About this opportunity
North Park Public Water District is soliciting bids for the exterior overcoat, wet interior repaint, and miscellaneous repairs of a 500,000-gallon double ellipse elevated water storage tank, with bids due today, October 29, 2026. The opportunity was posted October 27, 2026.
Exterior work requires high-pressure water cleaning at 5,000 to 10,000 PSI and spot power tool cleaning to SSPC-SP11, followed by a three-coat epoxy urethane fluoropolymer system. The wet interior requires abrasive blast cleaning to SSPC-SP10 near-white metal and a three-coat zinc epoxy system. Pit piping requires SSPC-SP6 commercial blast cleaning and a two-coat epoxy system, and foundation repair includes grout repair and a two-coat epoxy system. Polyurethane caulk is applied to roof lap seams. Repair and modification tasks include replacing the riser manway gasket, the wet interior roof hatch, and the roof vent with a pressure vacuum vent; overflow discharge modification; balcony drain holes and balcony access modification; and installing a roof and sidewall platform, a wet interior ladder, a roof handrail with painter's railing, bowl rigging couplings, a riser grate, and cathodic clips with a pressure fitting. The aviation light is relocated.
Two alternates are priced separately: an impressed current cathodic protection system and a mechanical mixer. The tank's low-water level is 130 feet.
The jurisdictions listed are Rock Island County and Manteno Village, Illinois.
Opportunity text
The structure is a 500,000 gal. Double ellipse elevated water storage tank with a low-water level of 130'. Exterior: high-pressure water clean (5,000 to 10,000 PSI) and spot power tool clean to an SSPC-SP11 standard. Apply a 3 coat epoxy urethane fluoropolymer system. Wet interior: abrasive blast clean to an SSPC-SP10 near-white metal standard. Apply a 3 coat Zinc epoxy system. Apply a polyurethane caulk to the roof lap seams. Pit piping: abrasive blast clean to an SSPC-SP6 commercial standard. Apply a 2 coat epoxy system. Foundation: repair grout. Water clean and apply a 2 coat epoxy system. Cathodic protectionalternate: install an impressed current cathodic protection system. Mixer-alternate: install a mechanical mixer. Repairs: replace the riser manway gasket. Replace the wet interior roof hatch. Overflow discharge modification. Install a roof/sidewall platform. Install a wet interior ladder. Balcony drain holes. Balcony access modification. Replace roof vent with a pressure vacuum vent. Install cathodic clips and pressure fitting. Install a roof handrail with a painter's railing. Install bowl rigging couplings. Install a riser grate. Relocate the aviation light.