This document is a Combined Synopsis/Solicitation Notice for a Request for Quote (RFQ) to remove and replace the deaeration (DA) tank at the Perry Point VA Medical Center (VAMC).
The key details are:
- Solicitation Number: 36C24524Q0605
- Product/Service Code: J045 - Plumbing, Heating, and Sanitation Equipment
- NAICS Code: 238220 - Plumbing, Heating, and Air-Conditioning Contractors
- Agency: Department of Veterans Affairs (VA), Veterans Health Administration, Veterans Integrated Service Network 5
- Scope of Work: Remove and replace the existing DA tank in kind, providing a new tank capable of producing 70,000 lb/hr of de-oxygenated feedwater at 7-9 psi steam pressure. The work includes piping modifications, safety device replacements, and third-party inspections. A temporary rental DA tank must be provided if the new tank is not fully operational by October 9, 2024.
- Response Deadline: July 15, 2024, 10AM Eastern Time
- Period of Performance: 120 days
This solicitation does not use Recovery Act funds and is not set-aside. Pricing for an optional Belzona or approved equal tank lining is requested.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24524Q0605 RFQ PP DA Tank.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Combined Synopsis/Solicitation Notice Combined Synopsis/Solicitation Notice
| SUBJECT* |
| Request for Quote: DA Tank Remove and Replace |
Perry PT VAMC 512-24-4-444-0163
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 21201 |
| SOLICITATION NUMBER* |
| 36C24524Q0605 |
| RESPONSE DATE/TIME/ZONE |
| 07-15-2024 10AM EASTERN TIME, NEW YORK, USA |
| ARCHIVE |
| 30 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
SET-ASIDE
| PRODUCT SERVICE CODE* |
| J045 |
| NAICS CODE* |
| 238220 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
VAMC
Service Team One 10 N Greene St Baltimore MD 21201
POINT OF CONTACT*
Contracting Officer William Chris Galletta willaim.galletta@va.gov Service Team One
PLACE OF PERFORMANCE
| ADDRESS |
| Department of Veterans Affairs |
Perry PT VAMC
59 Avenue D
Perry Pt MD
| POSTAL CODE |
| 21902 |
| COUNTRY |
| USA |
ADDITIONAL INFORMATION
| AGENCY’S URL |
| https://www.va.gov |
| URL DESCRIPTION |
| VA |
| AGENCY CONTACT’S EMAIL ADDRESS |
| william.galletta@va.gov |
| EMAIL DESCRIPTION |
| NCO5 Contracting |
DESCRIPTION
SCOPE OF WORK
1. PROJECT DATA:
TITLE: Deaeration Tank Replacement
PROJECT No: 512A5-24-009
FACILITY: Perry Point VA Campus
COR: Matt Hargrove P.E., Facilities & Engineering
DURATION: 120 days
2. GENERAL SCOPE: The Contractor shall provide all supervision, labor, materials and equipment to remove and replace the existing deaeration tank in kind.
· Provide deaeration (DA) tank capable of producing 70,000 lb/hr of de-oxygenated feedwater at 7-9 psi saturated steam pressure.
· Connections to existing piping shall be made at the nearest available flanged connection, reconfiguration of piping to accommodate new tank system is permissible with approved shop drawing.
· Remove existing cast iron DA tank feedwater piping and replace with forged steel fittings and cast steel valves. 2.5” and above, welded or flanged. 2” and below threaded sch 80.
· During demolition segregate waste streams, all recyclable materials shall be recycled to the extend practical. Provide waste manifest tickets for waste to landfill and recycled waste.
· Match construction and certification of tank in every aspect. The construction certification report has been provided for bidder’s information.
· Include optional pricing for Belzona or approved equal lining
· Provide U-1A Manufacturers Data Report for Pressure Vessels
· Replace existing safety devices matching existing. Rebuild and recertify existing safety valves and return to the VA.
· Provide third party insurance inspection of installed tank with field inspection report and certification to operate.
· A rental deareation tank is in place currently, the new replacement tank must be online and fully operational by October 9th, 2024 or a temporary deaeration tank must be provided until the stationary replacement is complete. The temporary tank must be capable of providing 40,000 lb/hr deaerated water with 100% soft water make-up. The tank and pump set-up must deliver feedwater at all flow rates at 230 psi.
See attached document: 36C24524Q0605 RFQ PP DA Tank.