The Naval Facilities Engineering Systems Command, Pacific (NAVFAC Pacific) is conducting a market survey to identify potential sources for three Schneider Electric PowerLogic ION8650B meters or equivalent alternatives. The procurement supports FY26 Military Construction Army Project P-219 Pacific Deterrence Initiative: Guam Defense System, Forward Operating Sites, JR Marianas, Guam. The required meters must be fully compatible with existing Schneider PowerLogic ION enterprise control system platform servers in Building 3190 and support revenue metering, power quality analysis, equipment monitoring, and energy management applications. The specifications include true RMS measurement with 1024 samples per cycle, 0.1% measurement accuracy for current and voltage, and compatibility with various voltage and current input ranges. This sources sought notice was posted on August 19, 2025, with responses due by September 3, 2025.

This procurement does not include any set-aside designations and is open to all qualified vendors. The notice specifically mentions Schneider Electric as the brand name product provider, suggesting they may be the current or preferred supplier for this type of equipment. The procurement quantity is limited to three meters, indicating a relatively small-scale acquisition focused on compatibility with existing infrastructure rather than a large-scale deployment. The meters must meet stringent technical specifications including specific voltage ranges (57V to 277V V L-N, 600V L-L maximum), current ratings (1A, 2A, 5A, and 10A nominal), and various power supply options ranging from 120-480V AC configurations. The project is part of the Pacific Deterrence Initiative, reflecting its strategic importance to defense operations in the Pacific region.

Notice text

Notice of intent to use a brand name product.  The Naval Facilities Engineering Systems Command, Pacific (NAVFAC Pacific) is performing a market survey to determine if other potential sources of supply can provide meters that have equal performance and listing/approval requirements to the Schneider Electric PowerLogic ION8650B, 64MB Memory Meter.

FY26 Military Construction Army Project P-219 Pacific Deterrence Initiative: Guam Defense System, Forward Operating Sites, JR Marianas, Guam requires three (3) meters with the following characteristics:

a.  Fully compatible with existing Schnieder Power Logics ION enterprise control system platform servers in Building 3190.

b.  Application: Revenue metering, cogeneration and IPP monitoring, compliance monitoring, power quality analysis, demand and power factor control, load curtailment, equipment monitoring and control; energy pulsing and totalization, instrument transformer correction and outage notification.

c.  Type of measurement:  True rms 1024 samples per cycle.

  1. Measurement accuracy
    • 0.1% Reading for current and voltage
    • 0.1% Power
    • ±0.001 Hz
    • 0.1% Power factor
    • 0.1% Energy

d.  Date update rate: 0.5 cycle or 1 second

e.  Input-voltage characteristics

  1. 57V to 277V V L-N rms nominal voltage
  2. 600 V L-L rms (9s) maximum voltage
  3. 5MΩ/Phase impedance
  4. Inputs: V1, V2, V3, VREF

f.  Input-current characteristics

  1. 1A, 2A, 5A and 10A rated nominal current
  2. 0.01-20A accuracy range
  3. 0.001-24A measurement range
  4. 500A rms for 1 second, non-recurring permissible overload
  5. Socket, 3W, 8VA/Phase, 3 Phase

g.  Standard Power Supply:

  1. 120-277V, L-N RMS (-15%/+20%) 47-63Hz or
  2. 120-480V, L-L RMS (-15%/+20%) 47-63Hz

h.  Auxiliary powered low voltage:

  1. AC: 65-120 (+/- 15%) VLN RMS, 47-63Hz
  2. DC: 80-160 (+/- 20%) VDC

i.  Auxiliary powered high voltage:

  1. AC: 160-277 (+/- 20%) VLN RMS, 47-63Hz
  2. DC: 200-300 (+/- 20%) VDC

j.  Digital Outputs: 4 (Form C) solid state relays (130V AC/200V DC) 50mA AC/DC, 1 (Form A) output

k.  Digital Inputs: up to 3 self-excited, dry contact sensing inputs

l.  Environmental:

  1. Operating Temperature: -40 Degree Celsius to 85 Degree Celsius
  2. Display Operating Range: -40 Degree Celsius to 70 Degree Celsius
  3. Storage Temperature: -40 Degree Celsius to 85 Degree Celsius
  4. Humidity Rating: 5% to 95% RH non-condensing
  5. Dielectric withstand: 2.5kV

m.  Communication:

  1. RS-232/RS-485 port (COM1): 300-115,200 baud (RS-485 to 57,600 bps); Protocols: ION, Modbus/RTU/Mastering, DLMS, DNP 3.0, GPSTRUETIME/DATUM
  2. Internal modem port (COM2): 300-57,600 bps
  3. ANSI 12.18 Type Optical Port (COM3): up to 57,600 bps
  4. RS-485 (COM4): up to 57,600 baud, Modbus, direct connection to a PC or Modem
  5. Ethernet port: 10/100BASE-T, RJ45 connector, protocols: DNP, ION, Modbus/TCP/Mastering, IEC 61850 Ed.2 or 100BASE-FX multimode, male ST connectors, DLMS
  6. EtherGate: Up to 31 Slave devices via serial ports
  7. ModemGate: Up to 31 slave devices

n. Memory: 64MB

This notification is for market research purposes only to identify if other potential sources of supply can meet the requirements of the Government.  This is not a request for proposals, quotes, or an invitation for bid.  The intent of this notice is to identify other potential sources of this product.

To be considered, please submit detailed technical data in order for the Government to conduct a comprehensive evaluation of your product to ensure compatibility with the existing system.  In accordance with FAR 15.201(e), a response to this notice is not an offer and cannot be accepted by the Government to form a binding contract.  The responder is solely responsible for the information it submits and any associated costs.  The Government reserves the right to disregard any submittal that is incomplete or vague.  Please do not submit company brochures.

Please submit complete information by electronic mail to Ms. Carly Essex at carly.t.essex.civ@us.navy.mil no later than 3 September 2025 at 2:00 p.m. H.S.T.  Information received after the due date/time will not be considered.  Any information provided to the Government in response to this Request for Information (RFI) will become U.S. Government property and will not be returned. All proprietary or classified information will be treated appropriately.

Similar open opportunities

Opportunity Agency Set-aside Responses due
Meter, electrical frequ NAICS 334514 Land and Maritime No set-aside
Voltmeter NAICS 334220 Land and Maritime No set-aside
Wattmeter NAICS 334515 Land and Maritime No set-aside
Power supply NAICS 335931 Naval Supply Systems Command No set-aside
Power distribution- NAICS 335931 Land and Maritime No set-aside

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors