02.10.2026 Grayson Highlands Ranger Residence.pdf
PDF 5 MB Posted
- Solicitation number
- IFB-116621
- Issued by
- Goochland County, Virginia
About this file
This is a design and construction document set for the Virginia Department of Conservation and Recreation (DCR) for a new ranger residence at Grayson Highlands State Park located at 323 Camille Lane, Mouth of Wilson, Virginia 24363. The project involves the demolition of an existing 43-by-28-foot prefabricated modular residence (approximately 1,225 square feet) and replacement with a new single-story, three-bedroom ranger residence utilizing DCR Prototype #199-18366-001. The proposed residence will be 1,554 square feet with an 83-square-foot porch, classified as Use Group R-5 (single family dwelling) with Construction Type V-B (combustible/unprotected). The project includes site work consisting of approximately 9,511 square feet of disturbance, new utility connections to the existing well and septic systems, erosion and sediment control measures, asphalt parking area with 18 stalls, concrete sidewalks, exterior lighting, and an electric vehicle charging station. The construction documents reference the approved prototype drawings (Project Code 199-18366-000) and include detailed plans for civil site work, architectural layout, mechanical systems, plumbing, and electrical infrastructure.
The project incorporates specific design standards including 2021 Virginia Uniform Statewide Building Code compliance, a design snow load of 43 pounds per square foot, ultimate design wind speed of 110 miles per hour, and 36-inch minimum frost depth for footings. Mechanical systems include a Daikin heat pump (41,000 BTU/h capacity) with an air handling unit featuring variable speed ECM motor and electric supplemental heating. Utility connections require coordination with park maintenance staff and existing infrastructure, with water and sewer lines requiring minimum three-foot cover. The contractor is responsible for contacting Virginia 811 at least 72 hours prior to excavation and verifying utility locations. No lead or asbestos concerns are anticipated as the existing building was constructed after January 1, 1985. All erosion and sediment control measures must comply with the Virginia Stormwater Management Handbook, with silt fence installation as the initial grading step and temporary seeding to follow immediately after grading on the estimated 0.2-acre disturbance area.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET:
DATE:
NO. REVISION DATE
Fi le
: F :\D
C R
\G R
AY
SO
N H
IG
H
LA
N
D S
ST
AT
E
PA
R K\
N
EW
R
AN
G
ER
R
ES
ID
EN
C E\
SI
TE
D
ES
IG
N
\G R
AY
SO
N H
IG
H
LA
N
D S
R
AN
G
ER
R
ES
ID
EN
C E_
1_
7_
B2
D D
FB
.S
V$ .D
W G
DRAWN BY CHECKED BY
PROJECT NO.
02/10/2026
MPH MRL
TLG-2369
LA
N E
GR
OU
P en gi ne er in g ar ch ite ct ur e en vi ro nm en ta l
V A
LL
EY
S
TR
EE
T
N W
A
BI
N
G D
O N
, V A
Ph on e:
.2
.8 w w w .th el an eg ro up in c.
co m th e
VI
R
G
IN
IA
D
EP
AR
TM
EN
T O
F C
O N
SE
R
VA
TI
O N
R
EC
R
EA
TI
O N
R
AN
G
ER
R
ES
ID
EN
C E
G R
AY
SO
N H
IG
H
LA
N
D S
ST
AT
E
PA
R K
C
AM
IL
LE
L
AN
E M
O U
TH
O
F W
IL
SO
N , V
A
PC
: 1
-1
-0
C001
TI
TL
E
SH
EE
T
VIRGINIA DEPARTMENT OF
CONSERVATION AND RECREATION
RANGER RESIDENCE
GRAYSON HIGHLANDS STATE PARK
PC# 199-18366-000
FE%R8ARY 10� �0�6
VICINITY MAP
SCALE: 1" = 1000
PROPOSED RANGER RESIDENCE
323 CAMILLE LANE
MOUTH OF WILSON, VA 24363
HIGHLANDS PKWY
GRAYSONHIGHLANDS LN
GRAYSON HIGHLANDS
STATE PARK
H
AW
O R
C H
AR
D
LN
TUG LN
LITTLEHELTONCREEK
PREPARED BY:
The Lane Group, Inc.
310 Valley St. NW Abingdon, Virginia 24210
OWNER:
VIRGINIA DEPARTMENT OF
CONSERVATION AND RECREATION
600 E. MAIN STREET, 24TH FLOOR,
RICHMOND, VIRGINIA 23219
CONTACT: SCOTT GORDON
PH: 804.644.5202
STATE MAP
CHARLOTTESVILLE
RICHMOND
NORFOLK
ROANOKE
WYTHEVILLE
BRISTOL SOUTH
BOSTON
LYNCHBURG
FARMVILLE
MARTINSVILLE
WASHINGTON, D.C.
TENNESSEE
NORTH CAROLINA
WES
T V
IRG
INI
A
KENTUCKY
MARYLAND
WEST VIRGINIA
NORTH CAROLINA
CONSTRUCTION INFORMATION:
· GROSS AREA 3 BEDROOM RANGER RESIDENCE
BUILDING AREA: 1,554 SF & 83 SF PORCH COMBINED.
· PARKING (EACH) EXISTING
· BUILDING PURPOSE RANGER RESIDENCE
· USE GROUP R-5 (SINGLE FAMILY DWELLING)
· OCCUPANCY LOAD 8
· FLOOR LIVE LOAD 40 PSF
· NO. OF STORIES ONE
· CONSTRUCTION TYPE V-B, COMBUSTIBLE/UNPROTECTED
· FIRE PROTECTION RATING NONE
APPLICABLE CODES:
· 2021 VUSBC
· 2021 VRC
· ADA 90-TITLE II
· 2025 CPSM
PROJECT DESCRIPTION
THE VIRGINIA DEPARTMENT OF RECREATION AND
CONSERVATION INTENDS TO CONSTRUCT A RANGER
RESIDENCES FOR GRAYSON HIGHLAND STATE PARK.
THE RESIDENCE IS LOCATED AT THE EXISTING
RANGER RESIDENCE NEAR HAW ORCHARD LANE
AND CONSTRUCTION WILL CONSIST OF DEMOLITION
OF THE EXISTING RESIDENCE AND REPLACEMENT
WITH DCR PROTOTYPE #199-18366 001.
LEAD STATEMENT
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR
COATED BUILDING COMPONENTS HAS NOT BEEN
CONDUCTED BECAUSE THE BUILDING WAS CONSTRUCTED
AFTER JANUARY 1, 1985 AND THE OWNER HAS NO
KNOWLEDGE OF LEAD CONTAINING OR COATED BUILDING
COMPONENTS IN THE BUILDING. IT IS THE CONTRACTOR’S
RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA
OCCUPATIONAL SAFETY AND HEALTH (VOSH)
REGULATIONS AS THEY PERTAIN TO EMPLOYEE
EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED
BUILDING COMPONENTS SHALL BE RECYCLED TO THE
EXTENT POSSIBLE.
WELL NOTE
THE NEW RESIDENCE WILL BE CONNECTED TO AN
EXISTING WELL SYSTEM THAT SERVES OTHER BUILDINGS
IN THE PARK
SEPTIC NOTE
THE NEW RESIDENCE WILL BE RECONNECTING TO AN
EXISTING SEPTIC TANK AND DRAINFIELD
EXISTING DRAINFIELD LOCATION SHALL BE FLAGGED BY
THE GENERAL CONTRACTOR BEFORE CONSTRUCTION
BEGINS TO MAKE SURE NO EQUIPMENT IS DRIVEN OVVER
THE FIELD.
PROJECT
LOCATION
ASBESTOS STATEMENT
AN ASBESTOS INSPECTION WAS NOT PERFORMED
BECAUSE ALL PORTIONS OF THE EXISTING BUILDING THAT
MAY BE AFFECTED BY THE WORK WERE ORIGINALLY
CONSTRUCTED AFTER JANUARY 1, 1985.
DIG NOTICE
CONTACT VIRGINIA 811 AT 811, 1-800-552-7001, OR
HTTPS://WWW.VA811.COM NO LESS THAN 72 HOURS PRIOR
TO EXCAVATION AND DO NOT DISTURB THE SOIL UNTIL DIG
TICKET HAS BEEN PROCESSED.
RANGER RESIDENCE ADDRESS
323 CAMILLE LANE
MOUTH OF WILSON, VIRGINIA 24363
CIVIL PLAN SHEET INDEX:
PART 1
C001 TITLE SHEET
C002 CONSTRUCTION NOTES & LEGEND
C101 DEMOLITION PLAN
C201 SITE PLAN
C301 CONSTRUCTION DETAILS AND E&S DETAILS
A111 FLOOR PLAN
A211 BUILDING ELEVATIONS
M001 MECHANICAL GENERAL NOTES AND SCHEDULES
M101 MECHANICAL HVAC PLAN
P001 PLUMBING GENERAL NOTES
P101 PLUMBING WASTE PLAN
E001C ELECTRICAL LEGEND, SPECS AND GENERAL NOTES
E101C ELECTRICAL LIGHTING AND POWER
PART 2
VIRGINIA DCR RANGER RESIDENCE PROTOTYPE 199-18366-001
SEE SHEET G-001 OF THE ATTACHED PROTOTYPE DRAWING
SET FOR INDEX OF DRAWINGS
02.10.2026
NO. REVISION DATE
Fi le
: F :\D
C R
\G R
AY
SO
N H
IG
H
LA
N
D S
ST
AT
E
PA
R K\
N
EW
R
AN
G
ER
R
ES
ID
EN
C E\
SI
TE
D
ES
IG
N
\G R
AY
SO
N H
IG
H
LA
N
D S
R
AN
G
ER
R
ES
ID
EN
C E_
1_
7_
B2
D D
FB
.S
V$ .D
W G
DRAWN BY CHECKED BY
PROJECT NO.
02/10/2026
MPH MRL
TLG-2369
LA
N E
GR
OU
P en gi ne er in g ar ch ite ct ur e en vi ro nm en ta l
V A
LL
EY
S
TR
EE
T
N W
A
BI
N
G D
O N
, V A
Ph on e:
.2
.8 w w w .th el an eg ro up in c.
co m th e
VI
R
G
IN
IA
D
EP
AR
TM
EN
T O
F C
O N
SE
R
VA
TI
O N
R
EC
R
EA
TI
O N
R
AN
G
ER
R
ES
ID
EN
C
E G
R
AY
SO
N
H
IG
H
LA
N D
S
ST
AT
E
PA
R
K
C
AM
IL
LE
L
AN
E
M O
U
TH
O F
W
IL
SO
N
, V A
PC
: 1
-1
-0
C002
C O
N
ST
R U
C
TI
O N
N O
TE
S
LE
G
EN
D
GENERAL CONSTRUCTION NOTES:
1. THE EXACT LOCATION AND QUANTITY OF EXISTING UNDERGROUND UTILITIES IS UNKNOWN. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
CONTACT ALL EXISTING UTILITY OWNERS PRIOR TO START OF CONSTRUCTION AND HAVE UTILITIES MARKED IN THE FIELD.
2. ALL CONSTRUCTION SHALL CONFORM TO THE LANE GROUP PLANS AND SPECIFICATIONS.
3. ALL WATER AND SEWER CONSTRUCTION SHALL BE COORDINATED WITH THE GRAYSON HIGHLANDS STATE PARK MAINTENANCE STAFF.
4. ALL WATER AND SEWER LINES SHALL HAVE A MINIMUM OF THREE (3) FEET COVER.
5. ALL AREAS SHALL BE GRADED AS TO PRECLUDE THE PONDING OF WATER.
6. ALL AREAS DISTURBED BY CONSTRUCTION SHALL BE PAVED, GRAVELED, OR RESEEDED AS REQUIRED.
7. THE CONTRACTOR SHALL INSTALL AND MAINTAIN EROSION AND SEDIMENT CONTROL MEASURES AS NECESSARY TO PROTECT AND
REVEGETATE ALL AREAS DISTURBED BY CONSTRUCTION.
MANAGEMENT STRATEGIES:
1. THE SILT FENCE SHALL BE INSTALLED AS THE INITIAL SITE GRADING STEP.
2. TEMPORARY SEEDING AND/OR OTHER STABILIZATION WILL FOLLOW IMMEDIATELY AFTER GRADING.
3. AREAS WHICH ARE NOT REQUIRED TO BE DISTURBED SHALL REMAIN UNDISTURBED TO THE GREATEST EXTENT POSSIBLE.
GENERAL EROSION AND SEDIMENT CONTROL NOTES:
1. UNLESS OTHERWISE INDICATED, ALL VEGETATIVE AND STRUCTURAL EROSION AND SEDIMENT CONTROL PRACTICES WILL BE CONSTRUCTED AND
MAINTAINED ACCORDING TO MINIMUM STANDARDS AND SPECIFICATIONS OF THE VIRGINIA STORMWATER MANAGEMENT HANDBOOK.
2. THE PLAN APPROVING AUTHORITY MUST BE NOTIFIED ONE WEEK PRIOR TO THE PRECONSTRUCTION CONFERENCE, ONE WEEK PRIOR TO THE COMMENCEMENT OF LAND DISTURBING ACTIVITY, AND ONE WEEK PRIOR TO THE FINAL INSPECTION.
3. ALL EROSION AND SEDIMENT CONTROL MEASURES ARE TO BE PLACED PRIOR TO OR AS THE FIRST STEP OF LAND DISTURBANCE.
4. PRIOR TO COMMENCING LAND DISTURBING ACTIVITIES IN AREAS OTHER THAN INDICATED ON THESE PLANS (INCLUDING, BUT NOT LIMITED TO, OFF-SITE BORROW OR WASTE AREAS), THE CONTRACTOR SHALL SUBMIT A SUPPLEMENTARY EROSION AND SEDIMENT CONTROL PLAN AS
DETERMINED BY THE PLAN APPROVING AUTHORITY.
5. THE CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF ANY ADDITIONAL EROSION CONTROL MEASURES NECESSARY TO PREVENT EROSION AND
SEDIMENTATION AS DETERMINED BY THE PLAN APPROVING AUTHORITY.
6. THE ENGINEER, INSPECTOR, LOCAL BUILDING OFFICIAL, OR VDCR RESERVE THE RIGHT TO REQUIRE EROSION CONTROL MEASURES IN ADDITION TO
THOSE SHOWN IF CONDITIONS WARRANT IN ORDER TO ADDRESS EROSION.
7. ALL DISTURBED AREAS ARE TO DRAIN TO APPROVED SEDIMENT CONTROL MEASURES AT ALL TIMES DURING LAND DISTURBING ACTIVITIES AND
DURING SITE DEVELOPMENT UNTIL FINAL STABILIZATION IS ACHIEVED.
8. THE TOTAL AREA OF DISTURBANCE IS ESTIMATED TO BE 0.2 ACRES.
9. THE CONTRACTOR SHALL INSPECT ALL EROSION CONTROL MEASURES NO LESS THAN EVERY 7 CALENDAR DAYS AND AFTER EACH RUNOFF-PRODUCING RAINFALL EVENT PRODUCING 1/2 INCH OF PRECIPITATION OR GREATER. ANY NECESSARY REPAIRS OR CLEANUP TO MAINTAIN
THE EFFECTIVENESS OF THE EROSION CONTROL DEVICES SHALL BE MADE IMMEDIATELY.
10. ALL DISTURBED AND UNPAVED AREAS ARE TO BE SEEDED AND MULCHED.
11. ALL SLOPES DISTURBED IN EXCESS OF 2% SHALL BE MULCHED WITH EROSION CONTROL MATTING, PROPERLY ANCHORED.
12. FOLLOWING PROJECT COMPLETION AND STABILIZATION, ALL TEMPORARY EROSION CONTROL MEASURES SHALL BE CLEANED UP/REMOVED.
13. A PERMANENT VEGETATIVE COVER SHALL BE ESTABLISHED ON ALL DENUDED AREAS NOT OTHERWISE PERMANENTLY STABILIZED. PERMANENT VEGETATION SHALL NOT BE CONSIDERED ESTABLISHED UNTIL A GROUND COVER IS ACHIEVED THAT, IN THE OPINION OF THE LOCAL PROGRAM ADMINISTRATOR OR HIS DESIGNATED AGENT, IS UNIFORM, MATURE ENOUGH TO SURVIVE, AND WILL INHIBIT EROSION.
14. THE CONTRACTOR SHALL CLEAN SEDIMENT FROM ANY SEDIMENT TRAPPING DEVICE WHEN SEDIMENT BUILDUP REACHES THE CLEANOUT ELEVATION.
15. REFER TO THE VESCH FOR INSTALLATION REQUIREMENTS FOR ANY MEASURE(S) REQUIRED THAT ARE NOT DETAILED ON THIS PLAN SHEET.
16. SOIL STABILIZATION SHALL BE ACHIEVED ON ANY AREA OF THE SITE WHERE LAND-DISTURBING ACTIVITIES HAVE TEMPORARILY OR PERMANENTLY
CEASED ACCORDING TO THE FOLLOWING SCHEDULE:
A. ALL PERIMETER DIKES, SWALES, DITCHES, PERIMETER SLOPES AND ALL SLOPES STEEPER THAN THREE (3) HORIZONTAL TO VERTICAL (3:1) SHALL
BE PROVIDED TEMPORARY OR PERMANENT STABILIZATION WITH GROUND COVER AS SOON AS PRACTICABLE BUT IN ANY EVENT WITHIN 7
CALENDAR DAYS FROM THE LAST LAND-DISTURBING ACTIVITY.
B. ALL OTHER DISTURBED AREAS SHALL BE PROVIDED TEMPORARY OR PERMANENT STABILIZATION WITH GROUND COVER AS SOON AS PRACTICABLE BUT IN ANY EVENT WITHIN 14 CALENDAR DAYS FROM THE LAST LAND-DISTURBING ACTIVITY.
LEGEND
PROPOSED GRADING CONTOUR & ELEVATION
SURVEY HUB & TRAVERSE
VEGETATION
STREAM
FENCE
EXISTING PARKING AREA
EXISTING SIDEWALK
PROPOSED SIDEWALK
PROPOSED STRUCTURE
PROPOSED DEMOLITION
EXISTING PROPERTY LINE
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
EXISTING UTILITY POLE
EROSION CONTROL MEASURES LEGEND
LOD LIMITS OF DISTURBANCE
3.02 STONE CONSTRUCTION ENTRANCE
3.05 SILT FENCE
PS
MU
TS 3.31 TEMPORARY SEEDING
3.32 PERMANENT SEEDING
3.35 MULCHINGSF SF
CE
SNOW AND WIND LOAD NOTES:
UNLESS NOTED OTHERWISE, ALL DESIGN LOADS ARE BASED ON THE FOLLOWING
DATA IN ACCORDANCE WITH THE 2021 VRC.
2. RISK CATEGORY II
3. LIVE LOADS
FLOOR = 40 PSF
PORCHES = 40 PSF
RAILINGS = 50 PLF OR 200 LB
4. ROOF LIVE LOAD
Lr= 30 PSF
5. SNOW LOADS
DESIGN SNOW LOAD = 43 PSF
6. WIND LOADS
ULTIMATE DESIGN WIND SPEED, Vult = 110 MPH ALLOWABLE STRESS DESIGN WIND SPEED, Vasd = 85 MPH
EXPOSURE CATEGORY D
INTERNAL PRESSURE COEFFICIENT, Gcpi = +/- 0.18
7. SEISMIC LOADS
SEISMIC IMPORTANCE FACTOR, Ie = 1.0
MAPPED SPECTRAL RESPONSE ACCELERATIONS
SS = 0.263
S1 = 0.080
SITE CLASS D
SPECTRAL REPONSE COEFFICIENTS
SDS = 0.279
SD1 = 0.129
SEISMIC DESIGN CATEGORY B
SEISMIC-FORCE RESISTING SYSTEMS:
LIGHT FRAME WOOD WALLS WITH STRUCTURAL PANELS, R = 6.5
SEISMIC RESPONSE COEFFICIENT, Cs = 0.063
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
8. FROST DEPTH
BOTTOM OF FOOTING BELOW GRADE = 36" MINIMUM
9. SOIL LOAD BEARING
THE MINIMUM DESIGN LOAD BEARING VALUE OF THE SOILS = 2000 PSF
LO
D
LO
D
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
EX. RESIDENCE
TO BE DEMOLISHED
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
EX. 120 SF PREFABRICATED SHED
HAS BEEN RELOCATED BY PARK
SF
EX. 24 SY PATH TO BE DEMOLISHED
EX. 8 SY PATH TO BE DEMOLISHED
EX. TREE
TO REMAIN
CE
HAND
AUGER 1
HAND
AUGER 2
HAND
AUGER 3
HAND
AUGER 4
SHEET:
DATE:
NO. REVISION DATE
Fi le
: F :\D
C R
\G R
AY
SO
N H
IG
H
LA
N
D S
ST
AT
E
PA
R K\
N
EW
R
AN
G
ER
R
ES
ID
EN
C E\
SI
TE
D
ES
IG
N
\G R
AY
SO
N H
IG
H
LA
N
D S
R
AN
G
ER
R
ES
ID
EN
C E_
1_
7_
B2
D D
FB
.S
V$ .D
W G
DRAWN BY CHECKED BY
PROJECT NO.
02/10/2026
MPH MRL
TLG-2369
LA
N E
GR
OU
P en gi ne er in g ar ch ite ct ur e en vi ro nm en ta l
V A
LL
EY
S
TR
EE
T
N W
A
BI
N
G D
O N
, V A
Ph on e:
.2
.8 w w w .th el an eg ro up in c.
co m th e
VI
R
G
IN
IA
D
EP
AR
TM
EN
T O
F C
O N
SE
R
VA
TI
O N
R
EC
R
EA
TI
G
ER
R
ES
ID
EN
C
E G
R
AY
SO
N
H
IG
H
LA
N D
S
ST
AT
E
PA
R
K
C
AM
IL
LE
L
AN
E
M O
U
TH
O F
W
IL
SO
N
, V A
PC
: 1
-1
-0
SCALE IN FEET
010 10 20 40
C101
D
EM
O
LI
TI
O
N
PL
AN
EX. RESIDENCE TO BE
DEMOLISHED
EX. RESIDENCE
TO BE DEMOLISHED AND
EX. 120 SF PREFABRICATED
SHED RELOCATED BY PARK
1. THE INTENT OF THIS DRAWING IS TO INDICATE THE
COMPLETE REMOVAL OF THE EXISTING "DOUBLE WIDE"
MOBILE HOME.
2. IT IS NOT EXPECTED THAT HAZARDOUS MATERIALS WILL
BE ENCOUNTERED. IF SUSPECT MATERIALS ARE
UNCOVERED, STOP WORK AND NOTIFY THE CONTRACT
OFFICER. REMOVAL OF HAZARDOUS MATERIALS WILL BE
ACCOMPLISHED UNDER A SEPARATE CONTRACT.
3. PROVIDE A SILT FENCE AT THE DRIP LINE OF THE
EXISTING TREE, WEST OF THE EXISTING STRUCTURE, TO
PROTECT THE TREE'S ROOT SYSTEM FROM
UNNECESSARY COMPACTION.
4. REMOVE THE EXISTING ELECTRICAL SERVICE BACK TO
THE EXISTING SERVICE POLE.
5. DISCONNECT THE EXISTING WATER SERVICE AND
PROTECT THE SERVICE LINE FOR REUSE ON THE NEW
RESIDENCE.
6. DISCONNECT THE EXISTING SANITARY SEWER AND
PROTECT THE DISCHARGE LINE FOR REUSE ON THE NEW
RESIDENCE.
7. COMPLETELY REMOVE THE EXISTING 43'X28' PRE-FAB
MODULAR RESIDENCE (APPROX. 1225 S.F.) . REMOVAL
INCLUDES PORCHES, STOOPS, FOUNDATION WALLS,
FOOTINGS, ETC. TO A DEPTH OF 3-FEET. REMOVE AND
LEGALLY DISPOSE OF ALL DEBRIS. BURNING OR BURIAL
OF MATERIAL ON THE SITE IS NOT ALLOWED.
8. REMOVE CONCRETE PATHWAYS, AS INDICATED.
9. PREPARE THE SITE FOR A NEW RESIDENTIAL STRUCTURE
AND NEW UTILITY STRUCTURE TO BE CONSTRUCTED ON
THE PREMISES.
10. ON COMPLETION OF DEMOLITION, LEAVE SITE IN CLEAN
CONDITIONS AND READY FOR NEW CONSTRUCTION.
DEMOLITION PLAN NOTES
LO
D
LO
D
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
PROP. SHED
PROP. 3' WIDE
CONCRETE SIDEWALK
EX. GRAVEL
ENTRANCE
EX. DRAINFIELD SITE
TO REMAIN
EX. SEPTIC TANK
TO REMAIN
PORCH
LIMITS OF DISTURBANCE
9,511 SQ FT.
EX. POWER POLE
AND TRANSFORMER
PROP. 33 SY SIDEWALK TO
EX. GRAVEL PARKING AREA
PROP. 13 SY SIDEWALK TO
EX. PARKING AREA
EX. PARKING AREA
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
PROP. HVAC
W/ 4'X4' CONC. PAD
PROP. GENERATOR CONC. PAD
PROP. PROPANE TANK CONC. PAD
PROPOSEDRANGER RESIDENCEAPPROVED PROTOTYPE:PC#199-18366-000FFE: 3553.0
TS MUPS
PROP . BUILDING PAD
ELEV: 3549.00 PROVIDE
5% GRADE AWAY FROM
BUILDING PAD FOR MIN.
10' TO MAINTAIN POSITIVE
DRAINAGE
CE
HAND
AUGER 1
HAND
AUGER 2
HAND
AUGER 3
HAND
AUGER 4
NEW ELECTRICAL CONNECTION
TO BE CONNECTED TO EXISTING
TRANSFORMER
RAMP
DECK
18'
PARKINGSTALLS
12'
PROP. POLE MOUNTED LIGHT
PROP. ASPHALT
PARKING AREA
PROP. ADA ACCESSIBILITY
SIGNAGE AND MARKING
WITH EV CHARGER
PROP. 3 SY SIDEWALK TO
EX. PARKING AREA
U G
E U
G E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
U G
E U
G E
U G
E
UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
U G
E U
G E
U G
E U
G E
U G
E
UGE
UGE
PROP. CLEANOUT (TYP.)
PROP. 52 LF 4" SANITARY SEWER LINE
@ 1.92% SLOPE
SEPTIC TANK INV: 3546.00
4" SANITARY SEWER CONNECTION
TO PROPOSED PLUMBING INV: 3547.00
SHEET:
DATE:
NO. REVISION DATE
Fi le
: F :\D
C R
\G R
AY
SO
N H
IG
H
LA
N
D S
ST
AT
E
PA
R K\
N
EW
R
AN
G
ER
R
ES
ID
EN
C E\
SI
TE
D
ES
IG
N
\G R
AY
SO
N H
IG
H
LA
N
D S
R
AN
G
ER
R
ES
ID
EN
C E_
1_
7_
B2
D D
FB
.S
V$ .D
W G
DRAWN BY CHECKED BY
PROJECT NO.
02/10/2026
MPH MRL
TLG-2369
LA
N E
GR
OU
P en gi ne er in g ar ch ite ct ur e en vi ro nm en ta l
V A
LL
EY
S
TR
EE
T
N W
A
BI
N
G D
O N
, V A
Ph on e:
.2
.8 w w w .th el an eg ro up in c.
co m th e
VI
R
G
IN
IA
D
EP
AR
TM
EN
T O
F C
O N
SE
R
VA
TI
O N
R
EC
R
EA
TI
O N
R
AN
G
ER
R
ES
ID
EN
C E
G R
AY
SO
N H
IG
H
LA
N
D S
ST
AT
E
PA
R K
C
AM
IL
LE
L
AN
E M
O U
TH
O
F W
IL
SO
N , V
A
PC
: 1
-1
-0
SCALE IN FEET
010 10 20 40
C201
SI
TE
P
LA
N
5% FOR 10'
5%
FO
R 10'
5% F
O R
0'
5% FOR 10'
NO. REVISION DATE
Fi le
: F :\D
C R
\G R
AY
SO
N H
IG
H
LA
N
D S
ST
AT
E
PA
R K\
N
EW
R
AN
G
ER
R
ES
ID
EN
C E\
SI
TE
D
ES
IG
N
\G R
AY
SO
N H
IG
H
LA
N
D S
R
AN
G
ER
R
ES
ID
EN
C E_
1_
7_
B2
D D
FB
.S
V$ .D
W G
DRAWN BY CHECKED BY
PROJECT NO.
02/10/2026
MPH MRL
TLG-2369
LA
N E
GR
OU
P en gi ne er in g ar ch ite ct ur e en vi ro nm en ta l
V A
LL
EY
S
TR
EE
T
N W
A
BI
N
G D
O N
, V A
Ph on e:
.2
.8 w w w .th el an eg ro up in c.
co m th e
VI
R
G
IN
IA
D
EP
AR
TM
EN
T O
F C
O N
SE
R
VA
TI
O N
R
EC
R
EA
TI
G
ER
R
ES
ID
EN
C
E G
R
AY
SO
N
H
IG
H
LA
N D
S
ST
AT
E
PA
R
K
C
AM
IL
LE
L
AN
E
M O
U
TH
O F
W
IL
SO
N
, V A
PC
: 1
-1
-0
C301
C O
N
ST
R U
C
TI
O N
AN
D
E &S
D
ET
AI
LS
SHEET FLOW INSTALLATION
(PERSPECTIVE VIEW)
POINTS A SHOULD BE HIGHER THAN POINT B.
DRAINAGEWAY INSTALLATION
(FRONT ELEVATION)
IT INTO THE TRENCH.
A
FLOWFLOW
B
FLOW
3. STAPLE FILTER MATERIAL
TO STAKES AND EXTEND
1. SET THE STAKES.
FLOW
6'MAX.
A
3'MAX.
2. EXCAVATE A 4"X 4" TRENCH
UPSLOPE ALONG THE LINE OF
4. BACKFILL AND COMPACT
THE EXCAVATED SOIL.
STAKES.
4"
SILT FENCE
VDCR STD 3.05
NOT TO SCALE
TEMPORARY SEEDING
VESCH STD. 3.31
NOT TO SCALE
(LOLIUM MULTI-FLORUM)
SPECIFICATION 02710
TEMPORARY SEEDING SCHEDULE
SEEDINGS MADE IN FALL FOR WINTER COVER AND DURING HOT AND
DRY SUMMER MONTHS SHALL BE MULCHED IMMEDIATELY UPON
COMPLETION OF SEED APPLICATION WITH TACKIFIED STRAW, IN
ACCORDANCE WITH VA E&S STD 3.35.
MAY 1-AUG 31 50(SETARIA ITALICA)
GERMAN MILLET
ACCEPTABLE TEMPORARY SEEDING PLANT MATERIALS
PLANTING DATES
SEPT 1-FEB 15
FEB 16-APR 20
50-100
50/50 MIX OF
ANNUAL RYEGRASS
(LOLIUM MULTI-FLORUM)
SPECIES
(LBS/ACRE)
RATE
60-100
(SECALE CEREALE)
ANNUAL RYEGRASS
CEREAL (WINTER) RYE
PERMANENT SEEDING
VESCH STD. 3.32
NOT TO SCALE
GENERAL SLOPE (3:1 OR LESS)
SPECIFICATION 02710
PERMANENT SEEDING SCHEDULE
AUGUST 16 THROUGH SEPTEMBER,OCTOBER
SEEDINGS TO BE MULCHED AT THE RATE OF 2 TONS PER
ACRE WITH TACKIFIED STRAW, IMMEDIATELY UPON COMPLETION
OF SEED APPLICATION, IN ACCORDANCE W/ VA E&S STD 3.35.
LIME AND FERTILIZER NEEDS SHALL BE DETERMINED BY SOIL TESTS.
RED TOP GRASS
WHITE CLOVER
KENTUCKY 31 FESCUE
KENTUCKY BLUEGRASS
SEASONAL NURSE CROP
MARCH, APRIL THROUGH MAY 15
MAY 16 THROUGH AUGUST 15
NOVEMBER THROUGH FEBRUARY
SEASONAL NURSE CROP
PER ACRE
TOTAL LBS
200 LBS.
10 LBS.
30 LBS.
10 LBS.
2 LBS.
252 LBS.
ANNUAL RYE
ANNUAL RYE
WINTER RYE
FOXTAIL MILLET
THE SLABS BETWEEN EXPANSION
JOINTS SHALL BE DIVIDED INTO
5' SECTIONS BY GROOVED OR
SAWN JOINTS APPROX.
1/8" WIDE & 1.5" DEEP
A 1/2" EXPANSION JOINT SHALL BE
REQUIRED IN THE CONCRETE
SIDEWALK AT 50' INTERVALS - CURB
EXPANSION JOINTS SHALL COINCIDE
WITH SIDEWALK EXPANSION JOINTS
A 1/2" EXPANSION JOINT SHALL BE
REQUIRED IN THE CONCRETE
SIDEWALK AT 50' INTERVALS - CURB
EXPANSION JOINTS SHALL COINCIDE
WITH SIDEWALK EXPANSION JOINTS
SIDEWALK REPLACEMENT DETAIL
SCALE: 1/2" = 1'-0"
EXPANSION
JOINT
GROOVED OR
SAW JOISTS (TYP)
PROP. 4" THICK SIDEWALK -
4000psi REINFORCED CONCRETE
W/ W2.9xW2.9 WW FABRIC
PLACED 2" FROM BOTTOM
SECTION VIEW
PLAN VIEW
THE SLABS BETWEEN EXPANSION
JOINTS SHALL BE DIVIDED INTO
5' SECTIONS BY GROOVED OR
SAWN JOINTS APPROX.
1/8" WIDE & 1.5" DEEP
GROOVED OR
SAW JOINTS (TYP)
1/2" EXPANSION
JOINT MATERIAL
1/2" EXPANSION
JOINT MATERIAL
3'
WIDTH
SIDEWALK REPLACEMENT NOTES:
1. DETAIL REFLECTS INSTALLATION OF 4" THICK CONCRETE SIDEWALK.
2. TOP OF SIDEWALK TO COINCIDE WITH TOP OF ADJACENT PROPOSED CG-6 CURB AND GUTTER.
5' (TYP)
WIDTH BETWEEN
EXPANSION JOINTS
PROP. 4" THICK SIDEWALK -
4000psi REINFORCED CONCRETE W/ W2.9xW2.9 WW FABRIC
PLACED 2" FROM BOTTOM
PROVIDE ADDITIONAL
SOIL FILL MATERIAL AS
NEEDED TO REPAIR
DISTURBED WORK AREA
& TRANSITION TO NEW
SIDEWALK -
REVEGETATE
1'-0" (TYP) OR
WIDTH AS REQ'D
5' (TYP)
WIDTH BETWEEN
EXPANSION JOINTS
5' (TYP)
WIDTH BETWEEN
EXPANSION JOINTS
PROP. 6" DEPTH COMPACTED
VDOT 21B STONE BENEATH
ALL SIDEWALKS
M
AX
S
LO
PE
1%
CONSTRUCTION ENTRANCE
VESCH STD. 3.02
NOT TO SCALE
STONE CONSTRUCTION ENTRANCE
SECTION B-B
SECTION A-A
PLAN VIEW
SIDE ELEVATION
SOURCE: ADAPTED from 1983 Maryland Standards for Soil erosion and Sediment Control, and Va. DSWC Plate 3.02-1
CE
12"
**FOR PIPE LESS THAN 12" THE TRENCH
WIDTH MAY BE 36" MAXIMUM
(FOR PIPES LESS THAN 12",
6" MIN. BOTH SIDES OF PIPE)
(FOR PIPES LESS THAN 12",
6" MIN. BOTH SIDES OF PIPE)
FINAL BACKFILL
- COMPACTED
INITIAL HAND
TAMPED
BACKFILL
(CLASS I OR II)
4" MIN. STONE
OR SAND
BEDDING
UTILITY LINE
MARKING TAPE
INITIAL HAND TAMPED
BACKFILL (CLASS III -
SUITABLE SOIL, SAND,
OR CRUSHED STONE)
FINAL BACKFILL
- COMPACTED
36" MIN.
COVER
SHAPE TRENCH
BOTTOM TO
MATCH PIPE
UTILITY LINE
MARKING TAPE
36" MIN. COVER
4" MIN.
(CLASS I OR II)
O.D./2
O.D. O.D.
O.D./2
CLASS C - FOR D.I. PIPECLASS B - FOR PVC PIPE
O.D. + 12" MIN.**
12"
O.D. + 12" MIN.**
UTILITY LINE BEDDING DETAILS
PAVEMENT TYPICAL SECTION
N.T.S.
SUBGRADE SHALL BE PROOF-ROLLED PRIOR
TO PLACING AGGREGATE BASE- ALL FILL SHALL
BE COMPACTED TO 95% OF STANDARD
PROCTOR ASTM 698
ASPHALT SURFACE COURSE
(2.0") - VDOT SM-9.5 A
AGGREGATE BASE COURSE 6"
COMPACTED VDOT 21B
COMPACTED TO 100% OF
STANDARD PROCTOR PER ASTM 698
ASPHALT BASE COURSE
(4.0") - VDOT BM - 25.0
ELECTRIC VEHICLE CHARGING STATION
(EVCS) DETAIL
N.T.S.
ANCHOR BASE POLE FOUNDATION DETAIL
N.T.S.
COVERED
PORCH
(REAR)
NEW
RANGER
RESIDENCE
(REFERENCE
PROTOTYPE
DRAWINGS)
RAMP DOWN
1"/FT. MAX.
CONTRACTOR TO
VERIFY GRADE AND
COORDINATE
LENGTH OF RAMP
ON-SITE.
20'-0"
6' -0
/4
3'
-1 0"
12" MIN.
" C
LR
M
IN
12" MIN.
1'-10"
1' -6
4'
-6
/4
11'-8 1/2" 22'-9 3/4"
11'-8 1/2"
WP
WPWPWP
WP
WP WP
B-3B-3
B-
B-
B-
B-
B-3B-3
1'-10" 3'-10 3/8" 3'-10 7/8" 3'-10 7/8"
WP
WP
WP
WP
WP
WP
WP
WP
3 3 3
WP
WP
6' -0
/4
3'
-1 0"
5'-0"5'-0"5'-0"5'-0"
WP
B-3
BEAMMARK
B-1
BEAM SCHEDULE
NOTES
(3) 2x10 PT FLOOR GIRDER
B-2 (2) 2x10 --
B-3
B-4
(2) 2x8 PT
2x12 PT
PORCH
RAMP
NOTES:
1. FASTEN ALL BEAM PLIES TOGETHER
USING 2 ROWS OF 10d NAILS AT 8" OC
(STAGGERED).
2. USE 1/2" PLYWOOD SPACERS AS REQD.
5/
8"
CBSQ 44 STAND-OFF
BASE
1' DIA. CONC. FORM
TUBE, 3' DEEP FILLED
W/ 3,000 PSI CONC.
1/4"=1'-0" 0' 4' 12'1' 8'
SHEET:
DATE:
NO. REVISION DATE
Fi le
: J :\2
G R
AY
SO
N H
IG
H
LA
N
D S
D C
R \2
.4 A
R C
H \C
AD
\A
\A -1
F
LO
O
R P
LA
N
.D W
G
DRAWN BY CHECKED BY
PROJECT NO.
VA
. D
EP
T.
O F
C O
N
SE
R
VA
TI
O
N A
N D
R
EC
R
EA
TI
O
N R
AN
G
ER
R
ES
ID
EN
C
ES
G
R
AY
SO
N
H
IG
H
LA
N D
S
ST
AT
E
PA
R
K
PC
9-
6-
02/10/2026
ZRB DCV
24039
LA
N E
GR
OU
P en gi ne er in g ar ch ite ct ur e en vi ro nm en ta l
V A
LL
EY
S
TR
EE
T
N W
A
BI
N
G D
O N
, V A
Ph on e:
.2
.8 w w w .th el an eg ro up in c.
co m A
BI
N
G D
O N
B
IG
S
TO
N
E G
A P
G
A
LA
X th e
Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011 540.342.6001
SPECTRUMPC.COM
2/10/26
1. REFERENCE CIVIL DRAWINGS FOR GRADING ELEVATIONS. VERIFY ACTUAL SITE ELEVATIONS AND NOTIFY THE ARCHITECT IF RAMP AND STAIR DIMENSIONS WILL CHANGE, PRIOR TO CONSTRUCTION.
2. THE PURPOSE OF THIS DRAWING IS FOR LAYOUT OF STAIRS SPECIFIC TO THIS SITE. REFERENCE RANGER RESIDENCE PROTOTYPE DRAWINGS AND PROJECT MANUAL FOR TYPICAL STAIR ELEVATIONS, SECTIONS AND DETAILS AND SPECIFICATIONS. PROTOTYPE DETAILS FOR STAIRS PROVIDE GENERAL CONSTRUCTION DETAILS AND REQUIREMENTS, ADJUST DIMENSIONALLY AS NECESSARY FOR EACH
SITE SPECIFIC CONDITIONS.
3. NOTE THAT THIS RANGER RESIDENCE PLAN ORIENTATION DIFFERS FROM THE PROTOTYPE TO SUIT THIS SITE REQUIREMENT. ALL BUILDING DIMENSIONS AND FLOOR PLAN RELATIONSHIPS REMAIN THE SAME. CONTRACTOR TO TAKE INTO ACCOUNT THE ORIENTATION OF ALL THE PROTOTYPE DRAWINGS.
REFER TO SHEET C401.
4. LOCATION OF CRAWL SPACE ACCESS & HVAC CONDENSER MAY VARY FROM PROTOTYPE.
GENERAL NOTES
SCALE: 1/4" = 1'-0"
STAIR & RAMP FRAMING PLAN
NOTE: REFER TO TYPICAL PILE AND
FLOOR FRAMING DETAILS ON
SHEET S-501 OF PROTOTYPE SET
A-111
FL
O
O R
P
LA
N
1. 2x8 DECK JOISTS AT 16" OC MAX., GALV. SIMPSON LU28 JOISTS HANGER EACH END.
2. PT 2x12 STAIR STRINGERS
3. PT 2x12 RAMP JOISTS AT 16" OC MAX.
4. GALV. SIMPSON LB212AZ TOP FLANGE JOISTS HANGER, 2x12 RAMP JOIST TO BEAM
5. PT 4x4 GUARDRAIL POST SANDWICHED BETWEEN BEAM (TYP.)
6. SIMPSON HUS28-2 HANGER, BEAM TO FLOOR RIM BOARD
5. GALVANIZED JOIST HANGERS BY SIMPSON, CLARK-DIETRICH, OR MITEK.
PROVIDE HANGERS EQUIVALENT TO SIMPSON MODEL NUMBERS LISTED AS BASIS OF DESIGN.
KEYNOTES
FINISH SCHEDULE
ROOM
FLOOR BASE
WALLS CEILING
NUMBERED NOTES, REMARKS
NUMBER NAME MATERIAL FINISH MATERIAL HEIGHT
100 FOYER HARDWOOD WOOD GPDW PNT-1 GPDW, PNT-1 8'-1"
101 GREAT ROOM HARDWOOD WOOD GPDW, WD PNT-1 GPDW, PNT-1 8'-1" 1
102 BATH 1 CERAMIC TILE CT GPDW PNT-1 GPDW, PNT-2 8'-1" 2
103 HALL VINYL PLANK WOOD GPDW, WD PNT-1 GPDW, PNT-1 8'-1" 1
104 BEDROOM 3 VINYL PLANK WOOD GPDW PNT-1 GPDW, PNT-1 8'-1"
105 BEDROOM 2 VINYL PLANK WOOD GPDW PNT-1 GPDW, PNT-1 8'-1"
106 MASTER BEDROOM VINYL PLANK WOOD GPDW PNT-1 GPDW, PNT-1 8'-1"
107 BATH 2 CERAMIC TILE CT GPDW, CT PNT-1 GPDW, PNT-2 8'-1" 2, 3
108 UTILITY VINYL PLANK WOOD GPDW PNT-1 GPDW, PNT-1 8'-1"
109 KITCHEN VINYL PLANK WOOD GPDW, WD PNT-1 GPDW, PNT-1 8'-1" 1
- CLOSET VINYL PLANK WOOD GPDW PNT-1 GPDW, PNT-1 8'-1"
- LINEN CLOSET VINYL PLANK WOOD GPDW PNT-1 GPDW, PNT-1 8'-1"
- PANTRY HARDWOOD WOOD GPDW PNT-1 GPDW, PNT-1 8'-1"
NUMBERED NOTES:
1. WALLS TO HAVE WOOD CHAIR RAIL AND WOOD WAINSCOT. SEAL WAINSCOT
BOARDS ON ALL SIDES PRIOR TO INSTALLATION.
2. PROVIDE MR-GPDW AND SEMI-GLOSS PAINT AT WALLS AND CEILINGS.
3. PROVIDE CERAMIC TILE AT WALLS OF SHOWER.
GENERAL NOTES:
1. ALL INTERIOR WOOD TRIM TO BE PAINTED.
2. CEILING PAINT SHALL BE FLAT SHEEN AND WALL PAINT SHALL BE SATIN
SHEEN, UNLESS OTHERWISE NOTED.
3. DOORS, WINDOWS, AND TRIM SHALL BE SEMI-GLOSS SHEEN.
4. PROVIDE ADA COMPLIANT TRANSITION BETWEEN ALL FLOOR FINISHES.
SCALE: 1/4" = 1'-0"
FLOOR PLAN
SCALE: 3/4" = 1'-0"
TYP. CONCRETE FORM TUBE FOOTING DETAIL
12" MIN.
B
2' -0
2' -0
8' -1
/2
2' -0
FINISH
FLOOR
TRUSS
BEARING
BA
AAAA
1'-6" X 2'-0" ALUMINUM
ATTIC VENT W/ INSECT
SCREEN W/ 1X FC TRIM
ALUM FLASHING
ROUND CHIMNEY
CAP & FLASHING
FC BOARD &
BATTEN SIDING
PVC RAKE ASPHALT SHINGLE
ROOF
VENTED ASPHALT
SHINGLE CAP
ASPHALT SHINGLE
ROOF
VINYL RAISED
PANEL SHUTTERS
(3 PAIR)
4" BRICK OR
STONE VENEER
ALUM CHASE PAN
AND FLASHING
PREFIN ALUM
FLASHING ROUND CHIMNEY
CAP & FLASHING
ALUM CHASE PAN
AND FLASHING
BOARD AND
BATTEN BEYOND
(NOT SHOWN FOR
CLARITY)
1'-6" X 2'-0" PREFIN
ALUMINUM ATTIC VENT
W/ INSECT SCREEN W/
1X FC TRIM
FC BOARD &
BATTEN SIDING
PVC RAKE
BOARD AND
BATTEN BEYOND
(NOT SHOWN
FOR CLARITY)
24" X 24" PREFIN ALUM
INSULATED ACCESS DOOR
CONT SHINGLE
RIDGE CAP OVER
RIDGE VENT
ASPHALT SHINGLE
ROOF
8' -1
/2
FINISH
FLOOR
TRUSS
BEARING
8' -1
/2
FINISH
FLOOR
TRUSS
BEARING
8' -1
/2
FINISH
FLOOR
TRUSS
BEARING
12"x12" BRICK
VENEER PIER
FC BOARD &
BATTEN SIDING
4" BRICK OR
STONE VENEER
PT WD DECK W/ PT
WD RAIL ASSEMBLY,
PICKETS AT 5" OC
ASPHALT
SHINGLE
ROOF
CRAWLSPACE
FLOOR
4' -0
M
IN
CRAWLSPACE
FLOOR
4' -0
M
IN
HORIZ JOINT
HORIZ JOINT
VENTED ASPHALT
SHINGLE CAP
A A A
PVC FASCIA
PVC FASCIA
PT WD DECK W/ PT
WD RAIL ASSEMBLY,
PICKETS AT 5" OC
PVC FASCIA
PVC FASCIA
PVC
FASCIA
PT WD DECK W/ PT
WD RAIL ASSEMBLY,
PICKETS AT 5" OC
PVC FASCIA
PVC FASCIA
CRAWLSPACE
FLOOR
4' -0
M
IN
CRAWLSPACE
FLOOR
4' -0
M
IN
VENTED ASPHALT
SHINGLE CAP
FLASHING
3/4" x 3-1/2" FIBER
CEMENT TRIM
WEATHER
BARRIER
4'-0"
1'-0"1'-0" 1'-0" 1'-0"
2x4 BLOCKING
SPACED 2'-0" OC,
VERT
GAP BETWEEN
PANELS W/ SLNT
3/4" x 2-1/2" FIBER
CEMENT BATTENS
FIBER CEMENT
SIDING PANELS
3/4" x 3-1/2" FIBER
CEMENT TRIM
WALL
SHEATHING
FIBER CEMENT
SIDING PANELS
WEATHER
BARRIER
3/4" x 2-1/2" FIBER
CEMENT BATTENS
2" M
IN
FL
SH
G
CONT ALUM FLSHG
CUT WEATHER BARRIER
AT FLASHING AND TURN
OUT OVER TOP OF FLASHING
DO NOT SEAL JOINT
WALL SHEATHING
2x4 BLOCKING
SPACED 2'-0"
OC, VERT
2x4 WALL
BLOCKING AT JOINT
SIDING OUTSIDE CORNERSIDING INSIDE CORNER
TYPICAL SIDING
HORIZONTAL JOINT
A-211
BU
IL
D
IN
G
EL
EV
AT
IO
N
S
SCALE: 1/4" = 1'-0"
LEFT ELEVATIONA
A-101 A-201
1/4"=1'-0" 0' 4' 12'1' 8'
SCALE: 1/4" = 1'-0"
FRONT ELEVATIONB
A-101 A-201
SCALE: 1/4" = 1'-0"
RIGHT ELEVATIONC
A-101 A-201 SCALE: 1/4" = 1'-0"
REAR ELEVATIOND
A-101 A-201
1. RAMP IS NOT SHOWN FOR CLARIFY OF DRAWINGS. RAMP IS FOR
ACCESSIBLE RESIDENCES ONLY.
2. LOCATION OF CRAWLSPACE ACCESS SHALL VARY BASED ON SITE
CONDITIONS. SEE SITE ADAPT DRAWINGS AND S-101.
3. COORDINATE SIDING PANEL JOINTS WITH BATTENS AND HORIZONTAL JOINT.
SEE STANDARD SIDING DETAILS ON A-201.
4. FOUNDATION VENEER (BRICK OR STONE) SHALL BE DETERMINED BY
AGENCY.
5. PAINT ALL SIDING PT-1 (SATIN SHEEN). PAINT ALL SOFFIT, FASCIA, RAKE, AND
TRIM PT-2 (SEMI-GLOSS SHEEN).
GENERAL NOTES
SHEET:
DATE:
NO. REVISION DATE
Fi le
: J :\2
G R
AY
SO
N H
IG
H
LA
N
D S
D C
R \2
.4 A
R C
H \C
AD
\A
\A -2
B
U
IL
D
IN
G E
LE
VA
TI
O
N S.
D W
G
DRAWN BY CHECKED BY
PROJECT NO.
VA
. D
EP
T.
O F
C O
N
SE
R
VA
TI
O
N A
N D
R
EC
R
EA
TI
O
N R
AN
G
ER
R
ES
ID
EN
C
ES
G
R
AY
SO
N
H
IG
H
LA
N D
S
ST
AT
E
PA
R
K
PC
9-
6-
02/10/2026
ZRB DCV
24039
LA
N E
GR
OU
P en gi ne er in g ar ch ite ct ur e en vi ro nm en ta l
V A
LL
EY
S
TR
EE
T
N W
A
BI
N
G D
O N
, V A
Ph on e:
.2
.8 w w w .th el an eg ro up in c.
co m A
BI
N
G D
O N
B
IG
S
TO
N
E G
A P
G
A
LA
X th e
Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011 540.342.6001
SPECTRUMPC.COM
2/10/26
AIR HANDLING UNIT - ELECTRIC HEAT
MARK
FAN ELECTRICAL CONNECTION COOLING HEATING
MANUFACTURER MODEL REMARKSSUPPLY
AIRFLOW (CFM)
OUTSIDE
AIR CFM
EXT. STATIC
PRESSURE
(IN. W.C)
V PH F MCA MOCP
RATED
CAPACITY
(BTU/H)
ENTERING
DRY BULB
ENTERING
WET BULB
RATED
CAPACITY
(BTU/H).
ENTERING
DRY BULB
ELECTRIC
HEATER (KW)
HEATER MODEL
AHU-1 1,400 135 0.90 230 1 60 6.5 15 41,000 78.3 65.2 42000 63.1 5 HKTSD5X1 DAIKIN DFVE60DP1300 ALL
1. SUPPLY FAN SHALL OPERATE CONTINUOUSLY DURING OCCUPIED MODE.
2. AHU MOTOR SHALL BE VARIABLE SPEED ECM TYPE.
3. PROVIDE AIR HANDLING UNITS WITH INTEGRAL ELECTRICAL DISCONNECTING MEANS.
4. PROVIDE CIRCUIT BREAKER DISCONNECT FOR HEAT KIT.
5. SUPPLEMENTAL AUXILIARY HEATING SHALL BE PROGRAMMED AS TO NOT TURN ON , EXCEPT DURING DEFROST AND EMERGENCY HEATING, UNLESS THE OUTSIDE AIR TEMPERATURE IS BELOW 40 °F.
6. IF THE SPACE TEMPERATURE AS SENSED BY THE THERMOSTAT RISES ABOVE 78 °F, ADJUSTABLE, THE UNIT SHALL ENTER COOLING MODE. THE UNIT SHALL RUN UNTIL THE SPACE SET POINT IS SATISFIED.
7. IF THE SPACE TEMPERATURE AS SENSED BY THE THERMOSTAT FALLS BELOW 68 °F, ADJUSTABLE, THE UNIT SHALL ENTER HEATING MODE. THE UNIT SHALL RUN UNTIL THE SPACE SET POINT IS SATISFIED.
1. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK, AIR DEVICES, DAMPERS, AND DUCT MOUNTED HOT WATER COILS WHERE APPLICABLE. DIRTY FILTER AND UNIT CASING MUST BE ADDED TO EXTERNAL STATIC PRESSURE TO OBTAIN TOTAL PRESSURE LOSS. INCREASE HORSEPOWER AS REQUIRED TO MEET YOUR TOTAL PRESSURE LOSS. COORDINATE WITH ELECTRICIAN.
2. MAINTAIN MINIMUM CLEARANCE FOR COIL PULL AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM
ELECTRICAL CLEARANCE AS REQUIRED BY NEC.
3. UNIT TO BE INSTALLED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
4. REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S REQUIREMENTS.
5. COOLING AND HEATING CAPACITY BASED ON AHRI CONDITIONS.
6. PROVIDE AIR HANDLER UNITS WITH CONDENSATE OVER FLOW SWITCH.
7. UNIT SHALL BE CONTROLLED BY 7-DAY PROGRAMMABLE WIRED THERMOSTAT COORDINATE LOCATION WITH OWNER.
REMARKS:
GENERAL NOTES:
HEAT PUMP
MARK
NOM. TOTAL
CAPACITY
(BTU/H)
MINIMUM
EER2 / SEER2 /
HSPF2
ELECTRICAL CONNECTION RELATED
UNIT
MARK
MANUFACTURER MODEL REMARKS
V PH F MCA MOCP
HP-1 41,000 10.0 / 17.5 / 8.8 230 1 60 37.5 40.0 AHU-1 DAIKIN DH7VSA4210A ALL
1. PROVIDE WITH LOW AMBIENT CONTROL DOWN TO 20°F.
2. REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S REQUIREMENTS.
3. PROVIDE WITH COIL GUARD.
4. PROVIDE UNITS WITH NAME PLATES TO REFERENCE CORRESPONDING AIR HANDLER UNIT.
1. MAINTAIN MINIMUM CLEARANCE FOR CONDENSER AIR FLOW AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM ELECTRICAL CLEARANCE AS REQUIRED BY NEC.
GENERAL NOTES:
REMARKS:
F ile
C
U
S E
R S
\W Y
A T
T .S
M
IT
H E
R S
\D E
S K
T O
P \T
B X
D C
R .D
W G salasobrien.com
Project No:
Roanoke
119 Norfolk Avenue, Suite 310 Roanoke, Virginia 24011
2450-71138-00
540-952-9651
SPECTRUMPC.COM
L A N E
Plaza Suite 1
10 Church Avenue, SE
Roanoke, VA 24011
540.342.6001
SHEET:
DATE:
NO. REVISION DATE
DRAWN BY CHECKED BY
PROJECT NO.
24039
G R
O U
P e n g in e e ri n g a rc h it e c tu re e n v ir o n m e n ta l
V
A
LL
E Y
S
TR
E E T
N W
A
B
IN
G D
O N
V
A
P h o n e
.2
.8 w w .t h e la n e g ro u p in c .c o m
A B
IN
G
D O
N
B
IG
S
TO
N E G
A P
G A
LA
X th e
V A
D
E P
T O
F C
O N
S E
R V
A T
IO
N
A N
D R
E C
R E
A T
IO
N
R A
N G
E R
R E
S
ID
E N
C E
S
G R
A Y
S O
N H
IG
H
L A
N D
S S
T A
T E
P A
R K
P C
-1
-0
M001
02/10/2026
MDA SSL
02/10/2026
BASIS OF DESIGN
THE MANUFACTURER AND MODEL NUMBER LISTED IN THE DRAWINGS OR SPECIFICATIONS ARE THE BASIS OF DESIGN.
WHEN PROVIDING EQUIPMENT THAT IS NOT THE BASIS OF DESIGN, THE CONTRACTOR SHALL PROVIDE AN ITEMIZED LIST OF ALL DEVIATIONS FROM THE INFORMATION DETAILED IN BOTH THE SPECIFICATION SECTION AND SCHEDULE. ADDITIONALLY, THE EQUIPMENT MUST MEET THE PHYSICAL CONSTRAINTS OF ROOM INCLUDING COORDINATION WITH OTHER TRADES AND ALL EQUIPMENT CLEARANCES, INCLUDING OTHER TRADES. FINALLY, THE CONTRACTOR SHALL PROVIDE AT THE CONTRACTOR'S COST ANY SCOPE INCREASE AND DEDUCTIONS BASED ON THE NON-BASIS OF DESIGN EQUIPMENT FOR
THE FOLLOWING MINIMUM ITEMS:
• ELECTRICAL MODIFICATIONS, INCLUDING WIRING, CONDUIT, DISCONNECTS, OVERCURRENT PROTECTION, PANELS, ETC.
• STRUCTURAL MODIFICATIONS.
• CIVIL MODIFICATIONS.
• PLUMBING MODIFICATIONS.
• DUCT AND PIPE CONNECTIONS OR ARRANGEMENTS.
• SPACE HEATING AND COOLING REQUIREMENTS.
• EXHAUST OR VENTILATION MODIFICATIONS.
• VIBRATION ISOLATION REQUIREMENTS.
• CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH THE EQUIPMENT MANUFACTURER FOR ANY CHANGES TO
THE REFRIGERANTS REQUIRED PER NEW EPA GUIDELINES. CONTRACTOR SHALL COORDINATE WITH OTHER
DISCIPLINES FOR CHANGES IN EQUIPMENT SIZE OR ELECTRICAL REQUIREMENTS.
1. INSTRUCT THE OWNER IN THE PROPER OPERATION AND MAINTENANCE OF THE
MECHANICAL SYSTEMS UNTIL THE OWNER IS FULLY PREPARED TO OPERATE AND MAINTAIN
THE MECHANICAL SYSTEM. HOWEVER, LENGTH OF INSTRUCTION TIME SHALL BE LIMITED
TO ONE DAY.
2. EQUIPMENT, MATERIALS AND LABOR REQUIRED BY THESE CONTRACT DRAWINGS SHALL BE
GUARANTEED TO BE FREE FROM DEFECTIVE MATERIALS OR WORKMANSHIP FOR ONE YEAR
AFTER FINAL ACCEPTANCE OF THE PROJECT UNLESS SPECIFIED OTHERWISE. DEFECTIVE
MATERIALS OR WORKMANSHIP OCCURRING DURING THIS PERIOD SHALL BE CORRECTED AT NO
ADDITIONAL COST.
3. GENERAL CONTRACTOR TO VERIFY THE FINAL LOCATION OF ALL THERMOSTATS,
TEMPERATURE SENSORS, PANELS AND CONTROL INSTRUMENTS WITH THE ARCHITECT AND
OWNER PRIOR TO ROUGH-IN.
4. CEILING GRID AND OTHER ITEMS SHALL NOT BE SUPPORTED FROM OR IN CONTACT WITH
MECHANICAL EQUIPMENT. CONDUIT, WIRING, PIPING AND SUPPORTS SHALL NOT BE
LOCATED IN FRONT OF FAN COIL ACCESS PANELS.
5. MATERIAL AND INSTALLATION SHALL COMPLY WITH LOCAL CODES, APPLICABLE
PROVISIONS OF LATEST EDITION OF NATIONAL FIRE PROTECTION ASSOCIATION, LOCAL
UTILITY REGULATIONS AND GOVERNMENTAL DEPARTMENTS HAVING JURISDICTION.
6. MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL ALL SUPPORTS REQUIRED TO
MOUNT MECHANICAL EQUIPMENT, PIPING AND DUCTWORK. EQUIPMENT SHALL BE
INSTALLED ACCORDING TO THE MANUFACTURER'S SPECIFICATIONS AND
RECOMMENDATIONS.
7. PROVIDE FLEXIBLE DUCT CONNECTIONS BETWEEN THE SUPPLY AND RETURN DUCTS FROM
ALL AIR UNITS AND AT BUILDING EXPANSION JOINTS. FLEXIBLE CONNECTIONS SHALL BE
WEATHERTIGHT WHEN EXPOSED.
MECHANICAL GENERAL NOTES:
Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011 540.342.6001
TO ILETCIM ARRO NK-31644
TO
ILET
CIM
ARRO
N K-31644
AHU-1
HP-1
F ile
C
U
S E
R S
\W Y
A T
T .S
M
IT
H E
R S
\D E
S K
T O
P \T
B X
D C
R .D
W G salasobrien.com
Project No:
Roanoke
119 Norfolk Avenue, Suite 310 Roanoke, Virginia 24011
2450-71138-00
540-952-9651
SPECTRUMPC.COM
L A N E
Plaza Suite 1
10 Church Avenue, SE
Roanoke, VA 24011
540.342.6001
SHEET:
DATE:
NO. REVISION DATE
DRAWN BY CHECKED BY
PROJECT NO.
24039
G R
O U
P e n g in e e ri n g a rc h it e c tu re e n v ir o n m e n ta l
V
A
LL
E Y
S
TR
E E T
N W
A
B
IN
G D
O N
V
A
P h o n e
.2
.8 w .t h e la n e g ro u p in c .c o m
A B
IN
G
D O
N
B
IG
S
TO
N E G
A P
G A
LA
X th e
V A
D
E P
T O
F C
O N
S E
R V
A T
IO
N
A N
D R
E C
R E
A T
IO
N
R A
N G
E R
R E
S
ID
E N
C E
S
G R
A Y
S O
N H
IG
H
L A
N D
S S
T A
T E
P A
R K
P C
-1
-0
M101
02/10/2026
MDA SSL
02/10/2026
Scale: 1/4" = 1'-0"1
MECHANICAL FLOOR PLAN
MECHANICAL NOTES:
1. THE MECHANICAL DESIGN IS INCLUDED IN THE DEB APPROVED
PROTOTYPE PROJECT (PROJECT CODE 199-18366-000). ANY
ALTERATIONS TO THE PROTOTYPE SCOPE OF WORK SHALL BE
APPROVED BY THE PROTOTYPE ENGINEER OF RECORD. REFER TO
BOLDED EQUIPMENT FOR ADAPTATION MODIFICATIONS REQUIRED TO
SUPPORT THE PROTOTYPE BUILDING.
Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011
1. ALL WORK, METHODS AND INSTALLATIONS INVOLVED IN THE PLUMBING DESIGN SHALL BE IN
ACCORDANCE WITH THE CITY BUILDING CODE, INSPECTION REGULATIONS AND ALL OTHER
OFFICIALS HAVING JURISDICTION.
2. ALL SANITARY PIPING 3" AND LARGER ROUTED AT 1/8" SLOPE PER FOOT UNLESS OTHERWISE
NOTED. ALL PIPE LESS THAN 3" SHALL BE ROUTED AT 1/4" SLOPE PER FOOT.
3. EACH VENT SHALL TERMINATE VERTICALLY NOT LESS THAN 6" ABOVE ROOF, MAINTAIN MINIMUM 10'-0" DISTANCE BETWEEN VENT TERMINALS THROUGH ROOF AND ALL FRESH AIR INTAKES, AND A
MINIMUM 5'-0" FROM ANY EXTERIOR WALL.
4. CONTRACTOR TO FIELD VERIFY AS NECESSARY THE EXACT ROUTING AND SIZES OF ALL PIPING.
5. PROVIDE A TWO-WAY CLEANOUT AT CIVIL'S POINT OF CONNECTION.
6. CONTRACTOR SHALL COORDINATE ROUTING OF PIPING BELOW SLAB WITH COLUMN FOOTINGS, GRADE BEAMS, UNDERGROUND PLUMBING AND ELECTRICAL UTILITIES, AND OTHER SUB-SURFACE
BUILDING ELEMENTS.
7. CONTRACTOR SHALL COORDINATE ROUTING OF PIPING IN CEILING SPACES WITH MECHANICAL AND
ELECTRICAL EQUIPMENT, DUCTWORK AND CONDUIT. SHOULD A CONFLICT OCCUR THE
CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO INSTALLING AN ALTERNATE
PIPING PLAN.
8. COORDINATE ALL FIXTURE AND EQUIPMENT LOCATIONS AND CONNECTION REQUIREMENTS WITH
LATEST ARCHITECTURAL DRAWINGS AND SPECIFICATIONS PRIOR TO ANY ROUGH-INS.
9. DO NOT ROUGH-IN FROM THESE DRAWINGS. REFER TO LATEST ARCHITECTURAL DRAWINGS FOR
DIMENSIONED LOCATIONS.
10. PRIOR TO BEGINNING CONSTRUCTION, COORDINATE BUILDING BACKFLOW PREVENTION
REQUIREMENTS WITH THE LOCAL AUTHORITY HAVING JURISDICTION AND PROVIDE AS DIRECTED.
PLUMBING GENERAL NOTES
PRESSURE REDUCING VALVE (PRV)
EXISTING
NEW
DELTA CHANGE SYMBOL
NEW CONNECTION
(E)
(N)
BRANCH CONNECTION OUT OF BOTTOM
BRANCH CONNECTION OUT OF TOP
WYE & 1/8TH BEND BRANCH CONNECTION
BRANCH CONNECTION OUT OF SIDE
WYE BRANCH CONNECTION
HOT WATER RETURN PIPING (HWR)
REDUCED PRESSURE BACKFLOW PREVENTER (RPBFP)
EXTERIOR CLEANOUT WITH 18"x18"x4" CONCRETE PAD (ECO)
TWO-WAY CLEANOUT (PROVIDE 18"x24"x4" CONCRETE PAD OUTSIDE)
CLEANOUT (WALL OR CEILING) (CO)
PIPING UP -OR- PIPING UP & DOWN
COMPRESSED AIR PIPING (A)
AUTOMATIC SPRINKLER PIPING (AS)
FIRE PROTECTION PIPING (F)
CHILLED DRINKING WATER PIPING (CDW)
SOFT COLD WATER PIPING (SCW)
UNION
FLOOR CLEANOUT (FCO)
RISE OR DROP PIPING
CAP ON END OF PIPE
REDUCER OR INCREASER
STRAINER
PIPING DOWN
ECCENTRIC REDUCER
HORIZONTAL SWING CHECK
FLOW DIRECTIONAL ARROW
SOLENOID VALVE (SV)
BALANCING VALVE (BV)
BALL VALVE
SHUT-OFF VALVE
GAS VENT PIPING (GV)
NATURAL GAS PIPING (G)
TRAP PRIMER LINE (TP)
G
A
AS
GV
CDW
SCW
F
TP
CONDENSATE - INDIRECT DRAIN PIPING (D)
SANITARY OR WASTE PIPING BELOW GRADE (SAN)
SANITARY OR WASTE PIPING ABOVE GRADE (SAN)
CONDENSATE DRAIN PIPING (CD)
GREASE WASTE PIPING BELOW GRADE (GW)
GREASE WASTE PIPING (GW)
ACID WASTE PIPING BELOW GRADE (AW)
SUB-SOIL DRAIN OR FOOTING DRAIN (SSD)
HOT WATER PIPING (HW)
COLD WATER PIPING (CW)
VENT PIPING (V)
ACID WASTE PIPING (AW)
PUMPED WASTE (PW)
D
AW
PW
CD
STORM DRAIN PIPING (SD)
DESCRIPTION
GW
SSD
SD
SYMBOLS
GW
VENT THRU ROOFVTR
BELOW FINISHED FLOORB.F.F.
ABOVE FINISHED FLOORA.F.F.
PLUMBING PIPING LEGEND
AW
REFER TO KEYED NOTE0
DEMOLISH TO THIS POINT
TEPID WATER PIPING (TW)
FILTERED WATER PIPING (FW)
TW
FW
PLUMBING SPECIFICATIONS
PLUMBING FIXTURES AND FIXTURES CARRIERS:
A. ACCEPTABLE MANUFACTURERS:
A. CLEANOUTS: ZURN, J.R. SMITH, JOSAM, WADE, WATTS/ANCON, MIFAB
B. INSTALLATION:
1. INSTALLATION SHALL BE ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
2. PROVIDE NECESSARY STOPS, VALVE, TRAPS, UNIONS, VENTS, COLD WATER, HOT WATER, SANITARY, ETC. FOR A COMPLETE INSTALLATION.
3. REMOVE PIPING AND SERVICES ROUGHED-IN INCORRECTLY AND INSTALL CORRECTLY, WITHOUT COST.
4. EXPOSED PIPING, FITTINGS AND APPURTENANCES SHALL BE CHROME-PLATED BRASS.
5. PROVIDE ISOLATION VALVES IN DOMESTIC WATER LINES TO ISOLATE ALL EQUIPMENT, RESTROOMS, HOSEBIBS, AND WHERE SHOWN ON DRAWINGS.
PLUMBING ALTERATIONS
A. INSPECT AND SERVICE EXISTING EQUIPMENT, FIXTURES AND MATERIALS THAT ARE TO REMAIN OR TO BE
REUSED.
B. DISPOSAL OF EQUIPMENT, FIXTURES, MATERIALS, OR HOUSEKEEPING PADS TO BE ABANDONED. PRIOR TO DISPOSAL, THE CONTRACTOR SHALL VERIFY WITH THE OWNER WHAT IS TO BE SALVAGED BY THE OWNER
AND WHAT IS TO BECOME THE PROPERTY OF THE CONTRACTOR.
C. HANDLING OF EQUIPMENT AND MATERIALS TO BE REMOVED.
D. INSPECTION: EXISTING MATERIALS AND EQUIPMENT INDICATED ON THE DRAWINGS OR IN THE SPECIFICATIONS TO BE REUSED SHALL BE INSPECTED FOR DAMAGE OR MISSING PARTS. CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER, IN WRITING ACCORDINGLY. IF USING MATERIALS SPECIFIED OR
SHOWN ON THE DRAWING VOIDS OR DIMINISHES THE WARRANTY OR OPERATION OF REMAINING
EQUIPMENT OR SYSTEMS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER, IN WRITING.
DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION, AND WHEN AVAILABLE, EXISTING
RECORD DOCUMENTS. REPORT DISCREPANCIES TO ARCHITECT BEFORE DISTURBING EXISTING
INSTALLATION, AND IMMEDIATELY AFTER SUCH DISCREPANCIES ARE DISCOVERED.
E. APPLICATION: EXISTING MATERIALS AND EQUIPMENT INDICATED ON THE DRAWINGS OR IN THE SPECIFICATIONS TO BE REUSED SHALL BE CLEANED AND RECONDITIONED, INCLUDING CLEANING OF PIPING SYSTEMS AND HVAC COILS PRIOR TO INSTALLATION AND REUSE. MATERIAL AND EQUIPMENT REMOVED THAT IS NOT TO BE SALVAGED FOR OWNER'S USE OR FOR REUSE ON THE PROJECT SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND BE REMOVED FROM THE SITE. MATERIAL OR EQUIPMENT SALVAGED FOR OWNER'S USE SHALL BE CAREFULLY HANDLED AND STORED WHERE DIRECTED BY THE OWNER OR THE ARCHITECT/ENGINEER. RELOCATE MATERIAL AND / OR EQUIPMENT AS DIRECTED BY OWNER.
MATERIALS AND EQUIPMENT NOT INDICATED TO BE REMOVED OR ABANDONED SHALL BE RECONNECTED TO THE NEW SYSTEM. PRIOR TO START OF CONSTRUCTION, CONTRACTOR SHALL WALK AREAS TO BE RENOVATED WITH OWNER TO IDENTIFY AND DOCUMENT ITEMS TO BE SALVAGED FOR OWNER'S USE.
F. SEQUENCE AND SCHEDULE: COORDINATE UTILITY SERVICE OUTAGES WITH UTILITY COMPANY, ARCHITECT AND OWNER. REMOVE CONCRETE HOUSEKEEPING PAD WHERE MATERIALS OR EQUIPMENT HAVE BEEN
REMOVED.
EARTHWORK
A. EXCAVATE AND BACKFILL FOR PIPE TRENCHES FOR UNDERGROUND PIPING, AND EXCAVATE FOR
STRUCTURES INSTALLED AS PART OF MECHANICAL WORK.
B. REMOVE EXCESS EXCAVATION MATERIAL OR MATERIAL UNSUITABLE FOR BACKFILL. EXCESS MATERIAL CAN BE SPREAD ON GRADE, OR SHALL BE REMOVED FROM SITE AS DIRECTED BY THE OWNER/ARCHITECT.
GENERAL
A. PERFORM WORK IN ACCORDANCE WITH APPLICABLE STATUTES, ORDINANCES, CODES AND REGULATIONS
OF GOVERNMENTAL AUTHORITIES HAVING JURISDICTION.
B. OBTAIN ALL PERMITS REQUIRED.
C. CONTRACT DRAWINGS ARE DIAGRAMMATIC ONLY AND DO NOT GIVE FULLY DIMENSIONED LOCATIONS OF
VARIOUS ELEMENTS OF WORK. DETERMINE EXACT LOCATIONS FROM FIELD MEASUREMENTS.
D. GUARANTEE WORK FOR 1 YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION OF THE PROJECT.
DURING THAT PERIOD MAKE GOOD ANY FAULTS OR IMPERFECTIONS THAT MAY ARISE DUE TO DEFECTS OR OMISSIONS IN MATERIAL, EQUIPMENT OR WORKMANSHIP. AT THE OWNER'S OPTION, REPLACEMENT OF
FAILED PARTS OR EQUIPMENT SHALL BE PROVIDED.
E. PROVIDE FINISHES TO MATCH APPROVED SAMPLES. ALL EXPOSED FINISHES SHALL BE APPROVED BY THE
ARCHITECT. SUBMIT COLOR SAMPLES AS REQUIRED.
F. PROVIDE EQUIPMENT HOUSEKEEPING PADS UNDER ALL FLOOR MOUNTED AND GROUND MOUNTED PLUMBING EQUIPMENT, AND AS SHOWN ON THE DRAWINGS. CONCRETE PADS ARE TO BE 4" THICK UNLESS
OTHERWISE INDICATED ON THE DRAWINGS.
G. PROVIDE NAMEPLATES WITH 1/2" HIGH LETTERS AND FASTENED WITH EPOXY OR SCREWS.
H. MAINTAIN QUALITY CONTROL OVER SUPERVISION, SUBCONTRACTORS, SUPPLIERS, MANUFACTURERS, PRODUCTS, SERVICES, SITE CONDITIONS AND WORKMANSHIP TO PRODUCE WORK IN ACCORDANCE WITH
CONTRACT DOCUMENTS.
I. COMPLY WITH INDUSTRY STANDARDS EXCEPT WHEN MORE RESTRICTIVE TOLERANCES OR SPECIFIED
REQUIREMENTS INDICATE MORE RIGID STANDARDS OR MORE PRECISE WORKMANSHIP.
J. PERFORM WORK BY PERSONS QUALIFIED TO PRODUCE WORKMANSHIP OF SPECIFIED QUALITY.
K. SECURE PRODUCTS IN PLACE WITH POSITIVE ANCHORAGE DEVICES DESIGNED AND SIZED TO WITHSTAND STRESSES, VIBRATION, AND RACKING. UNDER NO CONDITIONS SHALL MATERIAL OR EQUIPMENT BE
SUSPENDED FROM STRUCTURAL BRIDGING
L. COMPLY WITH INSTRUCTIONS IN FULL DETAIL, INCLUDING EACH STEP IN SEQUENCE. SHOULD
INSTRUCTION CONFLICT WITH CONTRACT DOCUMENTS, REQUEST CLARIFICATION FROM
ARCHITECT/ENGINEER BEFORE PROCESSING.
DOMESTIC WATER PIPING AND APPURTENANCES
A. FURNISH AND INSTALL DOMESTIC HOT AND COLD WATER PIPING.
B. BELOW SLAB ON GRADE PIPING. FURNISH ASTM B 88 AND ANSI/NSF STANDARD 61 COLD DRAWN, TYPE K COPPER WATER TUBE. RUN CONTINUOUS WITH NO JOINTS UNDER THE FLOOR SLAB. PROVIDE COPPER PIPE
CORROSION PROTECTION AS SPECIFIED IN THIS SECTION.
C. ABOVE SLAB PIPING: PEX SYSTEM MUST BE LISTED ASTM F876/F877. TUBING SHALL BE LISTED PEX 5006 FOR CHLORINE RESISTANCE FOR CONTINUOUS USAGE UP TO 140°F. ALL TUBING INSTALLED IN RETURN AIR PLENUMS SHALL BE LISTED ASTM E84. THE LISTING MAY BE FOR THE TUBING ITSELF OR FOR THE TUBING INCLUDING INSULATION TO ACHIEVE THE LISTING. THE FITTINGS SHALL BE OF THE SAME MANUFACTURER AS THE TUBING AND THE INSTALLATION INSTRUCTIONS OF THE MANUFACTURER SHALL BE STRICTLY ADHERED
TO.
D. WATER HAMMER ARRESTORS: PROVIDE PISTON TYPE HYDRAULIC ENGINEERED/MANUFACTURED WATER HAMMER ARRESTORS IN COLD AND HOT WATER SUPPLY LINES IN CHASES OR WALLS TO EACH FIXTURE BRANCH OR BATTERY OF FIXTURES SERVING QUICK CLOSING VALVES OF ELECTRICAL, PNEUMATIC, SPRING LOADED TYPE, OR QUICK HAND CLOSURE VALVES ON FIXTURE TRIM. PROVIDE WATER HAMMER ARRESTORS AT THE END OF THE BRANCH LINE BETWEEN THE LAST TWO FIXTURES SERVED. PROVIDE PRECISION PLUMBING PRODUCTS, INC., OR EQUAL. SIZE UNITS ACCORDING TO WATER HAMMER ARRESTOR'S STANDARD
PDI WH-201; REFER TO SCHEDULE ON DRAWINGS.
E. AIR CHAMBERS: PROVIDE A MINIMUM 18-INCH LONG AIR CHAMBER, OF THE SAME SIZE AND CONNECTING PIPE MATERIAL AT EACH SINGLE LAVATORY, SINK, DRINKING FOUNTAIN OR FIXTURE THAT DOES NOT HAVE A QUICK-CLOSING VALVE OR ELECTRICAL, PNEUMATIC, SPRING LOADED TYPE, OR FLUSH VALVE. AIR CHAMBERS TO BE USED FOR REMOTE FIXTURES AND NOT MIXED WITH WATER HAMMER ARRESTORS AT
GROUP TOILETS.
F. TESTING: TEST UNDER A COLD WATER HYDROSTATIC PRESSURE OF NOT LESS THAN 50 PSI. THIS PRESSURE SHALL BE HELD FOR NOT LESS THAN 15 MINUTES AND CAREFULLY CHECK FOR LEAKS. REPAIR LEAKS AND RETEST SYSTEM UNTIL PROVEN WATERTIGHT. USE ONLY POTABLE WATER FOR THE TEST. PERFORM THE
TEST BEFORE FIXTURES, FAUCETS, TRIM OR FINAL CONNECTIONS ARE MADE TO EQUIPMENT.
G. COPPER PIPE CORROSION PROTECTION: CORROSION PROTECT COPPER TUBE PIPING SYSTEMS: IN THE
BUILDING SLAB.
H. COVER COPPER TUBING PIPING SYSTEM WITH: "TAPECOAT" TC PRIMER. EXTEND THE CORROSION
PROTECTION 2 INCHES ABOVE CONCRETE SLAB ON GRADE.
I. STERILIZE THE WATER SYSTEM WITH SOLUTION CONTAINING NOT LESS THAN 50PPM AVAILABLE CHLORINE.
ALLOW CHLORINATING SOLUTION TO REMAIN IN SYSTEM FOR PERIOD OF 8 HOURS (MINIMUM). HAVE VALVES AND FAUCETS OPENED AND CLOSED SEVERAL TIMES DURING THE PERIOD. AFTER STERILIZATION, FLUSH THE SOLUTION FROM THE SYSTEM WITH CLEAN WATER UNTIL RESIDUAL CHLORINE CONTENT IS LESS THAN 0.2
PARTS PER MILLION.
SOIL, WASTE AND SANITARY DRAIN PIPING, VENT PIPING AND APPURTENANCES
A. ABOVE SLAB PIPING: SCHEDULE 40 PVC PLASTIC PIPE AND DWV FITTINGS WITH SOLVENT WELDED JOINTS.
PIPE AND FITTINGS SHALL CONFORM TO ASTM D 1784-82.
B. BELOW SLAB ON GRADE PIPING: SCHEDULE 40 PVC PLASTIC PIPE AND DWV FITTINGS. SOLVENT WELDED DWV JOINTS SHALL CONFORM TO IAPMO INSTALLATION STANDARD IS-9. PIPE AND FITTINGS SHALL CONFORM TO
ASTM D 1784, ASTM D 1785, ASTM D 2665, ASTM D 3311 AND NPS STANDARD 14 & 61.
C. BELOW SLAB ON GRADE PIPING FOR GREASY WASTE: SCHEDULE 40 PVC PLASTIC PIPE AND DWV FITTINGS WITH SOLVENT WELDED DWV JOINTS SHALL CONFORM TO ASTM D3311 AND BE PRODUCED TO DIMENSIONS SPECIFIED IN ASTM F2818, NSF INTERNATIONAL, UPC, IAPMO IGS 210 AND INTERNATIONAL PLUMBING CODE.
SOLVENT CEMENT, HEAVY BODY; MUSTARD YELLOW COLOR, AS TESTED BY ASTM F2618/ASTM F493.
MANUFACTURER - SPEARS.
D. VENT PIPE AND FITTINGS: ABOVE SLAB PIPING. PROVIDE SCHEDULE 40 PVC PLASTIC PIPE AND DWV FITTINGS
WITH SOLVENT WELDED JOINTS. PIPE AND FITTINGS SHALL CONFORM TO ASTM D 1784-82.
E. BELOW SLAB ON GRADE PIPING: SAME AS DRAIN PIPE AND FITTINGS LISTED ABOVE.
F. TESTING: BELOW SLAB ON GRADE AND ALL FLOORS IN MULTI-STORY BUILDINGS: TEST PIPE BELOW SLAB ON GRADE BEFORE BACKFILLING AND CONNECTING TO CITY SEWERS. MAINTAIN NOT LESS THAN 10 FOOT OF
HYDROSTATIC HEAD FOR 1 HOUR WITHOUT A LEAK.
G. RODDING SEWERS: ALL SANITARY SOIL AND WASTE LINES, BOTH IN THE BUILDING AND OUT, SHALL BE RODDED OUT AND FLUSHED OUT AFTER COMPLETION OF CONSTRUCTION AND PRIOR TO FINISH FLOOR BEING INSTALLED. ALL WORK MUST BE COMPLETED PRIOR TO SUBSTANTIAL COMPLETION. ALL FLOOR DRAINS AND
CLEANOUT LOCATIONS MUST BE INCLUDED IN THIS WORK.
H. PIPING TO BE INSULATED:
a. MAKE-UP WATER
b. HORIZONTAL SANITARY DRAIN PIPING THAT RECEIVES CONDENSATE.
c. EXPOSED TO VIEW STORM DRAINAGE SYSTEM INCLUDING ROOF AND OVERFLOW DRAIN BODIES, VERTICAL
PIPING FROM DRAIN BODY AND ALL HORIZONTAL RAIN LEADERS TO FIRST ELBOW TURNING.
F ile
C
U
S E
R S
\W Y
A T
T .S
M
IT
H E
R S
\D E
S K
T O
P \T
B X
D C
R .D
W G salasobrien.com
Project No:
Roanoke
119 Norfolk Avenue, Suite 310 Roanoke, Virginia 24011
2450-71138-00
540-952-9651
SPECTRUMPC.COM
L A N E
Plaza Suite 1
10 Church Avenue, SE
Roanoke, VA 24011
540.342.6001
SHEET:
DATE:
NO. REVISION DATE
DRAWN BY CHECKED BY
PROJECT NO.
24039
G R
O U
P e n g in e e ri n g a rc h it e c tu re e n v ir o n m e n ta l
V
A
LL
E Y
S
TR
E E T
N W
A
B
IN
G D
O N
V
A
P h o n e
.2
.8 w .t h e la n e g ro u p in c .c o m
A B
IN
G
D O
N
B
IG
S
TO
N E G
A P
G A
LA
X th e
V A
D
E P
T O
F C
O N
S E
R V
A T
IO
N
A N
D R
E C
R E
A T
IO
N
R A
N G
E R
R E
S
ID
E N
C E
S
G R
A Y
S O
N H
IG
H
L A
N D
S S
T A
T E
P A
R K
P C
-1
-0
P001
02/10/2026
JER JDW
02/10/2026
PLUMBING FIXTURE CONNECTION SCHEDULE
MARK DESCRIPTION
BASIS OF DESIGN CONNECTION SIZE
REMARKS
MANUFACTURER MODEL NO.
CW
(IN)
HW
(IN)
SS
(IN)
V
(IN)
ECO
EXTERIOR CLEANOUT, DURA-COATED CAST IRON BODY AND ADJUSTABLE TOP
ASSEMBLY, AND GAS/WATER TIGHT THREADED ABS TAPERED PLUG.
ZURN Z1400-BZ1 - - 4 -
Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011
ILET
CIM
ARRO
N K-31644
4"4"
ECO
3"
2"
3"
2"
2"
2"
2"
WC-2
L-2
SH-1
WC-1
L-1
TS-1
S-1
CB-1
CB-3
3"
1 1/2" 2"
/2
2" V UP
TO VTR
4" SAN BEL. GRADE.
PROVIDE MINIMUM 3'-0"
COVER AND EXTEND AND
CONNECT TO CIVIL. 4" CO
2" VTR
4" CO
3" 2"
3"3" 4"
2"
2" 2"
2"
3"
/2
/2 "1
/2
2"
1 1/2"
1 1/2"
2"
4" ECO
4"SAN
CB-3 S-1
TS-1
L-1
CB-1
WC-2
L-2
SH-1
WC-1
DSP-1
4"
4" SAN TO CIVIL
CONNECTION
MAIN SEWER FLOW
12"X12"X4" THICK CONCRETE PAD
FLUSH WITH GRADE OR PAVEMENT
CLEANOUT - SEE SCHEDULE.
F ile
C
U
S E
R S
\W Y
A T
T .S
M
IT
H E
R S
\D E
S K
T O
P \T
B X
D C
R .D
W G salasobrien.com
Project No:
Roanoke
119 Norfolk Avenue, Suite 310 Roanoke, Virginia 24011
2450-71138-00
540-952-9651
SPECTRUMPC.COM
L A N E
Plaza Suite 1
10 Church Avenue, SE
Roanoke, VA 24011
540.342.6001
SHEET:
DATE:
NO. REVISION DATE
DRAWN BY CHECKED BY
PROJECT NO.
24039
G R
O U
P e n g in e e ri n g a rc h it e c tu re e n v ir o n m e n ta l
V
A
LL
E Y
S
TR
E E T
N W
A
B
IN
G D
O N
V
A
P h o n e
.2
.8 w .t h e la n e g ro u p in c .c o m
A B
IN
G
D O
N
B
IG
S
TO
N E G
A P
G A
LA
X th e
V A
D
E P
T O
F C
O N
S E
R V
A T
IO
N
A N
D R
E C
R E
A T
IO
N
R A
N G
E R
R E
S
ID
E N
C E
S
G R
A Y
S O
N H
IG
H
L A
N D
S S
T A
T E
P A
R K
P C
-1
-0
P101
02/10/2026
JER JDW
02/10/2026
Scale: 1/4" = 1'-0"2
PLUMBING NEW WORK PLAN
Scale:1
RISER DIAGRAM - WASTE
GENERAL NOTES:
1. CURRENT PLUMBING DESIGN INDICATES SITE
ADAPTED MODIFICATIONS. REFERENCE DEB
APPROVED PROTOTYPE PROJECT (PROJECT CODE
199-18366-000) FOR ADDITIONAL INFORMATION. ANY
ALTERATIONS TO THE PROTOTYPE SCOPE OF
WORK SHALL BE APPROVED BY THE PROTOTYPE
ENGINEER OF RECORD.
2. REFERENCE DEB APPROVED PROTOTYPE PROJECT
(PROJECT CODE 199-18366-000) FOR PLUMBING
FIXTURE SCHEDULE AND ANY OTHER PLUMBING
EQUIPMENT INFORMATION.
PLUMBING FIXTURE CONNECTION SCHEDULE
MARK DESCRIPTION
BASIS OF DESIGN CONNECTION SIZE
REMARKS
MANUFACTURER MODEL NO.
CW
(IN)
HW
(IN)
SS
(IN)
V
(IN)
ECO
EXTERIOR CLEANOUT, DURA-COATED CAST IRON BODY AND ADJUSTABLE TOP
ASSEMBLY, AND GAS/WATER TIGHT THREADED ABS TAPERED PLUG.
ZURN Z1400-BZ1 - - 4 -
Scale: NONE3
EXTERIOR CLEANOUT
Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011
1. SCOPE OF WORK: THE CONTRACTOR SHALL PROVIDE SUPERVISION, LABOR, MATERIAL, EQUIPMENT, MACHINERY, PLANT AND OTHER ITEMS NECESSARY FOR A COMPLETE AND OPERABLE ELECTRICAL SYSTEM. WHERE VARIANCES OCCUR BETWEEN DRAWINGS AND SPECIFICATIONS OR WITHIN EITHER DOCUMENT ITSELF, INCLUDE IN THE CONTRACT PRICE THE ITEM OR ARRANGEMENT OF BETTER QUALITY, GREATER QUANTITY, OR HIGHER COST.
This is the start of the file's text. The full file is on GovTribe.