C1DA-- EHRM Infrastructure Upgrades – North Bexar CBOC

Closed Pre-Solicitation Posted

This opportunity was awarded. See the award notice from , or the latest solicitation from .

Solicitation number
36C24W23Q0026
Agency
Department of Veterans Affairs
Responses due
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

NAICS code
541330 Engineering Services
PSC
C1DA Architect And Engineering- Construction: Hospitals And Infirmaries
Place of performance
North Bexar OPC San Antonio, Texas 78247, United States

Notice details come from SAM.gov. Updated .

About this opportunity

This pre-solicitation notice requests design and construction services to upgrade infrastructure at the North Bexar Outpatient Clinic in San Antonio, Texas, to support the Department of Veterans Affairs' transition to a new electronic health record system. Key requirements include meeting standards for electrical, HVAC, physical security and IT systems to support power, temperature control, remote monitoring and networking equipment. Responses are due by June 6, 2023, with construction to be completed within 150 days of award and the design package due within 60 days.

The opportunity is set aside for service-disabled veteran-owned small businesses. The work includes upgrades to electrical, HVAC, physical security and IT infrastructure and must be completed according to milestones between the initial meeting and 150 days after award. The location of the work is the North Bexar OPC clinic in San Antonio, Texas, and all work must comply with manuals and standards for telecommunications, HVAC, construction and meet safety and infection control requirements.

Notice text

Please subject Title the email as follows: RFQ 36C24W23Q0026

A site visit is scheduled for Wednesday May 17th, 2023, at 2:00 PM CST at North Bexar OPC located at 16019 Nacogdoches, Suite 110, San Antonio, TX 78247. Mark Anthony Tabucbuc, Healthcare Engineer, Phone: (210) 617-5300 ext.14874, Email: markanthony.tabucbuc@va.gov

General Requirements: VHA requests the Contractor provide design and construction services to include all labor, materials, tools, equipment ,transportation, supervision, and other services necessary to upgrade the leased property in accordance with the scope of work listed below:

South Texas Veterans Health Care System

7400 Merton Minter Blvd

San Antonio, TX 78229

LEASE AMENDMENT SCOPE OF WORK

EHRM INFRASTRUCTURE UPGRADES North Bexar OPC CBOC

PROJECT NO: 671-23-705NB

PROJECT NAME: EHRM Infrastructure Upgrades North Bexar CBOC

1. GENERAL INTENT:

The Contractor shall provide design and construction work necessary at the North Bexar OPC located at

16019 Nacogdoches, Suite 110, San Antonio, TX 78247 to support the Veterans Health Administration s

(VHA) change to the new Electronic Health Record Management (EHRM). VHA requests the Contractor

provide design and construction services to include all labor, materials, tools, equipment,

transportation, supervision, and other services necessary to upgrade the leased property in accordance

with this scope of work.

1.1 General Requirements

1.1.1 The Contractor shall provide design services and a complete design package containing

drawings and specifications. The design drawings and specifications shall follow all

applicable codes, manuals, standards, and guides, including those listed in Paragraph 4.

1.1.2 The Contractor shall provide construction services for the following infrastructure

improvements, as necessary to meet listed requirements:

1.1.2.1 Electrical infrastructure including bonding and Building Management (BMS)

interfaces to manage and monitor UPS.

1.1.2.2 HVAC infrastructure including temperature and humidity upgrades, rack and

space sensors, and BMS interfaces to manage and monitor temperature and

humidity.

1.1.2.3 Physical security upgrades including telecommunication room cameras,

alarms, and necessary interfaces to existing security system. Location and

quantities to be determined and approved during DID drawings review.

1.2 Design Effort

1.2.1 Contractor shall coordinate a Design Intent Drawings (DID) workshop with their respective

design and construction team and VHA to develop, review, and complete final DIDs.

1.2.2 Design shall be completed in accordance with the schedule listed in Paragraph 3.

South Texas Veterans Health Care System

7400 Merton Minter Blvd

San Antonio, TX 78229

1.2.3 Contractor shall take meeting minutes and distribute meeting minutes to VA COR/LCO

within three days of meeting. Meeting minutes shall be submitted by the Contractor and

approved by VHA.

1.2.4 Contractor shall provide as-builts 15 days after final inspection approval by COR.

1.3 Clinic Operations

1.3.1 It is the Contractor s responsibility to provide a work plan allowing for continued operations

of the CBOC. The VHA COR shall review and approve the work plan. The work plan may

require after hours or weekend work.

1.3.2 Execute work to interfere as minimally as possible with normal functioning of the North

Bexar OPC Clinic, including operations of utility services, fire protection systems and any

existing equipment, and work being done by others. Use of equipment and tools that

transmit vibrations and noises through the building structure, are not permitted in

buildings that are occupied by Veterans or VHA staff, except as approved by COR.

1.3.3 Do not store materials and equipment in other than assigned areas.

1.3.4 Utilities Services: Where necessary to cut existing pipes, electrical wires, conduits,

cables, etc., of utility services, or of fire protection systems or communications systems

(except telephone), they shall be cut and capped at suitable places as directed by Contractor

and approved by VHA COR. All such actions shall be coordinated with the Contractor and

VHA COR. Contractor shall submit a request to interrupt any such services to VHA COR, in

writing, 7 days in advance of proposed interruption. Request shall state reason, date,

exact time of, and approximate duration of such interruption. Interruptions may have to

be scheduled outside of normal CBOC operational hours.

1.3.4 The Contractor shall take all measures and provide all material necessary for protecting

existing equipment and property in affected areas of construction against dust and

debris, so that equipment and affected areas to be used in CBOC operations will not be

hindered. Contractor shall permit access to Department of Veterans Affairs personnel

and patients through other construction areas which serve as routes of access to such

affected areas and equipment. These routes whether access or egress shall be isolated

from the construction area by temporary partitions and have walking surfaces, lighting

etc. to facilitate patient and staff access. Coordinate alteration work in areas occupied by

Department of Veterans Affairs so that CBOC operations will continue during the

construction period.

1.4 Testing

1.4.1 The Contractor shall provide a written testing plan in accordance with specifications and

Building Industry Consulting Service International (BICSI) standards. The plan will provide

a schedule and a written sequence of what will be tested, how and what the expected

outcome will be. This document will be submitted for approval prior to commencing

testing. The Contractor shall document testing results and submit to VHA.

South Texas Veterans Health Care System

7400 Merton Minter Blvd

San Antonio, TX 78229

1.4.2 Contractor will coordinate final tests with VHA COR and conduct final tests in his/her

presence. Contractor shall furnish all labor, materials, equipment, instruments, and forms, to

conduct and record such tests.

1.5 Safety During Construction

1.5.1 The Contractor shall designate a minimum of one Site Safety and Health Officer (SSHO) at

each project site that will be identified as the SSHO to administer the Contractor s safety

program.

1.5.2 The designated SSHO must meet the requirements of all applicable OSHA standards and

be capable (through training, experience, and qualifications) of ensuring that the

requirements of 29 CFR 1926.16 and other appropriate Federal, State and local

requirements are met for the project. As a minimum the SSHO must have completed the

OSHA 30-hour Construction Safety class and have five (5) years of construction industry

safety experience or three (3) years if he/she possesses a Certified Safety Professional

(CSP) or certified Construction Safety and Health Technician (CSHT) certification or have

a safety and health degree from an accredited university or college.

1.6 Infection Control

1.6.1 An Accident Hazard Analysis associated with infection control will be performed by the

Contractor and VHA COR in accordance with FGI Guidelines (i.e., Infection Control Risk

Assessment (ICRA)). The ICRA procedure found on the American Society for Healthcare

Engineering (ASHE) website will be utilized. Construction Matrix (ashe.org)

1.6.2 The approved ICRA shall be reviewed and approved by the VHA Infection Prevention

service and posted at the work site.

1.6.3 The Contractor shall implement all measures required by the ICRA.

2. STATEMENT OF WORK:

2.1 The Contractor shall ensure all below requirements from the VA Office of Electronic Healthcare

Modernization Site Infrastructure and End User Device Requirements are met.

2.2 Local Area Network (LAN)

2.2.1 Reference: Infrastructure Standard for Telecommunications Spaces, Version 3.1,

https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecomSpaces.pdf.

2.2.12 Network Infrastructure devices supported by UPS and Emergency Power / Backup

Generator as described below in 2.3.

2.3 Power

South Texas Veterans Health Care System

7400 Merton Minter Blvd

San Antonio, TX 78229

2.3.1 UPS Functional Requirements: This Scope of Work includes UPS requirements for OIT

equipment only. All OIT equipment in the Telecommunications Room shall be connected to the

UPS.

2.3.1.1 All UPS units supporting Information Technology infrastructure shall be

functional and maintain a 10-minute run-time. Existing UPS to be reused;

capability for remote monitoring to be installed by Contractor under this project.

2.3.1.2 UPS shall be managed and report the following information to a management

system.

2.3.1.2.1 Overload

2.3.1.2.2 Battery Temperature High

2.3.1.2.3 Battery Charge Low

2.3.1.2.4 Battery Failure

2.3.1.2.5 Critical Condition (fan failure, low output voltage, etc)

2.3.1.3 UPS shall support both monitoring and remote management to include full

compliance with RFC-1628 UPS Management Information Base Support for

Simple Network Management Protocol (SNMP) v3.0, BaCnet and Modbus

protocols.

2.3.1.4 UPS shall be connected to a monitoring system by Ethernet (wired or wireless)

or serial interface (RS-232 or RS-485).

2.3.2 Upstream bonding requirements to the Secondary Bonding Busbar or Primary Bonding

Busbar must use two lugs. Bonding for telecommunications equipment must be

performed per manufacturer's specifications. All grounding shall comply with

ANSI/NECA/BICSI 607-C, Generic Telecommunications Bonding and Grounding (Earthing)

for Customer Premises, November 2015.

2.4 Heating, Ventilation, and Air Conditioning (HVAC) Design Requirements

2.4.1 Reference: U.S. Department of Veterans Affairs Office of Construction & Facilities

Management HVAC Design Manual, dated May 1, 2019,

https://www.cfm.va.gov/til/dManual/dmHVAC.pdf.

2.4.2 Telecommunications Rooms, Class B space temperature range 41°F to 95°F, relative

humidity: 8 to 80% noncondensing.

2.4.2.1 Temperature and humidity shall be monitored in proximity to the OIT

equipment rack. Place sensors either on populated rack or within 6 feet of

rack.

2.4.2.2 Temperature and humidity shall be connected to a monitoring system by

Ethernet (wired or wireless) or serial interface (RS-232 or RS-485).

South Texas Veterans Health Care System

7400 Merton Minter Blvd

San Antonio, TX 78229

2.5 Physical Security Design Requirements

2.5.1 Reference: Infrastructure Standard for Telecommunications Spaces,

https://www.cfm.va.gov/til/dManual/dmTelecomm.pdf .

2.5.2 Provide an electronic Security Management System (SMS) with a Physical Access Control

System (PACS). The system shall be compatible with existing PACS, coordinate with COR

and obtain approval from STXVHS police.

2.5.3 Doors shall include a mechanical spring loaded deadlocking feature (not separate

deadbolt lock), PACS associate electronic Personal Identity Ve rification (PIV) card

access device with keypad, electric strike and digital Closed Caption Television (CCTV)

color camera routed to and directly controlled by the facility SMS.

2.5.4 Telecommunication Room security system shall be connected to a UPS or emergency

backup power system.

2.5.5 Facility programmable door controller shall be fully functional in a standalone status if

connection to the SMS is lost. Once the connection is restored, the local door control

system shall update the SMS, regarding all operations that occurred after the

connection was interrupted. Then, the SMS shall update the local door control units to

current operational function.

2.5.6 The PACS and SMS shall be fully compliant with VA s PII, PIV "Smart" ID Card and at a

minimum, FIPS 201-1 and NRTL (i.e. UL) listed and labeled.

2.6 Contractor/Contractor Provided Equipment

2.6.1 Rack Sensor

2.6.1.1 Manufacturer: APC

2.6.1.2 Model: NetBotz Rack Sensor Pod 150 NBPD0150

2.6.2 IT Equipment Room CheckPoint Wireless Temperature and Humidity Sensor

2.6.2.1 Manufacturer: Medical Resources

2.6.2.2 Model: TEMP125

3. PERIOD OF PERFORMANCE:

3.1 Work timelines and completion progress shall be communicated to the COR for tracking purposes.

3.2 Work shall be completed in accordance with milestones in the following paragraph (project schedule

table). Note: Completion date should be 6 months prior to station Go-Live date.

3.3 Work shall meet project milestones as outlined here.

South Texas Veterans Health Care System

7400 Merton Minter Blvd

San Antonio, TX 78229

Award Day 0

In itial meetin g with Go v t Day 10

Schematic Design due to VA Day 20

AE meeting (Schematic Design) Day 25

35% Design due to VA Day 40

AE meeting (35%) Day 45

95% Design due to VA Day 60

AE meeting (95%) Day 65

100% Design due to VA Day 70

AE meeting (100%) Day 75

Final CD submission due to VA Day 78

Go v t ap p ro ves CD Day 90

Construction Complete Day 150

4. MANUALS, STANDARDS AND DESIGN GUIDES: The work will be completed in compliance with the

following manuals, standards, and design guides. Where there appear to be contradictions, VA shall

make a final determination on applicability of manuals, standards, and design guides.

4.1 VA OEHRM Site Infrastructure and End User Device (EUD) Requirements Version 2.0 (Attachment

1)

4.2 Infrastructure Standards for Telecommunications Spaces Version 3.1 (dated July 1, 2021)

4.3 HVAC Design Manual (dated November 1, 2017 with Rev dated March 1, 2020)

5. GENERAL REQUIREMENTS FOR PRIVACY INFORMATION:

5.1 Information Systems Officer, Information Protection: The contractor will not have access to VA

Desktop computers, nor will they have access to online resources belonging to the government

while conducting services.

5.2 Privacy Officer: The contractor will not have access to Patient Health Information (PHI) nor will

they have the capability of accessing patient information during the services provided to the VA.

5.3 Records Manager: There will be no federal records created, maintained, used or dispositioned

with this contract; regardless of format [paper, electronic, etc.] or mode of transmission [e -mail,

fax, etc.].

Attachments

Files attached to this notice, newest first
File Type Posted
RFQ VA OEHRM Site Infrastructure Requirements - 2_0_Signed.pdf PDF
RFQ 2023 Bexar County Wage Determination (1).pdf PDF
36C24W23Q0026.docx DOCX document

Notice history

Notices posted for this opportunity, newest first
Notice Type Posted
DD01--Project 671-23-705NB EHRM Infrastructure Upgrades – North Bexar CBOC (VA-23-00024196) Award Award Notice
C1DA-- EHRM Infrastructure Upgrades – North Bexar CBOC Latest solicitation Solicitation
C1DA-- EHRM Infrastructure Upgrades – North Bexar CBOC This notice · Original Pre-Solicitation

On GovTribe

Work this opportunity on GovTribe

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity