This is a project description document for the Hawaii Army National Guard B1788 Boiler Room Improvements project. The project encompasses hot water system upgrades at a National Guard facility, including removal and replacement of existing hot water tanks, associated piping modifications, installation of a solar hot water system, and related electrical work to support the new systems. The scope of work addresses the modernization and efficiency improvements of the boiler room infrastructure to enhance hot water delivery capabilities and reduce operational costs through solar integration.
The document provides technical specifications and project requirements for contractors bidding on the improvements. Specific details regarding bid submission deadlines, site visit schedules, pre-bid meetings, contract award timelines, and the contract term are not detailed in the available file summary. Pricing terms, any small business or minority-owned business set-asides, funding sources, and the total project budget amount should be referenced in the complete solicitation documents to fully understand the financial and compliance requirements for potential bidders.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
i
BID DOCUMENTS AND SPECIFICATIONS FOR
HAWAII ARMY NATIONAL GUARD B1788 BOILER ROOM
IMPROVEMENTS, KALAELOA, OAHU, STATE OF HAWAII,
DEPARTMENT OF DEFENSE, HAWAII ARMY NATIONAL GUARD,
JOB NO. CA-202610-C
ISSUED BY:
STATE OF HAWAII
DEPARTMENT OF DEFENSE
3949 DIAMOND HEAD ROAD,
HONOLULU, HAWAII 96816-4495
TELEPHONE: 808-369-3567
AUGUST 2026
Hawaii Army National Guard B1788 Boiler Room Improvements, Kalaeloa, Oʻahu, State of Hawai’i, Department of Defense, Hawaii Army National Guard, CA-202610-C
TABLE OF CONTENTS
Content. Page No.
Notice to Bidders 1 – 2 Drawings 3 - 27 Special Notice to Bidders 28 - 36 Special Provisions for Construction Contracts 37 - 43
Attachments.
1. Offer Form 44 - 52
2. General Conditions 53 - 109
3. Additional General Conditions 110 - 112
4. Special Conditions 113 - 114
STATE OF HAWAI’I
DEPARTMENT OF DEFENSE
OFFICE OF THE ADJUTANT GENERAL
3949 DIAMOND HEAD ROAD
HONOLULU, HAWAI’I 96816-4495
NOTICE TO BIDDERS - CONSTRUCTION
COMPETITIVE SEALED BIDDING (IFB) for “HAWAII ARMY NATIONAL GUARD B1788 BOILER ROOM
IMPROVEMENTS, KALAELOA, OAHU, STATE OF HAWAII, DEPARTMENT OF DEFENSE, HAWAII
ARMY NATIONAL GUARD, JOB NO. CA-202610-C" will be issued and awarded by the Department of Defense, Engineering Office via Hawai’i Electronic Procurement System (HIePRO). All bids shall be submitted and uploaded through HIePRO prior to and no later than 2:00 P.M. HST on Thursday, SEPTEMBER 10, 2026. The record of each Bidder and their respective proposal shall be open to public inspection by request for copies of bids. Late bids will not be accepted after the due date and time or received in any other form than electronically through HIePRO.
Proposed Scope of Work consists of, but not limited to: Removal and replacement of the domestic hot water system serving multiple buildings, including a new air-source heat pump water heater, five hot water storage tanks, a new water softener, and an expanded 12-panel solar hot water collector array with associated piping, pumps, and controls; new electrical service (transformer, circuit breaker, feeders, and branch circuits) to support the new mechanical equipment; and associated minor architectural and civil work, including concrete equipment pad repair and extension, roof membrane flashing at new penetrations, exterior painting, and a new sanitary sewer lateral.
The estimated cost is between $250,000 and $500,000.
A Site Visit/Pre-bid meeting will be held on TUESDAY, AUGUST 25, 2026 at 11:00 a.m. Park on the road shoulder across the entrance gate. Contractors are to meet Major Randall Duldulao or Allied Security Guard at the entrance gate. Please register through HIePRO or email Major Randall Duldulao at randall.s.duldulao@hawaii.gov and Cc jesper.h.andersen@hawaii.gov before 10:00 pm on Friday August 21, 2026, to register for the site visit. Provide your company information, attendees names, an email and a contract number, if you are intending to register for the site visit. All interested bidders and sub-contractors are welcome but not required to attend.
Bidders are advised that they should not wait until the last minute to submit their bid through HIePRO.
Bidders are solely responsible for ensuring that their electronic submission through HIePRO is complete and all mandatory bid files are attached to their bid prior to the due date and time. The Engineering Office shall not be responsible for any delay or failure of any Bidder to submit any materials updated through the IFB process on a timely basis.
QUESTIONS AND REQUESTS FOR CLARIFICATION
Questions and Requests for Clarification regarding the Technical Specifications or any other aspect of the IFB must be submitted via HIePRO by 10:00 p.m. Thursday, August 27, 2026. Responses are scheduled to be posted on Friday, September 4, 2026. The Department of Defense, Engineering Office shall not be required to answer Questions or Requests for Clarification not submitted via HIePRO or received after the Questions and Requests for Clarification deadline.
Bidders are responsible for checking for any addenda for this project. The addenda will be posted on the HIePRO listing and at the State Department of Defense website at http://dod.hawaii.gov/hieng/
All documents can be downloaded from HIePRO and at the State Department of Defense website at http://dod.hawaii.gov/hieng/.
mailto:randall.s.duldulao@hawaii.gov mailto:jesper.h.andersen@hawaii.gov http://dod.hawaii.gov/hieng/ http://dod.hawaii.gov/hieng/
REQUIREMENT FOR CONTRACTORS LICENSING CLASSIFICATIONS
Due to the nature of the work contemplated Bidder must possess a valid State of Hawai’i Contractor's license in the appropriate classification, which includes a Licensed Plumber and C-37 Contractor.
General Engineering Contractors holding an ‘A’ license and General Building Contractors holding a ‘B’ license are reminded that due to the Hawai’i Supreme Court’s January 28, 2002 decision in Okada Trucking Co., Ltd. v. Board of Water Supply, et al., 97 Haw. 450 (2002), they are prohibited from undertaking any work, solely or as part of a larger project, which would require the General Contractor to act as a specialty Contractor in any area in which the General Contractor has no license.
Bidders are solely responsible to review the project requirements, determine the appropriate licenses required, and ensure that they possess and that the Subcontractor(s) listed in their OFFER FORM possess the necessary specialty licenses to perform the work for this project.
PROJECT LABOR AGREEMENT
A Project Labor Agreement (PLA) will be required for any construction project in excess of one million five hundred thousand dollars ($1,500,000).
The Contractor who is awarded the project shall be required to submit to the Department of Defense, Engineering a complete, fully executed Agreement-To-Be-Bound within fourteen (14) calendar days of project award, or as soon thereafter as is practicable as determined by the Department. The Contractor must also obtain Letters of Assent from each subcontractor of whatever tier who may be employed on the project and submit copies of such Letters to the Department of Defense, Engineering within fourteen
(14) calendar days of project award, or as soon thereafter as is practicable as determined by the Department. The required form of the Contractor's Agreement To Be Bound and the subcontractors' Letter of Assent may be found in the solicitation packet. Failure to timely submit any required Agreement- To-Be-Bound or any required Letter of Assent shall be cause for the State in its sole discretion to rescind the subject award and to award the project to: the responsive and responsible offerer with the next lowest bid price for solicitations made under HRS 103D-302; or the next highest ranked offerer satisfying all solicitation requirements for solicitations made under HRS 103D-303.
OFFER DEEMED FIRM/AUTHORITY TO SUBMIT OFFER
Submission of an electronic response to the State of Hawai’i constitutes and shall be deemed an offer to sell the specified goods and/or services to the State of Hawai’i at the price shown in the response and under the State's Terms and Conditions. The electronic response submitter certifies that he/she is authorized to sign the response for the submitting vendor and that the response is made without connection with any person, firm, or corporation making a response for the same goods and/or services and is in all respects fair and without collusion or fraud.
CAMPAIGN CONTRIBUTIONS BY STATE AND COUNTY CONTRACTORS PROHIBITED
If awarded a contract in response to this solicitation, offeror agrees to comply with HRS §11-355, which states that campaign contributions are prohibited from a State and County government contractor during the term of the contract if the contractor is paid with funds appropriated by the legislative body between the execution of the contract through the completion of the contract.
HAWAI’I PRODUCTS’ PREFERENCE
In accordance with ACT 174, SLH 2022, effective June 27, 2022, Hawai’i Products Preference shall not apply to solicitations for public works construction. Therefore, the Hawai’i Products Preference shall not apply to this project.
Stephen F. Logan Major General Adjutant General Posted on: August 17, 2026
ISLAND OF OAHU
PROJECT
LOCATION
S H A N G R I L A S T R E E T
SECURITY
GUARD SHED
B U
I L D
I N
G
B U
I L D
I N
G
(N I
C)
BL
DG
FE
NC
E
LI
NE
CU
RB
B U
I L D
I N
G
BL
DG
BL
DG
BLDG1785
BLDG 1788
FENCELINE
B E L L E A U W O O D S
P A
R K
I N G
P A
R K
I N G
B U
N K
E R
H I
L L
S T
R E
E T
E N
T E
R P
R I S
E
S T
R E
E T
AREA OF WORK
VICINITY PLAN
PROJECT DATA
LOCATION MAP
SCALE: NTS
DESCRIPTION : BOILER ROOM IMPROVEMENTS
LOCATION : 91-1152 ENTERPRISE AVE
KAPOLEI, HI 96707
TAX KEY MAP : 9-1-013-050
LOT AREA : 5.93 ACRES
EXISTING
BUILDING AREA : BLDG 1788 APPROX 2,457 SQ. FT.
GENERAL NOTES
1.
2.
3.
REPAIR ALL DAMAGE CAUSED BY CONSTRUCTION OF THIS
PROJECT.
COMPLY WITH THE LATEST CITY, STATE, AND FEDERAL
LAWS, BUILDING CODES, THEIR ADDITIONS, ADDENDA, AND
AMENDMENTS IN THE CONSTRUCTION OF THIS PROJECT.
USE DIMENSIONS NOTED ON DRAWINGS ONLY, DO NOT
SCALE DIMENSIONS FROM THE DRAWINGS.
KALAELOA, OAHU, HAWAI'I
DEPARTMENT OF DEFENSE, STATE OF HAWAI'I
JOB NO. CA-202610-C
HAWAII ARMY NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
BID SET: ISSUE FOR CONSTRUCTION
CONSULTANTS
MASON
119 MERCHANT STREET, SUITE 501
HONOLULU, HI 96813
(808) 536-0556
WAI'OLU GROUP LLC
615 PIIKOI STREET, SUITE 2003
HONOLULU, HI 96814
(808) 582-0478
INSYNERGY ENGINEERING, INC
1001 BISHOP STREET, SUITE 2500
HONOLULU, HAWAII 96813
(808) 521-3773
ARCHITECT
CIVIL
ELECTRICAL
PLUMBING,
FIRE PROTECTION,
MECHANICAL
PHOTOVOLTAIC
SHEET REF NO SHEET NO TITLE REV
GENERAL
1 001 PROJECT DATA, LOCATION MAP, SITE PLAN & GENERAL NOTES
ARCHITECTURE
A-001 ABBREVIATIONS, LEGENDS AND GENERAL NOTES
SPECIFICATIONS
A-101 FLOOR AND ROOF PLAN
A-50110
P-001 PLUMBING GENERAL NOTES AND LEGEND
P-101 PLUMBING PLAN - REMOVAL WORK
PLUMBING PLAN - NEW WORK
P-103 PLUMBING ROOF PLAN
PLUMBING DETAILSP-501
P-002 PLUMBING SITE PLAN
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES AND SPECIFICATIONS
E-002 BUILDING 1788 ELECTRICAL SYMBOL LIST & MOUNTING HEIGHT LIST
ED001 ELECTRICAL DEMOLITION PLAN
E-101 ELECTRICAL FLOOR PLAN
E-601 ELECTRICAL ONELINE DIAGRAMS
P-102
PLUMBING SCHEDULESP-601
HOT WATER SCHEMATICP-701
HOT WATER PIPING ISOMETRICP-901
A-002
A-003 SPECIFICATIONS
DETAILS
PLUMBING
DEPARTMENT OF DEFENSE
STATE OF HAWAII
REV NO. SYM. DESCRIPTION DATE
OF___
SHT__
DOD ADMINISTRATOR
APPROVED:
DRAWING NO.JOB NO.
SHEETDATE
OF________SHEETS
CHECKED BY:DESIGNED BY:
APPROVED BY:DRAWN BY:
SCALE:
FILE______ DRAWER______ FOLDER______
MASON
This work was prepared by me or under my supervision, and construction of this project will be under my observation.
No. 4073
W
N
ARCHITECT
PROFESSIONAL
LICENSED
AH
NELG
A.
,IIA S.
U.
NO
ME. AS
BUILDING 1788
Signature Expiration Date of the License 4/30/2028
PROJECT SCOPE
THE PROJECT FOCUSES ON HOT WATER UPGRADES: REMOVAL AND
REPLACEMENT OF HOT WATER TANKS, STORAGE TANKS, PIPING AND A SOLAR
HOT WATER SYSTEM AND ELECTRICAL WORK.
SHEET INDEX
E-003 ELECTRICAL SITE PLAN
CIVIL
C001 CONSTRUCTION NOTES
ESCP NOTES
C201 MISCELLANEOUS DETAILS
C002
C101 UTILITY PLAN
_______ 25
KALAELOA, OAHU, HAWAII
HAWAII ARMY NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
CONSTRUCTION NOTES
1. ALL APPLICABLE CONSTRUCTION WORK SHALL BE DONE IN ACCORDANCE WITH THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION, SEPTEMBER 1986 AND STANDARD DETAILS FOR PUBLIC WORKS CONSTRUCTION, SEPTEMBER 1984, AS AMENDED, OF THE DEPARTMENT OF PUBLIC WORKS, CITY AND COUNTY OF HONOLULU AND THE COUNTIES OF KAUAI, MAUI, AND HAWAII.
2. THE UNDERGROUND PIPES, CABLES OR DUCTLINES KNOWN TO EXIST BY THE ENGINEER FROM HIS SEARCH OF RECORDS ARE INDICATED ON THE PLANS. THE CONTRACTOR SHALL VERIFY THE LOCATIONS AND DEPTHS OF THE FACILITIES AND EXERCISE PROPER CARE IN EXCAVATING IN THE AREA. WHEREVER CONNECTIONS OF NEW UTILITIES TO EXISTING UTILITIES ARE SHOWN ON THE PLANS, THE CONTRACTOR SHALL EXPOSE THE EXISTING LINES AT THE PROPOSED CONNECTIONS TO VERIFY THEIR LOCATIONS AND
DEPTHS PRIOR TO EXCAVATION FOR THE NEW LINES.
3. NO CONTRACTOR SHALL PERFORM ANY CONSTRUCTION OPERATION SO AS TO CAUSE FALLING ROCKS, SOIL OR DEBRIS IN ANY FORM TO FALL, SLIDE OR FLOW INTO EXISTING CITY DRAINAGE SYSTEMS, OR ADJOINING
PROPERTIES, STREETS OR NATURAL WATERCOURSES. SHOULD SUCH VIOLATIONS OCCUR, THE
CONTRACTOR MAY BE CITED AND THE CONTRACTOR SHALL IMMEDIATELY MAKE ALL REMEDIAL ACTIONS
NECESSARY.
4. THE GENERAL CONTRACTOR/DEVELOPER/OWNER OF THE PROJECT SHALL BE RESPONSIBLE FOR CONFORMANCE WITH APPLICABLE PROVISIONS OF THE HAWAII ADMINISTRATIVE RULES, TITLE 11, CHAPTER 54, "WATER QUALITY STANDARDS," AND TITLE 11, CHAPTER 55, "WATER POLLUTION CONTROL", AS WELL AS CHAPTER 18A OF THE REVISED ORDINANCES OF HONOLULU, AS AMENDED. BEST MANAGEMENT PRACTICES
SHALL BE EMPLOYED AT ALL TIMES DURING CONSTRUCTION.
THE GENERAL CONTRACTOR/DEVELOPER/OWNER OF THE PROJECT SHALL OBTAIN NATIONAL POLLUTANT
DISCHARGE ELIMINATION SYSTEM (NPDES) PERMIT COVERAGE(S) FOR THE FOLLOWING:
A. STORM WATER DISCHARGES ASSOCIATED WITH CONSTRUCTION ACTIVITIES THAT DISTURB ONE (1)
ACRE OR MORE, AND
B. DISCHARGES OF HYDROTESTING EFFLUENT, DEWATERING EFFLUENT, AND WELL DRILLING EFFLUENT
TO STATE WATERS.
IN ACCORDANCE WITH STATE LAW, ALL DISCHARGES RELATED TO PROJECT CONSTRUCTION OR
OPERATIONS ARE REQUIRED TO COMPLY WITH STATE WATER QUALITY STANDARDS (HAWAII
ADMINISTRATIVE RULES, CHAPTER 11-54). BEST MANAGEMENT PRACTICES SHALL BE USED TO MINIMIZE OR PREVENT THE DISCHARGE OF SEDIMENT, DEBRIS, AND OTHER POLLUTANTS TO STATE WATERS. PERMIT
COVERAGE IS AVAILABLE FROM THE DEPARTMENT OF HEALTH, CLEAN WATER BRANCH AT
HTTP://HEALTH.HAWAII.GOV/CWB. THE OWNER/DEVELOPER/CONTRACTOR IS RESPONSIBLE FOR OBTAINING
OTHER FEDERAL, STATE, OR LOCAL AUTHORIZATIONS AS REQUIRED BY LAW.
5. CONFINED SPACE
FOR ENTRY BY CITY PERSONNEL, INCLUDING INSPECTORS, INTO A PERMIT REQUIRED CONFINED SPACE AS DEFINED IN 29 CFR PART 1910.146(B), THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING:
I. ALL SAFETY EQUIPMENT REQUIRED BY THE CONFINED SPACE REGULATIONS APPLICABLE TO ALL PARTIES OTHER THAN THE CONSTRUCTION INDUSTRY, TO INCLUDE, BUT NOT LIMITED TO, THE
FOLLOWING:
a. FULL BODY HARNESSES FOR UP TO TWO PERSONNEL.
b. LIFELINE AND ASSOCIATED CLIPS.
c. INGRESS/EGRESS AND FALL PROTECTION EQUIPMENT.
d. TWO-WAY RADIOS (WALKIE-TALKIES) IF OUT OF LINE-OF-SIGHT. E. EMERGENCY (ESCAPE)
RESPIRATOR (10 MINUTE DURATION). F. CELLULAR TELEPHONE TO CALL FOR EMERGENCY
ASSISTANCE.
e. CONTINUOUS GAS DETECTOR (CALIBRATED) TO MEASURE OXYGEN, HYDROGEN SULFIDE, CARBON MONOXIDE AND FLAMMABLES (CAPABLE OF MONITORING AT A DISTANCE AT LEAST
20-FEET AWAY).
f. PERSONAL MULTI-GAS DETECTOR TO BE CARRIED BY INSPECTOR.
II. CONTINUOUS FORCED AIR VENTILATION ADEQUATE TO PROVIDE SAFE ENTRY CONDITIONS.
III. ONE ATTENDANT/RESCUE PERSONNEL TOPSIDE (TWO, IF CONDITIONS WARRANT IT).
6. PURSUANT TO CHAPTER 6E, HRS, IN THE EVENT ANY ARTIFACTS OR HUMAN REMAINS ARE UNCOVERED DURING CONSTRUCTION OPERATIONS, THE CONTRACTOR SHALL IMMEDIATELY SUSPEND WORK AND
NOTIFY THE HONOLULU POLICE DEPARTMENT, THE STATE DEPARTMENT OF LAND AND NATURAL
RESOURCES-HISTORIC PRESERVATION DIVISION (692-8015). IN ADDITION, FOR NON-CITY PROJECTS, THE
CONTRACTOR SHALL INFORM THE CIVIL ENGINEERING BRANCH, DEPARTMENT OF PLANNING AND
PERMITTING (768-8084); AND FOR CITY PROJECTS, NOTIFY THE RESPONSIBLE CITY AGENCY.
MAXIMUM
MECHANICAL
MANHOLE
MISCELLANEOUS
MINIMUM
NORTH
NOT TO SCALE
NUMBER
ON CENTER
OUTSIDE DIAMETER
OFFSET
PORTLAND CEMENT CONCRETE
PAVEMENT
POUNDS PER SQUARE FOOT
PROPERTY LINE, PLACE
POLYVINYL CHLORIDE
POWER POLE
POUNDS PER SQUARE INCH
RADIUS
REQUIRED
REINFORCEMENT
REVISION/REVISED
RIGHT OF WAY
SOUTH, SLOPE, SEWER
SCHEDULE
SQUARE FOOT
SHEET
SEWER LINE
SEWER MANHOLE
SPECIFICATION
SQUARE
STAINLESS STEEL
STREET
STATION
STANDARD
SQUARE YARD
TOP
THICK
TYPICAL
VALVE BOX
VITRIFIED CLAY PIPE
VERTICAL
WATER, WEST
WITH
WATERLINE
WATER MANHOLE
WATER METER
WATER VALVE
WELDED WIRE FABRIC
WASTEWATER SYSTEM
MAX
MECH
MH
MISC
MIN
N
NTS
NO
OC
OD
O/S
PCC
PAV'T
PSF
PL
PVC
PP
PSI
R
REQ'D
REINF
REV
ROW
S
SCH
SF
SHT
SMH
SPEC
SQ
SST
ST
STA
STD
SY
T
THK
TYP
VB
VCP
VERT
W
WL
WMH
WM
WV
WWF
WWS
ASPHALTIC CONCRETE
AMERICANS WITH DISABILITIES ACT
AMERICANS WITH DISABILITIES ACT
ACCESSIBILITY GUIDELINES
AND
APPROXIMATE, APPROXIMATELY
AMERICAN SOCIETY FOR TESTING
MATERIALS
AT
BOTTOM
BUILDING
BOTTOM OF CURB, BEGIN CURVE
CAST IN PLACE
CATCH BASIN
CUBIC FEET PER SECOND
CLEAN OUT
CONNECT, CONNECTION
CENTERLINE
CONCRETE
CONTINUE, CONTINUOUS
CLEAN OUT TO GRADE
CUBIC YARD
DETAIL
DIAMETER
DRAIN INLET, DUCTILE IRON
DRAIN MANHOLE
DEPARTMENT OF PLANNING &
PERMITTING
DEPARTMENT OF PUBLIC WORKS
DRAWING
EAST, EASTING
EACH
EXPANSION JOINT
ELECTRIC, ELECTRICAL
EDGE OF PAVEMENT
ELEVATION
EQUAL
EACH WAY
EXISTING
FOOT, FEET
FIRE HYDRANT
FINISH FLOOR ELEVATION
FINISH GRADE
GALVANIZED
GATE VALVE
HORIZONTAL
INSIDE DIAMETER
INVERT
LATERAL
LENGTH OF CURVE
LINEAR FOOT
LINEAR
POUND(S)
AC
ADA
ADAAG
APPROX
ASTM
B, BOT
BLDG
BC
CIP
CB
CFS
CO
CONN
C
CONC
CONT
COTG
CY
DET
DIA
DI
DMH
DPP
DPW
DWG
E
EA
EJ
ELEC
EP
ELEV, EL
EQ
EW
EXIST, EX
FT
FH
FFE
FG
GALV
GV
HORIZ
ID
INV
LAT
LC
LF
LIN
LB(S)
ABBREVIATIONS:
L
SL
W/
MATCHMA
CITY AND COUNTY OF HONOLULUCCH
CLEARCLR
DRAIND
SANITARY SEWERSS
STORM DRAINSD
EROSION AND SEDIMENTESCP
WATER QUALITY VOLUMEWQV
FIRE DEPARTMENT CONNECTIONFDC
FIRE LINEFL
HIGH-DENSITY POLYETHYLENEHDPE
LENGTHL
CLASSCL
GALLONS PER MINUTEGPM
CAST IRONCI
GROUNDG
SIDEWALKS
SEWER NOTES
1. ALL SEWER CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH THE CITY'S "STANDARD SPECIFICATIONS," SEPT. 1986, THE DEPARTMENT OF ENVIRONMENTAL SERVICES "WASTEWATER SYSTEM DESIGN STANDARDS," JULY 2017, AND "WASTEWATER SYSTEM STANDARD DETAILS," JULY 2017, CURRENT CITY
PRACTICES AND REVISED ORDINANCES OF HONOLULU, 1990 AS AMENEDED.
2. THE UNDERGROUND PIPES, CABLES OR DUCTLINES KNOWN TO EXIST BY THE ENGINEER FROM HIS RESEARCH OF RECORDS ARE INDICATED ON THE PLANS. THE CONTRACTOR SHALL VERIFY THE LOCATION AND DEPTH OF THE FACILITIES, INCLUDING AND AFFECTING SEWER LINES, IN THE PRESENCE OF THE WASTEWATER INSPECTOR AND EXERCISE PROPER CARE IN EXCAVATING THE AREA. THE CONTRACTOR SHALL BE
RESPONSIBLE AND SHALL PAY FOR ALL DAMAGED UTILITIES.
3. SEWER LATERALS SHALL BE CLEAR OF AND NOT CONFLICTING WITH ANY OTHER UTILITY. MINIMUM
HORIZONTAL AND VERTICAL CLEARANCES SHALL BE STRICTLY OBSERVED AND FOLLOWED.
4. SLOPE FOR SEWER LATERALS SHALL BE A MINIMUM OF 2.00%.
5. BUILDING PLUMBING FACILITIES SHALL BE CONTROLLED BY SEWER LATERAL INVERTS.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING CONTINUOUS SEWER SERVICE TO ALL
AFFECTED AREAS DURING CONSTRUCTION.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY SEWAGE SPILLS CAUSED DURING CONSTRUCTION. THE CONTRACTOR SHALL NOTIFY THE STATE DEPARTMENT OF HEALTH AND UTILIZE APPROPRIATE SAMPLING AND ANALYZING PROCEDURES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PUBLIC NOTIFICATIONS AND
PRESS RELEASES.
8. CONFINED SPACE
FOR ENTRY BY CITY PERSONNEL, INCLUDING INSPECTORS, INTO A PERMIT-REQUIRED CONFINED SPACE AS DEFINED IN 29 CFR PART 1910.146(B), THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING:
A. ALL SAFETY EQUIPMENT REQUIRED BY THE CONFINED SPACE REGULATIONS APPLICABLE TO ALL PARTIES OTHER THAN THE CONSTRUCTION INDUSTRY, TO INCLUDE, BUT NOT LIMITED TO, THE
FOLLOWING:
a. FULL BODY HARNESSES FOR UP TO TWO PERSONNEL.
b. LIFELINE AND ASSOCIATED CLIPS.
c. INGRESS/EGRESS AND FALL PROTECTION EQUIPMENT.
d. TWO-WAY RADIOS (WALKIE-TALKIES) IF OUT OF LINE-OF-SIGHT.
e. EMERGENCY (ESCAPE) RESPIRATOR (10 MINUTE DURATION).
f. CELLULAR TELEPHONE TO CALL FOR EMERGENCY ASSISTANCE.
g. CONTINUOUS GAS DETECTOR (CALIBRATED) TO MEASURE OXYGEN, HYDROGEN SULFIDE, CARBON MONOXIDE AND FLAMMABLES (CAPABLE OF MONITORING AT A DISTANCE AT
LEAST 20-FEET AWAY).
h. PERSONAL MULTI-GAS DETECTOR TO BE CARRIED BY INSPECTOR.
B. CONTINUOUS FORCED AIR VENTILATION ADEQUATE TO PROVIDE SAFE ENTRY CONDITIONS.
C. ONE ATTENDANT/RESCUE PERSONNEL TOPSIDE (TWO, IF CONDITIONS WARRANT IT).
9. WHEN CONNECTING TO A LIVE SEWER LINE, THE CONTRACTOR SHALL ABIDE BY ALL CONDITIONS THAT THE STATE DEPARTMENT OF HEALTH SETS FORTH TO MITIGATE ANY WASTEWATER SPILL THAT MAY OCCUR. THE CONTRACTOR SHALL INFORM THE CITY INSPECTOR FIVE (5) WORKING DAYS PRIOR TO THE ACTUAL CONNECTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY FINES AND PENALTIES DUE TO ANY
SPILLS RESULTING FROM THE CONNECTION.
10. THE CONTRACTOR SHALL MAINTAIN VISIBILITY AND MAINTENANCE ACCESS TO LIVE SEWER MANHOLE
LOCATIONS AT ALL TIMES, INCLUDING DURING NON-WORK HOURS AND PAVING OPERATIONS.
CONTROL PLAN
PUBLIC HEALTH SAFETY & CONVENIENCE NOTES
1. THE CONTRACTOR SHALL OBSERVE AND COMPLY WITH ALL FEDERAL, STATE, AND LOCAL LAWS REQUIRED
FOR THE PROTECTION OF THE PUBLIC HEALTH AND SAFETY AND ENVIRONMENTAL QUALITY.
2. THE CONTRACTOR AT THEIR OWN EXPENSE SHALL KEEP THE PROJECT AND ITS SURROUNDING AREAS FREE FROM DUST NUISANCE. THE WORK SHALL BE IN CONFORMANCE WITH THE AIR POLLUTION CONTROL
STANDARDS AND REGULATIONS OF THE STATE DEPARTMENT OF HEALTH.
3. NO CONTRACTOR SHALL PERFORM ANY CONSTRUCTION ACTIVITY SO AS TO CAUSE FALLING ROCK, SOIL OR DEBRIS IN ANY FORM TO FALL, SLIDE OR FLOW ONTO ADJOINING PROPERTIES, STREETS OR NATURAL WATERCOURSES. SHOULD SUCH VIOLATIONS OCCUR, THE CONTRACTOR SHALL IMMEDIATELY MAKE ALL
REMEDIAL ACTIONS NECESSARY.
4. THE CONTRACTOR SHALL PROVIDE, INSTALL AND MAINTAIN ALL NECESSARY SIGNS, LIGHTS, FLARES, BARRICADES, MARKERS, CONES AND OTHER PROTECTIVE FACILITIES AND SHALL TAKE ALL NECESSARY PRECAUTIONS FOR THE PROTECTION, CONVENIENCE AND SAFETY OF THE PUBLIC. THE CONTRACTOR SHALL
APPLY FOR A CONSTRUCTION PERMIT WITH A NOISE POLLUTION CONTROL PLAN.
DEPARTMENT OF DEFENSE
STATE OF HAWAII
REV NO. SYM. DESCRIPTION DATE
OF___
SHT__
DOD ADMINISTRATOR
APPROVED:
DRAWING NO.JOB NO.
DATE
CHECKED BY:DESIGNED BY:
APPROVED BY:DRAWN BY:
SCALE:
FILE______ DRAWER______ FOLDER______
MASON
This work was prepared by me or under my supervision, and construction of this project will be under my observation.
BUILDING 1788
Signature Expiration Date of the License 4/30/2028
CONSTRUCTION NOTES
C001
SHEET
OF________SHEETS
KALAELOA, OAHU, HAWAII
HAWAII NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
KALAELOA, OAHU, HAWAII
EROSION PREVENTION/ SEDIMENT CONTROL NOTES:
1. THE CONTRACTOR SHALL FOLLOW THE GUIDELINES IN THE CITY AND COUNTY OF HONOLULU'S "RULES
RELATING TO WATER QUALITY".
2. MEASURES TO CONTROL EROSION AND OTHER POLLUTANTS SHALL BE IN PLACE BEFORE ANY
EARTHWORK IS INITIATED.
3. TEMPORARY STABILIZATION
TEMPORARY STABILIZATION IS REQUIRED ON DISTURBED AREAS WHICH ARE AT FINAL GRADE OR WHEN
THE DISTURBED AREA WILL NOT BE WORKED FOR 7 CONSECUTIVE DAYS OR MORE. TEMPORARY
STABILIZATION MAY BE ACHIEVED USING SEED AND MULCHING FOR SLOPES LESS THAN 5% AND EITHER
RIP-RAP OR SOD FOR SLOPES IN EXCESS OF 5%.
4. PERMANENT STABILIZATION
ALL DISTURBED AREAS SHALL BE PERMANENTLY STABILIZED USING VEGETATIVE COVERING, PAVEMENT, OR EQUIVALENT, PRIOR TO REMOVING EROSION AND SEDIMENT MEASURES. TRAPPED SEDIMENT AND AREAS OF DISTURBED SOIL WHICH RESULT FROM THE REMOVAL OF THE TEMPORARY MEASURES SHALL
BE IMMEDIATELY AND PERMANENTLY STABILIZED.
5. PRESERVE EXISTING VEGETATION.
CLEARLY MARK THE AREAS TO BE PRESERVED WITH FLAGS OR TEMPORARY FENCING. WHERE
TEMPORARY FENCING IS USED, FENCING MUST BE ADEQUATELY SUPPORTED BY POSTS AND
MAINTAINED IN AN UPRIGHT POSITION.
6. PERIMETER CONTROLS
PERIMETER CONTROLS ARE REQUIRED DOWN SLOPE OF ALL DISTURBED AREAS. MAINTAIN
DOWNSTREAM VEGETATED BUFFER AREA.
7. TRACKING CONTROL
· MINIMIZE SEDIMENT TRACK-OUT ONTO OFF-SITE STREETS, OTHER PAVED AREAS, AND SIDEWALKS FROM VEHICLES EXITING THE CONSTRUCTION SITE BY RESTRICTING VEHICLE TRAFFIC TO PROPERLY DESIGNATED AREAS AND USING ADDITIONAL CONTROLS TO REMOVE SEDIMENT FROM VEHICLE TIRES
PRIOR TO EXITING THE SITE.
· VEHICULAR PARKING AND MOVEMENT ON PROJECT SITES MUST BE CONFINED TO PAVED SURFACES OR PREDEFINED PARKING AREAS AND VEHICLE PATHS, WHICH SHALL BE MARKED WITH FLAGS OR
BOUNDARY FENCING.
· ALL POLLUTANTS AND MATERIALS THAT ARE DROPPED, WASHED, TRACKED, SPILLED, OR OTHERWISE DISCHARGED FROM A PROJECT SITE TO OFF-SITE STREETS, OTHER PAVED AREAS, SIDEWALKS OR
THE MS4 MUST BE CLEANED USING DRY METHODS SUCH AS SWEEPING OR VACUUMING.
· WASHING POLLUTANTS AND MATERIALS THAT ARE DISCHARGED FROM THE PROJECT SITE TO THE MS4 INTO DRAIN INLETS OR CATCH BASINS IS PROHIBITED UNLESS THE MATERIAL IS SEDIMENT AND
THE INLETS ARE DIRECTED TO A SEDIMENT BASIN OR SEDIMENT TRAP.
8. BEST MANAGEMENT PRACTICES (BMPS) SHALL NOT BE REMOVED UNTIL FINAL STABILIZATION IS
COMPLETE FOR THAT PHASE.
9. REFER TO CITY AND COUNTY OF HONOLULU BEST MANAGEMENT PRACTICES MANUAL - CONSTRUCTION, FOR MORE INFORMATION ON BMPS.
GOOD HOUSEKEEPING BMPs:
1. STREET SWEEPING AND VACUUMING
ALL POLLUTANTS DISCHARGED FROM CONSTRUCTION SITE TO OFF-SITE AREAS MUST BE SWEPT OR
VACUUMED EACH DAY BEFORE LEAVING THE JOB SITE.
2. MATERIALS DELIVERY, STORAGE AND USE MANAGEMENT
PREVENT, REDUCE OR ELIMINATE THE DISCHARGE OF POLLUTANTS FROM MATERIAL DELIVERY,
STORAGE AND USE TO THE STORM WATER SYSTEM OR WATERCOURSES BY MINIMIZING THE STORAGE OF HAZARDOUS MATERIALS ONSITE, STORING MATERIALS IN A DESIGNATED AREA, INSTALLING SECONDARY CONTAINMENT. CONSTRUCTION MATERIALS, WASTE, TOXIC AND HAZARDOUS SUBSTANCES, STOCKPILES AND OTHER SOURCES OF POLLUTION SHALL NOT BE STORED IN BUFFER AREAS, NEAR AREAS OF CONCENTRATED FLOW, OR AREAS ABUTTING THE MS4, RECEIVING WATERS, OR DRAINAGE IMPROVEMENTS THAT DISCHARGE OFF-SITE. PRIMARY AND SECONDARY CONTAINMENT CONTROLS AND
COVERS SHALL BE IMPLEMENTED TO THE MEP.
3. SPILL PREVENTION AND CONTROL.
CREATE AND IMPLEMENT SPILL PREVENTION AND RESPONSE PLANS TO ELIMINATE AND MINIMIZE THE
DISCHARGE OF POLLUTANTS TO THE MS4 AND RECEIVING WATERS FROM LEAKS AND SPILLS BY
REDUCING THE CHANCE FOR SPILLS, ABSORBING, CONTAINING AND CLEANING UP SPILLS AND
PROPERLY DISPOSING OF SPILL MATERIALS. AT A MINIMUM, ALL PROJECTS SHALL CLEANUP ALL LEAKS
AND SPILLS IMMEDIATELY.
4. HAZARDOUS MATERIALS
PREVENT OR REDUCE THE DISCHARGE OF POLLUTANTS TO STORM WATER FROM HAZARDOUS WASTE THROUGH PROPER MATERIAL USE AND WASTE DISPOSAL IN THE EVENT THAT HAZARDOUS MATERIALS ARE DISCHARGED TO THE MS4. THE PROPERTY OWNER OR ESCP COORDINATOR SHALL IMMEDIATELY NOTIFY THE DEPARTMENT OF FACILITY MAINTENANCE, HONOLULU FIRE DEPARTMENT, AND HONOLULU
POLICE DEPARTMENT OF THE DISCHARGE BY TELEPHONE. A WRITTEN REPORT DESCRIBING THE
POLLUTANTS THAT WERE DISCHARGED, THE REASONS FOR THE DISCHARGE, AND THE MEASURES THAT HAVE BEEN TAKEN OR WILL BE TAKEN TO PREVENT A REOCCURRENCE OF THE DISCHARGE SHALL BE
SUBMITTED TO THE DIRECTOR NO LESS THAN 3 DAYS AFTER NOTIFICATION BY PHONE.
5. NONHAZARDOUS MATERIALS
IN THE EVENT THAT NON HAZARDOUS MATERIALS ARE DISCHARGED TO THE MS4, THE PROPERTY OWNER OR ESCP COORDINATOR SHALL NOTIFY THE CITY DEPARTMENT OF FACILITIES MAINTENANCE BY
TELEPHONE NO LATER THAN THE NEXT BUSINESS DAY. A WRITTEN REPORT DESCRIBING THE
POLLUTANTS THAT WERE DISCHARGED, THE REASONS FOR THE DISCHARGE, AND THE MEASURES THAT HAVE BEEN TAKEN OR WILL BE TAKEN TO PREVENT A REOCCURRENCE OF THE DISCHARGE SHALL BE
SUBMITTED TO THE DIRECTOR NO LESS THAN 3 DAYS AFTER NOTIFICATION BY PHONE.
6. VEHICLE AND EQUIPMENT CLEANING
ELIMINATE AND MINIMIZE THE DISCHARGE OF POLLUTANTS TO STORM WATER FROM VEHICLE AND EQUIPMENT CLEANING OPERATIONS BY USING OFF-SITE FACILITIES WHEN FEASIBLE, WASHING IN DESIGNATED, CONTAINED AREAS ONLY, AND ELIMINATING DISCHARGES TO THE STORM DRAIN SYSTEM BY EVAPORATING AND/OR TREATING WASH WATER, AS APPROPRIATE OR INFILTRATING WASH WATER
FOR EXTERIOR CLEANING ACTIVITIES THAT USE WATER ONLY.
7. VEHICLE AND EQUIPMENT FUELING
PREVENT FUEL SPILLS AND LEAKS BY USING OFF-SITE FACILITIES, FUELING ONLY IN DESIGNATED AREAS, ENCLOSING OR COVERING STORED FUEL, AND IMPLEMENTING SPILL CONTROLS SUCH AS SECONDARY
CONTAINMENT AND ACTIVE MEASURES USING SPILL RESPONSE KITS.
8. VEHICLE AND EQUIPMENT MAINTENANCE
ELIMINATE AND MINIMIZE THE DISCHARGE OF POLLUTANTS TO STORM WATER FROM VEHICLE AND EQUIPMENT MAINTENANCE OPERATIONS BY USING OFF-SITE FACILITIES WHEN FEASIBLE, PERFORMING WORK IN DESIGNATED AREAS ONLY, USING SPILL PADS UNDER VEHICLES AND EQUIPMENT, CHECKING
FOR LEAKS AND SPILLS, AND CONTAINING AND CLEANING UP SPILLS IMMEDIATELY.
9. SOLID WASTE MANAGEMENT
PREVENT OR REDUCE DISCHARGE OF POLLUTANTS TO THE LAND, GROUNDWATER, AND IN STORM
WATER FROM SOLID WASTE OR CONSTRUCTION AND DEMOLITION WASTE BY PROVIDING DESIGNATED WASTE COLLECTION AREAS, COLLECT SITE TRASH DAILY, AND ENSURING THAT CONSTRUCTION WASTE
IS COLLECTED, REMOVED, AND DISPOSED OF ONLY AT AUTHORIZED DISPOSAL AREAS.
10. SANITARY/SEPTIC WASTE MANAGEMENT
TEMPORARY AND PORTABLE SANITARY AND SEPTIC WASTE SYSTEMS SHALL BE MOUNTED OR STAKED IN, WELL-MAINTAINED AND SCHEDULED FOR REGULAR WASTE DISPOSAL AND SERVICING. SOURCES OF SANITARY AND/OR SEPTIC WASTE SHALL NOT BE STORED NEAR THE MS4 OR RECEIVING WATERS.
11. STOCKPILE MANAGEMENT
STOCKPILES SHALL NOT BE LOCATED IN DRAINAGE WAYS, WITHIN 50 FEET FROM AREAS OF
CONCENTRATED FLOWS, AND ARE NOT ALLOWED IN THE CITY RIGHT-OF-WAY. SEDIMENT BARRIERS OR SILT FENCES SHALL BE USED AROUND THE BASE OF ALL STOCKPILES. STOCKPILES SHALL NOT EXCEED 15 FEET IN HEIGHT. STOCKPILES GREATER THAN 15 FEET IN HEIGHT SHALL REQUIRE 8 FOOT WIDE BENCHING IN ACCORDANCE WITH ROH CHAPTER 18A, ARTICLE 3. STOCKPILES MUST BE COVERED WITH PLASTIC SHEETING OR A COMPARABLE MATERIAL IF THEY WILL NOT BE ACTIVELY USED WITHIN 7 DAYS.
12. LIQUID WASTE MANAGEMENT
LIQUID WASTE SHALL BE CONTAINED IN A CONTROLLED AREA SUCH AS A HOLDING PIT, SEDIMENT BASIN , ROLL-OFF BIN, OR PORTABLE TANK OF SUFFICIENT VOLUME AND TO CONTAIN THE LIQUID WASTES GENERATED. CONTAINMENT AREAS OR DEVICES MUST BE IMPERMEABLE AND LEAK FREE AND SHOULD NOT BE LOCATED WHERE ACCIDENTAL RELEASE OF THE CONTAINED LIQUID CAN DISCHARGE TO WATER
BODIES, CHANNELS, OR STORM DRAINS.
13. CONCRETE WASTE MANAGEMENT
PREVENT OR REDUCE THE DISCHARGE OF POLLUTANTS TO STORM WATER FROM CONCRETE WASTE BY
CONDUCTING WASHOUT OFFSITE OR PERFORMING ONSITE WASHOUT IN A DESIGNATED AREA
CONSTRUCTED AND MAINTAINED IN SUFFICIENT QUANTITY AND SIZE TO CONTAIN ALL LIQUID AND CONCRETE WASTE GENERATED BY WASHOUT OPERATIONS. PLASTIC LINING MATERIAL CONTAINMENT AREAS OR DEVICES SHOULD NOT BE LOCATED WHERE ACCIDENTAL RELEASE OF THE CONTAINED LIQUID CAN DISCHARGE TO WATER BODIES, CHANNELS, OR STORM DRAINS. WASHOUT FACILITIES MUST BE CLEANED, OR NEW FACILITIES MUST BE CONSTRUCTED AND READY FOR USE ONCE THE WASHOUT IS 75 PERCENT FULL. ONCE CONCRETE WASTES ARE WASHED INTO THE DESIGNATED AREA AND ALLOWED TO HARDEN, THE CONCRETE SHOULD BE BROKEN UP, REMOVED, AND DISPOSED OF AS SOLID WASTES.
14. CONTAMINATED SOIL MANAGEMENT
AT MINIMUM CONTAIN CONTAMINATED MATERIAL SOIL BY SURROUNDING WITH IMPERMEABLE LINED BERMS OR COVER EXPOSED CONTAMINATED MATERIAL WITH PLASTIC SHEETING. CONTAMINATED SOIL
SHOULD BE DISPOSED OF PROPERLY IN ACCORDANCE WITH ALL APPLICABLE REGULATIONS.
15. DUST CONTROL.
DUST FROM A PROJECT SITE SHALL NOT BE TRANSPORTED OR DISCHARGED TO OFF-SITE AREAS. THE WORK MUST BE IN CONFORMANCE WITH AIR POLLUTION CONTROL STANDARDS CONTAINED IN THE HAWAII ADMINISTRATIVE RULES: TITLE 11 CHAPTER 60.1 "AIR POLLUTION CONTROL. "ALL ESCPS SHALL
PROVIDE FOR THE CONTROL OF DUST.
· MULCHING TO A DEPTH OF NO LESS THAN 1 INCH.
· SPRINKLING EXPOSED SOILS WITH WATER TO MAINTAIN MOISTNESS AT A DEPTH OF 2-3 INCHES
DURING WORKING HOURS AND NOT TO GENERATE ANY RUNOFF.
· VERTICAL DUST BARRIERS NO LESS THAN 6 FEET IN HEIGHT, CONSTRUCTED OF MATERIALS CAPABLE
OF EFFECTIVELY PREVENTING THE SPREAD OF DUST PARTICLES.
16. BMP AND SITE MAINTENANCE
ALL ESCP BMPS SHALL BE MAINTAINED THROUGHOUT THE DURATION OF THE PROJECT. ADDITIONAL BMPS SHALL BE IMPLEMENTED AS NECCESARY TO ADDRESS EROSION AND SEDIMENT CONTROL AT THE
PROJECT SITE.
EROSION AND SEDIMENT CONTROL PLAN SCHEDULE AND RAIN RESPONSE PLAN:
PROJECT SEQUENCE:
1. INSTALL PERIMETER CONTROLS, CLEARING AND GRUBBING AS NECESSARY FOR THE INSTALLATION OF
THESE BMPS.
2. CLEAR, GRUB AND GRADE THE SITE. RELOCATE, RECONSTRUCT AND MAINTAIN BMPS AS NEEDED TO KEEP THEM EFFECTIVE AT ALL TIMES. INITIATE TEMPORARY STABILIZATION IMMEDIATELY ONCE
GRADING IS COMPLETED.
3. PROCEED WITH CONSTRUCTION WITH LEAST POSSIBLE DISTURBANCE OF VEGETATIVE AREAS AND
TEMPORARY STRUCTURES.
4. PLANT PERMANENT GROUND COVER ACCORDING TO THE LANDSCAPING PLAN AS SOON AS POSSIBLE.
5. REMOVE OR DISMANTLE TEMPORARY EROSION CONTROL STRUCTURES AFTER FULL ESTABLISHMENT OF
PERMANENT VEGETATIVE COVER.
6. PRACTICE GOOD HOUSEKEEPING MEASURES THROUGHOUT THE DURATION OF CONSTRUCTION.
7. INSPECTIONS WILL BE PERFORMED MONTHLY.
RAIN RESPONSE PLAN:
1. THE FOLLOWING WILL BE PERFORMED WHEN HEAVY RAINS, TROPICAL STORM OR HURRICANE IS
IMMINENT OR IS FORECASTED IN THE NEXT 48 HOURS.
2. TEMPORARY SUSPENSION OF ACTIVE GRADING.
3. INSPECT ALL PERIMETER CONTROLS AND MAINTAIN AS NEEDED. REINSTALL ANY PERIMETER CONTROLS
THAT WERE REMOVED DUE TO ACTIVE WORK IN THE AREA.
4. COVER OR RELOCATE MATERIAL STOCKPILES AND LIQUID CONTAINERS TO AVOID CONTACT WITH
RAINWATER.
5. PLACE SPILL PANS OR OIL-ONLY SPILL PADS UNDER CONSTRUCTION VEHICLES TO PREVENT RUNOFF FROM CONTACTING ANY SPILLED PETROLEUM PRODUCTS. PROPERLY DISPOSE OF ANY ACCUMULATED
OILY WATER AFTER THE RAIN EVENT.
6. RE-INSPECT AFTER THE APPROACHING HEAVY RAINS, TROPICAL STORM OR HURRICANE AND REPLACE
OR MAINTAIN BMPS AS NEEDED.
DEPARTMENT OF DEFENSE
STATE OF HAWAII
REV NO. SYM. DESCRIPTION DATE
OF___
SHT__
DOD ADMINISTRATOR
APPROVED:
DRAWING NO.JOB NO.
DATE
CHECKED BY:DESIGNED BY:
APPROVED BY:DRAWN BY:
SCALE:
FILE______ DRAWER______ FOLDER______
MASON
This work was prepared by me or under my supervision, and construction of this project will be under my observation.
BUILDING 1788
Signature Expiration Date of the License 4/30/2028
ESCP NOTES
C002
SHEET
OF________SHEETS
KALAELOA, OAHU, HAWAII
HAWAII NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
KALAELOA, OAHU, HAWAII
HAWAII NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
KALAELOA, OAHU, HAWAII
FS
SANSAN
FS FS FS FS
FS
FS
FS
FSFSFSFS
SCALE: 1" = 40'
UTILITY PLAN
C101
DEPARTMENT OF DEFENSE
STATE OF HAWAII
REV NO. SYM. DESCRIPTION DATE
OF___
SHT__
DOD ADMINISTRATOR
APPROVED:
DRAWING NO.JOB NO.
DATE
CHECKED BY:DESIGNED BY:
APPROVED BY:DRAWN BY:
SCALE:
FILE______ DRAWER______ FOLDER______
MASON
This work was prepared by me or under my supervision, and construction of this project will be under my observation.
BUILDING 1788
Signature Expiration Date of the License 4/30/2028
G R A P H I C S C A L E
1" = 40' 40'20'40' 0 80'
L E G E N D
SEWER LINE
EXIST. SEWER LINE
TRENCH LIMITS
LIMITS OF CONSTRUCTION
PROPERTY LINE
UTILITY PLAN
C101
N N
BEGIN SL A STA 0+00.00
CONN. TO EXIST S6
1-WYE
CONTRACTOR TO VERIFY
INVERT AND LOCATION
SL A STA. 0+02.00
1-WYE
1-SEWER COTG
SEE DET. 3/C201
SL A STA. 0+07.00
CONN. TO BLDG STUB-OUT
SEE PLUMB. FOR CONT.
TRENCH LIMITS
LIMITS OF CONSTRUCTION
E N T E R P R I S E A V E N U E ( C I T Y )
B E
L L
E A
U W
O O
D
T R
E E
T ( P
R I
V A
T E
C I T
Y
M A
I N
T A
I N E
D
B U N K E R H I L L S T R E E T ( P R I V A T E - C I T Y M A I N T A I N E D )
TMK: 9-1-013: 050
SCALE: 1" = 5'
INSET
C101
SEE INSET
RESTORE CONC. SIDEWALK,
SAWCUT ALONG EDGE.
SEE DET. 1/C201 & 4/C201
1" = 5' 5' 0 5' 10'
FILTERSOCK PERIMETER
CONTROL, SEE DET. 5/C201
N O T E S :
1. SEE SHT. C002 FOR ESCP NOTES.
PRE-CONSTRUCTION BMPs
· FILTER SOCK PERIMETER CONTROL
DURING CONSTRUCTION BMPs
· TEMPORARY STABILIZATION
POST-CONSTRUCTION BMPs
· PERMANENT STABILIZATION
SAN SAN
FILTERSOCK PERIMETER CONTROLFS FS
4" PVC C900 DR18
SEWER LINE
BLDG 1786
BLDG 1787
BLDG 1784
BLDG 1788
BLDG 1788
STORAGE
PROPERTY LINE
BLDG 1785
BLDG 1788 STORAGE
SHEET
OF________SHEETS
KALAELOA, OAHU, HAWAII
HAWAII NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
KALAELOA, OAHU, HAWAII
HAWAII NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
KALAELOA, OAHU, HAWAII
1" TY
P.
2" CLR.
8"
4" THICK W/ 6x6-W2.9 WWF
REINF. CENTERED IN SLAB.
(BROOM FINISH)
AS NOTED ON PLAN
8"
FINISH W/ EDGER
(TYP.)
CROSS SLOPE
1% MIN., 2% MAX.
1-#4 (T & B)
CON'T
4"
COMPACTED SUBGRADE
NOTE:
THE CROSS SLOPE ALONG THE ACCESSIBLE ROUTE
SHALL NOT EXCEED 2%.
X-SECTION
6" AGGREGATE BASE
COURSE
* IF SAWCUT IS ≤4 FEET FROM NEAREST
SCORE LINE/JOINT, THEN SAWCUT
AT NEAREST SCORE LINE/JOINT.
PIPE O.D.
2'-0" TYP. 2'-0" TYP.
4'- 6"
M
AX
2'- 0"
M
IN
IM
UM
C
OV
ER
LANDSCAPE
SYMMETRICAL ABOUT CENTER LINE
CONCRETE WALKWAY
SEE DET. 1/C201
*6"
MIN.
SAWCUT AT NEAREST JOINT
OR SCORELINE. PROVIDE
CONN. TO EXIST. WALKWAY,
SEE DET. 2/C201
EXIST. CONC. SIDEWALK
EXIST. BASE
COURSE
6" MINIMUM BASE COURSE OR
MATCH EXISTING THICKNESS
WHICHEVER IS GREATER
COMPACTED SUBGRADE
DETECTABLE WARNING TAPE
6" GRANULAR PIPE CUSHION
(CRUSHED ROCK WELL
GRADED 3/4" MAXIMUM)
SATISFACTORY BACKFILL COMPACT
TO 95% MAXIMUM DENSITY
TOP SOIL
SEWER PIPE
PI
PE
O D 12
M
IN
6"
1/ 2"
FLOW
4" BRASS
COUNTERSUNK PLUG
FLUSH
PAVEMENT
BASE COURSE
4" 1/8 BEND
WYE
FINISH GRADE
1" CHAMFER
PLUG FOR TERMINAL
LINE CONDITION
4" PIPE (LENGTH
AS REQUIRED)
12"x 12"
CONC. PAD
FILTER
SOCK
LIMITS OF GRADING AND
DISTURBED AREA
PROTECTED AREA WORK AREASANDBAG
MIN. LENGTH = 18"
MIN. WIDTH = 12"
MIN. THICKNESS = 3"
PLACE EVERY 6' TYP.
SECTION
PLAN
OVERLAP
RUNOFF FLOW
WORK AREA
RUNOFF FLOW
FI
LT
ER
S
OC
K
PROTECTED AREA
SANDBAG TO
SECURE EACH END
9" DIA. FILTER SOCK
PROTECTED AREA
SANDBAG
MIN. LENGTH = 18"
MIN. WIDTH = 12"
MIN. THICKNESS = 3"
PLACE EVERY 6' TYP.
FILTER SOCK 6 MIN.
OVERLAP
FILTER SOCK
WORK
AREA RUNOFF
FLOW
6" 6"
1/4" MAX.
EXIST. CONC. WALKWAYCONCRETE WALKWAY,
SEE DET. 1/C201
FOR CONCRETE WALKWAY,
SEE DET. 1/C201
JOINT FILLER
NEW CONCRETE WALKWAY
EXISTING CONCRETE WALKWAY
1" DRILLED HOLE EMBED
12" LONG SMOOTH
DOWELS WITH EPOXY.
#5 SMOOTH DOWELS
12" LONG @ 9"O.C.
SECTION PLAN
3/4" = 1'-0" 0 1' 2' 3'
G R A P H I C S C A L E
SCALE: 3/4" = 1'-0"
CONCRETE WALKWAY DETAIL
C201
SCALE: 3/4" = 1'-0"
TYPICAL SEWER TRENCH DETAIL
C201
SCALE: 3/4" = 1'-0"
4'' SEWER CLEANOUT DETAIL
C201
NOT TO SCALE
FILTER SOCK DETAIL
C201
SCALE: 3/4" = 1'-0"
CONNECTION TO EXIST.
WALKWAY DETAIL
C201
DEPARTMENT OF DEFENSE
STATE OF HAWAII
REV NO. SYM. DESCRIPTION DATE
OF___
SHT__
DOD ADMINISTRATOR
APPROVED:
DRAWING NO.JOB NO.
DATE
CHECKED BY:DESIGNED BY:
APPROVED BY:DRAWN BY:
SCALE:
FILE______ DRAWER______ FOLDER______
MASON
This work was prepared by me or under my supervision, and construction of this project will be under my observation.
BUILDING 1788
Signature Expiration Date of the License 4/30/2028
MISCELLANEOUS DETAILS
C201
SHEET
OF________SHEETS
KALAELOA, OAHU, HAWAII
HAWAII NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
KALAELOA, OAHU, HAWAII
HAWAII NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
KALAELOA, OAHU, HAWAII
ABBREVIATIONSMATERIALS
ALL ITEMS & MATERIALS NOTED WITHIN THESE DRAWINGS
ARE NEW UNLESS INDICATED OTHERWISE.
GENERAL NOTES
2.
3.
4.
5.
1. COMPLY WITH THE LATEST CITY, STATE, AND FEDERAL
LAWS, BUILDING CODES, THEIR ADDITIONS, ADDENDA, AND
AMENDMENTS IN THE CONSTRUCTION OF THIS PROJECT.
USE DIMENSIONS NOTED ON DRAWINGS ONLY.
DO NOT SCALE DIMENSIONS FROM THE DRAWINGS.
REPAIR ALL DAMAGE CAUSED BY CONSTRUCTION OF THIS
PROJECT.
LEGEND
A1
AE201
A1
AE203
INT ELEVATION
OR SECTION
REFERENCE
SHT WHERE
OCCURS (TYP)
EXT ELEVATION OR
SECTION REFERENCE
TYP INT
ELEVATION
REFERENCE
DETAIL
REFERENCE
DOOR MARK
WINDOW MARK
A1
AE401
A
BD
C
A1
A-P6.9
FIRE SAFETY DURING CONSTRUCTION, ALTERATION OR
DEMOLITION SHALL BE IN ACCORDANCE WITH NFPA 1,
FIRE CODE, 2021 EDITION.
A-001
WALL TYPE
KEY NOTE
A1
ROOM NAME & NUMBER
ROOM NAME
DEPARTMENT OF DEFENSE
STATE OF HAWAII
REV NO. SYM. DESCRIPTION DATE
OF___
SHT__
DOD ADMINISTRATOR
APPROVED:
DRAWING NO.JOB NO.
DATE
CHECKED BY:DESIGNED BY:
APPROVED BY:DRAWN BY:
SCALE:
FILE______ DRAWER______ FOLDER______
MASON
This work was prepared by me or under my supervision, and construction of this project will be under my observation.
BUILDING 1788
Signature Expiration Date of the License
4/30/2028
SHEET
OF________SHEETS
KALAELOA, OAHU, HAWAII
HAWAII NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
KALAELOA, OAHU, HAWAII
HAWAII NATIONAL GUARD
B1788 BOILER ROOM IMPROVEMENTS
KALAELOA, OAHU, HAWAII
SPECIFICATIONS
CAST-IN-PLACE CONCRETE SPECIFICATIONS:
CAST-IN-PLACE CONCRETE
PROVIDE 4-INCH-THICK CONCRETE PADS UNDER MECHANICAL EQUIPMENT AS
REQUIRED OR THICKNESS INDICATED. REINFORCE AS INDICATED. DOWEL TO FLOOR
STRUCTURE AROUND PERIMETER OF PAD. REFER TO MECHANICAL DRAWINGS FOR
LOCATIONS. PAD SIZE TO EXTEND 6-INCHES BEYOND EDGE OF EQUIPMENT ON ALL
SIDES UNLESS OTHERWISE INDICATED. SET ANCHOR BOLTS FOR MACHINES AND
EQUIPMENT AT CORRECT ELEVATIONS, COMPLYING WITH DIAGRAMS OR TEMPLATES
OF MANUFACTURER FURNISHING MACHINES AND EQUIPMENT.
INCLUDE FORMWORK, REINFORCEMENT, CONCRETE MATERIALS, MIXTURE DESIGN,
BONDING AGENTS, CORROSION-INHIBITING MATERIALS, PLACEMENT PROCEDURES,
AND FINISHES.
SUBMITTALS
FOR EACH TYPE OF PRODUCT INDICATED AND REQUIRED FOR INSTALLATION. INCLUDE
THE FOLLOWING:
ADMIXTURES: INCLUDE LIMITATIONS OF USE, INCLUDING RESTRICTIONS ON
CEMENTITIOUS MATERIALS, SUPPLEMENTARY CEMENTITIOUS MATERIALS, AIR
ENTRAINMENT, AGGREGATES, TEMPERATURE AT TIME OF CONCRETE
PLACEMENT, RELATIVE HUMIDITY AT TIME OF CONCRETE PLACEMENT, CURING
CONDITIONS, AND USE OF OTHER ADMIXTURES.
DESIGN MIXTURES: FOR EACH CONCRETE MIXTURE. SUBMIT ALTERNATE DESIGN
MIXTURES WHEN CHARACTERISTICS OF MATERIALS, PROJECT CONDITIONS,
WEATHER, TEST RESULTS, OR OTHER CIRCUMSTANCES WARRANT
ADJUSTMENTS.
CONCRETE INSTALLATION: A QUALIFIED INSTALLER WHO EMPLOYS PROJECT
PERSONNEL QUALIFIED AS ACI-CERTIFIED FLATWORK TECHNICIAN AND FINISHER AND
SUPERVISOR WHO IS AN ACI-CERTIFIED CONCRETE FLATWORK TECHNICIAN.
INSTALLER SHALL BE EXPERIENCED CAST-IN-PLACE CONCRETE INSTALLER, WITH NOT
LESS THAN FIVE CONSECUTIVE YEARS' EXPERIENCE, SPECIALIZING IN INSTALLING
CAST-IN-PLACE CONCRETE SIMILAR IN MATERIAL, DESIGN, AND EXTENT TO THAT
INDICATED FOR THIS PROJECT AND WHOSE WORK HAS RESULTED IN CONSTRUCTION
WITH A RECORD OF SUCCESSFUL IN-SERVICE PERFORMANCE.
MATERIAL CERTIFICATES: FOR EACH OF THE FOLLOWING, SIGNED BY
MANUFACTURERS:
CEMENTITIOUS MATERIALS.
ADMIXTURES.
FORM MATERIALS AND FORM-RELEASE AGENTS.
STEEL REINFORCEMENT AND ACCESSORIES.
CURING COMPOUNDS.
BONDING AGENTS.
ADHESIVES.
SEMIRIGID JOINT FILLER.
JOINT-FILLER STRIPS.
REPAIR MATERIALS.
MINUTES OF PREINSTALLATION CONFERENCE.
DELIVERY, STORAGE, AND HANDLING
DELIVER, STORE, AND HANDLE STEEL REINFORCEMENT TO PREVENT BENDING AND
DAMAGE.
COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR MINIMUM AND
MAXIMUM TEMPERATURE REQUIREMENTS AND OTHER CONDITIONS FOR STORAGE.
STORE CEMENTITIOUS MATERIALS OFF THE GROUND, UNDER COVER, AND IN A DRY
LOCATION.
PRODUCTS
SOURCE LIMITATIONS:
PROVIDE ALL CONCRETE PRODUCT FROM SINGLE SOURCE AND FROM SINGLE
MANUFACTURER WITH RESOURCES TO PROVIDE PRODUCTS OF CONSISTENT
QUALITY IN APPEARANCE AND PHYSICAL PROPERTIES.
BONDING AGENTS:
EPOXY-MODIFIED, CEMENTITIOUS BONDING AND ANTICORROSION AGENT:
MANUFACTURED PRODUCT THAT CONSISTS OF WATER-INSENSITIVE EPOXY
ADHESIVE, PORTLAND CEMENT, AND WATER-BASED SOLUTION OF CORROSION-
INHIBITINGCHEMICALS THAT FORMS A PROTECTIVE FILM ON STEEL
REINFORCEMENT.
EPOXY BONDING AGENT: ASTM C881/C881M TYPE II OR TYPE V BONDING SYSTEM,
AS REQUIRED, FREE OF VOCS.
JOINT FILLER
EPOXY JOINT FILLER: TWO-COMPONENT, SEMIRIGID, 100 PERCENT SOLIDS,
EPOXY RESIN WITH A SHORE A DUROMETER HARDNESS OF AT LEAST 80 IN
ACCORDANCE WITH ASTM D2240.
CORROSION-INHIBITING MATERIALS
CORROSION-INHIBITING TREATMENT: WATERBORNE SOLUTION OF ALKALINE
CORROSION-INHIBITING CHEMICALS FOR CONCRETE-SURFACE APPLICATION
THAT PENETRATES CONCRETE BY DIFFUSION AND FORMS A PROTECTIVE FILM
ON STEEL REINFORCEMENT.
COMPOSITE REINFORCEMENT MATERIALS
COMPOSITE STRUCTURAL REINFORCEMENT: MANUFACTURER'S SYSTEM
CONSISTING OF CARBON-FIBER OR GLASS-FIBER REINFORCEMENT IN THE FORM
OF TOW SHEET WITH FIELD-APPLIED SATURANT OR PREIMPREGNATED SHEET
AND EPOXY PRIMERS, FILLERS, ADHESIVES, SATURANTS, AND TOPCOATS,
DESIGNED FOR USE AS EXTERNALLY BONDED STRUCTURAL REINFORCEMENT
FOR CONCRETE.
PERFORMANCE REQUIREMENTS
CONCRETE FORMWORK: DESIGN, ENGINEER, ERECT, SHORE, BRACE, AND
MAINTAIN FORMWORK, SHORES, AND RESHORES IN ACCORDANCE WITH ACI 301,
TO SUPPORT VERTICAL, LATERAL, STATIC, AND DYNAMIC LOADS, AND
CONSTRUCTION LOADS THAT MIGHT BE APPLIED, UNTIL STRUCTURE CAN
SUPPORT SUCH LOADS, SO THAT RESULTING CONCRETE CONFORMS TO THE
REQUIRED SHAPES, LINES, AND DIMENSIONS.
FORM-FACING MATERIALS
SMOOTH-FORMED FINISHED CONCRETE: FORM-FACING PANELS THAT WILL
PROVIDE CONTINUOUS, TRUE, AND SMOOTH CONCRETE SURFACES. FURNISH IN
LARGEST PRACTICABLE SIZES TO MINIMIZE NUMBER OF JOINTS. PLYWOOD,
METAL, OR OTHER APPROVED PANEL MATERIALS.
FORM-RELEASE AGENT: COMMERCIALLY FORMULATED FORM-RELEASE AGENT
THAT WILL NOT BOND WITH, STAIN, OR ADVERSELY AFFECT CONCRETE
SURFACES AND WILL NOT IMPAIR SUBSEQUENT TREATMENTS OF CONCRETE
SURFACES. FORMULATE FORM-RELEASE AGENT WITH RUST INHIBITOR FOR
STEEL FORM-FACING MATERIALS.
ADMIXTURES
AIR-ENTRAINING ADMIXTURE: ASTM C260.
CHEMICAL ADMIXTURES: IF USED, PROVIDE ADMIXTURES CERTIFIED BY
MANUFACTURERS TO BE COMPATIBLE WITH OTHER ADMIXTURES AND THAT
WILL NOT CONTRIBUTE WATER-SOLUBLE CHLORIDE IONS EXCEEDING THOSE
PERMITTED IN HARDENED CONCRETE. DO NOT USE CALCIUM CHLORIDE OR
ADMIXTURES CONTAINING CALCIUM CHLORIDE.
CURING MATERIALS
GENERAL: CURING MATERIALS USED SHALL BE GUARANTEED BY
MANUFACTURER, PRIOR TO APPLICATION AND USE, TO NOT AFFECT THE BOND
OR PERFORMANCE OF APPLIED FINISHES. NAMED PRODUCTS MAY BE USED
WHERE MANUFACTURER’S DOCUMENTATION IS PROVIDED DURING
SUBMITTALS.
ABSORPTIVE COVER: AASHTO M 182, CLASS 2, BURLAP CLOTH MADE FROM JUTE
OR KENAF, WEIGHING APPROXIMATELY 9 OZ./SQ. YD. WHEN DRY.
MOISTURE-RETAINING COVER: ASTM C171, POLYETHYLENE FILM OR WHITE
BURLAP-POLYETHYLENE SHEET..
WATER: POTABLE.
CLEAR, WATERBORNE, MEMBRANE-FORMING, DISSIPATING CURING COMPOUND:
ASTM C309, TYPE 1, CLASS B.
RELATED MATERIALS
• EXPANSION- AND ISOLATION-JOINT-FILLER STRIPS: ASTM D1751, ASPHALT-
SATURATEDCELLULOSIC FIBER, ASTM D1752 CORK OR SELF-EXPANDING CORK,
WITH CAP STRIP FOR SEALANT; OR CLOSED-CELL FOAM WITH TEAR-OFF STRIP.
• AT INTERIOR, ROUND, CURVED PENETRATIONS OR JOINTS: PROVIDE CLOSED
CELL, NEOPRENE FILLER. COMPATIBLE WITH SEALANTS AND USE INDICATED.
• SEMIRIGID JOINT FILLER: TWO-COMPONENT, SEMIRIGID, 100 PERCENT SOLIDS,
EPOXY RESIN WITH A TYPE A SHORE DUROMETER HARDNESS OF 80 PER ASTM D
2240.
• BONDING AGENT: ASTM C1059, TYPE II, NON-REDISPERSIBLE, ACRYLIC EMULSION
OR STYRENE BUTADIENE.
• EPOXY-BONDING ADHESIVE: ASTM C881, TWO-COMPONENT EPOXY RESIN,
CAPABLE OF HUMID CURING AND BONDING TO DAMP SURFACES, OF CLASS,
SUITABLE FOR APPLICATION TEMPERATURE AND GRADE TO SUIT
REQUIREMENTS, AND AS FOLLOWS: TYPES I AND II FOR NON-LOAD BEARING AND
TYPES IV AND V, LOAD BEARING, FOR BONDING HARDENED OR FRESHLY MIXED
CONCRETE TO HARDENED CONCRETE.
CONCRETE MIXTURES, GENERAL
• PREPARE DESIGN MIXTURES FOR EACH TYPE AND STRENGTH OF CONCRETE,
PROPORTIONED ON THE BASIS OF LABORATORY TRIAL MIXTURE OR FIELD TEST
DATA, OR BOTH, ACCORDING TO ACI 301 AND IN ACCORDANCE WITH THE
FOLLOWING:
o COMPRESSIVE STRENGTH: 4,000 PSI MINIMUM.
o LIMIT WATER-SOLUBLE, CHLORIDE-ION CONTENT IN HARDENED
CONCRETE TO 0.15 PERCENT BY WEIGHT OF CEMENT.
• ADMIXTURES, GENERAL: USE ADMIXTURES ACCORDING TO MANUFACTURER'S
WRITTEN INSTRUCTIONS. DO NOT ADD MULTIPLE ADMIXTURES
SIMULTANEOUSLY.
o USE WATER-REDUCING, HIGH-RANGE WATER-REDUCING OR PLASTICIZING
ADMIXTURE OR HIGH-RANGE WATER-REDUCING ADMIXTURE
(SUPERPLASTICIZER) IN CONCRETE, AS REQUIRED, FOR PLACEMENT AND
WORKABILITY.
o USE WATER-REDUCING AND RETARDING ADMIXTURE WHEN REQUIRED
BY HIGH TEMPERATURES, LOW HUMIDITY, OR OTHER ADVERSE
PLACEMENT CONDITIONS.
o USE WATER-REDUCING ADMIXTURE IN PUMPED CONCRETE, CONCRETE
FOR SLABS, CONCRETE REQUIRED TO BE WATERTIGHT, AND CONCRETE
WITH A WATER-CEMENTITIOUS MATERIALS RATIO BELOW 0.50.
o AT BOARD-FORMED CONCRETE, USE WATER-REDUCING AND
PLASTICIZING ADMIXTURES.
EXECUTION
FORMWORK
• DESIGN, ERECT, SHORE, BRACE, AND MAINTAIN FORMWORK, ACCORDING TO ACI
301, TO SUPPORT VERTICAL, LATERAL, STATIC, AND DYNAMIC LOADS, AND
CONSTRUCTION LOADS THAT MIGHT BE APPLIED, UNTIL CONCRETE STRUCTURE
CAN SUPPORT SUCH LOADS.
• CONSTRUCT FORMWORK SO CONCRETE MEMBERS AND STRUCTURES ARE OF
SIZE, SHAPE, ALIGNMENT, ELEVATION, AND POSITION INDICATED, WITHIN
TOLERANCE LIMITS OF ACI 117.
• LIMIT CONCRETE SURFACE IRREGULARITIES, DESIGNATED BY ACI 347R AS
ABRUPT OR GRADUAL, AS FOLLOWS:
o SURFACE FINISH-3.0: ACI 117 CLASS A, 1/8 INCH FOR SMOOTH-FORMED
FINISHED SURFACES.
o SURFACE FINISH-2.0: ACI 117 CLASS B, 1/4 INCH FOR ROUGH-FORMED
FINISHED SURFACES AND BOARD-FORMED CONCRETE.
• CONSTRUCT FORMS TIGHT ENOUGH TO PREVENT LOSS OF CONCRETE MORTAR.
• FABRICATE FORMS FOR EASY REMOVAL WITHOUT HAMMERING OR PRYING
AGAINST CONCRETE SURFACES. PROVIDE CRUSH OR WRECKING PLATES WHERE
STRIPPING MAY DAMAGE CAST CONCRETE SURFACES.
• SET EDGE FORMS, BULKHEADS, AND INTERMEDIATE SCREED STRIPS FOR SLABS
TO ACHIEVE REQUIRED ELEVATIONS AND SLOPES IN FINISHED CONCRETE
SURFACES. PROVIDE AND SECURE UNITS TO SUPPORT SCREED STRIPS; USE
STRIKE-OFF TEMPLATES OR COMPACTING-TYPE SCREEDS.
• CLEAN FORMS AND ADJACENT SURFACES TO RECEIVE CONCRETE. REMOVE
CHIPS, WOOD, SAWDUST, DIRT, AND OTHER DEBRIS JUST BEFORE PLACING
CONCRETE.
• RETIGHTEN FORMS AND BRACING BEFORE PLACING CONCRETE, AS REQUIRED,
TO PREVENT MORTAR LEAKS AND MAINTAIN PROPER ALIGNMENT.
• COAT CONTACT SURFACES OF FORMS WITH FORM-RELEASE AGENT, ACCORDING
TO MANUFACTURER'S WRITTEN INSTRUCTIONS, BEFORE PLACING
REINFORCEMENT.
JOINTS
• GENERAL: CONSTRUCT JOINTS TRUE TO LINE WITH FACES PERPENDICULAR TO
SURFACE PLANE OF CONCRETE.
• CONSTRUCTION JOINTS: INSTALL SO STRENGTH AND APPEARANCE OF
CONCRETE ARE NOT IMPAIRED, AT LOCATIONS INDICATED OR AS APPROVED BY
THE CO.
• USE A BONDING AGENT OR ROUGHEN INTERFACE TO 1/4-INCH AMPLITUDE AT
LOCATIONS WHERE FRESH CONCRETE IS PLACED AGAINST HARDENED OR
PARTIALLY HARDENED CONCRETE SURFACES.
• PROVIDE KEY PER DRAWINGS.
• DOWEL IN REBAR WERE INDICATED IN DRAWINGS
CONCRETE PLACEMENT
BEFORE PLACING CONCRETE, VERIFY THE FOLLOWING:
• THAT INSTALLATION OF FORMWORK, REINFORCEMENT, AND EMBEDDED ITEMS
IS COMPLETE AND THAT REQUIRED INSPECTIONS HAVE BEEN PERFORMED.
• DEPOSIT CONCRETE CONTINUOUSLY IN ONE LAYER OR IN HORIZONTAL LAYERS
OF SUCH THICKNESS THAT NO NEW CONCRETE WILL BE PLACED ON CONCRETE
THAT HAS HARDENED ENOUGH TO CAUSE SEAMS OR PLANES OF WEAKNESS. IF A
SECTION CANNOT BE PLACED CONTINUOUSLY, PROVIDE CONSTRUCTION JOINTS
AS INDICATED. DEPOSIT CONCRETE TO AVOID SEGREGATION.
• DEPOSIT CONCRETE IN HORIZONTAL LAYERS OF DEPTH TO NOT EXCEED
FORMWORK DESIGN PRESSURES AND IN A MANNER TO AVOID INCLINED
CONSTRUCTION JOINTS.
• CONSOLIDATE PLACED CONCRETE WITH MECHANICAL VIBRATING EQUIPMENT
ACCORDING TO ACI 301.
• DO NOT USE VIBRATORS TO TRANSPORT CONCRETE INSIDE FORMS. INSERT AND
WITHDRAW VIBRATORS VERTICALLY AT UNIFORMLY SPACED LOCATIONS TO
RAPIDLY PENETRATE PLACED LAYER AND AT LEAST 6 INCHES INTO PRECEDING
LAYER. DO NOT INSERT VIBRATORS INTO LOWER LAYERS OF CONCRETE THAT
HAVE BEGUN TO LOSE PLASTICITY. AT EACH INSERTION, LIMIT DURATION OF
VIBRATION TO TIME NECESSARY TO CONSOLIDATE CONCRETE AND COMPLETE
EMBEDMENT OF REINFORCEMENT AND OTHER EMBEDDED ITEMS WITHOUT
CAUSING MIXTURE CONSTITUENTS TO SEGREGATE.
• HOT-WEATHER PLACEMENT: COMPLY WITH ACI 301 AND AS FOLLOWS:
o MAINTAIN CONCRETE TEMPERATURE BELOW 90 DEG F AT TIME OF
PLACEMENT. CHILLED MIXING WATER OR CHOPPED ICE MAY BE USED TO
CONTROL TEMPERATURE, PROVIDED WATER EQUIVALENT OF ICE IS
CA…