The United States Air Forces in Europe and Africa, a component of the Department of the Air Force, is seeking a contractor to provide comprehensive inspection, testing, and maintenance (ITM) services for fire alarm and water-based suppression systems at the VM Hangar and SOF facilities. The primary objective is to maintain an Olympia Electronics BSR-1004 analogue addressable fire alarm panel and associated water-based suppression systems in a constant state of operational readiness and full compliance with applicable standards and manufacturer requirements. Key contract requirements include semi-annual system inspections and testing of all components per UNI 11224 standards, smoke detector cleaning at specified analog levels, preventive maintenance, emergency on-call repair services with a 4-hour normal working hour response requirement, and delivery of dual-language service reports and compliance certificates. The contractor must demonstrate a minimum of 5 years of continuous experience with commercial-grade analogue addressable fire alarm systems, employ fully trained and certified technicians, maintain designated points of contact with local language proficiency, and possess all required local, state, and national licenses and permits. The pre-solicitation notice was posted on March 25, 2026, with a response deadline of April 1, 2026, providing potential bidders with seven days to submit questions or indicate their interest in pursuing this opportunity.

This procurement carries no set-aside designation, meaning it is open to all eligible contractors without restrictions based on business size or socioeconomic status. The notice does not identify any incumbent contractor or provide a specific award value or budget range. The contract period consists of one 12-month base year with four optional 1-year renewal periods exercisable at the Government's sole discretion, potentially extending the engagement to five years if all options are exercised. The scope encompasses maintenance of a 4-loop fire alarm system and all associated peripheral devices, as well as water-based suppression system equipment including tamper switches, pressure switches, flow switches, fire pumps, water reservoir tanks, and air compressors. The contractor must provide an ITM service schedule within 10 working days of award and submit service reports within 2 working days of completion, demonstrating a requirement for rapid turnaround and detailed documentation throughout the contract performance period.

Notice text

1.0 General Information
1.1 Description of Services & Introduction This Performance Work Statement (PWS) requires a contractor to provide all personnel, equipment, tools, materials, supervision, and other non-personnel services necessary to perform comprehensive inspection, testing, and maintenance (ITM) for the existing fire alarm and suppression systems installed at the VM Hangar and SOF facilities, as defined in this PWS. The contractor shall perform all services to the standards specified in this contract.
1.2 Background The facilities are equipped with an Olympia Electronics analogue addressable fire alarm system and associated water-based suppression systems. Proper maintenance and inspection are critical to ensure the safety of all personnel and the protection of government property.
1.3 Objectives The primary objective of this contract is to ensure the fire alarm and suppression systems are maintained in a constant state of readiness and full operational capability, compliant with all applicable standards and manufacturer requirements.
1.4 Scope The contractor shall provide all necessary management, supervision, labor, materials, tools, and equipment to perform comprehensive ITM, smoke detector cleaning, repair services, and technical assistance for the fire alarm and water-based suppression systems. This scope covers the Olympia Electronics BSR-1004 Analogue Addressable Fire Alarm Panel, all connected peripheral devices, and all water-based suppression systems and associated equipment as detailed in Section 2.0.
2.0 Equipment to be Serviced
This PWS requires a contractor to provide services for the existing fire alarm and suppression systems installed at the facility. The contractor shall be responsible for all labor, tools, materials, and supervision necessary to perform maintenance, inspection, and potential repair or replacement services on the equipment detailed below.
2.1 Fire Alarm Control Panel Specifications
The fire alarm system is controlled by an Olympia Electronics analogue addressable panel. All work must be compatible with this specific model and its associated components.
Specification
Details
Equipment Type
Analogue Addressable Fire Alarm Panel
Manufacturer
Olympia Electronics
Model
BSR-1004
Serial Number (S/N)
2938
System Type
Analogue Addressable
System Capacity
4 Loops
Repeater Panel
Compatible with BSR-1000 Repeater Panel
Power Supply
220-240V AC, 50-60Hz, 130VA Max
Enclosure Rating
IP30
Country of Origin
Greece
2.2 WATER BASED SUPPRESSION SYSTEMS
These systems include but, are not limited to all associated equipment such as: tamper switches, pressure switches, flow switches, fire pumps, water reservoir tanks, liners, bladders, and air compressors. The Contractor’s area of service responsibility starts at Main Control Valve (MCV) (e.g., Post Indicator valve) with its tamper switch (if provided) and applies to all water suppression systems downstream of MCV.
2.3 Compliance and Standards
The contractor must ensure that all work performed, and any parts or components replaced, meet or exceed the original equipment manufacturer (OEM) specifications and comply with the following European standards to which the panel is certified, as well as all applicable local and national standards, regulations, and laws for the installation location.
• EN 54-2:1997+A1:2006 (Control and indicating equipment)
• EN 54-4:1997+A1:2002+A2:2006 (Power supply equipment)
• CE Mark (Notified Body: 1293)
• Construction Products Regulation (CPR) No: 1293 - CPR - 0658 Rev.1
• Declaration of Performance (DoP) No: 921100400_59_001
The contractor is responsible for verifying all site conditions and equipment details prior to commencing work.
3.0 Scope of Work
3.1 Required Tasks
Task
Description
3.1.1 Semi-Annual System Inspection & Testing
Conduct a complete functional and visual inspection of 100% of the fire alarm system components on a semi-annual basis. This includes testing every smoke detector, manual call point, and audible/visual notification appliance to ensure proper operation and communication with the main control panel, in line with UNI 11224 requirements for addressable systems.
3.1.2 Smoke Detector Cleaning
As part of the ITM service, clean all addressable smoke detectors that indicate a 49% or higher analog level at the FACP. The contractor must download and provide a status report from the FACP before and after cleaning.
3.1.3 Preventive Maintenance
Clean all system components as needed, check for environmental changes affecting device performance, and perform all manufacturer-recommended preventive maintenance actions during scheduled visits.
3.1.4 Emergency and Extraordinary Maintenance
Provide emergency, on-call repair services to correct any system deficiencies or malfunctions. The contractor must respond and be onsite within 4 normal working hours after receipt of a service call.
3.1.5 Deficiency Correction
Correct all deficiencies identified during inspection or testing. Minor deficiencies shall be corrected during the inspection visit. For major deficiencies requiring parts or extended labor, the contractor shall provide a written quote for repair within 5 business days of discovery.
3.2 Deliverables and Reporting
Deliverable
Description
3.2.1 ITM Service Schedule
No later than ten (10) working days after award of the contract, the contractor shall submit a detailed schedule for all mandatory ITM services for approval. This schedule must be adhered to and updated as necessary.
3.2.2 ITM Service Report
Within two (2) working days of completing any inspection, the contractor shall submit a detailed dual-language report. The report must include a list of all devices tested, their status (pass/fail), a description of any deficiencies found, and the corrective actions taken or recommended.
3.2.3 Certificate of Compliance
Upon completion of the first semi-annual inspection and annually thereafter, the contractor shall provide a formal Certificate of Compliance stating that the fire alarm system is fully operational and meets all relevant EN 54 and local fire code standards.
3.2.4 Emergency / Extraordinary Service Report
A service report shall be provided by the second working day following the completion of any emergency or extraordinary repair, detailing the nature of the fault, cause, description of work completed, hours expended, and materials used.
3.2.5 Weekly Service Submittals
The contractor shall provide a weekly summary including a parts history summary, a work order tracker, and performance metrics.
4.0 Period of Performance
The period of performance for this contract will be for one (1) Base Year of twelve (12) months, with the possibility of four (4) additional one-year Option Periods. The exercise of any Option Period will be at the sole discretion of the Government.
Period
Duration
Start Date
End Date
Base Year
12 Months
[Insert Start Date]
[Insert End Date]
Option Year 1
12 Months
[Insert Date]
[Insert Date]
Option Year 2
12 Months
[Insert Date]
[Insert Date]
Option Year 3
12 Months
[Insert Date]
[Insert Date]
Option Year 4
12 Months
[Insert Date]
[Insert Date]
5.0 Contractor Qualifications
The Contractor must meet the following minimum qualifications to be considered technically acceptable for this contract.
5.1 Corporate Experience The Contractor shall have a minimum of five (5) years of continuous corporate experience in the inspection, testing, maintenance, and repair of commercial-grade, analogue addressable fire alarm systems.
5.2 Technician Certification and Training All technicians must be fully trained and certified to work on analogue addressable fire alarm systems.
5.3 Key Personnel The Contractor shall appoint key personnel, including a primary and alternate point of contact, who are responsible for the performance of the work.
5.4 Language Proficiency All contractor personnel must be proficient in the local language. Key personnel who
interact with the Contracting Officer's Representative (COR) must also be proficient in English.
5.5 Licensing and Insurance The Contractor must possess and maintain all required local, state, and national licenses and permits necessary to legally perform fire alarm system services.
5.6 Emergency Response Capability The Contractor must demonstrate the capability to meet the emergency response time requirements as specified in Section 3.1.4.

Files

File Type Posted
FIRE ALARM PWS (1) (002).pdf PDF

Similar open opportunities

Opportunity Agency Set-aside Responses due
Fire Alarm/Suppression Inspection, Testing, and Maintenance Rome, New York 13441, United States · NAICS 561621 Air Force Research Laboratory No set-aside
Fire alarm replacement IDIQ Arlington, Virginia, United States · NAICS 238210 Office of Acquisition Management Total Small Business
H312--Fire Alarm Maintenance Service Contract FY27 - NEW Base + Four - 583 NAICS 561621 Veterans Integrated Service Network 10 No set-aside
Fire apparatus intercom system uplift and installation Eglin AFB, Florida 32542, United States · NAICS 811121 Air Force Test Center Total Small Business
Vertical Transportation Equipment (VTE): Maintenance, Repair, and Inspection at Aviano Air Base, Italy Aviano Pordenone 33080 Italy · NAICS 811310 Air Forces Europe and Africa No set-aside

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity