C1DA--Project 575-23-107 | Expand Electrical Capability | Design

Award Notice Posted

Solicitation number
36C25925R0113
Agency
Awarded
to Citrine LLC
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

Contract number
36C25926C0059 Federal contract award
NAICS code
541330 Engineering Services

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19 awarded a $769,409 contract to Citrine LLC for architectural and engineering design services to expand electrical capacity at the Grand Junction VA Medical Center, with the award made on July 16, 2026.

The contract was awarded under Service-Disabled Veteran-Owned Small Business set-aside. Place of performance is Grand Junction, Colorado (2121 North Ave, Grand Junction, CO 81501). The scope includes design of electrical infrastructure improvements across the 22-building, 321,557 gross-square-foot campus, specifically remodeling and expanding two existing electrical rooms by 800 square feet to the west and creating a new electrical room on the eastern side to support temporary facilities. The design must include a three-phase, 208V, 800A electrical distribution system with normal, critical, life safety, and emergency power circuits, and comply with VA Design Manuals, National Electric Code, NFPA standards, IBC 2003, and VA Information Security Handbook 6500.6. The contractor must obtain permits, conduct testing and commissioning, incorporate energy efficiency improvements, and submit red-line design documents within 30 days of construction completion.

Notice text

SCOPE OF WORK: This contract will provide designs for expanding the electrical capacity of the Grand Junction VA Medical Center.

The A-E is to provide design services to expand the electrical capacity of the Grand Junction VA Medical Center (2121 North Ave, Grand Junction, COÂ 81501).

The contractor shall design the following:

Statement of Work: The Grand Junction VA Medical Center campus has 22 buildings, with 321,557 gross square feet of space. To expand services, the VA requires additional electrical power on the north and east sides of the campus. The northern electrical room remodel will support future expansions while the newly created eastern electrical room will support temporary facilities that provide workspaces for displaced employees. In the past, temporary spaces have been modular in nature and could be tents, trailers or other types of temporary facilities.

Most work will be conducted indoors, however, Grand Junction, CO has a semi-arid climate, with hot summers and generally mild winters. During the summer months temperatures typically reach into the 90s Fahrenheit during the day, while evenings tend to remain comfortable and cool. Winters are usually mild, but snow does occur, and temperatures can cool down to freezing averages. Spring and fall tend to be transitional seasons with moderate temperatures. The area receives around ten (10) inches of precipitation per year with most of it falling from April through August.

Specific project tasks:

Remodel and add on to 1634-1 (433 SF) / 1635-1 (433 SF) to ensure adequate electrical utilities exist to support the north portion of the WCHCS on the Grand Junction, CO campus. This will include expanding the rooms by 800 SF to the west. This additional space will allow the hospital to add switchboards and panels when needed and enclose an Automatic Transfer Switch (ATS).

Add a new electrical room to ensure adequate electrical utilities are in place on the eastern side of the WCHCS on the Grand Junction, CO campus. This will provide electrical capacity from location 1 on the western side of the WCHCS to location 2 (see attachment A) on the eastern side.

The minimum power requirements are three-phase, 208V, 800A and include normal, critical, life safety and emergency power circuits. This electrical run will terminate in a new conditioned electrical space at location 2 after passing through necessary electrical step-down equipment at site 3. Any future projects that have temporary facilities will be designed to be compatible with 208V and use no more than 80% of the amperage available per branch circuit. These facilities will be expected to run power from their location to the new electrical room distribution point designed at location 2.

All aspects of the design must adhere to the NEC Design manuals posted on the VA technical information library at the following sites: http://www.cfm.va.gov/til/ and https://vatilms.va.gov/vatilms/catalog.

All electrical, architectural, and mechanical work for these systems will be designed by the A-E.

The installation must, at a minimum, be in accordance with all applicable codes indicated in the Department of Veterans Affairs (VA) Design Manuals and VA Publications (Master Construction Specifications, Construction Standards, National Fire Protection Association (NFPA), Underwriters Laboratory, International Building Code IBC 2003, NFPA and National Electric Code (NEC), building codes and standards, and VA Information Security Handbook 6500.6, etc.).

DESIGN CRITERIA: As part of the design the following list needs to be considered:

All electrical work will be terminated by the contractor. The design must be clear who and what is supplied for the termination equipment.

Any penetration through any fire barriers whether a floor or wall will be done in this contract to meet VA standards and National Fire Protection Association (NFPA). The contractor shall obtain permits issued by the facility before any penetration shall occur.

The installed system and its components shall be tested and commissioned. This will be included in the design and construction documents.

Implement new technologies in electrical systems to improve and facilitate energy usage reductions. The system will be compatible with the existing control systems on station.

All finishes will be coordinated with the VA interior designer and called out in a finish schedule.

All testing and balancing parameters will be provided by the A-E.

Design documents that show the red lines will be submitted by the contractor to the A-E, put into the AutoCAD drawings and submitted within 30 days of the completion of the construction project. According to VA standards as outlined in the VA Specifications Technical Library.

All existing utilities which are designed to be relocated or modified shall have directions to the contractor on the new location and modifications. Awarded contract 36C25926C0059 to CITRINE LLC for 769409.00 on 2026-07-16.

Files

File Type Posted
36C25926C0059_1.docx DOCX document

Notice history

Notice Type Posted
This notice Latest Award Notice
C1DA--Project 575-23-107 | Expand Electrical Capability | Design Award Notice
C1DA--Project 575-23-107 | Expand Electrical Capability | Design Latest pre-solicitation Pre-Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
C1DA--657-27-209JB Renovate Main Lobby, Bldgs 1 & 53 St. Louis Jefferson Barracks VA Medical Center St. Louis Missouri 63125 · NAICS 541310 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business
Z1DA--Project No. 539-24-101 - Replace Failing Electrical Equipment. Cincinnati VA Medical Center 3200 Vine Street · NAICS 238210 Veterans Integrated Service Network 10 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity