J044--Boiler Steam Safety Valves replaced New Requirement
Closed Solicitation Posted
- Solicitation number
- 36C24824Q1138
- Agency
-
Veterans Integrated Service Network 8
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- Service-Disabled Veteran-Owned Small Business
Opportunity facts
- NAICS code
- 238220 Plumbing, Heating, and Air-Conditioning Contractors
- PSC
- J044 Maint/Repair/Rebuild Of Equipment- Furnace, Steam Plant, And Drying Equipment; Nuclear Reactors
- Place of performance
- 619 S. Marion Ave. Lake City, Florida 32025, United States
- Points of contact
Notice details come from SAM.gov. Updated .
About this opportunity
Paragraph 1:
The Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 8 is seeking to procure the replacement of boiler steam safety valves and other boiler system deficiencies at the Lake City VA Medical Center in Lake City, Florida. The key requirements include having at least 5 years of experience working on boilers, OSHA 10-hour safety training for all personnel, and the ability to replace various boiler components such as combustion and purge air flow switches, gas pressure switches, boiler disconnects, condensate pump control panels, pressure relief valves, and 6 boiler steam safety valves with new cast steel fittings. Evaluation factors include the contractor's capability, capacity, managerial and technical expertise, past performance, and cost. Responses are due by 3:00 PM ET on July 12, 2024.
Paragraph 2:
This solicitation is set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBs) with the associated North American Industry Classification System (NAICS) code of 238220 and a small business size standard of $19.0M. The place of performance is 619 S Marion Ave, Lake City, FL 32025. The contract period is from July 31, 2024 to July 30, 2025, and the award will be made to the responsible offeror whose quote provides the best benefit to the Government.
Notice text
3 versions
Update #3 · Latest ·
Boiler Steam Safety Valves replacement
The purpose of this amendment is to:
1. Questions provided by contractors are due on July 5, 2024, at 12:00pm.
2. Extend the closing date of solicitation to July 12, 2024.
Updated Statement of Work is shown below:
Background: The Lake City VA Medical Center in Lake City, Florida has needs to have the Boiler Steam Safety Valves replaced with new cast steel safety valves. The VA is replacing cast iron fittings in the steam system with cast steel fittings. Other deficiencies have been identified and those deficiencies will also be corrected.
Objective: Upgrade the boilers at the Lake City VA to clear all deficiencies identified during routine inspection.
Scope of Work:
Coordinate all work with the Contracting Officers Representative (COR)
Replace with new, 6 Combustion Air Flow switches. Two on each boiler.
Replace with new, 6 Purge Air Flow switches. Two on each boiler.
Replace with new, 2 High Gas Pressure switches (1 natural gas, 1 propane) and install Audible Alarm to ring out in the Plant for both.
Replace Boiler 3 Disconnect in VFD Panel.
Replace Condensate Pump Control Panel and all the internals in that panel.
Replace with new, 4 Boiler estops. One by each door.
Replace with new, 2 Pressure Relief Valves for the two reducing stations supplying steam to the DA (cast steel). To include drip pan 90s and the drains run from those 90s.
Replace with new, 6 Boiler Steam Safety Valves. Two on each boiler (cast steel). To include drip pain 90s and the drains run from those 90s. Valves shall be sized and installed correctly to meet VA and BEI standards.
Re-pipe all 6 Boiler Steam Safety discharge pipes with larger piping. (Piping must be straight and sized correctly for the safety valves they serve to ensure proper steam discharge from plant.)
Test all new safety valves to ensure they are functioning are sized correctly. Valves must pass inspection and meet VA compliance once installed and inspected.
All Safety valves shall include drip pan 90s and adequate discharge piping to ensure correct operation per VA standard, BEI standard.
Core bore and repair the new roof penetrations for the new discharge piping. (roof must be resealed)
Discharge the new piping through the roof. Terminate discharge piping at same elevation from roof surface as the existing vents.
Set and test all new switches to ensure they are functioning and compliant.
Provide all documentation to the COR.
Materials:
3 Cast Steel Safety Valves (1 per boiler)
Kunkle Model 300 or approved equal
Setpoint 145 psi
Capacity 6183 lb/hr
3 Cast Steel Safety Valves (1 per boiler)
Kunkle Model 300 or approved equal
Setpoint 150 psi
Capacity 10458 lb/hr
1 Cast Steel Pressure Relief Valve
Kunkle Model 300 or approved equal
Setpoint 25psi
Capacity 2000 lb/hr
1 Cast Steel Pressure Relief Valve
Kunkle Model 300 or approved equal
Setpoint 60psi
Capacity 3700 lb/hr
Estops :
4 each
4 pole Emergency Stop Control Stations
Pressure Switches:
12 each
Antunes Controls
JD-2 Red
0.1 24 W.C.
Pressure Switch for Gas in to Boiler Plant:
1 each
Ashcroft 0-30 psi
Condensate Pump Control Panel
All components in the box
Disconnect Switch for Boiler 3
Qualifications/Certifications: The Contractor Technician shall possess:
Technician shall possess at least five years of experience working on Boilers to perform the services listed in the SOW.
The contractor and all individuals working on the project site must have taken the OSHA Certified 10-hour safety course.
Safety Regulations: All OSHA safety regulations shall be observed during the project. The VA Safety Officer shall have full authority to see that the contractor obeys all safety rules and regulations relative to the fulfillment of this project. Provide the necessary barricades/signage where required.
Scheduling and Hours of Work: All work in areas involved shall be scheduled with the COR. The 10 holidays observed by the Federal Government, are New Years Day, Labor Day, Columbus Day, Veterans Day, Thanksgiving Day, and Christmas or any other day specifically declared by the President of the United States to be a national holiday.
Evaluation/Selection Factor:
The project must be performed by a contractor that has the capability and capacity to perform the job. Managerial expertise, technical expertise, past performance, and, cost will be considered.
Update #2 ·
The closing date is extended to June 28, 2024. A site visit will be conducted for interested contractors on June 25th at 11:00am, location: 619 S Marion Ave, Lake City, FL 32025
Update #1 ·
Description
This is a combined synopsis/solicitation for commercial items prepared in accordance with the format in Federal Acquisition Regulation (FAR) subpart 12.6, Streamlined Procedures for Evaluation and Solicitation for Commercial Items, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation document will not be issued.
This solicitation is issued as an RFQ. The solicitation document and incorporated provisions and clauses are those in effect through Federal Acquisition Circular 2024-05 Effective date 05/22/2024.
This solicitation is set-aside for SDVOSB
The associated North American Industrial Classification System (NAICS) code for this procurement is 238220, with a small business size standard of $19.0 M.
The FSC/PSC is J044.
The Engineering department is seeking to purchase Boiler Safety Valves Replacement repair.
Place of Performance/Place of Delivery
Address:
619 S Marion Ave.
Lake City, FL
Postal Code:
32025
Country:
UNITED STATES
The following solicitation provisions apply to this acquisition:
FAR 52.212-1, Instructions to Offerors Commercial Products and Commercial Services (NOV 2021)
Offerors are to submit any questions regarding this requirement via email to jose.hernandez@va.gov on or before 3:00 pm on 6/17/2024 with the subject line, Boiler Safety Valves Replacement repair. An amendment responding to all questions, which may or not extend the response due date, will be published at the GPE.
Offerors shall e-mail complete quotes to jose.hernandez@va.gov at the date and time stated on the Combined Synopsis/Solicitation Notice and Description.
Provide the following information:
1. Solicitation number
2. Name and address of your company
3. Point of contact; name, e-mail, and phone number
4. UEI number
5. Unit and Total Prices as specified in Section Price Schedule.
Note: To be considered for award, an offeror shall have an active registration in the System for Award Management (SAM).
Offerors must complete annual representations and certifications electronically via the System for Award Management (SAM) website located at https://www.sam.gov/portal in accordance with FAR 52.212-3, Offerors Representations and Certifications Commercial Items. If paragraph (j) of the provision is applicable, a written submission is required.
All quoters shall submit the following:
Detailed quote with line item priced out.
Technician shall possess experience working on Boiler Controls to perform the services listed in the SOW.
The contractor and all individuals working on the project site must have taken the OSHA Certified 10-hour safety course.
The contractor will provide capability and capacity to perform the job. Managerial expertise, technical expertise and cost will be considered.
The Government will evaluate all quotations using the Comparative Evaluation process outlined in FAR 13.106-2(b)(3), where quotations will be compared to one another to determine which provides the best benefit to the Government. See E.3 E.4 52.212-1 Instructions to Quoters and E.5 52.212-2 Evaluation of Quotes for more information. There will be no formal site visit for this Solicitation.
Submission of your response shall be received not later than 3pm ET, June 21, 2024 at jose.hernandez@va.gov.
Late submissions shall be treated in accordance with the solicitation provision at FAR 52.212-1(f).
Any questions or concerns regarding this solicitation should be forwarded in writing via e-mail to the Point of Contact listed below.
Point of Contact
Jose J Hernandez, contract specialist jose.hernandez@va.gov
Files
| File | Type | Posted |
|---|---|---|
| 36C24824Q1138 0002.docx | DOCX document | |
| 36C24824Q1138 0001.docx | DOCX document | |
| RFQ 36C24824Q1138.docx | DOCX document |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| J048--NEW - Energy Center Steam Header& Boilers valves, gaskets, and vent replacement | Veterans Integrated Service Network 17 | Service-Disabled Veteran-Owned Small Business | |
| J045--FY27 Boilers Maintenance & Testing | Veterans Integrated Service Network 8 | Service-Disabled Veteran-Owned Small Business | |
| N048-- B41 Isolation Valve Installation | Veterans Integrated Service Network 16 | Service-Disabled Veteran-Owned Small Business | |
| 16292 Steam Boiler Replacement | Air Force Sustainment Center | Total Small Business | |
| White City, Oregon, Boiler Inspection Services Solicitation Base Year + Four Option Years (offers are now due on 11/13/2026) | Veterans Integrated Service Network 20 | Service-Disabled Veteran-Owned Small Business |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity