Repair Chapel Wiring

Awarded Award Notice Posted

Solicitation number
W911S6-17-B-0007
Agency
MICC Dugway Proving Ground Mission and Installation Contracting Command, Department of Defense
Awarded
to Soldier Ridge Construction LLC
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

Contract number
W911S617C0009 Federal contract award
NAICS code
238210 Electrical Contractors and Other Wiring Installation Contractors
PSC
Not on record
Place of performance
Building 5100 (English Village) Dugway, Utah Dugway, Utah 84022, United States

Notice details come from SAM.gov. Updated .

Notice text

Added: Jul 31, 2017 12:40 pm Combined Synopsis/Solicitation
The Mission and Installation Contracting Command (MICC) - Dugway Proving Ground is issuing an Invitation for Bid, to award a single, firm fixed-price contract requires the following: furnish all labor, equipment, transportation, and materials necessary to Repair Chapel Wiring, Building 5100 (English Village) Dugway, Utah. Chapel is in need to be brought up to code as per the National Electrical Code (NEC).
The Scope of Work includes the following:
1. In the meeting room section of the chapel, use the existing conduit, replace and dispose of the existing wire, then provide new wire and wire mold including a ground wire from the panelboard to all loads in accordance with (IAW) the National Electrical Code (NEC).
2. In the meeting room section of the chapel provide new grounded receptacles (20 Amp), to replace existing two wire receptacles, and Ground Fault Circuit Interrupter (GFCI) where required by the NEC.
3. In the kitchen, provide a new UL300A residential fire suppression system over the stove IAW NFPA 96 (current edition) that will provide an auto dialer alarm to dispatch, an audible strobe, be initiated by a high temperature (grease fire), and provide a shunt trip to isolate power to the stove and hood.
4. On the northeast wall of the chapel remove and dispose of the existing distribution panel. Provide a new panelboard, in the same location, with a minimum 70 Amp supply.
5. In the chapel, run the conduit behind the sound treatment wall. Temporarily remove existing furred out wall panels to run new conduit behind the wall. Reinstall wall panels upon completion of electrical installation.
6. Provide new breaker from existing feeder panelboard to the new panelboard IAW the NEC.
7. Provide new breakers for all spaces (used and spare) within the new panelboard.
8. Provide new conduit, wiring, and receptacles to power existing overhead projector from the newly installed panelboard.
9. Remove and dispose of existing carpet in the chapel. Saw-cut and trench the existing chapel floor and provide new conduit, wiring, and dedicated receptacles to provide power to existing sound systems. Patch concrete to enclose the trench and conduit. Provide new carpet over the entire chapel floor where carpet is currently installed.
10. Provide conduit through the floor to allow access to utility tunnel to run existing sound equipment signal cord to remove tripping hazard. 1
12. Paint existing conduit to match the existing wall color.
13 Provide all incidental related work

The Magnitude of Construction of this project is between $100,000 and $250,000. The NAICS code is 238210 and the size standard is $15M. This acquisition will be procured pursuant to the requirements in FAR Part 14 Sealed Bidding.

Closing date is August 31, 2017. A pre-proposal site visit meeting will be held at Dugway, Utah, and the exact date, time and location is noted in solicitation. . This solicitation is a 100% set aside for Service Disabled Veteran-Owned Small Business concerns only; no large business bids will be accepted for this procurement. The firm must be small business under relevant North American Industrial Classification
Standard (NAICS) code and the must be registered and current in www.sam.gov
Period of Performance 150 days from issued of Notice to Proceed.
The solicitation will be available by download only. Downloads are available only through the Federal Business Opportunities - FedBizOpps - website at http://www.fbo.gov. Amendments will be available from the FedBizOpps website by download only. It is the responsibility of all potential offerors to
monitor these sites for release of any future notices and/or release of the solicitation and amendments thereto. Questions may be address john.e.kurek.civ@mail.mil or alfred.j.keetch.civ@mail.mil. Offerors must be registered in the System for Award Management (SAM) in order to be eligible to receive an award from any Government solicitation. Call 1-866-606-8220 for more information or visit the SAM website at http://www.sam.gov. THE GOVERNMENT CHARGES NO FEES FOR REGISTRATION IN
SAM. IF YOU ARE REQUESTED TO SUBMIT A FEE, YOU ARE NOT DEALING WITH THE GOVERNMENT'S SITE. After completing SAM, in order to download documents, contractors and their subcontractors must register at www.fbo.gov. To locate this solicitation, Contractors can go to FedBizOpps at www.fbo.gov and search for the solicitation number. Contractors can register to be put on a plan
holders list that others can access through the FedBizOpps site. It is the Bidder's responsibility to check the Internet address provided as necessary for any posted changes to this solicitation and all amendments. For additional information or assistance, please contact John Kurek, Contract Specialist, phone 435-831-2369 or via email at john.e.kurek.civ@mail.milCombined Synopsis/Solicitation