Mobile Test Enclosure (MTE) Minimum Requirements
- Dimensions: 20 feet long, 10 feet wide*, 8 feet 6 inches high
- Qty (1) French-style double doors, each door with 28-inch clear opening, Qty (1) escape hatch with a 20-inch diameter opening, and Qty (1) 30-inch personnel door; doors and hatch are aluminum, insulated, and rated IP66 minimum
- Painted in accordance with Structural Steel Painting Council (SSPC) Specifications; coatings are to be applied by a certified SSPC professional
- All welding in accordance with American Welding Society Structural Welding Code D1.1 for any modifications that require welding;
- Structural panel stiffening to ABS High Speed Craft guidelines
- Prior to any modifications, the container shall be ISO/CSC certified and shall contain a CSC plate (International Convention for Safe Containers) dated within 5 years or have met a MIL-STD-3037 inspection and have a current DDFORM2282 decal; all certification documentation, plates, and decals shall be retained, in place, and intact; construction/modifications adheres to USCG Guide to Structural Fire Protection; IP66 complete MTE
- 14 gauge minimum panel container thickness
- Procure and install wire transits
- Procure materials and install a rooftop support structure adequate to support an 850 kg equipment piece; see the current design is shown below.
- Zone 1 Insulation with Ceiling: R30 minimum, Walls: R25 minimum, and Floor: R13 minimum R-Values
- Procure and install five standard EIA-310-D compatible racks - 42u, 19 inch; 24-inches wide, 39-inches depth, 79-inches height
- Procure and install a collapsible roof-top fall protection system
- Wired to accept a 3-phase power supply which shall operate either from a 480 VAC, ungrounded neutral system or 208 VAC
- Install a step-down/isolation transformer rated to isolate and convert the ship’s 480 VAC to the 208/115 VAC for the interior distribution.
- Interior power distribution in the MTE shall be 208/115 VAC with the neutral grounded to the MTE structure
- Procure and install interior lighting and Qty (20) 120V outlets of varying amperage
- Procure and install heating, ventilation, and air conditioning (HVAC) unit with 24,000 BTU cooling capacity minimum
- Non-Flammable insulation and sound absorption
Note: These minimum requirements and drawings are for quote purposes only and are subject to change; they are not the final specifications of the Portable Test Enclosure (MTE).
* This width is not standard; modifications will be required and it is understood ISO/CSC certifications will be rendered invalid.
Attachments
| File | Type | Posted |
|---|---|---|
| drawings.pdf |
Notice history
| Notice | Type | Posted |
|---|---|---|
| Mobile Test Enclosure (MTE) | Award Notice | |
| Mobile Test Enclosure (MTE) | Solicitation | |
| Mobile Test Enclosure (MTE) | Pre-Solicitation |
On GovTribe
Work this opportunity on GovTribe
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity