The floor plan shows the electrical layout, including power panels, disconnects, motors, and conduit routing. The electrical specifications cover requirements for conductors, conduit, safety switches, and other electrical materials and installation. The project is located at the 134th Air Refueling Wing and the engineering services are provided by Engineering Services Group, Inc. in Knoxville, Tennessee. This document does not contain any pricing, set asides, award dates, or other information typically found in a federal solicitation. It appears to be technical specifications for the electrical portion of the hydraulic test stand project.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E1.1
FL
O
O R
P
LA
N
E
LE
C
TR
IC
A
L
MWE
ECH
3.27.24
PSXE232004
H yd ra u lic T es t
S ta n d
4t h A ir R ef u el in g W in g
P r o j e c t
N o
E n g in e e r in g S e r v ic e s
G r o u p
In c
K n o x v il l e
T e n n e s s e e
(8
-0
E a s t H il l
A v e
S u it e
C o n s u l t in g E n g in e e r s
AutoCAD SHX Text
VARIABLE SPEED DRIVE
AutoCAD SHX Text N
AutoCAD SHX Text
%%UFLOOR PLAN - ELECTRICAL
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
PP4
AutoCAD SHX Text T6
AutoCAD SHX Text
LP4
AutoCAD SHX Text
T4 DISCONNECT SWITCH
AutoCAD SHX Text T4
AutoCAD SHX Text T5
AutoCAD SHX Text
T5 DISCONNECT SWITCH
AutoCAD SHX Text
LP3
AutoCAD SHX Text T3
AutoCAD SHX Text
PP3
AutoCAD SHX Text (2)2",4#3/0,1#3G
AutoCAD SHX Text
TERMINAL BLOCK IN HYDRAULIC TEST STATION
AutoCAD SHX Text
PROVIDE A 400/3 BREAKER IN EXISTING SPACE OF PANEL PP4 AND CONNECT
AutoCAD SHX Text
EXISTING GEAR TO REMAIN. PROVIDE NEW BREAKERS IN PANEL PP4 AS NOTED BELOW.
AutoCAD SHX Text
P-1, 1HP, 480/3, 3/4",3#12,#12G
AutoCAD SHX Text
CONNECT VARIABLE SPEED DRIVE FURNISHED BY MECHANICAL
AutoCAD SHX Text
PROVIDE A 15/3 BREAKER IN EXISTING SPACE OF PANEL "PP4" AND CONNECT
AutoCAD SHX Text
DISCONNECT SWITCH:
AutoCAD SHX Text
POWER PANELBOARD:
AutoCAD SHX Text
CONDUIT:
AutoCAD SHX Text
ELECTRIC MOTOR CONNECTION:
AutoCAD SHX Text E L E C T R I C A L S Y M B O L L E G E N D
AutoCAD SHX Text
BRANCH CIRCUIT HOMERUN:
AutoCAD SHX Text CONDUIT WITH CONDUCTORS EXTENDED AND CONNECTED TO OVERCURRENT DEVICE(S) NOTED. CROSSLINES INDICATE QUANTITY OF #12 AWG CONDUCTORS WHEN MORE THAN TWO. PROVIDE A DEDICATED NEUTRAL FOR EACH LINE-TO-NEUTRAL CIRCUIT IN A HOMERUN. WHERE ONE NEUTRAL IS PROVIDED FOR A MULTI-CIRCUIT HOMERUN THE CONTRACTOR SHALL PROVIDE DISCONNECTING MEANS FOR EACH CONDUCTOR AS REQUIRED BY THE NEC. GROUNDING CONDUCTOR IS NOT ILLUSTRATED.
AutoCAD SHX Text SOLID LINE AND CLOSED DOT INDICATE INSTALLED IN WALL OR CEILING SHOWN TURNING DOWN. ALL CONDUITS SHALL CONTAIN AN EQUIPMENT GROUNDING CONDUCTOR WHICH IS NOT ILLUSTRATED. BROKEN LINE AND OPEN DOT INDICATE INSTALLED IN FLOOR CONSTRUCTION OR UNDERGROUND SHOWN TURNING UP. ALL CONDUITS SHALL CONTAIN AN EQUIPMENT GROUNDING CONDUCTOR WHICH IS NOT ILLUSTRATED.
AutoCAD SHX Text
EXISTING TO REMAIN. REFER TO DRAWINGS NOTES FOR REWORK REQUIRED.
AutoCAD SHX Text HORSEPOWER RATED, FUSED, HEAVY DUTY "WP" INDICATES NEMA 3R ENCLOSURE UNLESS NOTED OTHERWISE.
AutoCAD SHX Text
USE FLEXIBLE CONDUIT WITH-IN 18" OF CONNECTION
AutoCAD SHX Text THE CONTRACTOR SHALL BE GOVERNED BY THE PRESENT SPECIFICATIONS TOGETHER WITH THE CURRENT RECOMMENDATIONS AND REGULATIONS OF THE LOCAL AUTHORITIES HAVING JURISDICTION AND UL STANDARDS. THE COR RESERVES THE RIGHT TO RELOCATE ANY EQUIPMENT UP TO 10 FEET IN ANY DIRECTION PRIOR TO ROUGH-IN.
AutoCAD SHX Text
1. ALL POWER WIRING FOR ITEMS FURNISHED BY THE MECHANICAL CONTRACTOR ALL POWER WIRING FOR ITEMS FURNISHED BY THE MECHANICAL CONTRACTOR SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. 2. ALL DISCONNECT SWITCHES SHALL BE FURNISHED AND INSTALLED BY THE ALL DISCONNECT SWITCHES SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. 3. TOGGLE SWITCHES FOR 1/2 HP MOTORS AND LESS SHALL BE FURNISHED AND TOGGLE SWITCHES FOR 1/2 HP MOTORS AND LESS SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. 4. WIRING AND CONDUIT FOR SOLENOID VALVES, AND CONTROL TRANSFORMERS WIRING AND CONDUIT FOR SOLENOID VALVES, AND CONTROL TRANSFORMERS INCLUDING THE TRANSFORMERS SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. 5. THE ELECTRICAL CONTRACTOR SHALL INSTALL ALL STARTERS, TOGGLE THE ELECTRICAL CONTRACTOR SHALL INSTALL ALL STARTERS, TOGGLE SWITCHES, DISCONNECTS, AND ALL WIRING TO THE RESPECTIVE MOTOR OR DEVICE. WIRING AND CONDUIT FROM STARTER TO A CONTROLLER SHALL BE BY THE MECHANICAL CONTRACTOR. 6. DEFINITIONS: DEFINITIONS: A. POWER WIRING: LINE VOLTAGE CIRCUITRY ROUGH-IN INCLUDING CONDUIT, POWER WIRING: LINE VOLTAGE CIRCUITRY ROUGH-IN INCLUDING CONDUIT, BOXES, CONDUCTORS, ETC. BETWEEN THE OVERCURRENT PROTECTION AND THE EQUIPMENT INCLUDING THE CONNECTION OF THE STARTERS BY THE ELECTRICAL CONTRACTOR. B. CONTROL WIRING: ANY VOLTAGE CIRCUITRY ROUGH-IN INCLUDING CONTROL WIRING: ANY VOLTAGE CIRCUITRY ROUGH-IN INCLUDING CONDUIT, BOXES, CONDUCTORS, ETC. BETWEEN CONTROL ACTIVATOR AND THE CONTROLLER OR STARTER BY THE MECHANICAL CONTRACTOR. 7. CONDUIT: ALL POWER WIRING AND 120V CONTROL WIRING SHALL BE IN CONDUIT: ALL POWER WIRING AND 120V CONTROL WIRING SHALL BE IN CONDUIT.
AutoCAD SHX Text
CONNECT ALL MOTORS WITH SHORT LENGTH OF LIQUIDTIGHT FLEXIBLE METAL CONDUIT.
AutoCAD SHX Text FURNISH SUBMITTALS AND SHOP DRAWINGS FOR ALL PRINCIPAL DEVICES AND PIECES OF EQUIPMENT FOR REVIEW BY THE COR. 1. DISCONNECT SWITCHES. DISCONNECT SWITCHES.
AutoCAD SHX Text SITE VISIT: BEFORE SUBMITIING BID, CONTRACTOR SHALL VISIT THE JOB SITE FOR THE PURPOSE OF EXAMINING THE SITE AND CONDITIONS UNDER WHICH THE WORK MUST BE PERFORMED. NO EXTRA CHARGES WILL BE ALLOWED FOR SITUATIONS ARISING FROM FAILURE OF CONTRACTOR TO THOROUGHLY FAMILIARIZE HIMSELF WITH SITE AND EXISTING BUILDING CONDITIONS, INCLUDING CHARGES AND REQUIREMENTS TO UTILITIES AS SHOWN FOR THE PROJECT. CONTRACTOR SHALL VERIFY THAT CONNECTIONS TO EXISTING EQUIPMENT ARE AS INDICATED ON DRAWINGS AND SPECIFICATIONS. ANY DEVIATIONS SHALL BE REPORTED TO THE COR IMMEDIATELY. ANY DEVIATIONS SHALL BE REPORTED PRIOR TO BIDDING.
AutoCAD SHX Text
SECTION 16030 BASIC MATERIALS
AutoCAD SHX Text
CONDUCTORS
AutoCAD SHX Text THE MINIMUM SIZE CONDUCTOR FOR ALL POWER AND LIGHTING SHALL BE NO. 12 AWG, SOLID FOR SIZES NO. 10 AWG AND SMALLER, STRANDED FOR NO. 8 AWG AND LARGER.
AutoCAD SHX Text UNLESS SPECIFICALLY INDICATED ON DRAWINGS TO BE ALUMINUM, CONDUCTORS SHALL BE 98% CONDUCTIVITY DRAWN COPPER AND MEET OR EXCEED UL STANDARD 83, FEDERAL SPECIFICATION A-A-59544A AND NATIONAL ELECTRICAL CODE.
AutoCAD SHX Text ALL CONDUITS SHALL CONTAIN A CODE SIZED EQUIPMENT GROUNDING CONDUCTOR WHICH MAY NOT BE ILLUSTRATED ON THE PLANS.
AutoCAD SHX Text REFER TO OTHER SECTIONS FOR COLOR CODING OR MARKING OF CONDUCTORS IN MULTI-VOLTAGE SYSTEM BUILDING. WHERE MORE THAN ONE VOLTAGE SYSTEM (I.E., 480/277V, 208/120V) IS PRESENT CONDUCTORS FOR EACH SYSTEM SHALL BE COLOR CODED. ORANGE, YELLOW, BROWN AND GREY FOR 480/277V SYSTEMS AND BLACK, RED, BLUE AND WHITE FOR 208/120V SYSTEMS. CODING SHALL BE CONSISTENT THROUGHOUT.
AutoCAD SHX Text NO LUBRICANT OTHER THAN POWDERED SOAPSTONE OR APPROVED PULLING COMPOUND MAY BE USED TO PULL CONDUCTORS.
AutoCAD SHX Text CONDUCTORS NO. 10 AWG AND SMALLER FOR LIGHTING AND POWER BRANCH CIRCUITS SHALL BE SPLICED WITH SPRING TYPE WIRE CONNECTORS. THE CONNECTOR SHALL BE A UL LISTED PRESSURE TYPE CONNECTOR RATED AT 600V AND 105° C. IN-LINE SPLICING OF NO. 8 AWG AND LARGER CONDUCTORS SHALLBE WITH COMPRESSION TYPE SLEEVES. WHERE CONDUCTORS ARE TAPPED OFF FEEDER CONDUCTORS NO. 6 AWG AND LARGER THE CONNECTION SHALL BE MADE AT POWER DISTRIBUTION BLOCKS SECURELY MOUNTED IN AN ENCLOSURE. THE POWER DISTRIBUTION BLOCK SHALL BE RATED AT 600V, 75° C AND ULRECOGNIZED. THE POWER DISTRIBUTION BLOCK SHALL BE NSI POLARIS, ILSCO, BURNDY OR APPROVED SUBSTITUTE.
AutoCAD SHX Text WHERE GROUNDING CONDUCTORS ARE TERMINATED IN JUNCTION OR OUTLET BOXES AN APPROVED GROUNDING SCREW OR CLIP SHALL BE USED. COVER SCREW IS NOT AN ACCEPTABLE MEANS OF TERMINATION. SURFACES SHALL BE FREE OF PAINT, RUST, AND GREASE OR OTHER FOREIGN MATERIAL.
AutoCAD SHX Text
CONDUCTORS SHALL BE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 310.
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
ELECTRICAL SPECIFICATIONS
AutoCAD SHX Text EACH LENGTH OF CONDUIT SHALL BE STAMPED WITH NAME AND TRADE MARK OF MANUFACTURER AND APPROVAL OF NATIONAL BOARD OF FIRE UNDERWRITERS.
AutoCAD SHX Text
PROTECT THREADS OF GALVANIZED RIGID STEEL CONDUIT AND IMC DURING STORAGE.
AutoCAD SHX Text
STACK CONDUIT ON BLOCKING OFF GROUND TO PREVENT THE ENTRY OF FOREIGN MATERIAL.
AutoCAD SHX Text TAKE EVERY PRECAUTION TO PREVENT ENTRY OF WATER AND FOREIGN MATTER IN CONDUIT DURING CONSTRUCTION. INSTALL FACTORY CONDUIT CAPS ON STUB-UPS DURING CONSTRUCTION. SWAB TRAPPED RUNS PRIOR TO PULLING CONDUCTORS.
AutoCAD SHX Text GALVANIZED RIGID STEEL CONDUIT OR "IMC" SHALL BE TERMINATED IN THREADED HUBS OR WITH DOUBLE LOCKNUTS (BONDNUT TYPE) DRAWN TIGHT AND CONDUIT BUSHING.
AutoCAD SHX Text FIELD CUT CONDUIT SHALL BE CUT SQUARE, REAMED SMOOTH AND THREADED PROPERLY AND FULL. PAINT FIELD CUT MALE THREADS WITH CONDUCTIVE AND RUST PREVENTIVE COMPOUND. CUTTING OIL AND DEBRIS SHALL BE REMOVED PRIOR TO INSTALLATION.
AutoCAD SHX Text "EMT" CONDUIT SHALL BE TERMINATED WITH STEEL SET-SCREW TYPE COUPLINGS, CONNECTORS AND FITTINGS. FIELD-CUT CONDUIT SHALL BE SQUARE AND REAMED SMOOTH. ALL CONDUIT 1-1/4" AND LARGER SHALL HAVE INSULATED GROUNDING BUSHINGS INSTALLED.
AutoCAD SHX Text CONDUIT SHALL BE INSTALLED AND SUPPORTED PER NATIONAL ELECTRICAL CODE ARTICLE 342 (INTERMEDIATE METAL CONDUIT), ARTICLE 344 (RIGID METAL CONDUIT), ARTICLE 350 (LIQUIDTIGHT FLEXIBLE METAL CONDUIT), ARTICLE 352 (RIGID POLYVINYL CHLORIDE CONDUIT), ARTICLE 358 (ELECTRICAL METALLIC TUBING), ARTICLE 300 (GENERAL REQUIREMENTS FOR WIRING METHODS) AND ARTICLE 110 (REQUIREMENTS FOR ELECTRICAL INSTALLATIONS).
AutoCAD SHX Text WHERE EXPOSED: 1. ORGANIZE THE RUNS INTO GROUPS AND COORDINATE WITH OTHER TRADES TO ORGANIZE THE RUNS INTO GROUPS AND COORDINATE WITH OTHER TRADES TO AVOID INTERFERENCE. 2. ARRANGEMENT SHALL BE NEAT AND ORDERLY WITH RUNS PARALLEL TO ARRANGEMENT SHALL BE NEAT AND ORDERLY WITH RUNS PARALLEL TO STRUCTURAL ELEMENTS. NO DIAGONAL RUNS WILL BE ALLOWED. 3. SUPPORTS SHALL BE "UNISTRUT" WITH SUITABLE CLAMPS THE UNISTRUT SUPPORTS SHALL BE "UNISTRUT" WITH SUITABLE CLAMPS THE UNISTRUT SHALL BE SUPPORTED FROM THE BUILDING STRUCTURES. PAINT CUT ENDS OF UNISTRUT WITH RUST PROHIBITOR.
AutoCAD SHX Text ALL CONDUITS ARE TO CONTAIN A CODE SIZED EQUIPMENT GROUNDING CONDUCTOR WHICH MAY NOT BE ILLUSTRATED.
AutoCAD SHX Text ALL JUNCTION BOXES SHALL BE PAINTED TO CORRESPOND TO THE ABOVE COLOR CODES. CIRCUIT NUMBERS CONTAINED WITH-IN A JUNCTION BOX SHALL BE MARKED ON INSIDE AND OUTSIDE OF JUNCTION BOX COVER WITH A PERMANENT MARKING.
AutoCAD SHX Text
METAL-CLAD CABLE
AutoCAD SHX Text
SAFETY SWITCHES
AutoCAD SHX Text SWITCHES SHALL BE HEAVY-DUTY, HORSEPOWER RATED, QUICK-MADE, QUICK-BREAK FUSED WITH ARC SHIELDS WITH ENCLOSED CONSTRUCTION.
AutoCAD SHX Text ALL SAFETY SWITCHES SHALL BE MECHANICALLY INTERLOCKED TO PREVENT OPENING WHILE ENERGIZED. SCREWS FROM DOOR TO CAN ARE NOT ACCEPTABLE.
AutoCAD SHX Text METAL-CLAD CABLE SHALL NOT BE UTILIZED OR PERMITTED. WHERE FLEXIBLE WIRING METHODS ARE REQUIRED, PROVIDE FLEXIBLE CONDUIT WITH INDIVIDUAL CONDUCTORS.
AutoCAD SHX Text
WIRING FOR MECHANICAL EQUIPMENT:
AutoCAD SHX Text CONDUCTORS SHALL NOT BE NICKED DURING INSULATION REMOVAL OR BENT AT SHARP ANGLES DURING DEVICE INSTALLATION OR PANELBOARD MAKE-UP.
AutoCAD SHX Text USE GALVANIZED RIGID STEEL CONDUIT OR INTERMEDIATE METAL CONDUIT UNDERGROUND, IN CONCRETE, OR WHERE MECHANICAL STRENGTH OR EXPOSURE TO PHYSICAL DAMAGE IS REQUIRED. SCHEDULE 40 RIGID NONMETALLIC CONDUIT MAY ALSO BE USED UNDERGROUND OR IN CONCRETE. ELECTRICAL METALLIC TUBING SHALL BE USED ELSEWHERE, UNLESS NOTED OTHERWISE. ALL CONDUCTORS SHALL BE INSTALLED IN CONDUIT. NON-METALLIC SHEATHED CABLES (TYPES NM, SE, UF, ETC) SHALL NOT BE USED. TYPE SO SERVICE CORD SHALL ONLY BE UTILIZED WHERE SPECIFICALLY NOTED. CONDUIT SHALL MEET: GALVANIZED RIGID STEEL - UL 6 AND ANSI C80.1; "IMC" - UL 1242 AND ANSI C80.6; "EMT" - UL 797 AND ANSI C80.3; "LFMC" - UL 360; "RNC" - UL 651 POLYVINYL CHLORIDE. MINIMUM SIZE FOR CONDUIT SHALL BE 3/4".
AutoCAD SHX Text ALL CONDUIT SHALL BE IDENTIFIED BY A COLOR CODED BAND EVERY 10 FEET. BAND SHALL BE PAINTED OR COLOR CODE TAPE, (DO NOT DIP FITTINGS IN PAINT) ONE INCH WIDE AND IDENTIFIED ACCORDING TO SYSTEMS AS FOLLOWS: 1. 120/208 VOLT NONE 120/208 VOLT NONE NONE 2. 480/277 VOLT ORANGE 480/277 VOLT ORANGE ORANGE
AutoCAD SHX Text ALL CONDUCTORS NO. 6 AWG AND SMALLER SHALL BE 600V INSULATED WITH TYPE "THWN/THHN" DUAL RATED INSULATION. ALL CONDUCTORS LARGER THAN NO. 6 AWG SHALL BE EITHER TYPE "THWN/THHN" DUAL RATED OR "THW" INSULATION.
AutoCAD SHX Text CURRENT CARRYING CAPACITY OF ALL CONDUCTORS IS TO BE BASED ON 60° CFOR 100 AMP AND LESS ALL OTHERS SHALL BE BASED ON 75° C, REGARDLESSOF THE CONDUCTOR INSULATION TYPE.
AutoCAD SHX Text COORDINATE ALL CONSTRUCTION DELIVERIES, DISPOSAL OF CONSTRUCTION TRASH, ETC. WITH OWNER AND GENERAL CONTRACTOR. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED BY THEIR WORK. COORDINATE WITH GENERAL CONTRACTOR.
AutoCAD SHX Text
WARRANTY
AutoCAD SHX Text THE CONTRACTOR SHALL WARRANT AND GUARANTEE ALL WORK EXECUTED UNDER THIS DIVISION TO BE FREE FROM DEFECTS FOR A PERIOD OF ONE YEAR AFTER SUBSTANTIAL COMPLETION.
AutoCAD SHX Text
RECORD DRAWING
AutoCAD SHX Text CONTRACTOR SHALL MAINTAIN A SET OF RECORD DRAWINGS SHOWING ANY CHANGES AND MODIFICATIONS THAT OCCURRED DURING THE CONSTRUCTION PERIOD. AFTER COMPLETION OF CONSTRUCTION THESE RECORD DRAWINGS SHALL BE TURNED OVER TO THE COR.
AutoCAD SHX Text FLEXIBLE CONDUIT SHALL BE INSTALLED NEATLY, TERMINATED WITH COUPLINGS LISTED FOR THE APPLICATION, AND SUPPORTED PER NEC.
AutoCAD SHX Text WHERE PERMITTED, ALUMINUM CONDUCTORS SHALL BE DRAWN ALUMINUM ALLOY AND MEET OR EXCEED UL STANDARD 83, FEDERAL SPECIFICATION A-A-59544A AND NATIONAL ELECTRICAL CODE. MINIMUM SIZE FOR ANY ALUMINUM UNGROUNDED (HOT) OR GROUNDED (NEUTRAL) CONDUCTORS SHALL BE NO. 1 AWG.
AutoCAD SHX Text JUNCTION AND/OR PULL BOXES, AND WIREWAYS, SHALL NOT CONTAIN CONDUCTORS FROM MORE THAN SIX LINE-TO-NEUTRAL BRANCH CIRCUITS (OR AN EQUIVALENT NUMBER OF LINE-TO-LINE CIRCUITS) UNLESS INDICATED ON THE PLANS OR APPROVED IN WRITING BY THE COR.
AutoCAD SHX Text JUNCTION AND/OR PULL BOXES, WIREWAYS, AND AUXILIARY GUTTERS, SHALL NOT CONTAIN CONDUCTORS ORIGINATING FROM MORE THAN ONE PANELBOARD.
AutoCAD SHX Text GENERAL NOTES: 1. ROUTE CONDUITS OVERHEAD. FOLLOW EXISTING CONDUIT ROUTING TO THE EXTENT ROUTE CONDUITS OVERHEAD. FOLLOW EXISTING CONDUIT ROUTING TO THE EXTENT POSSIBLE. MATCH EXISTING MATERIALS, SUPPORTS, AND INSTALLATION METHODS. WHERE EXISTING NEARBY CONDUIT AND SUPPORTS ARE PAINTED, PAINT NEW TO MATCH.
AutoCAD SHX Text
(LOCATED ON MECHANICAL MEZZANINE ABOVE)
AutoCAD SHX Text
42" MIN CLEARANCE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
PROJ. NO:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text 240 West Bessemer St. Alcoa, TN. 37701
AutoCAD SHX Text
ph. 865 980 3500 fax. 865 980 3555
AutoCAD SHX Text \\ESGSTOR\PROJECTS\2024\24644 TANG 134TH HYDRAULIC TEST STAND BUILDING 190\ELEC\24644 - E1.1.DWGPLOTTED ON:April 1, 2024 12:38 PM BY:COLBY JONESApril 1, 2024 12:38 PM BY:COLBY JONES12:38 PM BY:COLBY JONESBY:COLBY JONESCOLBY JONES
AutoCAD SHX Text Knoxville, Tennessee
AutoCAD SHX Text Knoxville, Tennessee