J045--Request for Quote: DA Tank Remove and Replace Perry PT VAMC 512-24-4-444-0163

Closed Solicitation Posted

Solicitation number
36C24524Q0605
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Place of performance
Department of Veterans Affairs Perry Pt Vamc Perry Pt, Maryland 21902, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs (VA), Veterans Health Administration, Veterans Integrated Service Network 5 is seeking a contractor to remove and replace the existing deaeration (DA) tank at the Perry Point VA Medical Center. The contractor shall provide all supervision, labor, materials, and equipment to remove and replace the DA tank in kind, with a new tank capable of producing 70,000 lb/hr of de-oxygenated feedwater at 7-9 psi saturated steam pressure. Key requirements include reconfiguration of existing piping, replacement of cast iron piping with forged steel fittings and cast steel valves, and third-party inspections. The contract will be awarded on a competitive basis, with quotes due by July 15, 2024 at 10AM Eastern Time.

This solicitation does not use any set-asides. The period of performance is estimated at 120 days, with a requirement that the new tank be fully operational by October 9, 2024 or a temporary rental DA tank must be provided. The place of performance is the Perry Point VA Medical Center in Perry Point, Maryland. The NAICS code is 238220 - Plumbing, Heating, and Air-Conditioning Contractors, and the PSC code is J045 - Maintenance/Repair/Rebuild of Plumbing, Heating, and Waste Disposal Equipment.

Notice text

SCOPE OF WORK

PROJECT DATA:

TITLE: Deaeration Tank Replacement

PROJECT No: 512A5-24-009

FACILITY: Perry Point VA Campus

COR: Matt Hargrove P.E., Facilities & Engineering

DURATION: 120 days

GENERAL SCOPE: The Contractor shall provide all supervision, labor, materials and equipment to remove and replace the existing deaeration tank in kind.

Provide deaeration (DA) tank capable of producing 70,000 lb/hr of de-oxygenated feedwater at 7-9 psi saturated steam pressure.

Connections to existing piping shall be made at the nearest available flanged connection, reconfiguration of piping to accommodate new tank system is permissible with approved shop drawing.

Remove existing cast iron DA tank feedwater piping and replace with forged steel fittings and cast steel valves. 2.5 and above, welded or flanged. 2 and below threaded sch 80.

During demolition segregate waste streams, all recyclable materials shall be recycled to the extend practical. Provide waste manifest tickets for waste to landfill and recycled waste.

Match construction and certification of tank in every aspect. The construction certification report has been provided for bidder s information.

Include optional pricing for Belzona or approved equal lining

Provide U-1A Manufacturers Data Report for Pressure Vessels

Replace existing safety devices matching existing. Rebuild and recertify existing safety valves and return to the VA.

Provide third party insurance inspection of installed tank with field inspection report and certification to operate.

A rental deareation tank is in place currently, the new replacement tank must be online and fully operational by October 9th, 2024 or a temporary deaeration tank must be provided until the stationary replacement is complete. The temporary tank must be capable of providing 40,000 lb/hr deaerated water with 100% soft water make-up. The tank and pump set-up must deliver feedwater at all flow rates at 230 psi.

Files

File Type Posted
36C24524Q0605 RFQ PP DA Tank.pdf PDF
36C24524Q0605_1.docx DOCX document

Similar open opportunities

Opportunity Agency Set-aside Responses due
657-27-107JC, Replace Select Hot Water Heating System Saint Louis, Missouri 63103, United States · NAICS 238220 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business Sole Source
Amendment CTX Steam Humidifier Temple, Texas 76504, United States · NAICS 238220 Veterans Integrated Service Network 17 Service-Disabled Veteran-Owned Small Business
Z1DA--FY27 NRM - Replace B98 and B88 Boiler and Sump Pumps Department of Veterans Affairs Va Northern California Health Care System McClellan Park CA 95652, United States · NAICS 236220 Veterans Integrated Service Network 21 No set-aside
Z2DA--FY27 NRM 558-24-160, Domestic Water, Chilled Water and Steam Piping (VA-26-00066009) Durham, North Carolina 27705, United States · NAICS 236220 Veterans Integrated Service Network 6 Service-Disabled Veteran-Owned Small Business
Z1DA--Local | 460-26- 4-5074-0108 | 460-26-999 | Condenser Water Piping Modification | (VA-26-00077929) Department of Veterans Affairs Wilmington Vamc Wilmington DE 19805 · NAICS 236220 Veterans Integrated Service Network 4 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity