Remove, dispose & replace 8KW emergency lighting inverter
Closed Solicitation Posted
- Solicitation number
- 70Z039-21-Q-PFA020
- Agency
- Coast Guard Department of Homeland Security
- Responses due
- Set-aside
- Total Small Business
Opportunity facts
- NAICS code
- 238210 Electrical Contractors and Other Wiring Installation Contractors
- Place of performance
- New London, Connecticut 06320, United States
Notice details come from SAM.gov. Updated .
Notice text
The Contractor shall furnish all necessary labor, material, equipment, transportation and supervision to remove, dispose and replace existing 8KW Emergency Lighting Inverter in the Electrical Room (Chase E Basement) located at US Coast Guard Academy New London, CT including removalf all existing batteries (Existing Model #HFT-8000-S-P-OCB12A20A). Dispose of batteries per EPA guidelines for hazardous material. Provide new batteries. Size and number of batteries determined by manufacturer, based on the inverter’s electrical capacity. Input Voltage is 277V at 36A. Connect to existing feeder source from MDP (277V, 60A, single phase). Inverter Output voltage –120VAC. Provide inverter with (12) 20A, 120V, single pole circuit breakers. Connect inverter outputs to existing lighting circuits. All work must be done as specified in the attached Scope of Work (SOW) with pictures.
Work must be completed 90 days after the award date
Site visit is highly recommended:
The POC to make an appointment for site visit is Gerry Gosselin, tel. no. 860.444.8312 (o) | 860.941.0843 (c/p) or email Gerry.G.Gosselin@uscg.mil.
Attachments
| File | Type | Posted |
|---|---|---|
| SF-1449.pdf | ||
| ADDENDUM (REv. 09.04.2020).doc | DOC document | |
| (3) REV 16 04-09-2021.pdf | ||
| (1) SOW_Replace Emergency Lighting Inverter_12667778_01Jul21.pdf | ||
| (2) LTR SAM (ref. only).docx | DOCX document |
On GovTribe
Work this opportunity on GovTribe
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity