Z1DA--676-21-704 EHRM Next Gen Wifi

Closed Pre-Solicitation Posted

Not the latest version. See the latest solicitation from .

Solicitation number
36C25222Q0857
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Notice details come from SAM.gov. Updated .

Notice text

3 versions

Update #3 · Latest ·

CANCELLATION RESCINDED. BIDS DUE 9/15 WITH ANTICIPATED AWARD IN OCTOBER

Update #2 ·

SOLICITATION HAS BEEN CANCELED DUE TO FUNDING. SHOULD BE RE-SOLICITED IN OCTOBER.

Update #1 ·

Solicitation is forthcoming.

Site Visit, Thursday, August 18, 2022 from 2PM TO 3PM. Short Notice is to assure award by Sept. 30, 2022.

CONSTRUCTION SCOPE OF WORK

EHRM NEXTGEN WIFI UPGRADES

PROJECT NO: 676-21-704

PROJECT NAME: EHRM NextGen WiFi Upgrades Tomah, WI

1. GENERAL INTENT:

The Contractor shall furnish all labor, tools, materials, and equipment to support installation of replacement and new WiFi Access Points at Tomah VA Medical Center campus located at 500 East Veterans Street, Tomah, WI. The AT&T NextGen WiFi Contractor is responsible for the bulk of the work under a separate OI&T contract. Please note that the scope of this work is limited and specifically as listed below.

2. STATEMENT OF WORK:

Provide and install conduit, raceways, horizontal and vertical penetrations, and fire stopping to support NextGen WiFi installation on the Tomah VA campus as shown and described in the project drawings and specifications. A list of required conduits and/or penetrations are provided in Appendix 1.

Work shall include:

1. Total estimated length of conduit to install is 1,024 linear feet, including junction boxes, pull cords, and fire stopping, throughout the Medical Center.

2. Work shall be performed during business hours, Monday thru Friday, 8 AM to 4:30 PM.

3. Conduit, straps and screws must be white in color. Final mounting location of conduit must

3. PERIOD OF PERFORMANCE:

3.1 Work timelines and completion progress shall be communicated to the COR for tracking purposes on a weekly basis. With work being completed in 60 days from notice to proceed. Â

Â

4. REFERENCES:

1. attached drawings sets for general conduit run location.

5. SPECIFICATIONS:

DIVISION 01 - GENERAL REQUIREMENTS

01 00 00 General Requirements

01 32 16.15 Project Schedule

01 33 23 Shop Drawings, Product Data, and Samples

01 35 26 Safety Requirements

01 74 19 Construction Waste Management

DIVISION 07 THERMAL AND MOISTURE PROTECTION

07 84 00 Firestopping

DIVISION 27 COMMUNICATIONS

27 05 11 Requirements for Communications Installations

27 05 33 Raceways and Boxes for Communications Systems

27 15 00 Communications Structured Cabling

6. SUBMITTALS:

The contractor shall submit the following submittals for review:

Product data and sample of conduit or raceway.

As-built drawings for all conduit run locations and final end location.

6. ATTACHMENTS:

6.1 Attachment 1: NextGen WiFi Access Point location drawings

6.2 Attachment 2: Specifications

The above paragraphs constitute a basic outline of the work to be accomplished and in no way comprises all the details for this project. Contractor shall refer to drawings and specifications for comprehensive construction requirements. The C&A requirements do not apply, and that a security Accreditation is Package is not required.

Appendix 1: Conduit Installation Checklist

Site

Bldg.

Floor

Area

Issue to be Addressed

Complete

VAMC

32

B

Hallway above 007

VA to provide conduit pathway from IT closet B32-F1-110 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP04 location

Yes

VAMC

36

1

107C

VA to provide conduit pathway from IT closet 110 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP01 location

Yes

VAMC

400

1

1030

VA to provide conduit pathway from IT closet 1068 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated vertically on wall at AP32 location

Yes

VAMC

400

1

1013

VA to provide conduit pathway from IT closet 1068 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated vertically on wall at AP33 location for room containing hard ceiling

Yes

VAMC

401

1

1184

VA to provide conduit pathway from IT closet 1145A to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP02 new location

Yes

VAMC

401

1

1183

VA to provide conduit pathway from IT closet 1145A to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP21 location

Yes

VAMC

402

1

1229

VA to provide conduit pathway from IT closet 1221 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated vertically at AP10 new location

Yes

VAMC

403

1

1300

VA to provide conduit pathway from IT closet 1329 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated vertically on wall at AP24 location

Yes

VAMC

403

1

1375

VA to provide conduit pathway from IT closet 1329 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated vertically on wall at AP27 location

Yes

VAMC

405

1

10510

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP11 location

Yes

VAMC

405

1

10511

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP12 location

Yes

VAMC

405

1

10517

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP13 location

Yes

VAMC

405

1

10523

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP14 location

Yes

VAMC

405

1

10528

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP16 location

Yes

VAMC

405

2

20593

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP02 location

Yes

VAMC

405

2

20508

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP07 location

Yes

VAMC

405

2

20510

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP08 location

Yes

VAMC

405

2

20511

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP09 location

Yes

VAMC

405

2

20517

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP10 location

Yes

VAMC

405

2

20520

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP11 location

Yes

VAMC

405

2

20523

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP12 location

Yes

VAMC

405

2

20537

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP21 location

Yes

VAMC

405

2

20539

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP21 location

Yes

VAMC

405

2

20543

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP21 location

Yes

VAMC

405

2

20584

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP17 location

Yes

VAMC

405

2

20577

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP18 location

Yes

VAMC

405

2

20581

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP19 location

Yes

VAMC

405

2

20587

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP20 location

Yes

VAMC

405

2

20588

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP21 location

Yes

VAMC

405

3

30595

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP02 location

Yes

VAMC

405

3

30512

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP06 location

Yes

VAMC

405

3

30511

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP07 location

Yes

VAMC

405

3

30515

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP08 location

Yes

VAMC

405

3

30520

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP09 location

Yes

VAMC

405

3

30521

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP10 location

Yes

VAMC

405

3

30525

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP11 location

Yes

VAMC

405

3

30537

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP12 location

Yes

VAMC

405

3

30539

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP13 location

Yes

VAMC

405

3

30543

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP14 location

Yes

VAMC

405

3

30545

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP15 location

Yes

VAMC

405

3

30546

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP21 location

Yes

VAMC

405

3

30583

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP17 location

Yes

VAMC

405

3

30588

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP18 location

Yes

VAMC

405

3

30583

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP17 location

Yes

VAMC

405

3

30588

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP18 location

Yes

VAMC

405

3

30587

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP19 location

Yes

VAMC

405

3

30593

VA to provide conduit pathway from drop ceiling hallway to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at new AP20 location

Yes

VAMC

407

1

1746

VA to provide conduit pathway from IT closet 1735 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP19 location

Yes

VAMC

407

1

1741

VA to provide conduit pathway from IT closet 1735 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP23 location

Yes

VAMC

407

2

20715

VA to provide conduit pathway from IT closet 2774 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP06 location

Yes

VAMC

407

2

20711

VA to provide conduit pathway from IT closet 2774 to designed AP location, in glued tile ceiling area, with 4-11/16 dual gang box situated horizontally at AP10 new location

Yes

VAMC

407

2

20736

VA to provide conduit pathway from IT closet 2774 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP17 new location

Yes

VAMC

407

2

20737

VA to provide conduit pathway from IT closet 2774 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP22 location for room containing hard ceilingÂ

Yes

VAMC

407

3

3786

VA to provide conduit pathway from IT closet 3772A to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP07 new location

Yes

VAMC

407

3

3738

VA to provide conduit pathway from IT closet 3772A to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP08 location

Yes

VAMC

408

1

1837

VA to provide conduit pathway from IT closet 1837 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP04 new location

Yes

VAMC

408

2

2826

VA to provide conduit pathway from IT closet 2848 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP24 location

Yes

VAMC

423

1

101

VA to provide conduit pathway from IT closet 100 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP01 location

Yes

VAMC

424

1

5C17

VA to provide conduit pathway from IT closet 1506 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP20 new location

Yes

VAMC

424

1

1531

VA to provide conduit pathway from IT closet 1506 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP21 new location

Yes

VAMC

trE

1

Upper right

VA to provide conduit pathway from IT closet 1506 to designed AP location, in open and hard ceiling area, with 4-11/16 dual gang box situated horizontally at AP02 location

Yes

Files

File Type Posted
36C25222Q0857_3.docx DOCX document
36C25222Q0857_2.docx DOCX document
36C25222Q0857_1.docx DOCX document