UPS battery backup
Closed Solicitation Posted
This opportunity was awarded. See the award notice from .
- Solicitation number
- 12639526Q0042
- Agency
- Marketing and Regulatory Programs Business Services Animal and Plant Health Inspection Service, Department of Agriculture
- Responses due
- Set-aside
- Total Small Business
Opportunity facts
- NAICS code
- 238210 Electrical Contractors and Other Wiring Installation Contractors
- Place of performance
- Fort Collins, Colorado 80521, United States
- Points of contact
-
- Jim Roloff james.g.roloff@usda.gov (612) 590-7603
Notice details come from SAM.gov. Updated .
About this opportunity
The U.S. Department of Agriculture's Animal and Plant Health Inspection Service is seeking to procure and install an uninterruptible power supply (UPS) backup system for a server at its National Wildlife Research Center in Fort Collins, Colorado. The solicitation requires installation of a 25kW UPS unit on a 60-amp circuit for the main server rack, including a Galaxy VS UPS 25kW 208V with 2 internal 9Ah smart modular battery strings (expandable to 4), a Galaxy VS Maintenance Bypass cabinet, and an Emergency Power Off button. Key requirements include a mandatory site visit scheduled for February 23, 2026, at 10 a.m. Mountain Time, all materials must be onsite the day of installation, contractor personnel must possess valid driver's licenses, and work must be limited to one day during weekday business hours (7 a.m. to 4 p.m.). Evaluation will be based on lowest price technically acceptable approach, considering price reasonableness, technical capability with relevant electrical equipment experience, and past performance based on contractor reputation, schedule adherence, and conformance to specifications. The deadline for submitting questions is March 4, 2026, at 12 p.m. Central Time, and quotations must be submitted by March 11, 2026, at 11 a.m. Mountain Time (extended by Amendment 0001).
This solicitation is designated as a Total Small Business Set-Aside with a small business size standard of $19.5 million, and no incumbent contractors are identified. The estimated project magnitude ranges between $25,000 and $100,000, with a firm-fixed price construction purchase order anticipated for award. Work must commence within five calendar days of receiving the notice to proceed and be completed within 90 days, with a payment bond required within 10 days of award. The battery runtime requirement is less than five minutes, with the primary purpose being to bridge the gap between power outage and generator activation (approximately 30 seconds). Performance will take place at the Animal Research Building, 4101 Laporte Avenue, Fort Collins, Colorado 80521, and prevailing wage rates determined under the Davis-Bacon Act apply to this federally funded construction project.
Notice text
4 versions
Update #4 · Latest ·
Work includes adding a UPS system to a server. Installation includes a 25kW UPS unit on one of the current 60-amp circuits for the main server rack. Equipment includes a Galaxy VS UPS 25kW 208V, 2 internal 9Ah smart modular battery strings, expandable to 4, Start-up 5x8, or equal, and Galaxy VS Maintenance Bypass cabinet, UL, Single-unit 10-40kW 208V, 20-80kW 480V, or equal. Also required is an Emergency Power Off button.
Solicitation and attachment are posted below.
Photos of room and equipment posted below.
RFI: Would you be able to tell me what the battery runtime requirement is for this opportunity? Response: Less than 5 min, main purpose is to run between power outage and when the generator will kick on, which should be less than 30 secs.
An amendment to postpone the closing date for quotes and RFIs and responses are posed below.
Update #3 ·
Work includes adding a UPS system to a server. Installation includes a 25kW UPS unit on one of the current 60-amp circuits for the main server rack. Equipment includes a Galaxy VS UPS 25kW 208V, 2 internal 9Ah smart modular battery strings, expandable to 4, Start-up 5x8, or equal, and Galaxy VS Maintenance Bypass cabinet, UL, Single-unit 10-40kW 208V, 20-80kW 480V, or equal. Also required is an Emergency Power Off button.
Solicitation and attachment are posted below.
Photos of room and equipment posted below.
RFI: Would you be able to tell me what the battery runtime requirement is for this opportunity? Response: Less than 5 min, main purpose is to run between power outage and when the generator will kick on, which should be less than 30 secs.
Update #2 ·
Work includes adding a UPS system to a server. Installation includes a 25kW UPS unit on one of the current 60-amp circuits for the main server rack. Equipment includes a Galaxy VS UPS 25kW 208V, 2 internal 9Ah smart modular battery strings, expandable to 4, Start-up 5x8, or equal, and Galaxy VS Maintenance Bypass cabinet, UL, Single-unit 10-40kW 208V, 20-80kW 480V, or equal. Also required is an Emergency Power Off button.
Solicitation and attachment are posted below.
Photos of room and equipment posted below.
Update #1 ·
Work includes adding a UPS system to a server. Installation includes a 25kW UPS unit on one of the current 60-amp circuits for the main server rack. Equipment includes a Galaxy VS UPS 25kW 208V, 2 internal 9Ah smart modular battery strings, expandable to 4, Start-up 5x8, or equal, and Galaxy VS Maintenance Bypass cabinet, UL, Single-unit 10-40kW 208V, 20-80kW 480V, or equal. Also required is an Emergency Power Off button.
Solicitation and attachment are posted below.
Attachments
| File | Type | Posted |
|---|---|---|
| RFIs and Responses.docx | DOCX document | |
| 12639526Q0042-0001.pdf | ||
| Photos_UPS project.pdf | ||
| Attachment 1_Federal Construction Wage Rates_Larimer County.txt | TXT text file | |
| Combined synopsis-solicitation_12639526Q0017.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| UPS battery backup | Award Notice | |
| UPS battery backup | Solicitation |
On GovTribe
Work this opportunity on GovTribe
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity