H335--Underground Storage Tanks Testing and Inspection Services at Edward Hines, Jr. VA Hospital in Hines, IL

Closed Pre-Solicitation Posted

Solicitation number
36C25226Q0450
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Place of performance
Edward Hines, Jr. VA Hospital Hines, Illinois 60141, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration is seeking sources for underground storage tank testing and inspection services at Edward Hines, Jr. VA Hospital in Hines, Illinois, with capability statements due by May 7, 2026. This is a pre-solicitation notice to inform acquisition strategy and does not constitute a formal solicitation; responses will assist the Government in determining the appropriate acquisition method.

The contractor will provide inspection, maintenance, testing, and repair services for nineteen storage tanks—sixteen underground and three above-ground diesel/unleaded tanks—located throughout the Hines VA Campus in compliance with 40 CFR Part 280. Core service requirements include monthly inspections (third or fourth week), annual inspections and triennial inspections (October), fuel testing for above-ground tanks (October), review of historical tank records and compliance documentation, coordination with the Office of the Illinois State Fire Marshal (OSFM) on permitting and compliance, formal inspection reports with findings and repair recommendations, transmission of inspection records to OSFM, and limited preventative maintenance by certified contractors. Work must comply with the Energy Policy Act of 2005, 40 CFR 280 under RCRA, VHA Directive GEMS 7700, and Illinois State Fire Marshal and Illinois Administrative Code Title 35, Part 731 requirements.

Required qualifications include certification by OSFM with Illinois Class ABC certification, Level A and B UST/AST inspector credentials, and state licensing. Inspections are conducted Monday through Friday, 7:00 AM to 3:30 PM, with at least one week advance notice required. Capability statements, not to exceed 25 pages, must address company experience with similar projects, customer references, number of employed technicians, 24/7 emergency availability, quality control procedures, SAM UEI and DUNS numbers, business size classification, socio-economic status, and GSA contract status if applicable.

Notice text

This is not a solicitation for proposals, proposal abstracts, bids, or quotations. The purpose of this notice is to obtain information regarding the availability and capability of all qualified sources to perform Siemens Uroskop De-Installation Services at Captain James A. Lovell Federal Health Care Center. Responses to the information requested will assist the Government in determining the appropriate acquisition method. It is understood that all firms submitting a response to this Sources Sought will have an established business in the industry of Underground Tank Testing and Inspection Services in accordance with requirements listed below.

DESCRIPTION OF SERVICES

Edward J. Hines Jr. VA hospital requires the services of a contractor for inspection, maintenance, testing, and repair services for nineteen (19) diesel/unleaded storage tanks located throughout the Hines VA Campus per 40 CFR Part 280.

(16) Underground Storage Tanks (UST)

(03) Above Ground Storage Tanks (AST)

Overview of requirements

The bidding contractors shall be certified by Office of the Illinois State Fire Marshall-(OSFM) & Illinois Class ABC certification

Review historical records of tank performance

Maintain Hines Storage Tank Records

Coordinate Storage Tank compliance and permitting efforts with OSFM

Work with engineering staff to evaluate maintenance and repair options

Inspect tank system for compliance with federal, state, and local environmental regulations

Provide formalized report on inspection and recommendations for each tank system

Transmit inspection records to OFSM to ensure Hines is compliant

Provide certification process guidance and ensure permits are current and displayed

Perform limited preventative maintenance repair that can be only accomplished by certified contractor

This contractor shall adhere to all regulatory program inspection requirements. These requirements shall include the Energy Policy Act of 2005, 40 CFR 280 under RCRA, VHA Directive GEMS 7700 and Illinois State Fire Marshall (ISFM). In addition, the inspections include adherence to air quality programs as identified by the Illinois Administrative Code Title 35, Part 731.

SCOPE

Contractor shall contact Hines VA Engineering, Contracting Officer Representative (COR) to request onsite inspections at least, one (1) week prior to the visit.

The contractor is required to perform inspections and maintenance during normal work hours 7:00am 3:30pm Monday through Friday. Inspections will not occur on weekends or government holidays.

Contractor shall review records to include Spill Prevention, Control, and Countermeasure (SPCC) plans, tank registrations and compliance reports, agency inspections, tank vendor operating manuals, layout drawings, and permits.

Contractor shall review the tank information available through Office of the Illinois State Fire Marshal agency databases and shall review state and local UST/AST code requirements with respect to the referenced tanks at the VA.

Inspection-On site

Contractor shall conduct on-site inspection of all tanks in Attachment 2, with VA personnel to verify the current state and conditions of the UST/AST systems. The site inspection shall be conducted by a certified Level A and B UST/AST Tank System Inspector and Illinois certified tank installer.

The inspection shall require both written and photo documentation if emergency or damage is discovered.

The inspection shall include demonstration of the operation using real time monitoring systems used by VA personnel.

This inspection shall include spill and overfill protection, corrosion protection, leak detection, secondary containment, spill preparedness kits for response, reporting of releases, and applicable compliance requirements.

Inspection-On site Time Frame and Delivery

Monthly Inspection: 3rd or 4th week of month

Annual Inspection: Month of October-No time constraints

Triennial Inspection: Month of October-No time constraints

AST Inspection Note

No monthly inspections needed on AST

Only Fuel is tested once a year : Month of October-No time constraints

Inspection Close out

At the completion of the on-site inspection, the contractor shall conduct an Inspection review meeting with VA representatives to present findings.

Meeting Agenda shall include identification of regulatory deficiencies discovered that could result in significant action by US EPA, IEPA, OISFM, state, local agencies or risk to patient health.

The contractor shall review Hines VA tank program documentation/records of Inspected elements such as: tank registration forms, financial responsibility, submittals, tank testing, and tank inspections.

Contractor to provide formalized report using OSFM Standards

REPORTING REQUIREMENTS

GEMS Documentation/Reports-Defined

The Contractor shall be responsible to provide VA Engineering Service with a typed formal report of services performed. This formal Vendor Engineering Service Report shall include results, details and data for all services performed.

Contractor shall provide a report presenting inspection findings and fix recommendations for each tank system.

Items to be included & reported during inspections:

Tank Conditions

Notification (failure to notify)

Corrosion protection Tank

Corrosion protection Piping

Condition on retractors, hoses, breakaways, vapor caps, rubber gaskets, and swivels (dispensing islands only)

Condition of all gauges and meters

Overfill/Spill

Overfill prevention is in place and operational

Spill prevention is in place and operational

Tank and piping release detection

Inspect piping/fitting conditions for failures, potential failures

Detection methods and appropriate equipment or procedures are in place: alarms, interstitial piping, sump sensors

Inspection, removal and disposal of debris in spill buckets.

Secondary containment is present where required

Required Documentation

Prior to approval of invoices, contractor shall provide documents of:

Tank and piping repairs performed by contractor

Any notice of Temporary tank closure or Permanent tank decommissioning and removal

Documentation on inspecting Operator training Class A, B, and C

Time stamps of equipment downtime/uptime and hours on-site for service call

Identification of equipment to be serviced

Inventory ID number, manufacturer's name, device name, model number, serial number, and any other manufacturer's identification numbers

Itemized description of service(s) performed

Name of Veteran Administration employee who witnessed service described

Name of Field Service Engineer (FSE) who performed services

Contractor service number or contractor log number

Pass or Fail per tank inspected

OSFM Quarterly Equipment Inspection Checklist/Operations & Maintenance Guidelines for UST System Inspections per tank

GENERAL REQUIREMENTS

Contractor to furnish all labor, materials, and transportation necessary to include:

All work under the provisions of this contract shall be performed by properly licensed and certified UST technicians directly employed by the contractor. UST Technicians shall be fully trained and experienced in the servicing of the systems and devices specified. Subject to COR approval.

In addition to the conformance section of the specifications all work under the provisions of this contract shall be performed and certified as being in full compliance with all applicable laws, regulations and codes.

At all times while performing work under the provisions of this contract the contractor s employees shall strictly observe the requirements of all applicable Occupational Safety and Health Administration, Environmental Protection Agency, Department of Veterans Affairs rules and the Illinois State Fire Marshal, regulations and policies.

Existing UST alarms, piping and system components or devices found to be in a state of failure shall be reported to the COR for appropriate corrective action.

Contractor shall troubleshoot and diagnosis as necessary to determine the cause of the problem identified.

Contractor shall provide a cost proposal to make corrections or repairs to identify deficiencies for consideration by facility personnel.

CONTRACTOR QUALIFICATIONS

The contractor shall maintain an adequate inventory of parts, materials and supplies as necessary to provide for the timely maintenance, testing and repair of the specified UST/AST systems components and devices. Failure by the contractor to satisfactorily accomplish required inspections by the provisions of this contract in a timely manner because of a lack of parts/equipment availability shall be considered justification to terminate the contract in accordance with the Default Clause.

Firms shall have been engaged in business of installing, repairing, testing, maintaining UST systems, and components verifying compliance with the Illinois State Fire Marshall and other regulatory offices for at least the past five (5) consecutive years. Bidders shall provide list of the names, addresses and telephone numbers of three (3) customer references with preference towards experience with the Federal or Illinois State governments.

Contractors shall provide proof of Illinois Class A,B, and C UST certification in bid.

Due to the dangers with Above and Underground Storage Tanks, there shall be no subcontracting opportunities for potential general contractors. Communications shall be from government to the self-performing contractor and vice versa only.

Files

File Type Posted
36C25226Q0450.docx DOCX document

Similar open opportunities

Opportunity Agency Set-aside Responses due
J091--Underground Storage Tanks - STC Department of Veterans Affairs St. Cloud VA health Care System St. Cloud, Minnesota 56303, United States · NAICS 811310 Veterans Integrated Service Network 23 No set-aside
H365--annual medical gas testing POP: 12/01/2026 - 09/30/2031 VA Loma Linda Healthcare System 11201 Benton Street Loma Linda CA 92357, United States · NAICS 541380 Veterans Integrated Service Network 22 Service-Disabled Veteran-Owned Small Business
F109--Underground Diesel Storage Tank Boot Replacement , Fargo VA Healthcare System. Department of Veterans Affairs Fargo VA Health Care System Fargo, North Dakota 58102, United States · NAICS 811310 Veterans Integrated Service Network 23 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors