UPS Maintenance
Closed Solicitation Posted
- Solicitation number
- N6471026Q0007
- Agency
-
Naval Strategic Systems Programs
Department of the Navy, Department of Defense
- Responses due
- Set-aside
- Total Small Business
Opportunity facts
- NAICS code
- 811210 Electronic and Precision Equipment Repair and Maintenance
- Place of performance
- Silverdale, Washington 98315, United States
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of the Navy Strategic Systems Programs is seeking comprehensive maintenance and repair services for three American Power Conversion (APC) Symmetra PX Uninterruptible Power Supply (UPS) units located at Strategic Weapons Facility Pacific (SWFPAC) on Naval Base Kitsap-Bangor. The contractor must be an APC-certified or authorized service provider and deliver 24/7/365 technical support via telephone and email, emergency on-site response within six hours for critical failures, next-business-day response for non-critical issues, and one annual preventative maintenance visit. All replacement parts, labor, and travel expenses must be covered at 100 percent, and only genuine original equipment manufacturer parts meeting APC specifications may be used to maintain warranty validity. The government will evaluate proposals based on technical merit including delivery date, price, and past performance, with no stated order of relative importance. The solicitation deadline is April 14, 2026 at 5:00 PM local time, and questions must be submitted one day prior to this closing date.
This opportunity is set aside as a total small business contract with specific designation for Women-Owned Small Business (WOSB) concerns, including economically disadvantaged women-owned small business (EDWOSB) status. No incumbent contractor or award value is disclosed in the available documentation. The contract period runs from April 15, 2026 through April 14, 2027, with two optional six-month extensions available through October 14, 2027, covering three UPS units consisting of one 20-kilovolt-ampere unit and two 40-kilovolt-ampere units. Prospective offerors must be registered in the System for Award Management (SAM) and able to obtain base access through DBIDS, Rapid Gate System, or approved equivalent security systems. The place of performance is Silverdale, Washington 98315, and the contract will be a firm-fixed-price commercial services award subject to Service Contract Labor Standards wage requirements and applicable Federal Acquisition Regulation and Defense Federal Acquisition Regulation Supplement clauses.
Notice text
Statement Of Work
UPS Maintenance and Repair
- BACKGROUND
Strategic Weapons Facility Pacific (SWFPAC) requires comprehensive maintenance and repair service contract for three (3) Uninterruptible Power Supply (UPS) units located at SWFPAC facilities on Naval Base Kitsap-Bangor in Silverdale, WA.
The purpose of this contract is to ensure the reliable operation of critical power infrastructure through proactive maintenance and timely emergency support.
2. Equipment Covered:
Make
Model
Description
Serial Number
APC
SYCF40KF
Symmetra PX UPS 20kVA 40 and/or PDU
QD1633340704
APC
SYCF40KF
Symmetra PX UPS 40kVA 40 and/or PDU
QD1830240733
APC
SYCF40KF
Symmetra PX UPS 40kVA 40 and/or PDU
QD1830240729
- SCOPE:
The contractor shall provide all-inclusive preventative maintenance, on-site emergency repair, and remote technical support for the UPS equipment listed in paragraph 2. To ensure the manufacturer's warranty remains valid, services must be delivered by an American Power Conversion (APC)-certified or authorized service provider. All components, parts, and consumables used for maintenance or repair must be new, genuine original equipment manufacturer parts that meet APC specifications.
3.1. Technical Support
The contractor shall provide 24 hours a day, 7 days a week, 365 days a year (24/7/365) telephone and email access to a technical support center for troubleshooting and service dispatch.
3.2. On-Site Support
Emergency On-Site Response: For any critical failure resulting in a loss of redundancy or an inability to support the protected load, a qualified technician must arrive on-site within six (6) hours of the service request being logged. This six (6) hour response shall be guaranteed 24/7/365.
Standard On-Site Response: For non-critical failures where the UPS remains operational, a qualified technician must arrive on-site no later than the next business day.
Parts & Labor: This contract shall cover 100% of the costs for all replacement parts, hardware, capacitors, fans, and any other components needed to restore the UPS units listed in paragraph 2 to full operational status. All associated labor, travel, and expenses for on-site visits shall be included.
Equivalent Hardware: If a failed hardware component is no longer manufactured, it shall be replaced with an equivalent or superior component that is fully compatible.
3.3. Preventative Maintenance (PM)
The contractor shall perform one (1) scheduled on-site preventative maintenance visit during the contract period. This visit shall include all UPS units listed in paragraph 2.
The PM service must include, at a minimum, the following tasks for each UPS:
- Visual Inspection: Check for loose connections, overheating, component discoloration, and physical defects.
- Environmental Checks: Measure and record ambient temperature and humidity.
- Cleaning: Clean and remove dust/debris from the interior and exterior of the UPS.
- Electrical Checks: Perform thermal scans on electrical connections to identify potential failure points. Check and tighten all terminal connections as needed.
- Battery Maintenance: Conduct a full battery string inspection, including voltage checks, impedance testing, and a system load test to verify battery performance and runtime.
- System Calibration: Calibrate and verify all system alarms, setpoints, and transfer mechanisms.
- Firmware & Software: Review installed firmware and operating system software. Install any necessary updates, patches, or security fixes after receiving approval from SWFPAC personnel.
- Functional Test: Perform a full functional test to ensure the unit operates correctly in all modes (e.g., normal, battery, bypass).
4. DELIVERABLES
The following deliverables are required:
Field Service Report: After each preventative maintenance visit or emergency repair, the contractor shall provide a detailed electronic service report within five (5) business days. This report must document all work performed, tests conducted, parts replaced, and findings or recommendations.
Annual System Health Report: At the conclusion of the contract period, the contractor shall provide a summary report detailing the overall health of the UPS fleet, a summary of service activities for the year, and recommendations for future maintenance or upgrades.
5. CONTRACTOR & PERSONNEL REQUIREMENTS
Certification: All on-site technicians must be certified by APC to work on the specified UPS models. Proof of certification may be requested.
Security & Access: The contractor and its personnel must comply with all SWFPAC security protocols, including requirements for background checks, site access, and safety procedures. The contractor will be escorted at all times unless prior arrangements are made.
Base Access: Contractors must be able to gain access to SWFPAC on Naval Base Kitsap – Bangor,
WA. Base access may be granted using the Rapid Gate System, DBIDS System, or other approved base
access system at the Contractor’s expense. Once base access is granted, Contractors will be required to
apply for a visitor badge (BAVR request) at https://www.bavr.cnic.navy.mil/. Coordination of the visitor
badge will be through the Government Point of Contract.
Vehicle Pass: In order to drive a non-Government vehicle to the work location, the contractor must
submit a SWFPAC Vehicle Pass Request and required documents to the COR. The non-Government
vehicle must be registered in the company’s name and must have a clear logo displayed on the vehicle
indicating the company it is registered to. When entering the base, the vehicle must have the approved
vehicle pass displayed in the driver’s side windshield at all times. No Bluetooth, telephonic, or electronic
devices are allowed in secured locations on base.
Files
Notice history
| Notice | Type | Posted |
|---|---|---|
| This notice | Solicitation | |
| UPS Maintenance | Pre-Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| UPS Refurbishment | Naval Sea Systems Command | No set-aside | |
| 26-SIMACQ-D20-0005 D-Dept Control System Parts/Supplies BPA | Naval Sea Systems Command | Total Small Business | |
| Power supply, unint | Naval Supply Systems Command | No set-aside | |
| UPS, nova 1. 25 KVA | Naval Supply Systems Command | No set-aside | |
| 100kW Diesel Generator Lease at PSNS&IMF | Naval Supply Systems Command | Total Small Business |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity