J061--Triennial Circuit Breaker and Feeder Testing

Closed Pre-Solicitation Posted

Not the latest version. See the latest solicitation from .

Solicitation number
36C26127Q0067
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Place of performance
Department of Veterans Affairs VA Reno Health Care System Reno NV 89502

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration is soliciting capability information for triennial circuit breaker and feeder testing at VA Reno Health Care System in Reno, Nevada, with responses due October 2, 2026 at 12:00 PM Pacific Time. This is a sources sought notice for planning purposes only; no solicitation is currently available, and the Government will use responses to determine procurement strategy and potential small business set-aside eligibility.

Work includes comprehensive testing of Medium Voltage oil-cooled switches, liquid-filled and air-cooled transformers, and circuit breakers (225A 3-pole and above) per ANSI/NETA MTS standards. Testing scope encompasses Very Low Frequency cable testing, connection torqueing and megger testing, functional breaker testing, standard and infrared photography at all Medium Voltage vaults, overcurrent protective device coordination studies with updated single-line diagrams, and arc flash hazard analysis with new labels. Performance must occur during off-hours (6 PM–6 AM and weekends) with photography during normal business hours. Period of performance is 60–90 days after Notice to Proceed, with final deliverables due within 7 days of completion in PDF and CAD format, including reports, photographs, studies, and cost estimates for deficiencies and cable replacement.

Estimated project value is between $250,000 and $750,000. NAICS code 238210 applies with a $19 million small business size standard. Potential offerors must be registered in SAM with current Online Representations and Certifications on file. Service-disabled veteran-owned small businesses and veteran-owned small businesses must have VA verification of ownership and control and SBA listing. Responses should be submitted to Contract Specialist Alex Arter at alex.arter@va.gov.

Notice text

No Solicitation is currently available.

This source's sought notice is for planning purposes only. All information contained herein is preliminary and subject to changes and/or cancellation at the discretion of the Government. Interested vendors shall respond to this notice voluntarily, and at no cost to the Government. The information requested will be used solely within the Department of Veterans Affairs to facilitate decision-making and will not be disclosed outside of the Government. Based upon information received in response to this Sources Sought Notice the Government shall decide on a procurement strategy, which shall include the type of small business set-aside, if appropriate. The eventual procurement strategy and set-aside, if appropriate, is solely within the discretion of the Government.

The applicable North American Industry Classification System (NAICS) Code is 238210, Commercial and Institutional Building Construction, and the small business size standard is $19M.

Potential Offerors must be registered in the System for Award Management (SAM) to be eligible for an award (See https://www.sam.gov/SAM/pages/public/index.jsf ). Potential Offerors must also have a current Online Representations and Certification Application on file with SAM. Service-disabled veteran-owned Small Businesses and Veteran-Owned Small Businesses shall have their ownership and control verified by the Department of Veterans Affairs (VA) and be listed in the U.S. Small Business Administration (SBA) at https://www.sba.gov/.

Description of Services

Triennial Circuit Breaker and Feeder Testing.

Location: VA Reno Health Care System (VARHCS), Reno, NV.

The Department of Veterans Affairs, Sierra Nevada Health Care System, Reno, NV has a requirement for Triennial Circuit Breaker and Feeder Testing per ANSI/NETA MTS. Contractor shall furnish all labor, materials, equipment, supervision and testing for the complete testing of Medium Voltage oil-cooled switches, liquid-filled and air-cooled transformers, low and medium voltage circuit breakers (225A 3-pole and above), and feeder cables. Work includes Very Low Frequency (VLF) testing of MV cables, torqueing and meggering of connections, functional testing/exercising of breakers, standard and infrared photography of electrical equipment, site visits of all MV vaults, overcurrent protective device coordination study with updated single-line diagrams, and arc flash hazard analysis with new labels for the entire campus. Testing shall be performed during off-hours (6PM-6AM and weekends), and photography during normal hours. Final report, photos, studies in PDF/CAD, and cost estimates for deficiencies and full MV cable replacement are required within 7 days of completion.

Period of Performance (POP)

Period of Performance: 60-90 days after NTP.

Sources Sought Information

The Government requests that interested parties review the Description of Services and provide the following capability information to the Contracting Specialist, Alex Arter, at alex.arter@va.gov, by 12:00 PM PST on October 2, 2026:

Business Size (Large/Small)

Business Socio-Economic Status (SDVOSB, WOSB, 8(a), HUBZone, etc.)

SAM record

UEI number

Ability and experience in managing projects between $250,000.00 and $750,000.00. Include general information and technical background describing your firm's experience on contracts requiring similar efforts to meet the program objectives [NETA testing, VLF, breaker testing 225A+, IR scanning, coordination/arc flash study].

Anticipated Teaming Arrangements (if any).

List of Projects (Government and Commercial) that are similar in scope and size.

List of Sub-Contractors you intend to use on a project of this size and scope.

How does your company intend to meet the Limitations on Subcontracting as per 13 CFR 125.6?

Are your Subcontractors from the local area or will they be coming from out of the area? If out of the area, from where?

Interested parties shall not submit more than 10 single-sided, type-written pages using Times New Roman 12-point font or larger. Published literature may be any number of pages.

The Government will use this information when determining its business type decision.

This Sources Sought Notice is not to be construed as a commitment by the Government.

No contract will be awarded as a direct result of this announcement.

Files

File Type Posted
36C26127Q0067.docx DOCX document

Notice history

Notice Type Posted
J061--Triennial Circuit Breaker and Feeder Testing Latest solicitation Solicitation
This notice Original Pre-Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
J061--SOURCES SOUGHT NOTICE - Triennial Electrical Inspection Testing and Maintenance Services Requirement - Louis A Johnson VA Medical Center 36C24527Q0039 Department of Veterans Affairs Louis A Johnson VA Medical Center Clarksburg, West Virginia 26301, United States · NAICS 238210 Veterans Integrated Service Network 5 No set-aside
J061--541 Electrical Power Distribution Equipment Testing, Inspection, and Maintenance - VAMC Cleveland Department of Veterans Affairs Louis Stokes Cleveland VA Medical Center Cleveland, Ohio 44106, United States · NAICS 238210 Veterans Integrated Service Network 10 Total Small Business
J061--triennial electrical maintenance FY26 amendment #3 q&a response, scope update, drawings and panel lists new deadline: 10/27/26 POP start date: 12/01/2026 Southeast Louisiana Veterans Healthcare System New Orleans Vamc New Orleans, Louisiana 77019, United States · NAICS 238210 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business
Z1DA--NRM| 460-26-007 Electrical Distribution Inspection Repairs | NCO 4 Construction East (VA-26-00057558) Department of Veterans Affairs Wilmington DE 19805 · NAICS 236220 Veterans Integrated Service Network 4 Service-Disabled Veteran-Owned Small Business
657A5-26-111, Triennial Electrical Testing Marion, Illinois 62959, United States · NAICS 238210 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business Sole Source

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity