Z2NB--657-26-110JB - Upgrade Boiler Safety Valves , STL

Closed Pre-Solicitation Posted

Not the latest version. See the latest solicitation from .

Solicitation number
36C25526R0035
Agency
Responses due
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 15 is seeking to procure construction services for the replacement and upgrade of steam safety valves within the steam boiler system in Building 75 at Jefferson Barracks VA Medical Center. The scope of work encompasses the removal and installation of eight steam safety valves total, including six valves across three separate boilers (two per boiler), one safety valve following the PRV station upstream of the deaerator, and one deaerator safety valve. All new equipment and work must comply with VHA Directive 1810, and the contractor is responsible for furnishing all labor, materials, equipment, scaffolding, system testing, and disposal of project-related waste. Award will be made using the Best Value Lowest Price Technically Acceptable source selection process. The presolicitation notice was posted December 8, 2025, with responses to the presolicitation due December 23, 2025 at 12:00 PM Central Time, while the formal solicitation package and drawings are scheduled to be available on or before January 29, 2026, with proposals due on or about February 25, 2026.

This procurement is set aside exclusively for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) under 38 USC 8127(d), and prospective contractors must be registered in both the System of Award Management (SAM) and the VetCert database. The estimated project cost ranges from $150,000 to $500,000, with a 180-calendar-day performance period following the Notice to Proceed. The work involves specific technical requirements, including Type 1 steam safety valves set at 130 psi relieving 28,000 lbs/hr and Type 2 valves set at 135 psi relieving 35,000 lbs/hr, along with a deaerator safety valve set to relieve at 15 psi with a capacity of 2,990 lbs/hr. The contract falls under NAICS code 238220 (Plumbing, Heating, and Air-Conditioning Contractors) with a small business size standard of $19.0 million. An organized site visit will be scheduled prior to solicitation issuance and attendance is highly encouraged, with all questions to be submitted via email to Kevin Farrell, the Contracting Officer, at Kevin.Farrell@va.gov.

Notice text

2 versions

Update #2 · Latest ·

Presolicitation Notice

Presolicitation Notice

Page 5 of 5

Presolicitation Notice

*=Required Field

Presolicitation Notice

Page 1 of 5

657-26-110JB Upgrade Boiler Steam Safety Valves

STATEMENT OF WORK (SOW)

for

CONSTRUCTION PROJECT:

1. This contract is for CONSTRUCTION services for the work required to replace and upgrade steam safety valves within the steam boiler system in Building 75 at the Jefferson Barracks VA.

2. Description: Existing steam safety valves found within the steam boiler system in Building 75 are in need of replacement and upgrading so to improve facility safety and efficiency. To do so, this Scope of Work (SOW) will address a total of eight steam safety valves, which is comprised of two steam safety valves per each of the three separate boilers, one safety valve following the PRV station upstream of the deaerator, and one deaerator safety valve. All new work and equipment shall comply with VHA Directive 1810. The following outlines the SOW for the different valve types, with respect to their adjacent structure/function:

a. Steam Safety Valves on Boiler (SVB) SOW: Removal of two existing SVB per each of the three separate boilers, totally in six SVB to be removed. Installation of two new SVB per each of the three separate boilers, totaling in six SVB to be installed. All new SVB being installed will require flange reducers 2½ x 4 flange reducers, properly upsized drip 90 bowl/cups, upgraded A193 flange steam bolts, and other related materials to complete their proper installation. For all new SVB being installed, steam escape piping contiguous with drip 90 bowl/cup and/or vertically extending upwards through the roof of Building 75 may require modification. For each of the three separate boilers, the two new SVB being installed are to be similar but have unique specifications, as outlined below:

SVB type 1:

Relieve Boiler Steam at 130 psi (Set Point)

Relieve 80% of total steam capacity of 35,000 lbs/hr, or 28,000 lbs/hr

SVB shall be constructed of Cast Steel

SVB type 2:

Relieve Boiler Steam at 135 psi / Set Point

Relieve 100% total steam capacity of 35,000 lbs/hr, or 35,000 lbs/hr

SVB shall be constructed of Cast Steel

b. Safety Valve Following PRV (SVFPRV) SOW: The existing SVFPRV, located upstream of the Deaerator, is to be removed. In its place, a new Kunkle is to be installed. Its installation will require newly upgraded A193 flange steam bolts and other related materials to complete proper installation. The new Kunkle being installed must meet the following specifications: Relieve steam at 15 psi (Set Point)

Relieve steam capacity of 17,972 lbs/hr

Shall be constructed of Cast Steel

c. Deaerator Safety Valve (DASV) SOW: The existing DASV is to be removed. In its place, a new DASV is to be installed, which must meet the following specifications:

Relieve steam at 15 psi (Set Point)

Relieve steam capacity of 2,990 lbs/hr. The acceptable relief steam capacity is 500 lbs/hr to 1,000 lbs/hr.

Shall be constructed of Cast Steel

The contractor shall furnish all labor, supervision, materials, products, tools, equipment, temporary structures (including scaffolding), and any other resources necessary to complete the work as described in this SOW, whether specifically listed or implied by the scope. The contractor shall provide a high level of quality and workmanship. The contractor is responsible for the removal and disposal of any project-related equipment and materials. The contractor shall also assist relevant Building 75 personnel, or independently perform the following duties as required:

Safely shut down, including lock out tag out, of boilers and steam lines

Scaffolding set up and removal

Test the steam system for leaks upon completion of all valve installation

Safely restart steam system, including lock out tag out, and verify proper operations

3. Note: Contractor to abide by all work & requirements set in the final release for construction project specifications.

4. Project shall conform to all Records Management and Privacy Language.

5. The period of performance for this project will be 180 calendar days after NTP issue date.

END OF STATEMENT OF WORK.

Pursuant to 38 USC 8127(d) and in accordance with Public Law 109-461, the Veterans Benefits, Healthcare and Information Technology Act of 2006, this procurement is set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) only.

The project construction cost range is between $150,000 and $500,000. The North American Industry Classification Code (NAICS) for this procurement is 238220 with a small business size standard $19.0 million. The duration of the project is estimated to be 180 calendar days after receipt of notice to proceed. This completion period includes final inspection and clean-up. Award will be made utilizing the Best Value Lowest Price Technically Acceptable Source Selection Process in accordance with Federal Acquisition Regulation Part 15. Proposal submission instructions will be included in the solicitation package. The government plans to award without discussions but reserves the right to hold discussions if necessary. The offeror is responsible for monitoring and downloading any amendments from the SAM Contract Opportunities website, which may be issued to this pre-solicitation.

In accordance with FAR 52.204-7, registration in SAM is required and in accordance with FAR 2.101, prospective contractors must be registered in SAM (System of Award

Management) under the applicable NAICS. Additionally, in accordance with the Veterans Affairs Acquisition Regulation (VAAR) 802.101, VIP Registration prospective (SDVOSB) and (VOSB) contractors must be registered in the VIP database which is now the Veteran Small Business Certification (VetCert) under the applicable NAICS. Firms may obtain SAM- information at http://www.SAM.gov and VIP information at Veteran Small Business Certification (sba.gov). The solicitation package and drawings should be available for download on or before January 29, 2026 and the proposal due date will be on or about February 25, 2026. An organized site visit will be scheduled, and the information will be made available on time for solicitation issuance. Only one site visit will be scheduled and interested offerors are highly encouraged to attend. No hard copies of the solicitation or drawings will be provided; and telephone requests or questions will NOT be accepted. Please email requests or questions to Kevin.Farrell@va.gov and ensure that the subject line reads "Upgrade Boiler Steam Safety Valves, Project #657-26-110JB, Solicitation No. 36C25526R0035 .

Pre-solicitation Notice 36C25526R0035 Project #657-26-110JB, Upgrade Boiler Steam Safety Valves

Update #1 ·

657-26-110JB Upgrade Boiler Steam Safety Valves

STATEMENT OF WORK (SOW)

for

CONSTRUCTION PROJECT:

1. This contract is for CONSTRUCTION services for the work required to replace and upgrade steam safety valves within the steam boiler system in Building 75 at the Jefferson Barracks VA.

2. Description: Existing steam safety valves found within the steam boiler system in Building 75 are in need of replacement and upgrading so to improve facility safety and efficiency. To do so, this Scope of Work (SOW) will address a total of eight steam safety valves, which is comprised of two steam safety valves per each of the three separate boilers, one safety valve following the PRV station upstream of the deaerator, and one deaerator safety valve. All new work and equipment shall comply with VHA Directive 1810. The following outlines the SOW for the different valve types, with respect to their adjacent structure/function:

a. Steam Safety Valves on Boiler (SVB) SOW: Removal of two existing SVB per each of the three separate boilers, totally in six SVB to be removed. Installation of two new SVB per each of the three separate boilers, totaling in six SVB to be installed. All new SVB being installed will require flange reducers 2½ x 4 flange reducers, properly upsized drip 90 bowl/cups, upgraded A193 flange steam bolts, and other related materials to complete their proper installation. For all new SVB being installed, steam escape piping contiguous with drip 90 bowl/cup and/or vertically extending upwards through the roof of Building 75 may require modification. For each of the three separate boilers, the two new SVB being installed are to be similar but have unique specifications, as outlined below:

SVB type 1:

Relieve Boiler Steam at 130 psi (Set Point)

Relieve 80% of total steam capacity of 35,000 lbs/hr, or 28,000 lbs/hr

SVB shall be constructed of Cast Steel

SVB type 2:

Relieve Boiler Steam at 135 psi / Set Point

Relieve 100% total steam capacity of 35,000 lbs/hr, or 35,000 lbs/hr

SVB shall be constructed of Cast Steel

b. Safety Valve Following PRV (SVFPRV) SOW: The existing SVFPRV, located upstream of the Deaerator, is to be removed. In its place, a new Kunkle is to be installed. Its installation will require newly upgraded A193 flange steam bolts and other related materials to complete proper installation. The new Kunkle being installed must meet the following specifications: Relieve steam at 15 psi (Set Point)

Relieve steam capacity of 17,972 lbs/hr

Shall be constructed of Cast Steel

c. Deaerator Safety Valve (DASV) SOW: The existing DASV is to be removed. In its place, a new DASV is to be installed, which must meet the following specifications:

Relieve steam at 15 psi (Set Point)

Relieve steam capacity of 2,990 lbs/hr. The acceptable relief steam capacity is 500 lbs/hr to 1,000 lbs/hr.

Shall be constructed of Cast Steel

The contractor shall furnish all labor, supervision, materials, products, tools, equipment, temporary structures (including scaffolding), and any other resources necessary to complete the work as described in this SOW, whether specifically listed or implied by the scope. The contractor shall provide a high level of quality and workmanship. The contractor is responsible for the removal and disposal of any project-related equipment and materials. The contractor shall also assist relevant Building 75 personnel, or independently perform the following duties as required:

Safely shut down, including lock out tag out, of boilers and steam lines

Scaffolding set up and removal

Test the steam system for leaks upon completion of all valve installation

Safely restart steam system, including lock out tag out, and verify proper operations

3. Note: Contractor to abide by all work & requirements set in the final release for construction project specifications.

4. Project shall conform to all Records Management and Privacy Language.

5. The period of performance for this project will be 180 calendar days after NTP issue date.

END OF STATEMENT OF WORK.

Pursuant to 38 USC 8127(d) and in accordance with Public Law 109-461, the Veterans Benefits, Healthcare and Information Technology Act of 2006, this procurement is set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) only.

The project construction cost range is between $150,000 and $500,000. The North American Industry Classification Code (NAICS) for this procurement is 238220 with a small business size standard $19.0 million. The duration of the project is estimated to be 180 calendar days after receipt of notice to proceed. This completion period includes final inspection and clean-up. Award will be made utilizing the Best Value Lowest Price Technically Acceptable Source Selection Process in accordance with Federal Acquisition Regulation Part 15. Proposal submission instructions will be included in the solicitation package. The government plans to award without discussions but reserves the right to hold discussions if necessary. The offeror is responsible for monitoring and downloading any amendments from the SAM Contract Opportunities website, which may be issued to this pre-solicitation.

In accordance with FAR 52.204-7, registration in SAM is required and in accordance with FAR 2.101, prospective contractors must be registered in SAM (System of Award

Management) under the applicable NAICS. Additionally, in accordance with the Veterans Affairs Acquisition Regulation (VAAR) 802.101, VIP Registration prospective (SDVOSB) and (VOSB) contractors must be registered in the VIP database which is now the Veteran Small Business Certification (VetCert) under the applicable NAICS. Firms may obtain SAM- information at http://www.SAM.gov and VIP information at Veteran Small Business Certification (sba.gov). The solicitation package and drawings should be available for download on or before December 19th, 2025 and the proposal due date will be on or about January 15th, 2026. An organized site visit will be scheduled, and the information will be made available on time for solicitation issuance. Only one site visit will be scheduled and interested offerors are highly encouraged to attend. No hard copies of the solicitation or drawings will be provided; and telephone requests or questions will NOT be accepted. Please email requests or questions to Kevin.Farrell@va.gov and ensure that the subject line reads "Upgrade Boiler Steam Safety Valves, Project #657-26-110JB, Solicitation No. 36C25526R0035 .

Pre-solicitation Notice 36C25526R0035 Project #657-26-110JB, Upgrade Boiler Steam Safety Valves

Files

File Type Posted
36C25526R0035_2.docx DOCX document
36C25526R0035.docx DOCX document

Notice history

Notice Type Posted
Z2NB--657-26-110JB - Upgrade Boiler Safety Valves , STL Latest solicitation Solicitation
This notice Original Pre-Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
J048--NEW - Energy Center Steam Header& Boilers valves, gaskets, and vent replacement Department Of Veterans Affairs VA North Texas Health Care System Dallas TX 75216 · NAICS 238220 Veterans Integrated Service Network 17 Service-Disabled Veteran-Owned Small Business
Z1DA--Project 695-24-107 Replace Boilers 4 and 5 Clement J. Zablocki, VA Medical Center 5000 West National Avenue Milwaukee, WI 53295 United States · NAICS 238220 Veterans Integrated Service Network 12 Service-Disabled Veteran-Owned Small Business
N048-- B41 Isolation Valve Installation Department of Veterans Affairs Veterans Health Administration North Little Rock AR 72114 · NAICS 238220 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business
Z2DA--657-27-103JB, FCA Replace Building 51 Roof, JB St. Louis Vamc St. Louis MO 63125 · NAICS 236220 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business
Z1DA--550-20-121 Demo Old Boiler Plant B100 (CON) Veterans Affairs Illiana Healthcare System -Vaihcs Danville, Illinois 61832, United States · NAICS 236220 Veterans Integrated Service Network 12 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors