5. Will the cameras located on the poles require fiber?
A: Possibly, contractor will need to run a bandwidth test.
6. It mentions that we need to provide network switches. Can you confirm if this is required or will the cameras be tied into existing network infrastructure? Also, in order to determine the distances, can you provide the exact locations of cameras and nearest IDF locations?
A: Contractor will be able to use existing in closets but will need to provide switch at poles.
7. It mentions to include licenses and integrate the new cameras into existing video system. We will need to know what manufacturer of licensing and video system so we can correct the correct parts.
A: Exact Vision Client
8. What VMS platform is currently used to integrate with CCURE?
A: Exact Vision Client
9. Are there available ports on the existing switches in closets? If so, how many?
A: Yes, 2 ports
10. Will cable be terminated onto existing patch panels?
A: Yes
11. What is the estimated distance from closets to Camera poles?
A: Approximately 200 feet
12. Are there existing pathways from closets to poles and are they re-usable?
A: Yes
13. Will cable need to be in conduit? If not, is there a cable tray or will J-hooks be sufficient support?
A: NO
14. Are the existing switches POE+? Does the government wish to reuse the existing switches?
A: Yes and Yes if they are still usable
15. Section 1.5 states that work hours will be Monday through Friday 0600 - 1800 hours, however section 4.1 states that work will vary by location and some work will occur after hours or on the weekends. Can you please clarify these statements?
A: Weekend work hours and after hours work is authorized as long as it is coordinated/requested through the customer.
16. Please provide existing floor plans and site drawings for the associated buildings and grounds?
A: Some of the installation is identified as a secure facility therefor, pictures are not allowed.
17. Is there existing infrastructure to the exterior camera locations? If so is the medium fiber?
A: Yes and Yes
18. Is there existing/usable 110VAC at the exterior camera locations?
A: Yes
19. Are the outside plant locations run underground?
A: Yes
20. Is CAT-6 already run to each camera location, then into a media converter?
A: Unsure, installation of old system took place before anyone on ground was stationed here.
21. Do you have any available C-Cure 9000 camera licenses or will we procure these?
A: licenses will have to be procured.
22. Will recording be required to be setup, or is there current recording in place? If so, what Manufacturer is handling the recording, and is it compatible with these Axis cameras?
A: Recording is already in place, manufacturer is unknown.
* No more questions will be excepted after 3:00 pm 18APR2019. Please submit Bids and capability statements for this requirement no later than the 11:00 am on 25APR2019 to CPT Daryle S. Palmer.
.
Update #2 ·
Solicitation response date changed to conduct site visit and to answer some RFI'S. (see below for information)
*SITE VIST*
A site visit has been scheduled for 18APR2019 at 1000 hours in front of building 1-1621 to allow potential vendors the opportunity to see the requirement location and current systems that are in place. Vendors will be able to ask questions and receive answers from the customer. A record will be kept of all questions and answers to be posted in a solicitation modification for any vendor who cannot attend the site visit. This site visit is not required and all vendors can still bid on this requirement regardless of attendance. Please contact the Fort Bragg visitor's center for information on what is required to get on post at 910-907-5165/5166. The visitor's center is located at 3550 All American Fwy, Fort Bragg, NC 28310.
RFI's and answers:
1. This is a removal of the existing 5 cameras and replacement with 3 - AXIS P3707-PE IP Cameras and one PTZ and one fixed (model not stated in SOW) cameras?
(ANSWER): Generally yes, the current cameras are analog with digital converters and associated hardware. The new cameras will require integration into the current security software with appropriate licenses. The fixed camera should either be the Axis M3045-V or like to monitor an interior entrance.
2. Are the any specific requirements for the PTZ and fixed cameras? i.e. Megapixel, Day/Night, ect..
(ANSWER): See attached documentation for Q6155E camera or like camera compatible
3. What are the est. heights of the individual cameras? (ANSWER): 15-20 Feet on poles exterior; 6-8 feet interior.
4. Do all the existing analog cameras currently run back to a central location? (Answer) Yes
.
Update #1 ·
XVIII Airborne Corps, we will replace and integrate five IP based Power-over-Ethernet (POE) security cameras consisting of three network cameras with an 8-megapixel multi-sensor fixed camera with four varifocal lenses that enable overview and detailed surveillance (AXIS P3707-PE Network Camera or similar). Installation will include two additional security cameras around the perimeter of the Corps HQs; one camera with the same capabilities is to be mounted in an existing location on the exterior of BLDG 1-1326 to replace a non-functioning PTZ camera and one fixed camera (AXIS M3045-V or similar) to be interior mounted and installed in the entryway of BLDG 1-1621 to provide surveillance of interior access into the Stimson Hall and the Corps HQs compound. The four exterior cameras are to be mounted onto existing poles and positions around the perimeter using contractor purchased mounts and protective pendants. Integrate four (4) mounted AXIS P3707-PE, or same capability, IP based power-over-Ethernet cameras into the existing C-CURE 9000 security system software. These cameras will require three (3) pole mount adapters and one (1) corner mount with pendant kits to protect them from the elements. Provide one (1) wall mounted AXIS M3045-V/2MP, or same capability, IP base power-over-Ethernet interior mounted camera into the existing C-CURE 9000 security system software in building 1-1621. These cameras are IP based and monitored from the Security Desk within building 1-1326. An additional work station is available within building 1-1621 to reduce the requirement to access the main HQs building during installation. Contract must include configuration, licensing, programming and testing to integrate the new cameras into the existing CCURE 9000 Security Software and video system..