HELD IN
PLACE DURING CONCRETE
POUR TO ENSURE DRAINAGE
OF HATCH CHANNEL TO
INTERIOR OF SHAFT
SECTION A-A
PLAN
SECTION
SHAFT OPENING
39" X 42"
MINIMUM
58"
SHAFT
42"
LADDER BELOW
EXTENDABLE LADDER
SAFETY POST
LATCH PLATE
HATCH SENSOR
SWITCH
1"Ø DRAIN CHANNEL OUTLET A
A
S H
A F
T
WELDED ATTACHMENT
HOOKS FURNISHED W/
ACCESS HATCH
ACCESS HATCH DRAIN
CHANNEL ALL AROUND
DOOR HINGE
M
IN
IM
U
M
INTERIOR SHAFT WALL
TO BE FLUSH W/ INSIDE
OF DRAIN CHANNEL
115.00°
LADDER
NYSTROM 42"
LADDER SAFETY
POST OR APPROVED
EQUAL
LADDER SAFETY POST
4" x 3/8" STEEL BRACKET LADDER
SUPPORTS @ 6' - 0" OC MAX , TYP
3/4" Ø KNURLED RUNGS
2" x 3/8" BAR SIDE RAILS
M A
X
3/16
TYP
SIDE ELEVATION FRONT ELEVATION
PLUG WELD
ALL RUNGS
16" MIN TOP OF WALKING SURFACE
CLEARANCE
15" MIN
CLEARANCE
15" MIN
3/16
3/16
TYP
SANDBLAST AND
EPOXY AFTER
FABRICATION OR
GALVANIZATION
CLEARANCE
30" MIN
MIN
7"
TOP OF WALKING SURFACE
TOP OF
WALKING
SURFACE
M A
X
M A
X
M A
X
M A
X B
T W
S U
P P
O R
T S
M A
X
" 3
12" STEEL PIPE CAP
WELD 12" CAP TO
SECTION OF 12"Ø PIPE
SECTION OF 12"Ø
STEEL PIPE
STEEL WIRE MESH
PER PLAN
8"Ø SCHEDULE 40
STEEL PIPE TO VAULT
ACCESS VAULT LID
CONNECT 2"Ø AIR GAP VENT
TO EXHAUST STACK
SECTION
12"Ø SCHEDULE 40 STEEL PIPE
TACK WELD 1/2" X 1/2" HEAVY
GAUGE STEEL WIRE MESH
FOR BIRD SCREEN TO
BRACKETS AND PIPES
8"Ø SCHEDULE 40 STEEL PIPE
TACK WELD 1/2"x3"x3"
STEEL BRACKETS TO 12"Ø
PIPE AND 8"Ø PIPE
PLAN
A
B O
V E
G R
A D
E
B O
T H
V E
N T
S S
A M
E H
E
IG
H T
8"Ø INTAKE
VENT
8"Ø EXHAUST
VENT
GRADE
6" - 18" ABOVE FINISHED FLOOR
6" - 12" BELOW ROOF
6" (TYP)
DAMPER WITH LOCKING QUADRANT,
DAMPER HEIGHT NOT TO SCALE (TYP)
CONCRETE ROD ATTACHMENT PLATE
WITH ADJUSTABLE PIPE STANCHION &
U-BOLT FITTING (TYP)
COVER PLATE
PER
S201
(TYP)
S201
(TYP)
SANDBLAST AND EPOXY AFTER
FABRICATION OR
GALVANIZATION
LINK SEAL (TYP)
1/2"Ø STAINLESS STEEL
EXPANSION ANCHOR,
MINIMUM 3" EMBEDMENT
WATERTIGHT SEAL UNDER
COVER PLATE
12" SQ COVER PLATE, 1/4" STEEL1/4
2" MIN
V A
R
IE
S
CONCRETE SUPPORT
BLOCK WITH 18" MIN
BEARING LENGTH
1/16" THICK SHEET HDPE
W/ 1" OVERHAND ON
BOTH SIDES OF BLOCK
ALONG PIPE LENGTH
PIPE PER
MECHANICAL
UTILIDOR FLOOR
- 14' - 9"
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
20 MAY 2025
REPAIR LIFT
STATION B2212
022301
AECC511
5/16/2025 3:10:48 PM
PSB
PSB
STRUCTURAL
DETAILS
S201
3/4" = 1'-0"S201
1 UTILIDOR ACCESS HATCH
3/4" = 1'-0"S201
2 UTILIDOR ACCESS LADDER
1" = 1'-0"S201
3 ACCESS VAULT VENTILATION PIPE DETAIL
1/2" = 1'-0"S201
4 ELEVATION OF VAULT VENTING
1" = 1'-0"S201
5 VAULT ROOF SLAB PENETRATION DETAIL
1" = 1'-0"S201
6 PIPE SUPPORT DETAIL
A K
AF AL
T S
TA
E
O
49 TH
S
Patrick S. Brandon
SE 141370
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
MECHANICAL SYMBOLS
CONNECTION TO EXISTING
PIPE FLOW ARROW
PIPE CONNECTION
PIPE ELBOW TURNED DOWN
PIPE ELBOW TURNED UP
PIPE TEE DOWN
UNION
PIPE CAP
PIPE ANCHOR
PIPE GUIDE
PIPE BREAK
ISOLATION VALVE
CHECK VALVE
BALANCING COCK
PRESSURE REDUCING VALVE
STRAINER
STRAINER WITH BLOWDOWN
DRAIN VALVE
HOSE BIBB
PUMP
PRESSURE GAUGE
STEAM PRESSURE GAUGE
PRESSURE & TEMPERATURE
TEST PORT
2-WAY CONTROL VALVE
MECHANICAL LINETYPES
ABBREVIATION LINETYPE
W
V
CW
ST
CR
EXISTING PIPING/DUCTWORK/
EQUIPMENT TO BE REMOVED
EXISTING TO BE REMOVED
EXISTING
CONDENSATE RETURN
STEAM
COLD WATER
VENT
WASTE
FULL NAME
EXISTING TO REMAIN
MECHANICAL TAG LEGEND
PIPE TAG 6" (+2") GHS SYSTEM ABBREVIATION
NOMINAL PIPE SIZE
INSULATION THICKNESS
UNIT HEATER SCHEDULE (ELECTRIC)
CAPACITY
(BTU/HR)
SYMBOL AIR TEMP
RISE (F)
BASIS OF DESIGN REMARKS
17,060UH-1 QMARK
GUX500832
1. CLASS 1 DIV. 1 EXPLOSION PROOF UNIT HEATER
2. PROVIDE WITH BUILT IN THERMOSTAT
LOCATION STYLE
BYPASS
LIFT STATION
HORIZONTAL 22
MIN
CFM
MOTOR
DATA
5 KW
208/3Ø/60
MISCELLANEOUS EQUIPMENT SCHEDULE
ITEM CAPACITY / SIZE MOTOR
DATA
OPERATING
WEIGHT (LB)
BASIS OF DESIGN REMARKSSYMBOL
LS-1 LIFT STATION BASIN 10'ØX 24' ----- ----- FLYGT TOP 1. CUSTOM GLASS FIBER REINFORCED BASIN WITH ALUMINUM COVER AND
ACCESS HATCHES
2. INTERNAL DISCHARGE PIPING PROVIDED WITH BASIN WITH CHECK VALVES
AND DISCHARGE ISOLATION VALVES
3. PROVIDE WITH MINIMUM NUMBER OF EIGHT EXTERIOR ANCHOR LEGS.
MOTOR OPERATED VALVE SCHEDULE
SIZESYMBOL TORQUE
(FT-LB)
BASIS OF DESIGN REMARKS
18"ØPGV-1 VALVE: DEZURIK PEF
ACTUATOR: AUMA
SA07.6/GS160.3/AC01.2
1. AWWA C517-16 COMPLIANT VALVE
2. ELECTRIC MOTORIZED OPERATOR WITH MANUAL HANDWHEEL OPERATOR
OVERRIDE, 442:1 GEAR REDUCTION, & END-SWITCH FEEDBACK CONTACT.
3. NORMALLY OPEN VALVE.
LOCATION STYLE
UTILIDOR OFFSET PLUG
VALVE
MOTOR
DATA
1/2 HP
208/3Ø/60
PGV-2 UTILIDOR 18"Ø 1. AWWA C517-16 COMPLIANT VALVE
2. ELECTRIC MOTORIZED OPERATOR WITH MANUAL HANDWHEEL OPERATOR
OVERRIDE, 442:1 GEAR REDUCTION, & END-SWITCH FEEDBACK CONTACT.
3. NORMALLY CLOSED VALVE.
OFFSET PLUG
VALVE
VALVE: DEZURIK PEF
ACTUATOR: AUMA
SA07.6/GS160.3/AC01.2
30 1/2 HP
208/3Ø/60
CIRCULATING PUMP SCHEDULE
SERVICE STYLE
LP-1A
LP-1B
LIFT PUMP
GPM HEAD
(FT H2O)
RPM MOTOR
DATA
BASIS OF DESIGN MAX
BHP
900 25' 15 HP
200/3/60
VAUGHAN
S6U-100
10.4WET WELL
CHOPPER
SYMBOL REMARKS
1. CLASS 1 DIV. 1 EXPLOSION PROOF,
SUBMERSIBLE MOTOR.
2. 10" IMPELLER.
3. PROVIDE WITH SPARK PROOF GUIDE RAILS &
DISCHARGE ELBOW.
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
20 MAY 2025
REPAIR LIFT
STATION B2212
022301
AECC511
5/19/2025 7:49:45 PM
MPC
MJA
MECHANICAL
ABBREVIATIONS,
LEGENDS, AND
SCHEDULES
M001
ABBREVIATION FULL NAME
# NUMBER
& AND
(E) EXISTING
@ AT
A AIR
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
APPR APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASSOC ASSOCIATED
AUTO AUTOMATIC
BFF BELOW FINISHED FLOOR
C COMMON
CI CAST IRON
CO CLEAN OUT
CR CONDENSATE RETURN
Cv VALVE COEFFICIENT
CW COLD WATER
DB DECIBEL
DB DRYBULB
DI DUCTILE IRON
DIA DIAMETER
DN DOWN
DWDI DOUBLE WIDTH, DOUBLE INLET
EA EXHAUST AIR
EF EXHAUST FAN
ELEC ELECTRICAL
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXIST EXISTING
FC FORWARD CURVED
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FLA FULL LOAD AMPERAGE
FLEX FLEXIBLE
FP FIRE PROTECTION
GA GAUGE
GALV GALVANIZED
GI GALVANIZED IRON
HB HOSE BIBB
ID INSIDE DIAMETER
IE INVERT ELEVATION
INSUL INSULATION
IPS IRON PIPE SIZE
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
ABBREVIATION FULL NAME
MTR MOTOR
NC NORMALLY CLOSED
NC NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPSH NET PUMP SUCTION HEAD
NTS NOT TO SCALE
OAT OUTSIDE AIR TEMPERATURE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
ORD OVERFLOW ROOF DRAIN
ORL OVERFLOW RAIN LEADER
OSA OUTSIDE AIR
P&T PRESSURE AND TEMPERATURE
PD PRESSURE DROP
PH PHASE
PRDV PRESSURE REDUCING VALVE
PRV PRESSURE RELIEF VALVE
RA RETURN AIR
RHW RECIRCULATING HOT WATER
RL RAIN LEADER
RP RADIANT PANEL
RPM REVOLUTIONS PER MINUTE
S/M SHEET METAL
S/S START/STOP
SH SHOWER
SIM SIMILAR
SP STATIC PRESSURE
SPEC SPECIFICATIONS
SS SANITARY SEWER
ST STEAM
SWSI SINGLE WIDTH, SINGLE INLET
TDH TOTAL DYNAMIC HEAD
THW TEMPERED HOT WATER
TP TRAP PRIMER
TYP TYPICAL
V VENT
VAV VARIABLE AIR VOLUME
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VTR VENT THROUGH ROOF
W WASTE
W/ WITH
W/O WITHOUT
WB WETBULB
WCO WALL CLEAN OUT
MECHANICAL ABBREVIATIONS
CONTROLS SEQUENCE OF OPERATION
LIFT STATION PUMP CONTROLS
1. COMMENTARY: LIFT STATION INSTALLED AS PART OF THIS PROJECT WILL OPERATE AS A
BACKUP/REDUNDANT LIFT STATION TO THE BUILDING B2212. BUILDING 2212 PUMPS WILL
BE THE PRIMARY STATION WITH AUTOMATIC OR MANUAL SWITCH OVER TO THIS BYPASS
LIFT STATION IN THE EVENT OF PRIMARY FAILURE OR TO HANDLE MAINTENANCE WITHIN
B2212. AUTOMATIC SWITCHOVER WILL BE BASED ON SENSING EFFLUENT LEVELS WITHIN
THE B2212 WET WELL FROM THE NEW LIFT STATION CONTROL PANEL WHICH BASED ON
B2212 LEVELS WILL OPERATE 18” PLUG VALVES IN THE UTILIDOR TO DIVERT SEWAGE TO
THE BYPASS LIFT STATION.
2. LIFT STATION PUMPS LP-1A & LP-1B CYCLE THROUGH LIFT STATION PUMP CONTROLLER
TO DRAW DOWN WET WELL LEVEL PER SETPOINTS AS INDICATED ON DRAWINGS.
PRIMARY LEVEL SENSING THROUGH LOW-ENERGY RADAR SENSOR.
a. MONITOR B2212 WET WELL SEWAGE LEVEL THROUGH INTRINSICALLY SAFE MULTI-
PROBE LEVEL SENSOR. PROVIDE LEVEL SENSOR AND MOUNT WITHIN THE WET WELL
TO ALARM UPON SEWAGE RISE 6” BELOW EXISTING BAR SCREEN ELEVATION.
b. UPON DETECTION OF B2212 HIGH SEWAGE LEVEL, PROVIDE 120V CONTACT CLOSURE
SIGNAL TO UTILIDOR PLUG VALVE MOTOR OPERATORS TO CLOSE PGV-1 AND OPEN
PGV-2. MONITOR DRY CONTACTS OF EACH VALVE OPERATOR FOR END SWITCH
POSITION FEEDBACK.
i. IF VALVE POSITION IS NOT PROVED AFTER 2 MINUTES (ADJUSTABLE), GENERATE
LOCAL ALARM VIA AUDIBLE HORN AND RED ALARM LIGHT.
ii. UPON PROOF OF PGV-1 CLOSURE PROVIDE MOMENTARY CONTACT SIGNAL
TO SHUNT TRIP LOCATED WITHIN THE B2212 GENERATOR ROOM TO DE-
ENERGIZE EXISTING PUMP CONTROLS. SEE ELECTRICAL DRAWINGS FOR SHUNT
TRIP LOCATION.
c. SIGNAL BYPASS LIFT STATION OPERATION VIA AMBER LIGHT STROBE MOUNTED TO
LIFT STATION CONTROL PANEL.
d. PUMPS CYCLE THROUGH LEAD-LAG TO EQUALIZE PUMP RUN TIME.
e. LEAD PUMP RUNS ON A CALL TO RUN. IF NO PROOF OF FLOW IS RECEIVED BY
SENSING OPERATION CURRENT AT PUMP STARTER, START LAG PUMP. CONTINUE
ATTEMPT TO OPERATE LEAD PUMP FOR 30 SECONDS (ADJUSTABLE). IF LEAD PUMP
FAILS TO OPERATE GENERATE AN ALARM AT THE VISUAL STROBE.
f. UPON ACTIVATION OF LEAD PUMP, IF WET WELL LEVEL CONTINUES TO RISE, START
LAG PUMP PER THE INDICATED LEVEL SETPOINTS.
g. ANNUNCIATE THE FOLLOWING ALARM CONDITIONS TO THE CONTROL PANEL
MOUNTED VISUAL RED STROBE AND AUDIBLE ALARM:
i. FAILURE OF EITHER PLUG VALVE TO FULLY OPEN/CLOSE
ii. HIGH-HIGH LEVEL ALARM
iii. LEAD PUMP FAILURE
iv. LEAD AND LAG PUMP FAILURE
3. WET WELL ELECTRIC HEATING:
CLASS 1 DIV 1 ELECTRIC UNIT HEATER MOUNTED IN WET WELL OPERATES BASED ON
INTEGRAL, EXPLOSION PROOF THERMOSTAT TO MAINTAIN MINIMUM WET WELL TEMPERATURE
OF 50 DEGREES F.
A K
AF AL
T S
T A
E O
49 TH
S
R E
G
ISTERED
PROFESS IONAL
ENG
IN
E
E R
19-MAY-2025
Marcus P. Curley
ME 14660
LIFT STATION WALL
BARSCREEN
ROOM
B02
UTILIDOR
(E) 14" SS FORCE
MAIN AND
ASSOCIATED PUMPS
TO REMAIN
CUT SECTION
OF 14" SS
(E) EFFLUENT CHANNEL
(E) HATCH ABOVE UP TO GROUND
LEVEL FLOOR, HATCH BELOW DN
TO WET WELL
STAIR UP
STAIR DNSTAIR DN
STAIR DN
TO PUMP
ROOM P01
(E) SEWER MANHOLE
DEMOLISH SECTION OF 18" SS
UTILIDOR WALL
(E) 18" SS TO REMAIN (E) 18" SS TO REMAIN
UTILIDOR DEMOLITION PER
STRUCTURAL
S100
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
20 MAY 2025
REPAIR LIFT
STATION B2212
022301
AECC511
5/19/2025 7:49:45 PM
MPC
MJA
MECHANICAL
DEMOLITION PLAN
M100M100 1/4" = 1'-0"
1 UTILIDOR MECHANICAL DEMOLITION PLAN
A K
AF AL
T S
T A
E O
49 TH
S
R E
G
ISTERED
PROFESS IONAL
ENG
IN
E
E R
19-MAY-2025
(E) MANHOLE
(E) 22Ø SS
GRAVITY MAIN
(E) 14" SS FORCE MAIN
10" SS FORCE MAIN WITH
ELECTRICAL HEAT TRACE AND 3"
INSULATION. SEE CIVIL SITE PLAN
FOR ROUTING AND PROFILE
(E) 3" ST
(E) 2" CR
10" X 8"
DOUBLE
CLEANOUT
M300
(E) 18" SS
(E) 18" SS INLET FROM
UTILIDOR TO BAR
SCREEN ROOM
(E) 3" ST AND 2" CR FROM
UTILIDOR TO PUMP DRY
WELL ROOM
(E) HATCH
ABOVE
(E) UTILIDOR
PROVIDE HIGH-HIGH
LEVEL FLOAT SWITCH IN
EXISTING WET WELL
M300
STAIR DN
STAIR UP
STAIR DN
STAIR DN
TO PUMP
ROOM P01
18" SS
SECANT PILE RINGS PER
STRUCTURAL, TYP
PGV-1
PGV-2
18" SS 18" SS
LS-1
LIFT STATION CONTROL
PANEL MOUNTED TO
STRUT STAND PER
ELECTRICAL
ELECTRICAL CONDUIT INTO
LIFT STATION PER LIFT
STATION MANUFACTURER
STACKED IN (E)
UTILIDOR RACK 3"
ST, 2" CT TO B2212
10" X 8" DOUBLE
CLEANOUT
M300
ELECTRICAL
PANEL
M300
18"X8" DOUBLE
WYE CLEANOUT
ELECTRICAL HEAT
TRACE PER
ELECTRICAL
18" SS GRAVITY MAIN WITH
ELECTRICAL HEAT TRACE
AND 3" INSULATION. SEE
CIVIL SITE PLAN FOR
ROUTING AND PROFILE
LINK SEAL
SECANT PILE RING
PENETRATION PER
STRUCTURAL
LINK SEAL INTO LIFT
STATION ENCLOSURE
M300
M300
M300
M300
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
20 MAY 2025
REPAIR LIFT
STATION B2212
022301
AECC511
5/22/2025 5:32:34 PM
MPC
MJA
MECHANICAL SITE
PLAN
M200M200 1/4" = 1'-0"
1 MECHANICAL SITE PLAN
A K
AF AL
T S
T A E O
49 TH
S
R E
G
ISTERED
PROFESS IONAL
ENG
IN
E
E R
23-MAY-2025
CONCRETE ANCHOR BASE PER
STRUCTURAL
LIFT STATION ANCHOR LEGS,
MINIMUM EIGHT EVENLY SPACED
AROUND PERIMETER
6" SWING CHECK VALVE, TYP 2
2" MAX
LIFT STATION LID
6" GATE VALVE, TYP 2
FIELD APPLIED 2" INSULATION WITH
WATERPROOF SURFACE COATING
3 WRAPS OF 6 MIL POLYETHYLENE
SHEETING
This is the start of the file's text. The full file is on GovTribe.